GAS FIRED POWER PLANT FOR

IPP 2x35MW TANJUNG UNCANG


BATAM

SUBJECT : HIGH VOLTAGE TEST DATA (DIELECTRIC STRENGTH TEST)


Owner : PT ENERGI LISTRIK BATAM Temperature :______33˚C_____
Category : Test and Pre-Commissioning (MV Cell 11,5kV) Weather :_____Bright___
Location : MV CELL 1A Date : 19 January 15
Reference Drawing : TUB001-ELC-DWG-013

INSTALLED FROM : TO : CABLE TAG :


Station Service Transformer 1A 1A SST1 P002
1A MV CELL, Outgoing to 1A SST (HV Side) Cable Type : N2XSEY, 3c - 50
MEGGER TEST INSTRUMENT TEST NAME :
VOLTAGE : 5000 Volt (DC) Insulation Test Mega Ohm Meter Model : KEW3123
Merk : Kyoritsu

RESULT (G Ohm) TIME (Sec.) CONCLUSION


SERVICE
BEFORE AFTER BEFORE AFTER (ACCEPTED/REJECTED)

R-S ~ ~ 60 60 ACCEPTED
R-T ~ ~ 60 60 ACCEPTED
S-T ~ ~ 60 60 ACCEPTED
R - GROUND ~ ~ 60 60 ACCEPTED
S - GROUND ~ ~ 60 60 ACCEPTED
T - GROUND ~ ~ 60 60 ACCEPTED
Criteria : Min ≥ 1000 Ω/V
TYPE : Hipot 800 PL Series VOLTAGE TEST :
RATE VOLTAGE : 20 kV, 40, 80 kV DC :___28kV____
MANUFACTURER : Hipotronics AC : N/A

HIGH VOLTAGE TEST INSTRUMENT TEST NAME : SWITCHGEAR 6,6 kV

CONCLUSION
SERVICE VOLTAGE (kV) TIME (MIN) LEAKAGE (μA) (ACCEPTED/REJECTED

R-S 28 15 8.00 ACCEPTED


R-T 28 15 8.00 ACCEPTED
S-T 28 15 9.00 ACCEPTED
R,S,T - GROUND 28 15 0.10 ACCEPTED

REMARKS :

CONDUCTED BY, WITNESSED BY,

PT DALLE ENGINEERING PT ENERGI LISTRIK BATAM JASER


CONSTRUCTION

Print Name Very S

Signature

Date 19-Jan-15
GAS FIRED POWER PLANT FOR
IPP 2x35MW TANJUNG UNCANG
BATAM

SUBJECT : HIGH VOLTAGE TEST DATA (DIELECTRIC STRENGTH TEST)


Owner : PT ENERGI LISTRIK BATAM Temperature :______33˚C_____
Category : Test and Pre-Commissioning (MV Cell 11,5kV) Weather :_____Bright___
Location : MV CELL 1B Date : 19 January 15
Reference Drawing : TUB001-ELC-DWG-013

INSTALLED FROM : TO : CABLE TAG :


Station Service Transformer 1B 1B SST1 P002
1B MV CELL, Outgoing to 1B SST (HV Side) Cable Type : N2XSEY, 3c - 50
MEGGER TEST INSTRUMENT TEST NAME :
VOLTAGE : 5000 Volt (DC) Insulation Test Mega Ohm Meter Model : KEW3123
Merk : Kyoritsu

RESULT (G Ohm) TIME (Sec.) CONCLUSION


SERVICE
BEFORE AFTER BEFORE AFTER (ACCEPTED/REJECTED

R-S ~ ~ 60 60 ACCEPTED
R-T ~ ~ 60 60 ACCEPTED
S-T ~ ~ 60 60 ACCEPTED
R - GROUND ~ ~ 60 60 ACCEPTED
S - GROUND ~ ~ 60 60 ACCEPTED
T - GROUND ~ ~ 60 60 ACCEPTED
Criteria : Min ≥ 1000 Ω/V
TYPE : Hipot 800 PL Series VOLTAGE TEST :
RATE VOLTAGE : 20 kV, 40, 80 kV DC :___28kV____
MANUFACTURER : Hipotronics AC : N/A

HIGH VOLTAGE TEST INSTRUMENT TEST NAME : SWITCHGEAR 6,6 kV

CONCLUSION
SERVICE VOLTAGE (kV) TIME (MIN) LEAKAGE (μA) (ACCEPTED/REJECTED

R-S 28 15 21.00 ACCEPTED


R-T 28 15 10.00 ACCEPTED
S-T 28 15 16.00 ACCEPTED
R,S,T - GROUND 28 15 0.025 ACCEPTED

REMARKS :

CONDUCTED BY, WITNESSED BY,

PT DALLE ENGINEERING PT ENERGI LISTRIK BATAM JASER


CONSTRUCTION

Print Name Very S

Signature

Date 19-Jan-15
GAS FIRED POWER PLANT FOR
IPP 2x35MW TANJUNG UNCANG
BATAM

SUBJECT : HIGH VOLTAGE TEST DATA (DIELECTRIC STRENGTH TEST)


Owner : PT ENERGI LISTRIK BATAM Temperature :______33˚C_____
Category : Test and Pre-Commissioning (MV Cell 11,5kV) Weather :_____Bright___
Location : MV CELL 1A Date : 19 January 15
Reference Drawing : TUB001-ELC-DWG-013

INSTALLED FROM : TO : CABLE TAG :


