ARC900 Operation Manual OP900.1.1.7.

R5ENG

ALIAPANEL
®

Paperless Recorder
ARC900 Series
Operation Manual

ALIA Group Inc. URL : http://www.alia-inc.com


113 Barksdale Professional Center, Newark, DE 19711, USA e-mail : alia@alia-inc.com
TEL : +1 - 302 - 213 - 0106 FAX: +1 - 302 - 213 - 0107 OP900.1.1.7.R5ENG

1
ARC900 Operation Manual OP900.1.1.7.R5ENG

Index
1. Features --------------------------------------------------------------------------------------------------------------------------------4
2. Installation & Wiring diagram------------------------------------------------------------------------------------------------------5
2.1 Installation Position----------------------------------------------------------------------------------------------------------5
2.2 Panel Type --------------------------------------------------------------------------------------------------------------------6
2.3 Outdoor Type -----------------------------------------------------------------------------------------------------------------7
2.4 The Connection of Input/output Signal Cables -----------------------------------------------------------------------8
3. Dimensions ----------------------------------------------------------------------------------------------------------------------------8
3.1 Panel Type --------------------------------------------------------------------------------------------------------------------8
3.2 Outdoor Type -----------------------------------------------------------------------------------------------------------------8
4. Key Settings ---------------------------------------------------------------------------------------------------------------------------9
4.1 Open protective cover ---------------------------------------------------------------------------------------------------- 10
5. Display Type ------------------------------------------------------------------------------------------------------------------------ 11
5.1 Status Display -------------------------------------------------------------------------------------------------------------- 12
6. The Application Examples of ARC900 and ARC900 Outdoor type --------------------------------------------------- 13
6.1 ARC 900 4-20mA Signal Application Illustration ------------------------------------------------------------------- 13
6.2 ARC900 Temperature Transmitter Illustration---------------------------------------------------------------------- 14
6.3 ARC900 Outdoor Type 4-20mA Application Examples ---------------------------------------------------------- 15
6.4 ARC900 Outdoor Type Temperature Transmitter Illustration -------------------------------------------------- 16
7. Flow Chart --------------------------------------------------------------------------------------------------------------------------- 17
8. Operation Instructions ------------------------------------------------------------------------------------------------------------ 21
8.1 System Configuration Settings ----------------------------------------------------------------------------------------- 21
8.2 Display Configuration Settings ----------------------------------------------------------------------------------------- 22
8.3 Input Configuration Settings--------------------------------------------------------------------------------------------- 24
8.4 Output Configuration Settings ------------------------------------------------------------------------------------------ 26
8.5 Record Configuration Settings------------------------------------------------------------------------------------------ 27
8.6 Alarm Configuration Settings ------------------------------------------------------------------------------------------- 28
8.7 Report Configuration Settings ------------------------------------------------------------------------------------------ 30
8.8 Print Configuration Settings --------------------------------------------------------------------------------------------- 32
8.9 Communication Configuration Settings ------------------------------------------------------------------------------ 33
8.10 About ------------------------------------------------------------------------------------------------------------------------ 34
8.11 Configuration File Settings--------------------------------------------------------------------------------------------- 34
9. Temperature & Pressure Compensation Display Interface and Parameter Settings ----------------------------- 36
9.1 Display Interface ----------------------------------------------------------------------------------------------------------- 36
9.2 Configuration parameter Settings-------------------------------------------------------------------------------------- 37
10. How to Download Data from the Paperless Recorder ------------------------------------------------------------------ 45
11. Application of Data Analysis Software -------------------------------------------------------------------------------------- 46
11.1 Historical Graph ---------------------------------------------------------------------------------------------------------- 46

