AMD-42

Air Measuring Station with


VCD-42 Control Damper
Application and Design
The AMD-42 combines the functionality of an accurate airflow measuring station and a low leakage control damper
into one compact assembly that both measures and regulates airflow volumes to a target set-point. The AMD-42
comes standard with a modulating actuator and a properly sized pressure transducer that output a signal proportional
to cfm. A field supplied controller can then use the transducer's signal along with the flow formula:
CFM = Area * K * (P transducer)m to regulate the modulating actuator to the target set-point. K & m are factory
supplied variables specific to each damper.

Ratings
Velocity:
300 to 3000 fpm (1.5 - 15.2 m/s)
6 cfm/ft2 @ 4 in. wg
Leakage:
(110 cmh/m2 @ 1 kPa)
3 cfm/ft2 @ 1 in. wg
(55 cmh/m2 @ .25 kPa)
Temperature: -20°F to 180°F (-29°C to 82ºC)
Consult factory for temperature
lower than -20°F (-29°C)
Transducer Temperature: 0°F
Airflow Monitoring Accuracy: 5% of reading

Construction Standard Optional


Frame Material Galvanized Steel -
Frame Material
16 ga. (1.5mm) 12 ga. (2.7mm)*
Thickness
W & H dimension furnished approximately 1/4 in. (6mm) undersize.
Frame Type 5 in. x 1 in. hat channel -
Blade Material Extruded Aluminum -
Blade Type Airfoil - Blade Overlap
Blades overlap to provide
Blade Action Parallel - added resistance to leakage.
Plated steel out of When pressure increases,
the blade seals are forced
Linkage airstream, concealed 316SS
together creating a tighter
in jamb seal.
Synthetic (acetal)
Axle Bearings 316SS
sleeve type Features & Control Options
Axle Material Plated steel 316SS • 24 VAC modulating actuator mounted externally
Blade Seals TPE Silicone or internally (NEMA 2)
Jamb Seals Stainless Steel - • Factory supplied 0-10 VDC pressure transducer
12 in. 12 in. - 48 in. • Clean wrap
Sleeve
(305mm) (305mm - 1219mm) • Retaining Angles
Sleeve Gauge 20 ga. 14 ga. or 16 ga.
11⁄2 in. (38mm);
Upstream side,
Flange None
Downstream side, Minimum Size Maximum Size
Both Sides WxH Single Multiple
External Internal
Air Straightener
Polycarbonate
- Section Section*
Honeycomb
Inches 6x6 8x6 48 x 74 144 x 148
24 VAC w/ auxiliary
Actuator 24 VAC 50/60 Hz switches or manual mm 152 x 152 203 x 152 1219 x 1880 3658 x 3759
quadrant * For sizes larger than listed, consult factory.
*When 12 ga. frame is selected and the damper height is less than 17
inches, low profile top and bottom frame members are utilized. These low
profile frame members will be made from 16 ga. material.

Installation instructions available at www.greenheck.com


AMD-42 Mounting Styles and Specifications

Flange on Upstream Flange on Downstream

Airflow Direction

Leakage Data
Damper leakage (with blades fully closed) varies 6.0

based on the type of low leakage seals applied. 5.0

Model AMD-42-TD is available with silicone blade 4.0

seals and stainless steel jamb seals. Leakage 3.0


testing was conducted in accordance with AMCA
Static Pressure Difference (in. wg)

Standard 500-D and is expressed as cfm/ft2 of 2.0

damper face area. All data has been corrected to


represent standard air at a density of 0.075 lb/ft3
(1.201 kg/m3 ). 1.0
0.9
0.8
0.7

0.6

0.5

0.4

0.3

0.2

1 2 3 4 5 6 7 8 9 10 20 30 40 50 60

Air Leakage (cfm/ft2)


Pressure Drop AMD-42
This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations
shown. All data has been corrected to represent standard air at a density of 0.075 lb/ft 3(1.201kg/m3).
Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information
along with an analysis of other system influences should be used to estimate actual pressure losses for a damper
installed in a given HVAC system.

AMCA Test Figures


Figure 5.2 Illustrates a ducted damper exhausting air into an open area. This configuration has a lower pressure drop
than Figure 5.5 because entrance losses are minimized by a straight duct run upstream of the damper.

5D

D 4 (W) (H)
3.14

Figure 5.3 Illustrates a fully ducted damper. This configuration has the lowest pressure drop of the three test
configurations because entrance and exit losses are minimized by straight duct runs upstream and downstream of the
damper.

