A Method For Predicting The Performance of Steam Turbine-Generators 16,500 KW and Larger
A Method For Predicting The Performance of Steam Turbine-Generators 16,500 KW and Larger
EXHAUST LOSS
LAST ROW B L A D E HEIGHT 4 3 I N .
DOWNWARD EXHAUST
COMPARISON OF H E H B T S C H W E I L K R - B A R T L E T T ( H B )
VERSUS
S P E N C E R , COTTON k CANNON DATA (S.C.C.)
AT
MADE FOR 1 0 £ M O I S T U R E
EXPANSION L I N E END P O I N T
s.c.c
200 300 t00 500 600 700 80.0 900 1000 1100 1200 1300 140O
ANNULUS VELOCITY F T PER SEC
Fig. 3 2
Messrs. Davids and Heinze state that the difference in annulus In the range of unit capabilities studied by the authors' com-
velocity level between 1300 and 1400 ft/sec must be a hood loss. pany, it has not been found desirable to design high-pressure
Actually energy applied to the reheat turbine which results in sections with all the stages double flowed. However, the ef-
change in annulus velocity from sonic to a larger value does not ficiency of such sections would be determined on the basis of two
increase kw output. Whether you call this an increase in hood parallel flow sections (N = 2). High-pressure sections having a
loss or leaving loss is a matter of definition. double flow governing stage with the remainder of the stages
Mr. Schwartz has kindly pointed out that in order to determine single flowed have been built and tested. Negligible efficiency
efficiencies using these methods, certain turbine design parame- losses have been found to result from such double flowing of the
governing stage and the efficiency is determined on the basis of an
ters such as governing stage pitch diameter and number of con-
all single flow section (N = 1).
trol valves must be specified. The determination of these
Under the approach of rating conductor-cooled generators at
parameters are the result of many compromises between eco-
their maximum hydrogen pressure rating, the mechanical and
nomic, mechanical and thermodynamic design, and operating re-
generator losses (Figs. 19 through 23) should be determined at an
quirement factors by the turbine designer. In general, these equivalent capability at 15 psi less than maximum hydrogen pres-
factors have only a minor effect on heat rate. Typical governing sure. For generators built by the authors' company, the equiva-
stage parameters for reheat turbines as built by the authors' lent capability is equal to the maximum hydrogen pressure capa-
company are provided in Table 5. bility divided by 1.10.