To GeneraTor Transformer 1A, LV, 1A T P001 R1, 1A T P001 S1 & 1A T P001 T1
11,5kV MV CELL 1A Generator Transformer 1A Cable Type : N2XSY, 1C - 400
MEGGER TEST INSTRUMENT TEST NAME :
VOLTAGE : 5000 Volt (DC) Insulation Test Mega Ohm Meter Model : KEW3123
Merk : Kyoritsu

RESULT (G Ohm) TIME (Sec.) CONCLUSION


SERVICE
BEFORE AFTER BEFORE AFTER (ACCEPTED/REJECTED

R1 - S1 200 ~ 60 60 ACCEPTED
R1 - T1 200 ~ 60 60 ACCEPTED
S1 - T1 ~ ~ 60 60 ACCEPTED
R1 - GROUND ~ ~ 60 60 ACCEPTED
S1 - GROUND ~ ~ 60 60 ACCEPTED
T1 - GROUND ~ ~ 60 60 ACCEPTED
Criteria : Min ≥ 1000 Ω/V
TYPE : Hipot 800 PL Series VOLTAGE TEST :
RATE VOLTAGE : 20 kV, 40, 80 kV DC :___28kV____
MANUFACTURER : Hipotronics AC : N/A

HIGH VOLTAGE TEST INSTRUMENT TEST NAME : SWITCHGEAR 6,6 kV

CONCLUSION
SERVICE VOLTAGE (kV) TIME (MIN) LEAKAGE (μA) (ACCEPTED/REJECTED

R1 - S1 28 15 0.100 ACCEPTED
R1 - T1 28 15 0.100 ACCEPTED
S1 - T1 28 15 2.100 ACCEPTED
R1,S1,T1 - GROUND 28 15 0.025 ACCEPTED

REMARKS :

CONDUCTED BY, WITNESSED BY,

PT DALLE ENGINEERING PT ENERGI LISTRIK BATAM JASER


CONSTRUCTION

Print Name Very S

Signature

Date 19-Jan-15
GAS FIRED POWER PLANT FOR
IPP 2x35MW TANJUNG UNCANG
BATAM

SUBJECT : HIGH VOLTAGE TEST DATA (DIELECTRIC STRENGTH TEST)


Owner : PT ENERGI LISTRIK BATAM Temperature :______33˚C_____
Category : Test and Pre-Commissioning (MV Cell 11,5kV) Weather :_____Bright___
Location : MV CELL 1A Date : 19 January 15
Reference Drawing : TUB001-ELC-DWG-013

INSTALLED FROM : TO : CABLE TAG :


To GeneraTor Transformer 1A, LV, 1A T P001 R2, 1A T P001 S2 & 1A T P001 T2
11,5kV MV CELL 1A Generator Transformer 1A Cable Type : N2XSY, 1C - 400
MEGGER TEST INSTRUMENT TEST NAME :
VOLTAGE : 5000 Volt (DC) Insulation Test Mega Ohm Meter Model : KEW3123
Merk : Kyoritsu

RESULT (G Ohm) TIME (Sec.) CONCLUSION


SERVICE
BEFORE AFTER BEFORE AFTER (ACCEPTED/REJECTED

R2 - S2 ~ ~ 60 60 ACCEPTED
R2 - T2 ~ ~ 60 60 ACCEPTED
S2 - T2 ~ ~ 60 60 ACCEPTED
R2 - GROUND ~ ~ 60 60 ACCEPTED
S2 - GROUND ~ ~ 60 60 ACCEPTED
T2 - GROUND ~ ~ 60 60 ACCEPTED
Criteria : Min ≥ 1000 Ω/V
TYPE : Hipot 800 PL Series VOLTAGE TEST :
RATE VOLTAGE : 20 kV, 40, 80 kV DC :___28kV____
MANUFACTURER : Hipotronics AC : N/A

HIGH VOLTAGE TEST INSTRUMENT TEST NAME : SWITCHGEAR 6,6 kV

CONCLUSION
SERVICE VOLTAGE (kV) TIME (MIN) LEAKAGE (μA) (ACCEPTED/REJECTED

R2 - S2 28 15 0.800 ACCEPTED
R2 - T2 28 15 2.100 ACCEPTED
S2 - T2 28 15 0.300 ACCEPTED
R2,S2,T2 - GROUND 28 15 0.025 ACCEPTED

REMARKS :

CONDUCTED BY, WITNESSED BY,

PT DALLE ENGINEERING PT ENERGI LISTRIK BATAM JASER


CONSTRUCTION

Print Name Very S

Signature

Date 19-Jan-15
GAS FIRED POWER PLANT FOR
IPP 2x35MW TANJUNG UNCANG
BATAM

SUBJECT : HIGH VOLTAGE TEST DATA (DIELECTRIC STRENGTH TEST)


Owner : PT ENERGI LISTRIK BATAM Temperature :______33˚C_____
Category : Test and Pre-Commissioning (MV Cell 11,5kV) Weather :_____Bright___
Location : MV CELL 1A Date : 19 January 15
Reference Drawing : TUB001-ELC-DWG-013

INSTALLED FROM : TO : CABLE TAG :


To GeneraTor Transformer 1A, LV, 1A T P001 R3, 1A T P001 S3 & 1A T P001 T3
11,5kV MV CELL 1A Generator Transformer 1A Cable Type : N2XSY, 1C - 400
MEGGER TEST INSTRUMENT TEST NAME :
VOLTAGE : 5000 Volt (DC) Insulation Test Mega Ohm Meter Model : KEW3123
Merk : Kyoritsu

