Professional Documents
Culture Documents
2.1 Introduction
In the last chapter we have seen how an e.m.f. gets induced in an alternator. As long
as the alternator terminalsare open i.e. no load is connectedto an alternator,the induced
e.m.f. is same as the voltage availableat the terminals.Thus terminal voltage per phase
Vph and induced e,m.f. per phase Ephare same as long as alternator is on no load.
But when the alternator is loaded, the armature of an alternator carries current. We
know that, any current carrying conductor produces its own flux. Hence on load, armature
of an alternator produces its own flux called armature flux. This flux has significant effect
on the performance of an alternator on load. The terminal voltage Vph no longer remains
same as induced e.m.f. Eph on load conditions. The performance of an alternator on load is
mathematically expressed by a parameter called voltage regulation.
This chapter explains the effect of the armature flux on the performance of an
alternator and various analytical and graphical methods of finding the voltage regulation
of an alternator.
Q/ ph
2
the Atmatun• to be
any two line terminals
24 ArmatureLeakage Reactance
armaturv carries a current. it
its own flux, part of
completes its path through the air
around the conductors itself Such a is
called leakage flux. shown in the
25 Armature Reaction
is to alternator, the armature winding of the alternator
a current Every current carrying conductor produces its own so armature oi
its own flux. vshen carrying a curtvnt, so thetx•ate two fluxes
air gap, due to armature current while second is produced by the field
calkd main flux produced by the armature is called armature aux,
Key : SD —ect armatureflux on the "Nirt flux affecting its oalue and the
ze armature reaction
of armature flux not depends on the magnitude of the eurtx•nt
through armature winding but also depends on the nature of the power factor
to alternator.
Let us study effer-tof nature of the load power factor on the armature tvs•ction.
Armature Reaction & Regulation of Alte
Maintux Flux
Main flux
Armature flux
Arrnaüe
Time
irduced e.mf.
due to
Main flux
Armature 900
- - —Timo
s
Eph Induced e.m.f.
due to
- - e-Time
Eph
Induced e.m.f.
due to
Q/ph
For getting a standard frequency,
alternator is to be driven at
word synchronousused in
specifying the reactance and synchronotus speed • So
impedance is referred to the
and
Electrical Machines • 2-7 Armature Reaction & Regulation of Alternators
working speed of the alternator, Generally
impedance of the winding is constant but in
of altematot, synchronous reactance
depends on the load and its power factor
condition, hence synchronous impedance also
varieg with the load and its power factor
condition•.
ph 'Au E'ph
Vt Load
Xs Ra
ph Vt Load
of an Attemator
2.8 VoRnge Equation to the armature resistance drop and
that due
d € generators,wc e.m.f. available across the load. The
to all
same in case of
called tenninal voltage. The concept is
availabk• made availableto the load due to the various
c m.t.can denoted
avadaNe to the load is called terminal voltage
of thr« alternatorsas all the phases are identical, the equations and the
V phase basis.
arc pres-ed
are following voltage
if the mducede m.f. per phase in the alternator, there
drops tn an altetvtot.
Ra are per phase values.
il TIVdrcv acrossarmature resistance la Ra both la and
u) Thc across reactance la Xs,both la and Xs are per phase values.
Aftersupply-rag drops, the remaining voltage of Eph is available as the terminal
vcåtage
Key Point: Ra is always in phase with la due to a resistive drop while CUrrent
!c lags hv uqtk tesp•ct to drop laxs as it is a drop across purely inductive reactance.
Hence all quanuties can not be added or subtracted algebraically but must be
added or subtracted vectorially considering their individual phases. But we can write a
voltage equatvon its phasor form as,
a a s
laxs
Eph OA=Vph
AB = laRa
j IaR a : BC =
ph
ph AC-1aZs
a
1
o D E
e-zS
OA=V
oeser%edfe
4-4
F. 212
of ee ur«y = 1- So = O, V
So diagam be
Crrsi& OZ. we
As cm = If so sm OYeme
: Tre phasor d.agars drawn a reQzre
But to Qrive reiatxrshp„ pb—r a
much rsne is as a
& Regulation of
Annature Reaction
•q 2.12 for and
Eiecttfc•l
effects of armature
and
doc to
more than
reaction.
powct factot condition,
in gencral fot any 2
p.f. loads
Sign for lagging
p.f. loads
Sign for leading
terminal voltage
Per phase rated
armature current
— Per phase full load
the voltage regulation of an alternator.
define
From discussion,we can now
Regulation of an Alternator
2.10 Voltage of alternator is less than the induce
terminalvoltage and
load
v ph will change from Vph to Eph, if flux
disconrected, la is zero hence there
enf. Epwso if load is load is disconnected,
is because when reaction. This change in
armature flux to cause armature
no voltage drops and no the voltage regulation.
is significant in defining
terminal voltage is defined as the change in
regulation of an alternator
Key Point: The voltage excitation and speed constan
removed, keeping field
terminal mltage when full load is
divided by the rated terminal voltage.
