You are on page 1of 6

Design calculation sheet

Project no: S06050 Date: 27/5/2008 Sheet No. 1 of 5 Compute ASF


Subject: WSFU for Cold Water Supply -Plaza - Toilets Checked ASF
Makkah Hills Approved MA

(See ASPE Handbook - Volume (3) - Chapter 2)


(See PDI-WH 201- Fixture Unit Listing)

Load values , in water supply


Type of Supply GPM GPH
Fixture Occupancy fixture units (WSFU)
control
CW HW Total CW HW HW
Hose bib Public Faucet 2.0 --- 2.0 --- ---
Water closet Pubic Flush tank 5.0 --- 2.0 --- ---
Water closet Private Flush tank 3.0 --- 2.0 --- ---
Water closet Pubic Flush valve 10.0 --- 2.0 --- ---
Water closet Private Flush valve 6.0 --- 2.0 --- ---
Lavatory Public Faucet 1.5 1.5 2.0 1.5 1.5 6
Lavatory Private Faucet 0.75 0.75 1.0 1.0 1.0 2
Shower head Public Mixing valve 3.0 3.0 4.0 1.5 3.0 75
Shower head Private Mixing valve 1.5 1.5 2.0 1.5 3.0 75
Bathtub Private Faucet 3.0 3.0 4.0 4.5 4.5 20
Bidet Private Faucet 1.5 1.5 2.0 1.5 1.5 2
Pantry Public Faucet 3.0 3.0 4.0 4.5 4.5 10
Kitchen Sink Public Faucet 3.0 3.0 4.0 4.5 4.5 20
Mop Sink Public Faucet 3.0 3.0 4.0 4.5 4.5 20
Janitor Sink Public Faucet 3.0 3.0 4.0 4.5 4.5 20
Utility Sink Public Faucet 2.5 2.5 3.0 4.5 4.5 15
Drinking Fountain Public Faucet 1.0 --- 1.0 --- ---
Design calculation sheet
Project no: S06050 Date: 27/5/2008 Sheet No. 2 of 5 Computed by: ASF
Subject: WSFU for Cold Water Supply -Plaza - Toilets Checked by: ASF
Makkah Hills Approved by: MA

Fixture WSFU Qty Total

Hose bib 2.0 10 20


FT WC - Public 5.0 0
FT WC - Private 3.0 0
FV WC - Public 10.0 0
FV WC - Private 6.0 0
Lavatory - Public 1.5 0
Lavatory - Private 0.75 0
Shower head - Public 3.0 0
Shower head - Private 1.5 0
Bathtub 3.0 0
Bidet 1.5 0
Pantry 3.0 0
Kitchen Sink 3.0 0
Mop Sink 3.0 0
Janitor Sink 3.0 0
Utility Sink 2.5 0
Drinking Fountain 1.0 0

System Total = 20.0 WSFU

Flow Demand = 89.0 gpm (See Table B.5.4 NSPC 2003)


= 5.6 L/s
Design calculation sheet
Project no: S06050 Date: 27/5/2008 Sheet No. 3 of 5 Computed by: ASF
Subject: Booster pump Head Calculation - Plaza- Toilets Checked by: ASF
Makkah Hills Approved by: MA

(See Practical Plumbing design handbook & NSPC 2003)

1- Design Criteria
Sizing table based on Velocity Limitation
Copper Water tube, type (K)
Max. Frict 2 psi/100ft, Velocity = 5 ft/s
pipe size, in pipe size, mm Flow, gpm
1/2'' 15 2.1
3/4'' 22 5.5
1'' 28 12.5
1 1/4'' 35 20.0
1 1/2'' 42 28.0
2'' 54 50.0
2 1/2'' 67 75.0
3'' 76 150.0
4'' 108 195.0
5'' 133 285.0
6'' 159 420.0

1- Maximum velocity suggested for Copper pipes is 5 ft/s (See 2006 ASPE Handbook - Volume 2 - Ch.5)
2- WSFU demand converting into gpm. (See 2003 NSPC Handbook - Table B.5.4)
3- Friction losses depend on the following data.