RESULT (G Ohm) TIME (Sec.) CONCLUSION


SERVICE
BEFORE AFTER BEFORE AFTER (ACCEPTED/REJECTED

R3 - S3 ~ ~ 60 60 ACCEPTED
R3 - T3 ~ ~ 60 60 ACCEPTED
S3 - T3 ~ ~ 60 60 ACCEPTED
R3 - GROUND ~ ~ 60 60 ACCEPTED
S3 - GROUND ~ ~ 60 60 ACCEPTED
T3 - GROUND ~ ~ 60 60 ACCEPTED
Criteria : Min ≥ 1000 Ω/V
TYPE : Hipot 800 PL Series VOLTAGE TEST :
RATE VOLTAGE : 20 kV, 40, 80 kV DC :___28kV____
MANUFACTURER : Hipotronics AC : N/A

HIGH VOLTAGE TEST INSTRUMENT TEST NAME : SWITCHGEAR 6,6 kV

CONCLUSION
SERVICE VOLTAGE (kV) TIME (MIN) LEAKAGE (μA) (ACCEPTED/REJECTED

R3 - S3 28 15 0.200 ACCEPTED
R3 - T3 28 15 0.300 ACCEPTED
S3 - T3 28 15 0.100 ACCEPTED
R3,S3,T3 - GROUND 28 15 0.025 ACCEPTED

REMARKS :

CONDUCTED BY, WITNESSED BY,

PT DALLE ENGINEERING PT ENERGI LISTRIK BATAM JASER


CONSTRUCTION

Print Name Very S

Signature

Date 19-Jan-15
GAS FIRED POWER PLANT FOR
IPP 2x35MW TANJUNG UNCANG
BATAM

SUBJECT : HIGH VOLTAGE TEST DATA (DIELECTRIC STRENGTH TEST)


Owner : PT ENERGI LISTRIK BATAM Temperature :______33˚C_____
Category : Test and Pre-Commissioning (MV Cell 11,5kV) Weather :_____Bright___
Location : MV CELL 1A Date : 19 January 15
Reference Drawing : TUB001-ELC-DWG-013

INSTALLED FROM : TO : CABLE TAG :


To GeneraTor Transformer 1A, LV, 1A T P001 R4, 1A T P001 S4 & 1A T P001 T4
11,5kV MV CELL 1A Generator Transformer 1A Cable Type : N2XSY, 1C - 400
MEGGER TEST INSTRUMENT TEST NAME :
VOLTAGE : 5000 Volt (DC) Insulation Test Mega Ohm Meter Model : KEW3123
Merk : Kyoritsu

RESULT (G Ohm) TIME (Sec.) CONCLUSION


SERVICE
BEFORE AFTER BEFORE AFTER (ACCEPTED/REJECTED

R4 - S4 ~ ~ 60 60 ACCEPTED
R4 - T4 ~ ~ 60 60 ACCEPTED
S4 - T4 ~ ~ 60 60 ACCEPTED
R4 - GROUND ~ ~ 60 60 ACCEPTED
S4 - GROUND ~ ~ 60 60 ACCEPTED
T4 - GROUND ~ ~ 60 60 ACCEPTED
Criteria : Min ≥ 1000 Ω/V
TYPE : Hipot 800 PL Series VOLTAGE TEST :
RATE VOLTAGE : 20 kV, 40, 80 kV DC :___28kV____
MANUFACTURER : Hipotronics AC : N/A

HIGH VOLTAGE TEST INSTRUMENT TEST NAME : SWITCHGEAR 6,6 kV

CONCLUSION
SERVICE VOLTAGE (kV) TIME (MIN) LEAKAGE (μA) (ACCEPTED/REJECTED

R4 - S4 28 15 0.100 ACCEPTED
R4 - T4 28 15 0.100 ACCEPTED
S4 - T4 28 15 0.100 ACCEPTED
R4,S4,T4 - GROUND 28 15 0.025 ACCEPTED

REMARKS :

CONDUCTED BY, WITNESSED BY,

PT DALLE ENGINEERING PT ENERGI LISTRIK BATAM JASER


CONSTRUCTION

Print Name Very S

Signature

Date 19-Jan-15
GAS FIRED POWER PLANT FOR
IPP 2x35MW TANJUNG UNCANG
BATAM

SUBJECT : HIGH VOLTAGE TEST DATA (DIELECTRIC STRENGTH TEST)


Owner : PT ENERGI LISTRIK BATAM Temperature :______33˚C_____
Category : Test and Pre-Commissioning (MV Cell 11,5kV) Weather :_____Bright___
Location : MV CELL 1A Date : 19 January 15
Reference Drawing : TUB001-ELC-DWG-013

INSTALLED FROM : TO : CABLE TAG :


To GeneraTor Transformer 1A, LV, 1A T P001 R5, 1A T P001 S5 & 1A T P001 T5
11,5kV MV CELL 1A Generator Transformer 1A Cable Type : N2XSY, 1C - 400
MEGGER TEST INSTRUMENT TEST NAME :
VOLTAGE : 5000 Volt (DC) Insulation Test Mega Ohm Meter Model : KEW3123
Merk : Kyoritsu

RESULT (G Ohm) TIME (Sec.) CONCLUSION


SERVICE
BEFORE AFTER BEFORE AFTER (ACCEPTED/REJECTED

R5 - S5 ~ ~ 60 60 ACCEPTED
R5 - T5 ~ ~ 60 60 ACCEPTED
S5 - T5 ~ ~ 60 60 ACCEPTED
R5 - GROUND ~ ~ 60 60 ACCEPTED
S5 - GROUND ~ ~ 60 60 ACCEPTED
T5 - GROUND ~ ~ 60 60 ACCEPTED
Criteria : Min ≥ 1000 Ω/V
TYPE : Hipot 800 PL Series VOLTAGE TEST :
RATE VOLTAGE : 20 kV, 40, 80 kV DC :___28kV____
MANUFACTURER : Hipotronics AC : N/A

