A Brief Story of Construction Project


"If we can't explain it simply, we don't understand it well enough"

Flame Retardant and Fire Resistance Test

I was just surprised when I reviewed a flame retardant and fire resistance FAT certificate of the cable I purchased I got
certificate with the test date before we placed on Purchased Order. The cables PO was issued on April 2013, the FAT of
the cables was held on March 2013. They did the FAT before we purchased. What a shame Indonesian Cable
Manufacturer. However we consider it just only date type error then the vendor re-submit their flame retardant and fire
resistance cable test certificate with understandable date on 1st of August 2013. The vendor was just simply change
the date in a make sense time. Reviewed the new submitted certificate with a new ‘make sense’ FAT date drove me to
see the type of cables have been tested. Shockingly the type of cables on the flame retardant and fire resistance test
certificates are not the cables what we are being purchased. It’s totally different description, core & pair, and size
between cables on the PO and the FAT certificates. It means the certificate is a fake certificate. They just grabbed it
from old certificate and submitted to us  This a shame for me as Indonesian.

In the name of local content we purchased cables on the Eastern of Jakarta but they are trying to cheat us on the FAT
report certificate that I totally doubt that they did it. I am an engineer, not QA /QC who should witness it. This cable
manufacturer shall be totally black listed on the oil and gas industries. I could not mention the cable manufacturer
name on this blog, but I could give you the name of the vendor through personal channel.

What is Flame Retardant Test and What is Fire Resistance Test in accordance to IEC? At least we get a knowledge for
every case we are facing every day.

Kita sudah memiliki rule of thumb perbedaan penggunaan kabel flame retardant dan fire resistant di artikel blog saya
sebelumnya topik instrument cable. Fire resistant kabel digunakan untuk kritikal safety instrument seperti fire & gas.
Flame retardant kabel digunakan untuk non-kritikal atau normal monitoring atau regulatory kontrol BPCS atau PCS.
Sedangkan kabel untuk process safety (ke transmitter Hi-Hi/Lo-Lo atau ke SDV) harus dipilah-pilah berdasarkan tingkat
ke kritisannya. Contohnya SDV yang selalu fail safe (artinya kalau kabelnya terbakarpun SDV akan otomatis nutup dan
safe) tidak terlalu perlu untuk diberikan fire resistant kabel. Meskipun di beberapa proyek yang saya kerjakan
menggunakan fire resistant untuk kabel ke solenoidnya SDV. Flame Retardant menghambat propagasi api ketika terjadi
kebakaran. Fire Resistant anti api dan tidak terbakar konduktornya karena terdapat lapisan yang namanya MGT (mica
glass tape) yang konon tahan api (note: sampai batas suhu tertentu seharusnya. Karena kalau dibakar api neraka akan
habis juga kayaknya ^_^)

Bagaimana membuktikan bahwa kabel instrument yang dibeli berrated flame retardant atau fire resistance? Harus
dilakukan pengujian.
Pengujian fire resistance mengacu pada IEC60331. Ambil sepotong kabel sepanjang 1.2 meter, letakkan di atas burner
dan alirkan arus pada kabel tersebut dengan memberikan tegangan sesuai dengan voltage rating kabel tersebut.
Nyalakan api pada burner dan bakar kabel selama 3 jam dengan arus listrik yang mengalir pada kabel tersebut. Setelah
3 jam matikan api dan putuskan arus yang mengalir. Dan biarkan dingin selama 12 jam. Setelah 12 jam alirkan lagi arus
listrik melalui kabel tersebut dan kabel tersebut harus tidak menunjukkan penurunan performance jika dibandingkan
dengan sebelum dibakar.

Flame Retardant test dilakukan dengan membakar sekumpulan kabel pada posisi vertikal berdasarkan IEC-60332.
 Maksimum propagasi kebakaran alias yang gosong yang diukur dari letak burnernya. Maksimumnya adalah 2.5 meter.
Silahkan dibuka IEC-60332. Waktu saya untuk menulis semakin sempit.