Sizing table based on Velocity Limitation


Copper Water tube, type (K)
Max. Frict 2 psi/100ft, Velocity = 5 ft/s
pipe size, in pipe size, mm Frict, psi/100ft
1/2'' 15 5.0
3/4'' 22 5.0
1'' 28 5.0
1 1/4'' 35 4.0
1 1/2'' 42 3.0
2'' 54 2.2
2 1/2'' 67 1.8
3'' 76 1.5
4'' 108 0.95
5'' 133 0.75
6'' 159 0.6
Design calculation sheet
Project no: S06050 Date: 27/5/2008 Sheet No. 4 of 5 Computed by: ASF
Subject: Booster pump Head Calculation - Plaza - Toilets Checked by: ASF
Makkah Hills Approved by: MA

2- Head pump Calculations:


A- Static Head:
Hs = 11 m

B- Residual Pressure:
Hr = 8 Psi (see Table 5-21 - 2006 ASPE Handbook)
= 5.41 m (Hose Bib)

C- Friciton losses in Pipe Sizes :

Length of Pipe size Ф159 mm = 0 m 0.0 ft 0.60 psi/100ft


Length of Pipe size Ф133 mm = 0 m 0.0 ft 0.75 psi/100ft
Length of Pipe size Ф108 mm = 0 m 0.0 ft 0.95 psi/100ft
Length of Pipe size Ф76 mm = 11 m 36.1 ft 1.50 psi/100ft
Length of Pipe size Ф67 mm = 0 m 0.0 ft 1.80 psi/100ft
Length of Pipe size Ф54 mm = 0 m 0.0 ft 2.20 psi/100ft
Length of Pipe size Ф42 mm = 0 m 0.0 ft 3.00 psi/100ft
Length of Pipe size Ф35 mm = 0 m 0.0 ft 4.00 psi/100ft
Length of Pipe size Ф28 mm = 0 m 0.0 ft 5.00 psi/100ft
Length of Pipe size Ф22 mm = 0 m 0.0 ft 5.00 psi/100ft
Length of Pipe size Ф15 mm = 6 m 19.7 ft 5.00 psi/100ft

Losses in pipes Ф159 mm = 0.00 psi


Losses in pipes Ф133 mm = 0.00 psi
Losses in pipes Ф108 mm = 0.00 psi
Losses in pipes Ф76 mm = 0.54 psi
Losses in pipes Ф67 mm = 0.00 psi
Losses in pipes Ф54 mm = 0.00 psi
Losses in pipes Ф42 mm = 0.00 psi
Losses in pipes Ф35 mm = 0.00 psi
Losses in pipes Ф28 mm = 0.00 psi
Losses in pipes Ф22 mm = 0.00 psi
Losses in pipes Ф15 mm = 0.98 psi
Losses in fittings 20% = 1.8 psi

Total Losses in pipes = 3.3 psi


= 2.25 m

Losses in valves : Gate = 6.4 ft


= 1.95 m

D- Safety factor: = 10%


= 1.87 m

Total Pump Head = 22.5 m


= 2.2 bar
Design calculation sheet
Project no: S06050 Date: 27/5/2008 Sheet No. 5 of 5 Computed by: ASF
Subject: Booster Pump Power & Selection - Plaza - Toilets Checked by: ASF
Makkah Hills Approved by: MA

1- Demand of the System = 5.6 l/s

2- Head of the System = 22.48 m

3- Booster Pump Power Calculations:

Power = g x Q x H
pump h x motor h

= 9810 x 0.0056 x 22.48


0.6 x 0.75

= 2744 watt

= 2.7 Kw

= 3.7 Hp

4- Selection from Catalog:

Selection = Grundfos
Type = Booster Pump
Model No. = Hydro 2000 ME 2 CRE15-2

No. of Pumps = 2 working


1 stand-by

Power of each pump = 3 kw

Total Power = 6 kw

pump h = 70.2 %

motor h = 80.3 %

Pressure tank Volume = 50 liters

You might also like