HIGH VOLTAGE TEST INSTRUMENT TEST NAME : SWITCHGEAR 6,6 kV

CONCLUSION
SERVICE VOLTAGE (kV) TIME (MIN) LEAKAGE (μA) (ACCEPTED/REJECTED

R5 - S5 28 15 0.300 ACCEPTED
R5 - T5 28 15 0.300 ACCEPTED
S5 - T5 28 15 0.100 ACCEPTED
R5,S5,T5 - GROUND 28 15 0.025 ACCEPTED

REMARKS :

CONDUCTED BY, WITNESSED BY,

PT DALLE ENGINEERING PT ENERGI LISTRIK BATAM JASER


CONSTRUCTION

Print Name Very S

Signature

Date 19-Jan-15
GAS FIRED POWER PLANT FOR
IPP 2x35MW TANJUNG UNCANG
BATAM

SUBJECT : HIGH VOLTAGE TEST DATA (DIELECTRIC STRENGTH TEST)


Owner : PT ENERGI LISTRIK BATAM Temperature :______33˚C_____
Category : Test and Pre-Commissioning (MV Cell 11,5kV) Weather :_____Bright___
Location : MV CELL 1B Date : 20 January 15
Reference Drawing : TUB001-ELC-DWG-013

INSTALLED FROM : TO : CABLE TAG :


To GeneraTor Transformer 1B, LV, 1B T P001 R1, 1B T P001 S1 & 1B T P001 T1
11,5kV MV CELL 1B Generator Transformer 1B Cable Type : N2XSY, 1C - 400
MEGGER TEST INSTRUMENT TEST NAME :
VOLTAGE : 5000 Volt (DC) Insulation Test Mega Ohm Meter Model : KEW3123
Merk : Kyoritsu

RESULT (G Ohm) TIME (Sec.) CONCLUSION


SERVICE
BEFORE AFTER BEFORE AFTER (ACCEPTED/REJECTED

R1 - S1 ~ ~ 60 60 ACCEPTED
R1 - T1 ~ ~ 60 60 ACCEPTED
S1 - T1 ~ ~ 60 60 ACCEPTED
R1 - GROUND ~ ~ 60 60 ACCEPTED
S1 - GROUND ~ ~ 60 60 ACCEPTED
T1 - GROUND ~ ~ 60 60 ACCEPTED
Criteria : Min ≥ 1000 Ω/V
TYPE : Hipot 800 PL Series VOLTAGE TEST :
RATE VOLTAGE : 20 kV, 40, 80 kV DC :___28kV____
MANUFACTURER : Hipotronics AC : N/A

HIGH VOLTAGE TEST INSTRUMENT TEST NAME : SWITCHGEAR 6,6 kV

CONCLUSION
SERVICE VOLTAGE (kV) TIME (MIN) LEAKAGE (μA) (ACCEPTED/REJECTED

R1 - S1 28 15 1.000 ACCEPTED
R1 - T1 28 15 1.000 ACCEPTED
S1 - T1 28 15 0.300 ACCEPTED
R1,S1,T1 - GROUND 28 15 0.025 ACCEPTED

REMARKS :

CONDUCTED BY, WITNESSED BY,

PT DALLE ENGINEERING PT ENERGI LISTRIK BATAM JASER


CONSTRUCTION

Print Name Very S

Signature

Date 20 January 15
GAS FIRED POWER PLANT FOR
IPP 2x35MW TANJUNG UNCANG
BATAM

SUBJECT : HIGH VOLTAGE TEST DATA (DIELECTRIC STRENGTH TEST)


Owner : PT ENERGI LISTRIK BATAM Temperature :______33˚C_____
Category : Test and Pre-Commissioning (MV Cell 11,5kV) Weather :_____Bright___
Location : MV CELL 1B Date : 20 January 15
Reference Drawing : TUB001-ELC-DWG-013

INSTALLED FROM : TO : CABLE TAG :


To GeneraTor Transformer 1B, LV, 1B T P001 R2, 1B T P001 S2 & 1B T P001 T2
11,5kV MV CELL 1B Generator Transformer 1B Cable Type : N2XSY, 1C - 400
MEGGER TEST INSTRUMENT TEST NAME :
VOLTAGE : 5000 Volt (DC) Insulation Test Mega Ohm Meter Model : KEW3123
Merk : Kyoritsu

RESULT (G Ohm) TIME (Sec.) CONCLUSION


SERVICE
BEFORE AFTER BEFORE AFTER (ACCEPTED/REJECTED

R2 - S2 ~ ~ 60 60 ACCEPTED
R2 - T2 ~ ~ 60 60 ACCEPTED
S2 - T2 ~ ~ 60 60 ACCEPTED
R2 - GROUND ~ ~ 60 60 ACCEPTED
S2 - GROUND ~ ~ 60 60 ACCEPTED
T2 - GROUND ~ ~ 60 60 ACCEPTED
Criteria : Min ≥ 1000 Ω/V
TYPE : Hipot 800 PL Series VOLTAGE TEST :
RATE VOLTAGE : 20 kV, 40, 80 kV DC :___28kV____
MANUFACTURER : Hipotronics AC : N/A

HIGH VOLTAGE TEST INSTRUMENT TEST NAME : SWITCHGEAR 6,6 kV

CONCLUSION
SERVICE VOLTAGE (kV) TIME (MIN) LEAKAGE (μA) (ACCEPTED/REJECTED

R2 - S2 28 15 0.100 ACCEPTED
R2 - T2 28 15 0.600 ACCEPTED
S2 - T2 28 15 0.400 ACCEPTED
R2,S2,T2 - GROUND 28 15 0.025 ACCEPTED

