You are on page 1of 3

FRAME 8124N WINDING 6S

MODELS LL8124N / LL8134N REF: F8104NW6S-0 AUGUST 2002

WINDING DETAILS MECHANICAL DETAILS


Code 6S Insulation class H Standard protection IP23
Phase 3 Leads 6 Overspeed rpm 2250
Pole number 4 Pitch 2/3 Air flow 50Hz/60Hz m3/s 1.60 / 1.92

EXCITATION DETAILS WAVEFORM


Excitation system AREP/PMG Line voltage on no load or balanced linear rated load
AVR model R449 Total harmonic content THC <3.5%
Sustained short-circuit current 300%:10s Telephone influence factor TIF (NEMA) <50
Steady state voltage regulation ±0.5% Telephone harmonic factor THF (IEC) <2%

LINE VOLTAGE No overvoltage tolerance for 440V 50Hz excitation level


Frequency / speed 50Hz / 1500rpm 60Hz / 1800rpm
Star V 380 400 415 440 380 400 416 440 460 480
Delta V 220 230 240 220 230 240

1 2 3 4 6 7 8 9 10 11
RATING Power factor 0.8, Altitude <=1000m
Class H rise BR 125/40 kVA 1425 1425 1425 1345 1350 1425 1480 1565 1640 1710
kW 1140 1140 1140 1076 1080 1140 1184 1252 1312 1368
Class H rise PR 150/40 kVA 1510 1510 1510 1425 1430 1510 1570 1660 1740 1815
kW 1208 1208 1208 1140 1144 1208 1256 1328 1392 1452
Class H rise PR 163/27 kVA 1565 1565 1565 1480 1485 1565 1625 1720 1800 1880
kW 1252 1252 1252 1184 1188 1252 1300 1376 1440 1504
Class F rise BR 105/40 kVA 1283 1283 1283 1211 1215 1283 1332 1409 1476 1539
kW 1026 1026 1026 968 972 1026 1066 1127 1181 1231

EFFICIENCIES Power factor 0.8


110% Class H BR % 95.2 95.4 95.5 95.7 95.4 95.6 95.7 95.8 95.8 95.9
100% Class H BR % 95.4 95.6 95.7 95.8 95.6 95.7 95.8 95.9 96.0 96.0
75% Class H BR % 95.9 96.0 96.0 96.0 96.0 96.1 96.1 96.2 96.2 96.2
50% Class H BR % 96.1 96.0 96.0 95.7 95.9 96.0 96.0 96.1 96.1 96.1
25% Class H BR % 94.9 94.6 94.4 93.7 94.4 94.4 94.4 94.4 94.4 94.3

CHARACTERISTIC PARAMETERS Reactance base class H BR rating


Kc Short-circuit ratio 0.31 0.37 0.43 0.61 0.23 0.25 0.27 0.30 0.33 0.37
Xd D-Axis synchronous reactance (unsaturated) pu 3.91 3.53 3.28 2.75 4.44 4.23 4.07 3.84 3.68 3.53
X'd D-Axis transient reactance (saturated) pu 0.27 0.25 0.23 0.19 0.31 0.29 0.28 0.27 0.26 0.25
X''d D-Axis sub-transient reactance (saturated) pu 0.150 0.135 0.126 0.106 0.171 0.162 0.156 0.147 0.141 0.135
Xq Q-Axis synchronous reactance (unsaturated) pu 2.35 2.12 1.97 1.65 2.67 2.54 2.44 2.31 2.21 2.12
X''q Q-Axis sub-transient reactance (saturated) pu 0.187 0.168 0.156 0.131 0.212 0.202 0.194 0.183 0.176 0.168
X2 Negative-sequence reactance (saturated) pu 0.169 0.152 0.141 0.119 0.192 0.183 0.175 0.166 0.159 0.152
X0 Zero-sequence reactance (independent) pu 0.035 0.031 0.029 0.024 0.039 0.037 0.036 0.034 0.033 0.031
T'd D-Axis transient time constant ms 220 220
T''d D-Axis sub-transient time constant ms 20 20
T'do D-Axis open-circuit time constant ms 2720 2720
Ta Armature time constant ms 41 41
Tr Voltage recovery time ms < 500 < 500

EXCITATION VOLTAGE AND CURRENT

No load excitation voltage V 11.1 12.6 14.3 17.8 7.9 8.4 9.1 10.3 11.2 12.6
No load excitation current A 1.19 1.35 1.53 1.90 0.85 0.90 0.97 1.10 1.20 1.35
Class H BR excitation voltage V 47.7 47.7 48.6 49.6 39.7 41.0 42.1 43.9 45.3 47.2
Class H BR excitation current A 5.10 5.10 5.20 5.30 4.25 4.38 4.50 4.70 4.85 5.05

WINDING RESISTANCE At 20 o C
Stator line-to-line (series star) Ω 0.0023 Exciter field Ω 9.35
Main field Ω 0.513

According to: IEC 60034, UTE NFC51.111, VDE 0530, BS 4999/5000, NEMA MG 1-33
Values quoted are typical. In line with our policy of continuous improvement, we reserve the right to change specification without notice.
FRAME 8124N WINDING 6S

MODELS LL8124N / LL8134N REF: F8104NW6S-0 AUGUST 2002

LOCKED ROTOR MOTOR STARTING CURVES Power factor 0.4

50 Hz AREP / PMG

380V

400V

415V

440V
25

20
voltage dip %

15

10

0
0 500 1000 1500 2000 2500 3000 3500
kVA

60 Hz AREP / PMG
380V

400V

416V

440V

460V

480V

25

20
voltage dip %

15

10

0
0 500 1000 1500 2000 2500 3000 3500
kVA

According to: IEC 60034, UTE NFC51.111, VDE 0530, BS 4999/5000, NEMA MG 1-33
Values quoted are typical. In line with our policy of continuous improvement, we reserve the right to change specification without notice.
FRAME 8124N WINDING 6S

MODELS LL8124N / LL8134N REF: F8104NW6S-0 AUGUST 2002

THREE-PHASE SHORT-CIRCUIT DECREMENT CURVES No-load excitation at rated speed

400V 50Hz, 480V 60Hz Star

100000

asymmetrical
RMS current (A)

10000 symmetrical

1000
1 10 100 1000 10000
time (ms)

Multiplication Factors

50Hz Voltages 380 400 415 440

Multiplication Factor 0.95 1.00 1.04 1.10

Apply factor up to 2xT'd, remainder of curve unchanged

60Hz Voltages 380 400 416 440 460 480

Multiplication Factor 0.79 0.83 0.87 0.92 0.96 1.00

Apply factor up to 2xT'd, remainder of curve unchanged

Winding Connection Star Delta

Multiplication Factor 1.00 1.73

Apply factor to the complete curve

According to: IEC 60034, UTE NFC51.111, VDE 0530, BS 4999/5000, NEMA MG 1-33
Values quoted are typical. In line with our policy of continuous improvement, we reserve the right to change specification without notice.