2
ARC900 Operation Manual OP900.1.1.7.R5ENG
11.2 Circular Display Curve -------------------------------------------------------------------------------------------------- 46
12. Communication Address ------------------------------------------------------------------------------------------------------- 47
12.1 Modbus Communication Wiring Diagram -------------------------------------------------------------------------- 47
12.2 Modbus Communication Address------------------------------------------------------------------------------------ 48
12.3 Modbus Illustration------------------------------------------------------------------------------------------------------- 49

3
ARC900 Operation Manual OP900.1.1.7.R5ENG
1. Features

GENERAL
ALIAPANEL ARC900 Series Paperless Recorder features the most
advanced technology. It can be applied across a broad scope of industrial
applications. ARC900 is the product which with multi-channels, complete
functions, easy operation, high accuracy, low power but high performance.
And the series overcome the old-fashioned paperless recorder, which
has less channels, multiple installation and space-consuming problem.

FEATURES
Panel type's DIN Size (144mm*144mm), 320*240 Pixels, TFT truecolor (LCD)
128MB memory installed inside, applied to long terms data record
Common input signal, mA, Include VDC, T/C, RTD, Hz..etc
High Accuracy +/-0.15% of Reading
Maximum 12 points Relay, 4 point 4-20mA output and 24VDC output
16 channels maximum input
24VDC Aux. power supply available for 2 wires system
Display/Record single point, Multi-point, Trend, Totalizer, Bargraph
The recorded data could be stored in USB memory & SD memory card
and transferred to computer for soft analysis
Outdoor type (IP65), wall-mount

STANDARD SPECIFICATION
Number of Inputs : 1-16 Channels Display : 5.6" color-screen LCD
Input : T/C (K, S, B, E, J, N, T, R,N, etc.) Trend & Bargraph : Vertical / Horizontal
: RTD, CU50, CU53, BA1, BA2 Digital : 4-1/2 digits programmable
: DCA (4-20 mA, 0-10 mA, 0-20 mA) Engineer unit : 66 different ngineering units
: DCV (0-5V, 1-5V ,0-10V, 20mV, 100mV) Parameter Protection : Password entry (6 Digits)
: Frequency (1Hz ~ 5KHz) Logging Rate : 1 Seconds ~ 1800 Seconds Per Data
: Resistance (0-175 , 0-400 ) Recording Capability : 120 Hours (16 Points, 1 Data/Second)
Accuracy : +/-0.15% of Span : 789 Years (1 Point, 1 Data/Hour)
Response Time : 50 ms PC Software : Compatible with Windows 2000/XP/Vista
Alarm Type : High & Low alarm, Incr. & Decr. alarm Display : Trend, Digital, Circular, Alarm, Bargraph
Output : 4-20 mA *4 points Maximum, Load:800 Totalizer
: Relay, 3A/250V * 12 points Maximum Convert function : Saved as excel files
: 24VDC, 65 mA *4 points Maximum Protection Class : NEMA 3 / IP54 (Panel Type) /
Digit Input : 2 Points Maximum IP65 (Outdoor Type)
Storage Memory : 128 MB (on board) Weight : 2.6 Kg maximum
Recycling Mode : Newest Data overwrites to oldest data Dimensions : 144 mm (W) * 144 mm (H) * 219 mm (D)
Recording Data Shift : USB memory (8GB) / SD Card (4GB) : 280mm (W) * 242mm (H) *157mm (D)
Display update Rate : 1 Second Ambient Temperature : -10 to +60 °C
Keypad : 6 Keys (Page, Left, Right, Up, Down, Enter) Ambient Humidity : 10% to 85%RH (at 5 to 40 °C)
for programming and display control Power Supply : 85-260VAC, 50/60Hz
Parameter Storage : Operation parameters are stored by Vibration Test : 10~60Hz ,10m/S2 for 3 hours
EEPROM for more than 10 years Power Consumption : ≤20 W
Communication : RS232 / RS485 (MODBUS Protocol)

4
ARC900 Operation Manual OP900.1.1.7.R5ENG
2. Installation & Wiring diagram
2.1 Installation Position
Please install the instrument in the following position.
 Installation Method
Two types of installation, panel mounting and wall mounting.
 Installation Position
To prevent rain and direct sunlight, the instrument should be installed indoors.
 Well-ventilated position
To prevent the internal temperature rise, the instrument should be installed in a well-ventilated position.
 Minimum mechanical vibrations
The instrument should be installed in the place with minimum mechanical vibration.
 Horizontal
When installing instrument, please do not tilt left or right, try to remain horizontal (it can be tilted back to 30°).