REMARKS :

CONDUCTED BY, WITNESSED BY,

PT DALLE ENGINEERING PT ENERGI LISTRIK BATAM JASER


CONSTRUCTION

Print Name Very S

Signature

Date 20 January 15
GAS FIRED POWER PLANT FOR
IPP 2x35MW TANJUNG UNCANG
BATAM

SUBJECT : HIGH VOLTAGE TEST DATA (DIELECTRIC STRENGTH TEST)


Owner : PT ENERGI LISTRIK BATAM Temperature :______33˚C_____
Category : Test and Pre-Commissioning (MV Cell 11,5kV) Weather :_____Bright___
Location : MV CELL 1B Date : 20 January 15
Reference Drawing : TUB001-ELC-DWG-013

INSTALLED FROM : TO : CABLE TAG :


To GeneraTor Transformer 1B, LV, 1B T P001 R3, 1B T P001 S3 & 1B T P001 T3
11,5kV MV CELL 1B Generator Transformer 1B Cable Type : N2XSY, 1C - 400
MEGGER TEST INSTRUMENT TEST NAME :
VOLTAGE : 5000 Volt (DC) Insulation Test Mega Ohm Meter Model : KEW3123
Merk : Kyoritsu

RESULT (G Ohm) TIME (Sec.) CONCLUSION


SERVICE
BEFORE AFTER BEFORE AFTER (ACCEPTED/REJECTED

R3 - S3 ~ ~ 60 60 ACCEPTED
R3 - T3 ~ ~ 60 60 ACCEPTED
S3 - T3 ~ ~ 60 60 ACCEPTED
R3 - GROUND ~ ~ 60 60 ACCEPTED
S3 - GROUND ~ ~ 60 60 ACCEPTED
T3 - GROUND ~ ~ 60 60 ACCEPTED
Criteria : Min ≥ 1000 Ω/V
TYPE : Hipot 800 PL Series VOLTAGE TEST :
RATE VOLTAGE : 20 kV, 40, 80 kV DC :___28kV____
MANUFACTURER : Hipotronics AC : N/A

HIGH VOLTAGE TEST INSTRUMENT TEST NAME : SWITCHGEAR 6,6 kV

CONCLUSION
SERVICE VOLTAGE (kV) TIME (MIN) LEAKAGE (μA) (ACCEPTED/REJECTED

R3 - S3 28 15 0.100 ACCEPTED
R3 - T3 28 15 0.600 ACCEPTED
S3 - T3 28 15 0.400 ACCEPTED
R3,S3,T3 - GROUND 28 15 0.025 ACCEPTED

REMARKS :

CONDUCTED BY, WITNESSED BY,

PT DALLE ENGINEERING PT ENERGI LISTRIK BATAM JASER


CONSTRUCTION

Print Name Very S

Signature

Date 20 January 15
GAS FIRED POWER PLANT FOR
IPP 2x35MW TANJUNG UNCANG
BATAM

SUBJECT : HIGH VOLTAGE TEST DATA (DIELECTRIC STRENGTH TEST)


Owner : PT ENERGI LISTRIK BATAM Temperature :______33˚C_____
Category : Test and Pre-Commissioning (MV Cell 11,5kV) Weather :_____Bright___
Location : MV CELL 1B Date : 20 January 15
Reference Drawing : TUB001-ELC-DWG-013

INSTALLED FROM : TO : CABLE TAG :


To GeneraTor Transformer 1B, LV, 1B T P001 R4, 1B T P001 S4 & 1B T P001 T4
11,5kV MV CELL 1B Generator Transformer 1B Cable Type : N2XSY, 1C - 400
MEGGER TEST INSTRUMENT TEST NAME :
VOLTAGE : 5000 Volt (DC) Insulation Test Mega Ohm Meter Model : KEW3123
Merk : Kyoritsu

RESULT (G Ohm) TIME (Sec.) CONCLUSION


SERVICE
BEFORE AFTER BEFORE AFTER (ACCEPTED/REJECTED

R4 - S4 ~ ~ 60 60 ACCEPTED
R4 - T4 ~ ~ 60 60 ACCEPTED
S4 - T4 ~ ~ 60 60 ACCEPTED
R4 - GROUND ~ ~ 60 60 ACCEPTED
S4 - GROUND ~ ~ 60 60 ACCEPTED
T4 - GROUND ~ ~ 60 60 ACCEPTED
Criteria : Min ≥ 1000 Ω/V
TYPE : Hipot 800 PL Series VOLTAGE TEST :
RATE VOLTAGE : 20 kV, 40, 80 kV DC :___28kV____
MANUFACTURER : Hipotronics AC : N/A

HIGH VOLTAGE TEST INSTRUMENT TEST NAME : SWITCHGEAR 6,6 kV

CONCLUSION
SERVICE VOLTAGE (kV) TIME (MIN) LEAKAGE (μA) (ACCEPTED/REJECTED

R4 - S4 28 15 0.600 ACCEPTED
R4 - T4 28 15 0.800 ACCEPTED
S4 - T4 28 15 0.500 ACCEPTED
R4,S4,T4 - GROUND 28 15 0.025 ACCEPTED

REMARKS :

CONDUCTED BY, WITNESSED BY,

PT DALLE ENGINEERING PT ENERGI LISTRIK BATAM JASER


CONSTRUCTION

Print Name Very S

Signature

Date 20 January 15
GAS FIRED POWER PLANT FOR
IPP 2x35MW TANJUNG UNCANG
BATAM

SUBJECT : HIGH VOLTAGE TEST DATA (DIELECTRIC STRENGTH TEST)


