TEST REPORT ISSUED TO : Office of the EE, EHV (O&M) Division, Old Power House Area, Ballarshah - 442 901
REPORT # : TR18093101 DATE 26-Sep-2018
Transformer Details
Type : Power Transformer Ratio : 220/33 kV Sampling Point : Bottom (Main Tank)
Make : VIJAI ELECTRICALS Rating : 25 MVA Sampling Date : Tuesday, September 25, 2018
Serial # : 90075A01 Oil Temp : NA °C Sampling Location : TR-II, 25 MVA, 220 kV S/S BALLARSHAH
Mfg. Year : 2010 Oil Type : Service Last filtration done on : ---
Normal Warning
Key Key
Normal DGA indicates possible arcing due to Normal
Oil in normal condition; continue normal sampling Warning Acetylene. Resample again in 3 months for Warning
Critical trend analysis. Critical
35000
DGA Comparision
30000
25000
20000
Value (ppm)
15000
10000
5000
0
H2 O2 N2 CH4 CO CO2 C2H4 C2H6 C2H2 TDCG
27-May-18 22 10214 26054 4 101 1534 1 1 0 129
26-Sep-18 33 11314 33215 5 91 2042 4 1 7 141
Note 1. This report relates only to the particular sample received for testing in good condition at PE-LAB
2. This report can not be reproduced in part under any cirumstances.
3. Publication of this report requires prior permission in writing from Director, PE-LAB
4. Only the tests asked for by the customer have been carried out.
PREPARED BY APPROVED BY
(Technical Manager) (Technical Director)
(Mr. C.V.Patil) (Mr. S.M.Tajne)
PMF-14, Rev.01, w.e.f. 25.01.2018 Early Detection , Prevention and Care SHEET 1 OF 3
Transformer Insulating Oil Condition Reporting of Physical, Chemical & Electrical Parameters
•IS 1866:2017 (IEC 60422:2013) - Mineral Insulating Oils in Electrical Equipment Supervision and Maintenance Guidance (Fourth Revision)
• The value of Water Content is given at transformer operating temperature
Note Test Conditions for Breakdown Voltage Test Conditions for Resistivity & Dielectric Dissipation Factor
• Type of electrodes used : Spherical • Type of cell used : SS Three Terminal Oil Cell (IS 6103:1971, IS 6262:1971-Fig. 4)
• Gap between two Electrodes : 2.5 mm • Average voltage gradient in the sample while under test (rms) : 250 V/mm
• Frequency of applied voltage : 49.9 Hz • Frequency of applied voltage : 49.9 Hz
• Oil Temperature during testing : 26.4 °C • Temperature of room during test : 25 °C
Test Conditions for Flash Point • Humidity of room during test : 47 % RH
•The ambient barometric pressure in the vicinity of the • Method of Measurement - Section 1 of IS 6103:1971 & IS 6262:1971
apparatus : 947 Hpa
PREPARED BY APPROVED BY
(Technical Manager) (Technical Director)
(Mr. C.V.Patil) (Mr. S.M.Tajne)
PMF-14, Rev.01, w.e.f. 25.01.2018 Early Detection , Prevention and Care SHEET 2 OF 3
Tansformer Internal Condition Reporting of Dissolved Gas Analysis
PREPARED BY APPROVED BY
(Technical Manager) (Technical Director)
(Mr. C.V.Patil) (Mr. S.M.Tajne)
PMF-14, Rev.01,
Rev.01,w.e.f.
w.e.f.25.01.2018
25.01.2018 Early Detection
Detection , Prevention
Prevention and Care SHEET 33 OF
OF 33