Note
 Condensation may occur if the instrument is moved to another place where
both temperature & humidity are higher, or if the temperature change rapidly. In
addition, measurement errors will result when using thermocouples. In this
condition, let the instrument adapt to the surrounding environment for one hour or
more before using.
 The lifespan of LCD will be shortened (lower picture quality etc.) if the
instrument is used in high-temperature environment over a long period of time.
Please do not use the instrument in high-temperature (above 40 oC) environment.

Do not install the instrument in the following position.


 In direct sunlight and near heat sources
Please install the instrument in the place with small temperature change and near normal temperature(25 oC).
Install it in direct sunlight or near heat sources that will have a bad impact on its internal circuitry.
 Where an excessive amount of soot, steam, moisture, dust, corrosive gases are present.
Soot, steam, moisture, dust, corrosive gases will have a negative impact on instrument.
 Near strong magnetic field sources
Please do not bring magnets or instruments that produce electromagnetic fields close to the instrument. If install it
near the source of strong magnetic field that will cause display error.
 Bad angle for viewing the pictures
The instrument with TFT color LCD, it is difficult to view the display from an extreme angle. So please install it in the
position that the observer can view from the front.

5
ARC900 Operation Manual OP900.1.1.7.R5ENG
2.2 Panel Type

L N

X24

X13 X14 X15 X16 X17 X18 X19 X20 X21 X22 X23

Y24

Y13 Y14 Y15 Y16 Y17 Y18 Y19 Y20 Y21 Y22 Y23

Z24

Z13 Z14 Z15 Z16 Z17 Z18 Z19 Z20 Z21 Z22 Z23

X12

X1 X2 X3 X4 X5 X6 X7 X8 X9 X10 X 11

Y12

Y1 Y2 Y3 Y4 Y5 Y6 Y7 Y8 Y9 Y10 Y 11

Z12

Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8 Z9 Z10 Z 11

Input Terminals
Input
RTD VDC/mV mA T /C Channel 1-12 X1 / Y1 / Z1 …. X12 / Y12 / Z12
X b + Frequency
Channel 13-16 X21 / Y21 / Z21 …. X24 / Y24 / Z24
Output
Relay
Y B + X13 / Y13 …. X24 / Y24
+ Channel 1-12
4-20 mA
Y9 / Z9 …. Y12 / Z12
A _ _ _ Channel 1-4
Z 24VDC
Z13 / Z14 …. Z19 / Z20
Channel 1-4

Output

X X
Relay (NO) Z13 +
24VDC
Y + Y 65mA
4-20 mA Z14 -
_
Z Z

6
ARC900 Operation Manual OP900.1.1.7.R5ENG
2.3 Outdoor Type

LN
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
R R P1 P1 P
1A 1B 1C 3A 3B 3C 5A 5B 5C 7A 7B 7C 9A 9B 9C 11 11 11 P2 P
P2 P
P3 P
A B C R1 R1 R3 R3 R5 R5 R7 R7 R9 R9 11 11 + - + - + -
P3

2A 2B 2C 4A 4B 4C 6A 6B 6C 8A 8B 8C 10 10 10 12 12 12 R R R R
A B C A B C R2 R2 R4 R4 R6 R6 R8 R8 10 10 12 12 D+ D- RA TB G
37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72