The value of the regulation not only depends on the load current but also
power factorof the load. For lagging and unity p.f. conditions there is always drop
terminal voltagehence regulation values are always positive. While for leading
load conditions,the terminalvoltageincreasesas load current increases. Hence regt
is negativein such cases. The relationshipbetween load current and the terminal VOI
called load characteristicsof an alternator. Such load characteristics for various load
factor conditions are shown in Fig. 2.13.
Machines • Armature Reaction Regulation of Ajtemators
terminal
Loading p, t.
Unity p. f.
Lagging p. f.
6491.47- 6350.853
x 100 2.214%
6350.853
For lagging p.f. loads, regulation is always positive.
2.11 EVA Rating of an Alternator
designed to supply a specific voltage to the Various
n'e alternators are denoted as VL. The power drawn
rated terminal voltage
voltage is called its of specifying rating of an alternator in
dcf*nds its power factor. Hence
the maximum apparent power which it can supply to the
is $00fied in terms of is VLIL, measured in VA (volt
the apparent power
thr« pha.q circuits, rating of an
expressed in kilo volt amperes and is called kVA
is alternator can supply. So for a given rated
IL is rated Kill load current which
alternator, its full load rated current can be decided.
and kVA rating of an
alternator.
Consder kVA, 11 kV, three phase
3.15 A
This is fre rated full load current of an alternator.But load current is same as
armature current So from kVA rating, it is possible to determine full load armatzl
current of an alternator which is important in predicting the full load regulation of
alternator for various power factor conditions.Similarlyif load condition is different
full load, the correspondingarmature current can be determined from its fun
value
Key Point: la at half load= axla at full load. It reducesin the same proportion in
ltd condition reduces.
Hence regulation at any p.f. and at any load condition can be determined.
Example 2.2 : A 1200kVA, 6600V, 3 phasestar connectedalternatorhas its
resistanceas 0.25Q per phaseand its synchronous
reactanceas 5 Q per phase. Calculatt
regulation if it deliversa full load at i) 0.8 lagging
and ii) 0.8 leading p.f.
Solution :kVA 1200,h = 6600V, 0.250, Xs=5Q
Now kVA = ILxlo -3 i.e. 1200 =
IL 104.97 A
laph = 104.97A (Full
load current)
...As star
ph = = 60
- 3810.512v
Electrical Machines - 2-15 Armature Reaction & Regulation of Alternators
i) For 0.8 lagging p.f. load
(Eph ) 2 = (Vph Ra + (Vph sin
(Eph ) 2 = (3810.512xo.8+104.97xo.25) 2
Eph = 4166.06v
Eph-V 4166.06-3810.512
% Reg x 100 *100
ph 3810.512
= +9.33 %
(Eph
Eph 3543.47 v
Eph-Vph 3543.47 - 3810.512
% Reg x 100=
3810.512
= - 7.00%
The regulation is negative for leading p.f. loads.
TPST switch
Mechanical
Pomerover # Three
phase
load
armature
Rheostat A If
winding
of altemator
Supply
Fig. 2.14 Circuit diagram
for direct loading
Procedure : test on alternator
alternatoris first
prime mover. driven at its
synchronous speed NS by
means of a
Now
Eph
By giving dc.
supply to the field
flux so that rated
voltageis availablewindinb the field current
voltmeter connected across the is adjusted to adjust the
switch across the lines The terminals. This
load is then load is then be the
full load condition increased so that ammeter connected by meams
of the alternator. of a TPST
reads rated
Again adjust value of current. This is
the voltage
to its rated value
by means
älectrical Machines •Il 2-17 Armature Reaction & Regulation of Alternators
of field excitation using a rheostat connected. throw off the entire load by opcrvng
the TI'ST switch, without changing the speed and the field excitation. (%serv€ the
voltmeter reading. As load is thrown off, there is no armature current and ass«idtcd
drops.So the voltmeter reading in this situation indicates the value of internally induced
c m.f.called no load terminal voltage. Convert both the reading to phage values. The rated
voltageon full load is Vph while reading when load is thrown off is Eph.So by using the
formula,
Eph -V ph
% Reg x 100
ph
the full load regulation of the alternator can be determined. The value of the
regulationobtained by this method is accurate as a particular load at required p.f. is
actuallyconnectedto the alternator to note down the readings.
Key Point : But for high capacity alternators, that muchfull load can not be simulated or
directly connected to the alternator. Hence method is restricted only for small capacity
alternators.