5D 6D

Figure 5.5 Illustrates a plenum mounted damper. This configuration has the highest pressure drop because of
extremely high entrance and exit losses due to the sudden changes of area in the system.
Pressure Drop Data AMD-42
AMCA 5.2
5D

12 in. x 12 in. (305mm x 305mm) 24 in. x 24 in. (610mm x 610mm) 36 in. x 36 in. (914mm x 914mm) 12 in. x 48 in. (305mm x 1219mm) 48 in. x 12 in. (1219mm x 305mm)
Pressure Drop Pressure Drop Pressure Drop Pressure Drop Pressure Drop
Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) Velocity (fpm) Velocity (fpm)
(in. wg) (in. wg) (in. wg)
500 0.05 500 0.01 500 0.01 500 0.01 500 0.03
1000 0.18 1000 0.05 1000 0.04 1000 0.01 1000 0.11
1500 0.43 1500 0.12 1500 0.09 1500 0.14 1500 0.25
2000 0.76 2000 0.22 2000 0.17 2000 0.25 2000 0.44
2500 1.19 2500 0.34 2500 0.26 2500 0.39 2500 0.69
3000 1.71 3000 0.49 3000 0.38 3000 0.57 3000 1.00
3500 2.33 3500 0.66 3500 0.51 3500 0.77 3500 1.36
4000 3.04 4000 0.87 4000 0.67 4000 1.01 4000 1.78

AMCA 5.3
5D 6D

12 in. x 12 in. (305mm x 305mm) 24 in. x 24 in. (610mm x 610mm) 36 in. x 36 in. (914mm x 914mm) 12 in. x 48 in. (305mm x 1219mm) 48 in. x 12 in. (1219mm x 305mm)
Pressure Drop Pressure Drop Pressure Drop Pressure Drop Pressure Drop
Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) Velocity (fpm) Velocity (fpm)
(in. wg) (in. wg) (in. wg)
500 0.03 500 0.01 500 0.01 500 0.01 500 0.02
1000 0.12 1000 0.03 1000 0.02 1000 0.04 1000 0.06
1500 0.28 1500 0.06 1500 0.05 1500 0.09 1500 0.14
2000 0.49 2000 0.11 2000 0.08 2000 0.16 2000 0.25
2500 0.77 2500 0.17 2500 0.13 2500 0.25 2500 0.39
3000 1.11 3000 0.24 3000 0.19 3000 0.36 3000 0.57
3500 1.51 3500 0.33 3500 0.26 3500 0.49 3500 0.77
4000 1.98 4000 0.43 4000 0.34 4000 0.64 4000 1.01

AMCA 5.5

12 in. x 12 in. (305mm x 305mm) 24 in. x 24 in. (610mm x 610mm) 36 in. x 36 in. (914mm x 914mm) 12 in. x 48 in. (305mm x 1219mm) 48 in. x 12 in. (1219mm x 305mm)
Pressure Drop Pressure Drop Pressure Drop Pressure Drop Pressure Drop
Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) Velocity (fpm) Velocity (fpm)
(in. wg) (in. wg) (in. wg)
500 0.07 500 0.04 500 0.02 500 0.03 500 0.05
1000 0.28 1000 0.17 1000 0.12 1000 0.18 1000 0.19
1500 0.62 1500 0.37 1500 0.28 1500 0.40 1500 0.44
2000 1.11 2000 0.66 2000 0.50 2000 0.72 2000 0.78
2500 1.73 2500 1.04 2500 0.78 2500 1.12 2500 1.21
3000 2.50 3000 1.50 3000 1.13 3000 1.62 3000 1.75
3500 3.41 3500 2.04 3500 1.53 3500 2.21 3500 2.38
4000 4.45 4000 2.66 4000 2.01 4000 2.88 4000 3.11
Factory Supplied Controls
By adding a factory supplied controller AMD series airflow measuring dampers become a turn-key solution for
measuring and controlling the flow of air. Go to www.greenheck.com for complete instructions on these two
controllers.

Vari-Green® Constant Volume Controller


Greenheck’s Vari-Green Constant Volume Controller is a highly configurable analog based controller. The controller
can accept a cfm setpoint either remotely by way of an analog input or locally by using touch sensitive buttons on its
cover. The controller then regulates the position of the AMD’s actuator to deliver the requested cfm. An analog output
on the controller also supplies a signal that is proportional to the real-time cfm.
The Vari-Green Constant Volume Controller features a two line backlit LCD display to show the user the current CFM
setpoint, the real-time cfm, the current pressure reading, and the AMD’s actuator position.

Constant Volume

Varigreen Damper
Controller

Specifications
Control dampers meeting the following specifications turning in acetal bearings; TPE blade seals for 250°F
shall be installed where shown on plans as an air (121°C) maximum temperature; flexible stainless steel
monitor station integral to the minimum outside air jamb seals; and external (out of the airstream) blade-to-
damper. The air measuring damper shall control the blade linkage.
minimum amount of outside air as recommended by Damper leakage rating to be in compliance with the
ASHRAE Standard 62 or California Title 24. IECC (International Energy Conservation Code) and not
The air measuring damper shall consist of: 16 ga. to exceed 3 cfm/ft2 (55 cmh/m2) at 1 in. wg (0.25 kPa).
(1.5mm) galvanized steel hat channel frame with 5 in. Testing and ratings to be in accordance with AMCA
(127mm) depth; airfoil shaped, extruded aluminum standard 500-D.
blades (0.063 in. [1.6mm] thick) with metal blade Basis of design is model AMD-42.
to blade overlap (seal to seal only contact is not
acceptable). Axles shall be ½ in. (13mm) dia. plated steel

Copyright © 2019 Greenheck Fan Corporation


AMD-42 Rev. 11 July 2019