Input Teminals
T/C Input
RTD VDC/mV mA
Frequency Channel 1 - 12 1A / 1B / 1C . . . . 12A / 12B / 12C
A b + Channel 13- 16 13A / 13B / 13C . . . . 16A / 16B / 16C
Output

B B + Relay
+ Channel 1 - 12 R1 / R1 . . . . R12 / R12

A _ _ _
C Communication Rs232 or Rs485

24VDC
P1 + / P1 - . . . .P4 + /P4 -
Channel 1 - 4

Output
Rs232 Rs485

RA RXD A
R P+ +
24VDC
RB TXD B Relay (NO) 65mA

GND
R P- -
G SG

7
ARC900 Operation Manual OP900.1.1.7.R5ENG
2.4 The Connection of Input/output Signal Cables

Take measures to prevent noise from entering the measurement.


 Move the measurement circuit away from the power cable (power circuit) and ground cable.
 It is desirable that the object being measured does not generate noise. However, if this is unavoidable, isolate the
measurement circuit from the object, and ground the object being measured.
 Shielded wires should be used to minimize noise caused by electrostatic induction. Connect the shied to the ground
terminal of the instrument according to the need (please do not grounding at two points).
 For the interference caused by electromagnetic induction, if splicing the equidistant dense circuit wiring, it will be
more effective.
 The resistance of ground terminal is lower. (It should be lower than 10 ohms.)
When using the thermocouple input, please keep the temperature of input terminal stable.
 Please use input terminal cover.
 Please don't use thick cables. (Cross sectional area 0.5 mm2 or less is recommended.)
 Please try to keep external temperature stable. Large temperature fluctuations will occur if a nearby fan turns on/off.
If the input wires are connected in parallel with other instruments, that will cause signal degradation, affecting all
connected devices.
If you need to make a parallel connection, please note:
 Ground all instruments to the same point.
 Do not turn on/off another instrument during operation. Otherwise that will have a bad impact on other instruments.
 Thermal resistance can not be wired in parallel.
 Current signal can not be wired in parallel.

Warning
 To prevent electric shock, ensure the main power supply is turned off
when connecting signal cables.

3. Dimensions
3.1 Panel Type
Panel Cutout
149 mm
30 mm 219 mm +1
-
13 8 mm
149 mm

13 8 mm
+1
-
USB

EN

3.2 Outdoor Type


19 0m m
2 4 2mm

280mm 157mm 240mm

8
ARC900 Operation Manual OP900.1.1.7.R5ENG
4. Key Settings

Date/Time

4-1/2 Digits Display

Channels Engineering unit


6521.22 6589.25

Alarm
Totalizer
528.22 105.25

USB /SD Port


Key Setting
EN

4-1/2 Digits Display Date/Time


A L I A PA N E L

Group 1 2015-12-10 15:15:36

Channels CH01 C CH02 m 3/h

30. 2 530. 7
6521.22
USB /SD Port
Totalizer CH03
6589.25
Kg/h CH04 mA

52. 8 18. 0 Engineering unit


528.22 105.25

Alarm

Key Setting

Key Name Key Sign Basic Function Setting Function

Page Turning & Quit Page Turning & Quit Page Turning & Quit

Left/Right Left/Right Move Left/Right Move

Up/Down Up/Down Move Up/Down Move

ENTER EN Confirmation Confirmation

9
ARC900 Operation Manual OP900.1.1.7.R5ENG
4.1 Open protective cover
Panel Type
1. Loosen the 2 screws in the cover.
2. Gently push the cover by screwdriver or by hand.

Outdoor Type
Take the two screws as shown below.

10
ARC900 Operation Manual OP900.1.1.7.R5ENG
5. Display Type
G ro u p 1 2 0 1 0 -11 -1 8 1 5 : 1 5 : 3 6
CH01 C CH02 m 3/ h
Multichannel Display
30. 2 530. 7
Press to next page
6521.22 6589.25
CH03 Kg/h CH0 4 mA

52. 8 18. 0
528.22 105.25

Device Name 2010-11-18 15:15:36


CH01
1000.0
CH02
20.0
CH03
5000.0
CH04
450 Bar Chart Display
Press to next page.