Owner : PT ENERGI LISTRIK BATAM Temperature :______33˚C_____
Category : Test and Pre-Commissioning (MV Cell 11,5kV) Weather :_____Bright___
Location : MV CELL 1B Date : 20 January 15
Reference Drawing : TUB001-ELC-DWG-013

INSTALLED FROM : TO : CABLE TAG :


To GeneraTor Transformer 1B, LV, 1B T P001 R5, 1B T P001 S5 & 1B T P001 T5
11,5kV MV CELL 1B Generator Transformer 1B Cable Type : N2XSY, 1C - 400
MEGGER TEST INSTRUMENT TEST NAME :
VOLTAGE : 5000 Volt (DC) Insulation Test Mega Ohm Meter Model : KEW3123
Merk : Kyoritsu

RESULT (G Ohm) TIME (Sec.) CONCLUSION


SERVICE
BEFORE AFTER BEFORE AFTER (ACCEPTED/REJECTED

R5 - S5 ~ ~ 60 60 ACCEPTED
R5 - T5 ~ ~ 60 60 ACCEPTED
S5 - T5 200 ~ 60 60 ACCEPTED
R5 - GROUND ~ ~ 60 60 ACCEPTED
S5 - GROUND 200 ~ 60 60 ACCEPTED
T5 - GROUND ~ ~ 60 60 ACCEPTED
Criteria : Min ≥ 1000 Ω/V
TYPE : Hipot 800 PL Series VOLTAGE TEST :
RATE VOLTAGE : 20 kV, 40, 80 kV DC :___28kV____
MANUFACTURER : Hipotronics AC : N/A

HIGH VOLTAGE TEST INSTRUMENT TEST NAME : SWITCHGEAR 6,6 kV

CONCLUSION
SERVICE VOLTAGE (kV) TIME (MIN) LEAKAGE (μA) (ACCEPTED/REJECTED

R5 - S5 28 15 1.800 ACCEPTED
R5 - T5 28 15 1.800 ACCEPTED
S5 - T5 28 15 1.400 ACCEPTED
R5,S5,T5 - GROUND 28 15 0.025 ACCEPTED

REMARKS :

CONDUCTED BY, WITNESSED BY,

PT DALLE ENGINEERING PT ENERGI LISTRIK BATAM JASER


CONSTRUCTION

Print Name Very S

Signature

Date 20 January 15
GAS FIRED POWER PLANT FOR
IPP 2x35MW TANJUNG UNCANG
BATAM

SUBJECT : HIGH VOLTAGE TEST DATA (DIELECTRIC STRENGTH TEST)


Owner : PT ENERGI LISTRIK BATAM Temperature :______33˚C_____
Category : Test and Pre-Commissioning (Switchgear 6,6kV) Weather :_____Bright___
Location : Switchgear Room Date : 11 November 14
Reference Drawing : TUB001-ELC-DWG-013

INSTALLED FROM : TO : CABLE TAG :


1A MV P003
Cubicle M02, Switchgear 6,6kV 1A TX (AUX. TRAFO)
Cable Type : N2XSEY, 3c - 50
MEGGER TEST INSTRUMENT TEST NAME :
VOLTAGE : 5000 Volt (DC) Insulation Test Mega Ohm Meter Model : 5100 Merk :
AEMC

RESULT (G Ohm) TIME (Sec.) CONCLUSION


SERVICE
BEFORE AFTER BEFORE AFTER (ACCEPTED/REJECTED

R-S 90 ~ 60 60 ACCEPTED
R-T 130 ~ 60 60 ACCEPTED
S-T 100 ~ 60 60 ACCEPTED
R - GROUND 25 185 60 60 ACCEPTED
S - GROUND 30 185 60 60 ACCEPTED
T - GROUND 35 180 60 60 ACCEPTED
Criteria : Min ≥ 1000 Ω/V
TYPE : Hipot 800 PL Series VOLTAGE TEST :
RATE VOLTAGE : 20 kV, 40, 80 kV DC :___15kV____
MANUFACTURER : Hipotronics AC : N/A

HIGH VOLTAGE TEST INSTRUMENT TEST NAME : SWITCHGEAR 6,6 kV

CONCLUSION
SERVICE VOLTAGE (kV) TIME (MIN) LEAKAGE (μA) (ACCEPTED/REJECTED

R-S 15.3 15 0.50 ACCEPTED


R-T 15.3 15 0.50 ACCEPTED
S-T 15.3 15 0.50 ACCEPTED
RST - GROUND 15.3 15 0.50 ACCEPTED

REMARKS :

CONDUCTED BY, WITNESSED BY,

PT DALLE ENGINEERING PT ENERGI LISTRIK BATAM JASER


CONSTRUCTION

Print Name Very S

Signature

Date 11 Nov 2014


GAS FIRED POWER PLANT FOR
IPP 2x35MW TANJUNG UNCANG
BATAM

SUBJECT : HIGH VOLTAGE TEST DATA (DIELECTRIC STRENGTH TEST)


Owner : PT ENERGI LISTRIK BATAM Temperature :______33˚C_____
Category : Test and Pre-Commissioning (Switchgear 6,6kV) Weather :_____Bright___
Location : Switchgear Room Date : 10 November 14
Reference Drawing : TUB001-ELC-DWG-013

INSTALLED FROM : TO : CABLE TAG :


1A MV P003
Cubicle M10, Switchgear 6,6kV 1B TX (AUX. TRAFO)
Cable Type : N2XSEY, 3c - 50
MEGGER TEST INSTRUMENT TEST NAME :
VOLTAGE : 5000 Volt (DC) Insulation Test Mega Ohm Meter Model : 5100 Merk :
AEMC

