DC LOAD CALCULATION [INCOMER]

Qty:
Sr.No. Description of DC Equipment Rating in Watts QTY Total DC Load (W)
1 Circuit Breaker Type 3AH3 VCB Motor 500 1 500
2 Circuit Breaker Type 3AH3 VCB Closing Coil 140 1 140
3 Circuit Breaker Type 3AH3 VCB Tripping Coil 140 1 140
4 Numerical Protection Relay (7SJ62) 9 1 9
5 High Speed Tripping Relay (VAJH13) 150 1 150
6 Indicating LED Lamp 2.5 8 20
7 Annunciator 12 1 12
8 Hooter 30 1 30
9 Auxilary Contractor (3TH30) 6.2 1 6.2
10 Digital Ammeter (EM6459) 3.75 1 3.75
11 Digital multifunction meter (EM6400) 3.75 1 3.75

Momentary DC Load per Panel 500


Continous DC Load per Panel 84.7
Total DC Load per Panel 584.7

Client: NMDC Prep By : Suddhaditya Banerjee &


Consultant: Awais Nezam
Project: LADLE FURNACE
Work: DATA FOR BATTERY SIZING
Ckd By : Arunava Basak
DC LOAD CALCULATION [LINE PT]

QTY : 1
Sr.No. Description of DC Equipment Rating in Watts QTY Total DC Load (W)
1 Digital Voltmeter (EM6459) 3.75 1 3.75
2 Annunciator 12 1 12

Momentary DC Load per Panel 0


Continous DC Load per Panel 15.75
Total DC Load per Panel 15.75

Client: NMDC Prep By : Suddhaditya Banerjee &


Consultant: Awais Nezam
Project: LADLE FURNACE
Work: DATA FOR BATTERY SIZING
Ckd By : Arunava Basak

Sheet No: 2
DC LOAD CALCULATION [OUTGOING TO FURNACE TRANSFORMER]

QTY: 1
Sr.No. Description of DC Equipment Rating in Watts QTY Total DC Load (W)
1 Circuit Breaker Type 3AH3 VCB Motor 500 1 500
2 Circuit Breaker Type 3AH3 VCB Closing Coil 140 1 140
3 Circuit Breaker Type 3AH3 VCB Tripping Coil 140 1 140
4 Numerical Protection Relay (7SJ62) 9 1 9
5 High Speed Tripping Relay (VAJH13) 150 1 150
6 Indicating LED Lamp 2.5 8 20
7 Annunciator 12 1 12
8 Auxilary Contractor (3TH30) 6.2 1 6.2
9 Digital Ammeter (EM6459) 3.75 1 3.75
10 Digital multifunction meter (EM6400) 3.75 1 3.75

Momentary DC Load per Panel 500


Continous DC Load per Panel 54.7
Total DC Load per Panel 554.7

Client: NMDC Prep By : Suddhaditya Banerjee &


Consultant: Awais Nezam
Project: LADLE FURNACE
Work: DATA FOR BATTERY SIZING
Ckd By : Arunava Basak

Sheet No: 3
DC lOAD CALCULATION

QTY: 1
Sr.No. Description of DC Equipment Rating in Watts QTY Total DC Load (W)
1 Circuit Breaker Type 3AH3 VCB Motor 500 1 500
2 Circuit Breaker Type 3AH3 VCB Closing Coil 140 1 140
3 Circuit Breaker Type 3AH3 VCB Tripping Coil 140 1 140
4 Numerical Protection Relay (7SJ62) 9 1 9
5 Numerical Protection Relay (7SJ61) 9 1 9
6 High Speed Tripping Relay (VAJH13) 150 1 150
7 Indicating LED Lamp 2.5 8 20
8 Annunciator 12 1 12
9 Auxilary Contractor (3TH30) 6.2 1 6.2
10 Digital Ammeter (EM6459) 3.75 1 3.75
11 Digital multifunction meter (EM6400) 3.75 1 3.75

Momentary DC Load per Panel 500


Continous DC Load per Panel 63.7
Total DC Load per Panel 563.7

Client: NMDC Prep By : Suddhaditya Banerjee &


Consultant: Awais Nezam
Project: LADLE FURNACE
Work: DATA FOR BATTERY SIZING
Ckd By : Arunava Basak

Sheet No: 4
33 KV HT SWITCHBOARD LOAD CYCLE CALCULATION

A0 FROM 0 TO A1 AFTER 1 MIN


PANEL DESIGNATION TYPE OF LOAD DURATION IN MINS WATT AMPERE QTY TOTAL LOAD IN AMP 1MIN IN AMP UPTO 60 MIN
CONTINUOUS LOAD 60 84.7 0.39 1 0.39
INCOMER 2.66 0.39
MOMENTARY 1 500 2.27 1 2.27
LINE PT CONTINUOUS LOAD 60 15.75 0.07 1 0.07 0.07 0.07
CONTINUOUS LOAD 60 54.7 0.25 1 0.25
OUTGOING TO FURNACE TRANSFORMER 2.52 0.25
MOMENTARY 1 500 2.27 1 2.27
OUTGOING TO POWER FACTOR COMPENSATION CONTINUOUS LOAD 60 500 2.27 1 2.27
2.56 2.27
EQUIPMENT MOMENTARY 1 63.7 0.29 1 0.29
7.81 2.98
Considering design margin as 10% 8.59 3.28

Client: NMDC Prep By : Suddhaditya Banerjee &


Consultant: Awais Nezam
Project: LADLE
FURNACE
Work: DATA FOR
BATTERY SIZING Ckd By : Arunava Basak

Sheet No: 5