-100.0 4.0 500.0 20


350. 2 8. 0 4995. 0 320
mmH20 mA kg/h m 3/h

Group 1 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3

Real-time Curves Display


[30s e c / Div ] Label Mode CH01
100

320. 4
80
C
CH02

60
250. 0 Press to next page.
m3/h
CH03
40

0. 78
20
Mpa
CH04

0
16. 0
Time : 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3 mA

Group 1 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3
[30s ec / Div ] Label Mode
100
CH01

320. 4
Historical Data Display
80
CH02
C
Two modes: recall mode and cursor mode.
250. 0
Press or to check channel & historical data, this is cursor mode.
60

m /h
3

CH03

Press EN and press


40

0. 78
Mpa
or to modify date & time, press or to check. This
is recall mode.
20
CH04

0
16. 0
Time : 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3 mA

Fu n c t io n 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3

Function Pictures Display


FILE

FileList St o r e o p Backup Data Print Data Press or to check file list, store operation, backup data, print data, shift report,
S D H Y daily report, monthly report, year report, alarm record, power record and system log.
Press EN to check or backup data, and press
Shi f t R pt D a il y R p t Monthly Rpt Year Rpt
to exit.
! i
Alarm Record Power Record Sys Log Press to next page.

11
ARC900 Operation Manual OP900.1.1.7.R5ENG
5.1 Status Display

The following information is displayed in the status display section during the operation mode and the configuration
mode.
1 2 3 4 5 6 7 8 9

A D F

B E G

C H

I
① Screen name column
1. Data show the combination number of screen display, if no use the combination number, and then show 【Device name】.
2. Data query screen and configuration screen show the display name.
② Ethernet flag
A: Connection is working.

B: No plug network cable.

C: IP address conflict.

③ SD Card Connection flag


D: SD card connection is working.

E: Automatic backup of data is being written. (D/E displays in turns)

No show: No SD card connector or SD card connection fails.

④ USB Device Identification


Display: USB device connects to instrument.

No Show: No USB devices connect to instrument or connection fails.

⑤ Circulation display flag


Circulation icon: Circulation displays each group.

No Show: Fixed screen, there is no circulation.

⑥ Storage recording mode flag


F icon: Recording mode is circular, the file is recording.

G icon: Recording mode is circular, the file stops recording.

H icon: Recording mode is not circular, the file is recording.

I icon: Recording mode is not circular, the file stops recording.

⑦ Relay output flag


Display icon: There is relay output.

No Show: No relay output.

⑧ AD board working state flag


No Show: The instrument is working well.

Display icon: Abnormal working state of AD board.

Note: If the instrument displays this flag that means it doesn’t function well, please contact the supplier.
⑨ Current date and time
The running date/time of the instrument

12
ARC900 Operation Manual OP900.1.1.7.R5ENG
6. The Application Examples of ARC900 and ARC900 Outdoor type
6.1 ARC 900 4-20mA Signal Application Illustration

Connect AMC2100 (ALIA electromagnetic flowmeter) converter’s 4-20mA output to ARC900’s 4-20mA input. Since
AMC2100’s 4-20mA is active input, so AMC2100’s 4-20mA output cable can be connected to ARC900 directly. If
4-20mA is positive output, power supply should be connected in series in the loop.