RESULT (G Ohm) TIME (Sec.) CONCLUSION


SERVICE
BEFORE AFTER BEFORE AFTER (ACCEPTED/REJECTED

R-S 200 ~ 60 60 ACCEPTED


R-T 200 ~ 60 60 ACCEPTED
S-T 100 ~ 60 60 ACCEPTED
R - GROUND ~ ~ 60 60 ACCEPTED
S - GROUND ~ ~ 60 60 ACCEPTED
T - GROUND ~ ~ 60 60 ACCEPTED
Criteria : Min ≥ 1000 Ω/V
TYPE : Hipot 800 PL Series VOLTAGE TEST :
RATE VOLTAGE : 20 kV, 40, 80 kV DC :___15kV____
MANUFACTURER : Hipotronics AC : N/A

HIGH VOLTAGE TEST INSTRUMENT TEST NAME : SWITCHGEAR 6,6 kV

CONCLUSION
SERVICE VOLTAGE (kV) TIME (MIN) LEAKAGE (μA) (ACCEPTED/REJECTED

R-S 15.3 15 3.20 ACCEPTED


R-T 15.3 15 7.00 ACCEPTED
S-T 15.3 15 5.00 ACCEPTED
RST - GROUND 15.3 15 1.90 ACCEPTED

REMARKS :

CONDUCTED BY, WITNESSED BY,

PT DALLE ENGINEERING PT ENERGI LISTRIK BATAM JASER


CONSTRUCTION

Print Name Very S

Signature

Date 10 Nov 2014


GAS FIRED POWER PLANT FOR
IPP 2x35MW TANJUNG UNCANG
BATAM

SUBJECT : HIGH VOLTAGE TEST DATA (DIELECTRIC STRENGTH TEST)


Owner : PT ENERGI LISTRIK BATAM Temperature :______33˚C_____
Category : Test and Pre-Commissioning (Switchgear 6,6kV) Weather :_____Bright___
Location : Switchgear Room Date : 11 November 14
Reference Drawing : TUB001-ELC-DWG-013

INSTALLED FROM : TO : CABLE TAG :


1A 88CR GTG 1A 1A MV P002
Cubicle M03, Switchgear 6,6kV (Starting Motor) Cable Type : N2XSEY, 3c - 50
MEGGER TEST INSTRUMENT TEST NAME :
VOLTAGE : 5000 Volt (DC) Insulation Test Mega Ohm Meter Model : 5100 Merk :
AEMC

RESULT (G Ohm) TIME (Sec.) CONCLUSION


SERVICE
BEFORE AFTER BEFORE AFTER (ACCEPTED/REJECTED

R-S ~ ~ 60 60 ACCEPTED
R-T ~ ~ 60 60 ACCEPTED
S-T ~ ~ 60 60 ACCEPTED
R - GROUND 180 ~ 60 60 ACCEPTED
S - GROUND 150 ~ 60 60 ACCEPTED
T - GROUND 70 ~ 60 60 ACCEPTED
Criteria : Min ≥ 1000 Ω/V
TYPE : Hipot 800 PL Series VOLTAGE TEST :
RATE VOLTAGE : 20 kV, 40, 80 kV DC :___15kV____
MANUFACTURER : Hipotronics AC : N/A

HIGH VOLTAGE TEST INSTRUMENT TEST NAME : SWITCHGEAR 6,6 kV

CONCLUSION
SERVICE VOLTAGE (kV) TIME (MIN) LEAKAGE (μA) (ACCEPTED/REJECTED

R-S 15.3 15 10.00 ACCEPTED


R-T 15.3 15 10.00 ACCEPTED
S-T 15.3 15 9.00 ACCEPTED
RST - GROUND 15.3 15 15.00 ACCEPTED

REMARKS :

CONDUCTED BY, WITNESSED BY,

PT DALLE ENGINEERING PT ENERGI LISTRIK BATAM JASER


CONSTRUCTION

Print Name Very S

Signature

Date 11 Nov 2014


GAS FIRED POWER PLANT FOR
IPP 2x35MW TANJUNG UNCANG
BATAM

SUBJECT : HIGH VOLTAGE TEST DATA (DIELECTRIC STRENGTH TEST)


Owner : PT ENERGI LISTRIK BATAM Temperature :______33˚C_____
Category : Test and Pre-Commissioning (Switchgear 6,6kV) Weather :_____Bright___
Location : Switchgear Room Date : 10 November 14
Reference Drawing : TUB001-ELC-DWG-013

INSTALLED FROM : TO : CABLE TAG :


1B 88CR GTG 1B 1B MV P002
Cubicle M09, Switchgear 6,6kV (Starting Motor) Cable Type : N2XSEY, 3c - 50
MEGGER TEST INSTRUMENT TEST NAME :
VOLTAGE : 5000 Volt (DC) Insulation Test Mega Ohm Meter Model : 5100 Merk :
AEMC

RESULT (G Ohm) TIME (Sec.) CONCLUSION


SERVICE
BEFORE AFTER BEFORE AFTER (ACCEPTED/REJECTED

R-S 45 80 60 60 ACCEPTED
R-T 50 100 60 60 ACCEPTED
S-T 130 180 60 60 ACCEPTED
R - GROUND 70 100 60 60 ACCEPTED
S - GROUND 70 150 60 60 ACCEPTED
T - GROUND 80 130 60 60 ACCEPTED
Criteria : Min ≥ 1000 Ω/V
TYPE : Hipot 800 PL Series VOLTAGE TEST :
RATE VOLTAGE : 20 kV, 40, 80 kV DC :___15kV____
MANUFACTURER : Hipotronics AC : N/A