Eph Vph
% Reg x 100
ph
Voc v A Isc
Field
of alternator
Rheostat
Supply
Fig. 2.15 Circuit
diagramfor open
2.14.1 Open Circuit Test circuit and short circuit
test on alternator
Procedure to conduct this
test is as
follows :
i) start the prime
moverand adjust
the speed to the
ii) Keeping synchronous speed of the
in the field
circuitmaximum,
switch on the d.c.
supply-
Electrical Machines - Il 2-19 Armature Reaction & Regulation of Alternators
ili) the T.P.S.T.switch in the armature circuit is kept open.
iv)With the help of rheostat, field current is varied from its minimumvalue to
the rated value. Due to this, flux increases, increasing the induced e.m.f. Hence
voltmeter reading, which is measuring line value of open circuit voltage increases.
For various values of field current, voltmeter readings are observed.
The observations for open circuit test are tabulated as below :
(Voc)phvolts
(la)sc
in amp
s.c.c.
Full load.
circuit •
tot
Short circuit armature current
per phase (Inc) A
I krown,whrh can
Qf. be be observed on the
under ammeter. But internally
is voltaw across short circuit conditm. voltmeter con—
E short circuit. To
dnvtng determine Z, it is necessary
ZY
Electrical Machines • Il 2-21 Armature Reaction & Regulation of Alternators
Now internally induced e.m.f. is proportional to the
flux i.e. field current If.
Eph
From e.m.f. equation
So if the terminals of the alternator are opened
without disturbing If which was present at the time
of short circuited condition, internally induced
e.m.f. will remain same as Eph. But now current
Open
Eph 'N' circuit will be zero. Under this condition equivalent circuit
will become as shown in the Fig. 2.18.
It is clear now from the equivalent circuit that
as la — () the voltmeter reading (Voc)phwill be
Fig. 2.18 equal to internally induced e.m.f. (Eph).
Eph (Voc)phon open circuit
Thisis what we are interested in obtaining to calculatevalue of 70s.So expressionfor
Zs can be modified as,
(Voc
(1asc ph
for sameIf
OE sameIf OA
•-亂龕“fifi%
EEü•r..Ä • 2.23 Atr•ture &
z 14S Advantages and Limitations of Synchronous impedance Method
advantageof thu valueof
can calculated. f ferre regulatvn of tke
impdarce Z. for ny
alternatorat any
Load can determired. Actual "d reed re to
and methcx.ican u•ædfor very hi-'t capacity alternators.
man hmitatvm of this method is that the rrtefY•cÄ large vaEz
reactarre. This Jeads to high values of percatfzge regulatirn than utual
re.uits Hence this is caned pessimistic method.
Example 2.4 •w The open circuit and short circuit test is star
ccmåucted m a 3 pug,
866V, IT) kVA alternator.
amnected,
TheOC test results are,
I Amp 1 2 3 4 5 6 7
Voc line Volts 173 310 485 605 728 790 840
6667 A
1 = IL = 6667 A As star connected alternator
For calculationof Z, on full load, it is necessary to plot O.C.C.and S.C.C.to the scale.
Note : If for same value of If, both I and V can be obtained from the table itself,
graphneed not be plotted. In some problems, the values of V and I for same If are
directlygiven, in that case too, the graph need not be plotted.
In this problem, I = 25 A for If 1 A.
Electrical Mochine• 2-24 ArmatureReaction & Regulation
of Alter
SCC
oc.CF
300
FromS.C.C
Forla -66.67 A, 2.4m
FromO.C.C
For If = 2.4A, (V oc) = 240V
If in amp
Fig. 2.19
but we want to calculate
Zs for I asc= its full load value which
required to be plotted. is 66.67 A. So
graph!
For O.CC the
dividing each value by values of open circuit
O. voltage are converted to
phase b
From S.C.C.
= 66.67A, 2.4 A
From O.CC.
If - 2.4 A, (V
)ph = 240 V
From the graph,
ZEfor full load is,
oc ph
asc 240
forsame
excitation 66.67 For = 3.6 Q/ phase
If -2.4 A
Ra 0.15 Q/ phase
3.597Q/ phase
ph F.L 500 v,
cos = 0.8 and
sin • ().6 lagging
p.f.
Electric"Mochit»e•
2-25 Armature Ruction A Regulation of
fid) toad, 08 lagging p f. condition can be calculated
(Vt. cose Ra) 2 (Vph Sino
677.86
v
Eph -vph 677.86-500
00, Regulation = x 100 x 100
ph
= + 35.57%
armature current of 12.5 A. The armature resistance measured between two lines s
ohms.Find the regulation for the current of 10 amps at 0.8 lagging and 0.8 leading
pourr factors.
(1asc ph
for sameIf
(Voc)ph ¯ — v
132.79
132 79
' 10.623Q/ph
12.5
S
2 (10.623)2 -(0.9) 2 10.585Q/ph
Nowregulation is asked for = 10 A
Note: The value of Zs is calculated for la = 12.5A and not at la = 10 A, It will be
differentfor I = 10 A. But in this problem the test results are not given hence it is not
a