L N
 123.456 m3

+887.500m3/h
2016/07/18
X24

X13 X14 X15 X16 X17 X18 X19 X20 X21 X22 X23
ENT
Y24

Y13 Y14 Y15 Y16 Y17 Y18 Y19 Y20 Y21 Y22 Y23

I+ I- P+ P- R+R- Z24

Z13 Z14 Z15 Z16 Z17 Z18 Z19 Z20 Z21 Z22 Z23

X12
Power

+ Y1
X2

Y2
X3

Y3
X4

Y4
X5

Y5
X6

Y6
X7

Y7
X8

Y8
X9

Y9
X10

Y10
X 11

Y 11
Y12

Z12

- Z2 Z3 Z4 Z5 Z6 Z7 Z8 Z9 Z10 Z 11

ARC900 Input configuration setup steps are as below.

Suppose the corresponding output flow range of AMC2100 4-20mA is 0~1000m3/h.

Input 2016-07-18 15:15:36


Channel 1 D i sa b l e
Ta g 01
Unit M3 / h

C h an n e l Typ e Current
Si g n a l Typ e 4 20mA D e c. Po in t 1
Si g n a l sca l e 4 . 000 20 . 000
D ispla y Sca le 0. 0 1000 . 0
Ad j u st( KX + b ) 1 . 00 0 . 00
Bu rn o u t -.--

D a mp in g 0 . 00sec C u to ff 0. 0%

13
ARC900 Operation Manual OP900.1.1.7.R5ENG
6.2 ARC900 Temperature Transmitter Illustration
Connect ALIA PT100 to ARC900’s thermal resistance input.

Thermal resistance wiring diagram:

L N

X24

X13 X14 X15 X16 X17 X18 X19 X20 X21 X22 X23

Y24

Y13 Y14 Y15 Y16 Y17 Y18 Y19 Y20 Y21 Y22 Y23

Z24

Z13 Z14 Z15 Z16 Z17 Z18 Z19 Z20 Z21 Z22 Z23

X12

b X1 X3 X4 X5 X6 X7 X8 X9 X10 X 11

Y12

B Y1 Y3 Y4 Y5 Y6 Y7 Y8 Y9 Y10 Y 11

Z12

A Z1 Z3 Z4 Z5 Z6 Z7 Z8 Z9 Z10 Z 11

ARC900 Input Configuration setup steps are as below.

Suppose the corresponding output temperature range of PT100 is -200~650oC.

Input 2016-07-18 15:15:36


Channel 2 D i sa b l e
Ta g 02
Unit ℃

C h an n e l Typ e RTD
Si g n a l Typ e PT100 D e c. Po in t 1
Si g n a l sca l e 200 . 0 650 . 0
D ispla y Sca le 200 . 0 650 . 0
Ad j u st( KX + b ) 1 . 00 0 . 00
Bu rn o u t -.--

D a mp in g 0 . 00sec C u to ff 0. 0%

14
ARC900 Operation Manual OP900.1.1.7.R5ENG
6.3 ARC900 Outdoor Type 4-20mA Application Examples

Connect AMC2100 (ALIA electromagnetic flowmeter) converter’s 4-20mA output to ARC900’s 4-20mA input. Since
AMC2100’s 4-20mA is active input, AMC2100’s 4-20mA output cable can be connected to ARC900 directly. If 4-20mA is
positive output, power supply should be connected in series in the loop.

A L I APAN E L
Group 1 2015-12-10 15:15:36
Ch01 m3/h Ch02 C

887. 5 30. 2
6521.22 6589.25
CH03 Kg/h CH04 mA

 123.456 m3
52. 8 18. 0
+887.500m3/h 528.22 105.25
2016/07/18

ENT

I+ I- P+ P- R+R-

Power

LN
+ 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
1A 1B 1C 3A 3B 3C 5A 5B 5C 7A 7B 7C 9A 9B 9C 11 11 11 R R P1 P1 PP2 P
P2 P3
A B C R1 R1 R3 R3 R5 R5 R7 R7 R9 R9 11 11 + - + - + -
P PP3

- 10 10 10 12 12 12 R R R
2A 2B 2C 4A 4B 4C 6A 6B 6C 8A 8B 8C A B C A B C R2 R2 R4 R4 R6 R6 R8 R8 10 10 12 12 R D+ D- RA TB G

37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72

ARC900 Input Configuration setup steps are as below.