HIGH VOLTAGE TEST INSTRUMENT TEST NAME : SWITCHGEAR 6,6 kV

CONCLUSION
SERVICE VOLTAGE (kV) TIME (MIN) LEAKAGE (μA) (ACCEPTED/REJECTED

R-S 15.3 15 10.00 ACCEPTED


R-T 15.3 15 10.00 ACCEPTED
S-T 15.3 15 11.00 ACCEPTED
RST - GROUND 15.3 15 11.00 ACCEPTED

REMARKS :

CONDUCTED BY, WITNESSED BY,

PT DALLE ENGINEERING PT ENERGI LISTRIK BATAM JASER


CONSTRUCTION

Print Name Very S

Signature

Date 10 Nov 2014


GAS FIRED POWER PLANT FOR
IPP 2x35MW TANJUNG UNCANG
BATAM

SUBJECT : HIGH VOLTAGE TEST DATA (DIELECTRIC STRENGTH TEST)


Owner : PT ENERGI LISTRIK BATAM Temperature :______33˚C_____
Category : Test and Pre-Commissioning (Switchgear 6,6kV) Weather :_____Bright___
Location : Switchgear Room Date : 10 November 14
Reference Drawing : TUB001-ELC-DWG-013

INSTALLED FROM : TO : CABLE TAG :


1A SST 1A MV P001
Cubicle M04, Switchgear 6,6kV (Substation Transformer) Cable Type : N2XSEY, 3c - 50
MEGGER TEST INSTRUMENT TEST NAME :
VOLTAGE : 5000 Volt (DC) Insulation Test Mega Ohm Meter Model : 5100 Merk :
AEMC

RESULT (G Ohm) TIME (Sec.) CONCLUSION


SERVICE
BEFORE AFTER BEFORE AFTER (ACCEPTED/REJECTED

R-S ~ ~ 60 60 ACCEPTED
R-T ~ ~ 60 60 ACCEPTED
S-T ~ ~ 60 60 ACCEPTED
R - GROUND 180 195 60 60 ACCEPTED
S - GROUND 180 200 60 60 ACCEPTED
T - GROUND 190 200 60 60 ACCEPTED
Criteria : Min ≥ 1000 Ω/V
TYPE : Hipot 800 PL Series VOLTAGE TEST :
RATE VOLTAGE : 20 kV, 40, 80 kV DC :___15kV____
MANUFACTURER : Hipotronics AC : N/A

HIGH VOLTAGE TEST INSTRUMENT TEST NAME : SWITCHGEAR 6,6 kV

CONCLUSION
SERVICE VOLTAGE (kV) TIME (MIN) LEAKAGE (μA) (ACCEPTED/REJECTED

R-S 15.3 15 0.10 ACCEPTED


R-T 15.3 15 0.15 ACCEPTED
S-T 15.3 15 0.30 ACCEPTED
RST - GROUND 15.3 15 0.70 ACCEPTED

REMARKS :

CONDUCTED BY, WITNESSED BY,

PT DALLE ENGINEERING PT ENERGI LISTRIK BATAM JASER


CONSTRUCTION

Print Name Very S

Signature

Date 10 Nov 2014


GAS FIRED POWER PLANT FOR
IPP 2x35MW TANJUNG UNCANG
BATAM

SUBJECT : HIGH VOLTAGE TEST DATA (DIELECTRIC STRENGTH TEST)


Owner : PT ENERGI LISTRIK BATAM Temperature :______33˚C_____
Category : Test and Pre-Commissioning (Switchgear 6,6kV) Weather :_____Bright___
Location : Switchgear Room Date : 10 November 14
Reference Drawing : TUB001-ELC-DWG-013

INSTALLED FROM : TO : CABLE TAG :


1B SST 1B MV P001
Cubicle M08, Switchgear 6,6kV (Substation Transformer) Cable Type : N2XSEY, 3c - 50
MEGGER TEST INSTRUMENT TEST NAME :
VOLTAGE : 5000 Volt (DC) Insulation Test Mega Ohm Meter Model : 5100 Merk :
AEMC

RESULT (G Ohm) TIME (Sec.) CONCLUSION


SERVICE
BEFORE AFTER BEFORE AFTER (ACCEPTED/REJECTED

R-S ~ ~ 60 60 ACCEPTED
R-T ~ ~ 60 60 ACCEPTED
S-T ~ ~ 60 60 ACCEPTED
R - GROUND 180 200 60 60 ACCEPTED
S - GROUND 180 200 60 60 ACCEPTED
T - GROUND 180 190 60 60 ACCEPTED
Criteria : Min ≥ 1000 Ω/V
TYPE : Hipot 800 PL Series VOLTAGE TEST :
RATE VOLTAGE : 20 kV, 40, 80 kV DC :___15kV____
MANUFACTURER : Hipotronics AC : N/A

HIGH VOLTAGE TEST INSTRUMENT TEST NAME : SWITCHGEAR 6,6 kV

CONCLUSION
SERVICE VOLTAGE (kV) TIME (MIN) LEAKAGE (μA) (ACCEPTED/REJECTED

R-S 15.3 15 0.80 ACCEPTED


R-T 15.3 15 0.90 ACCEPTED
S-T 15.3 15 0.50 ACCEPTED
RST - GROUND 15.3 15 0.40 ACCEPTED

REMARKS :

CONDUCTED BY, WITNESSED BY,

PT DALLE ENGINEERING PT ENERGI LISTRIK BATAM JASER


CONSTRUCTION

Print Name Very S

Signature

Date 10 Nov 2014