Batam, 17 Mar 2014

Nova Kurniawan

Share this:

 Twitter  Facebook  LinkedIn  WhatsApp  Telegram

Like

Be the first to like this.

Related

Feedforward Loop Control It is a Head; Go A Head Instrument Thread Connection


In "Engineering" In "Engineering" In "Engineering"

August 12, 2013  7 Replies

« Previous Next »

Leave a Reply
Your email address will not be published. Required fields are marked *

Comment
Name

*
Email

*
Website

Post Comment

Notify me of new comments via email.

Notify me of new posts via email.

juare97 on August 13, 2013 at 1:42 pm

weleh…. weleh …. cak Nova dikadalin …


tidak mempan lah …. parah juga tuh vendor nov …
biasanya project beli kabel dari luar nov … sekarang sudah mulai beli dari dalam kah?

 Like
 Reply

novakurniawan on August 14, 2013 at 4:14 am

Iya, projek dalam negeri…. local content-nya harus diperbanyak..

 Like
 Reply

juare97 on August 31, 2013 at 2:09 am

wah kudu di black list tuh biar kapok ..

 Like
 Reply

Prigas Wibawa on August 28, 2013 at 6:13 am

Pak Nova,
Kalau begitu, silahkan beli kabel Flame Retardant ataupun Fire Resistant ke PT. JJ-Lapp Cable SMI.
Insya Alloh, FAT bisa dilakukan dengan kesaksian.
Hehehehe….

Flame Retardant standard : IEC 60332-1-2, IEC 60332-3-22 (Cat. A), IEC 60332-3-22 (Cat. B), IEC 60332-3-22 (Cat.
C)

Fire Resistant standard : IEC 60331, BS 6387 CWZ, AS/NZS 3013

Factory kami di Tangerang,


Bisa produksi kabel Instrumen sesuai category flame retardant di atas, sedangkan untuk Fire Resistant,
certificated ke BS 6387 CWZ category.

Wassalam,
Prigas Wibawa
(Technical Sales Executive)
PT. JJ-Lapp Cable SMI
Marketing Office.
Jl. Buncit Raya no. 22
Gedung Graha Inti Fauzi,
Lantai 7.
Jakarta Selatan 12510
Telp. : 021 – 2753 7051
Fax. : 021 – 2753 7052

 Like
 Reply

novakurniawan on September 14, 2013 at 11:22 pm

hehe noted mas Prigas Wibawa

 Like
 Reply

yurikarahma@gmail.com on November 19, 2013 at 8:02 am

pengujian kabel bisa di PT.qualis indonesia


Jl. Pajajaran No. 17 Desa Gandasari-Jatiuwung Tangerang Indonesia
tlp : (021) 55652583
fax : (021) 55652489

 Like
 Reply

syamsu on March 18, 2016 at 7:42 am


Materinya bagus, dan analisisnya tajam. Sangat membantu dilapanagan mas Nova

 Like
 Reply

Top Posts

Temperature; Dew Point & Saturation


SDV; Shutdown Valve
Ketika Arus Bocor
Control Valve Calibration
Instrument 24 Volt DC Terbalik Polaritynya (+) dan (-), maka akibatnya adalah?
Instrumentation and Automation in Oil and Gas Industries - Offshore
Instrument Clean Earth (IE) dan Protective Dirty Earth (PE), Mengapa harus berpisah?
Rangkaian Sederhana 4-20 mA, Tapi Malah Aneh
Pressure Test Vs Leak Test
Hydraulic Cleaning Criteria; NAS 1638 & ISO 4406

Recent Comments

novakurniawan on Cable Gland Accessories

khoirul on Cable Gland Accessories

novakurniawan on “Normally” pada…

Lovenri on “Normally” pada…

Ketika Valve Nge-Jam… on Hydraulic Cleaning Criteria; N…

Pages

Store
Story Teller

Recent Posts

“Normally” pada “E” Versus “Normally” pada “I”


Ketika Valve Nge-Jam
Cathodic Protection; Sacrificial Anode
Ketika Semua Tergantung Spesifikasi
Galvanic Corrosion; Dissimilar Metals