Suppose the corresponding output flow range of AMC2100’s 4-20mA is 0~1000m3/h.

Input 2016-07-18 15:15:36


Channel 1 D i sa b l e
Ta g 01
Unit M3 / h

C h an n e l Typ e Current
Si g n a l Typ e 4 20mA D e c. Po in t 1
Si g n a l sca l e 4 . 000 20 . 000
D ispla y Sca le 0. 0 1000 . 0
Ad j u st( KX + b ) 1 . 00 0 . 00
Bu rn o u t -.--

D a mp in g 0 . 00sec C u to ff 0. 0%

15
ARC900 Operation Manual OP900.1.1.7.R5ENG
6.4 ARC900 Outdoor Type Temperature Transmitter Illustration

Connect ALIA PT100 to ARC900 outdoor type’s thermal resistance input.

A L I A PA N E L
Group 1 2015-12-10 15:15:36
CH01 C Ch02 C

30. 2 50. 2
6521.22 6589.25
CH03 Kg/h CH04 mA

52. 8 18. 0
528.22 105.25

LN
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
R R P1 P1 P
1A 1B 1C 3A 3B 3C 5A 5B 5C 7A 7B 7C 9A 9B 9C 11 11 11 P2 P
P2 P
A B C R1 R1 R3 R3 R5 R5 R7 R7 R9 R9 11 11 + - + - + -
P3 P
P3

10 10 10 12 12 12 R R R
2A 2B 2C 4A 4B 4C 6A 6B 6C 8A 8B 8C A B C A B C R2 R2 R4 R4 R6 R6 R8 R8 10 10 12 12 R D+ D- RA TB G

37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72

ARC900 Input Configuration setup steps are as below.

Suppose the corresponding output temperature range of PT100 is -200~650oC.

Input 2016-07-18 15:15:36


Channel 2 Disable
Tag 02
Unit ℃
Channel Type RTD
Signal Type PT100 Dec . Point 1
Signal scale 200 . 0 650. 0
Display Scale 200 .0 650 .0
Adjust( KX + b) 1 . 00 0 . 00
Burnout -.--

Damping 0 . 00sec Cutoff 0. 0%

16
ARC900 Operation Manual OP900.1.1.7.R5ENG
7. Flow Chart
Login 2 0 1 0 -11 -1 8 1 4 :0 3 : 4 3

Password 000000

Exit

D10110126-0 10/11/10 [ 1 0 1 1 0 1 1 0]

EN

System Display Input Output


EN EN EN EN

Alias Bg Color Channel Channel

System time Brightness Disable Adjust (kX+b)

Language Direction Tag Exit

Password First View Unit

Cool Mode Group Channel Type

Factory-set Channel Signal Type

Purge data Exit Precision

Exit Signal Scale

View Scale

Adjust (kX+b)

Burnout

Filter Copy 01

Cut off Exit

17
ARC900 Operation Manual OP900.1.1.7.R5ENG

Flow Record Alarm


EN EN EN EN

LOOP Cut Record Mode Channel

Channel Volume Scale Rcd Type Relay Delay

Device Volume Unit Rcd Interval Hysteresis

Media Flow Unit Auto Backup I Alm Time

Multiple T Condition Trigger Event D Alm Time

Little Fill P Condition Purge record Alarm Type

Over Scale Finish Exit


Alarm Value

Shut Fill Relay

Local P Exit

Setting

Exit

18
ARC900 Operation Manual OP900.1.1.7.R5ENG

Report Print Comm About


EN EN EN EN

Precision Key Print Address Socket1

Settle Time Timing Print Byte Swap Socket2

Shift Nun Print Interval Baudrate Accumulation&


Report

Tag Exit Parity


Serial port
comm
From Exit

USB Port
To

SD card
Channel

Relay
Enable

Exit
Initial

Multiple

Clr Accu

Exit

19
ARC900 Operation Manual OP900.1.1.7.R5ENG

Cfg File Exit


EN

Device

File Name

Export Cfg

Device

File Name

Import Cfg

Exit

20
ARC900 Operation Manual OP900.1.1.7.R5ENG
8. Operation Instructions
8.1 System Configuration Settings
Login 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3

