Professional Documents
Culture Documents
No load excitation voltage V 11.3 12.5 13.5 15.8 8.7 9.2 9.7 10.6 11.3 12.5
No load excitation current A 0.48 0.53 0.57 0.67 0.37 0.39 0.41 0.45 0.48 0.53
Class H BR excitation voltage V 39.2 39.6 40.8 41.8 39.6 40.4 41.5 42.5 42.2 42.7
Class H BR excitation current A 1.66 1.68 1.73 1.77 1.68 1.71 1.76 1.80 1.79 1.81
WINDING RESISTANCE At 20 o C
Stator line-to-line (series star) Ω 1.130 Exciter field Ω 23.6
Main field Ω 2.30
According to: IEC 60034, UTE NFC51.111, VDE 0530, BS 4999/5000, NEMA MG 1-33
Values quoted are typical. In line with our policy of continuous improvement, we reserve the right to change specification without notice.
FRAME 1014L WINDING 6
50 Hz SHUNT
380V
400V
415V
440V
35
30
25
voltage dip %
20
15
10
0
0 5 10 15 20 25 30 35 40 45
kVA
60 Hz SHUNT
380V
400V
416V
440V
460V
480V
35
30
25
voltage dip %
20
15
10
0
0 5 10 15 20 25 30 35 40 45
kVA
According to: IEC 60034, UTE NFC51.111, VDE 0530, BS 4999/5000, NEMA MG 1-33
Values quoted are typical. In line with our policy of continuous improvement, we reserve the right to change specification without notice.
FRAME 1014L WINDING 6
1000
asymmetrical
RMS current (A)
symmetrical
100
10
1 10 100 1000 10000
time (ms)
Multiplication Factors
According to: IEC 60034, UTE NFC51.111, VDE 0530, BS 4999/5000, NEMA MG 1-33
Values quoted are typical. In line with our policy of continuous improvement, we reserve the right to change specification without notice.