Input Password
In running mode, press & EN at the same time to login password.
Password 000000

Press or to move cursor, press or to set value. (Initial password: 000000)


Exit Press EN to enter next setting.
D10110126-0 10/11/10 [ 1 0 1 1 0 1 1 0]

EN

Group 1 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3

Display
System Configuration
System
Input Output
Press or to move cursor, choose System, press EN to enter System
Report Alarm

Report Print Configuration and press to quit.


Comm About
Press to enter next setting.
Cfg File Exit

EN

Alias Alias Device Name


System Time 2010-12-21 Set the device name. Use that name to create the directory of data backup and auto
backup.
Language English

Password 000000

Alias Alias Time


System Time 2016-06-10 It’s used to set date & time (year / month / day / hour / minute / second).
Press to enter next setting.
Language English
Password 000000

Alias Alias System Language


System Time 2010-12-21 English and Chinese are available.
Language English
Press or to choose and EN for confirmation.
Press to enter next setting.
Password 000000

Alias Alias Password Setting


System Time 2010-12-21 Password is required to modify configuration parameters and prevent the system
Language English parameters from being accidentally modified.
Password is composed of 6 digits. It’s not recommended to modify password.
Password 000000

Cold Junction Compensation


Cool Mode 24.5 Cold Junction Compensation is necessary when measuring temperature with
Factory-set thermocouple. There is cold junction measuring circuit In the rear of the instrument. User
can adjust cold-junction temperature which measured by instrument. There are two modes:
Purge date
auto and manual. If choose auto, you do not need to input cold junction temperature. If
Exit choose manual, you need to input cold junction temperature value.

21
ARC900 Operation Manual OP900.1.1.7.R5ENG

Cool Mode 24.5 Factory Set


Factory-set Press EN and “Reset the configuration?” will pop up. Choose Yes to restore factory
Purge date setting and No to deny.
Press to enter next setting.
Exit

Cool Mode 24.5 Purge Data


Factory-set Purge all stored data in device memory, including historical data, totalizer, shift
Purge date report, alarm list, power down record, except system log.
Exit

Cool Mode 24.5 Exit


Factory-set Press EN and “save the configuration?” will pop up. Choose Yes to save and No to deny.
Purge date Press EN to confirm the choice.
Exit

8.2 Display Configuration Settings


Login 2 0 1 0 -11 -1 8 1 4 :0 3 : 4 3

Input Password
In running mode, press & EN to login Password.
Password 000000

Press or to move cursor, press or to set value (Initial password: 000000).


Exit Press EN to enter the next setting.
D10110126-0 10/11/10 [ 1 0 1 1 0 1 1 0]

EN

Group 1 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3

System Display
Display Configuration
Input Output
Press or to move cursor, choose Display & EN to enter Display Configuration;
Report Alarm
Report Print choose to exit Display Configuration.
Comm About
Press to enter next setting.
Cfg File Exit

EN

Bg Color Black Background Color


Brightness 10 Press or to choose background color. Black and white are available.
Direction Horizontal Press to enter next setting.
First View View AII

Bg Color Black Brightness(1~10)


Brightness 10 Press or to move cursor, press or to change brightness. The higher the
Direction Horizontal value is, the brighter the screen will be. (The value can be set from 0 to10).
Press to enter next setting.
First View View AII

22
ARC900 Operation Manual OP900.1.1.7.R5ENG

Bg Color Black Curve Direction (Horizontal or Vertical)


Brightness 10 Set the curve display. (Real-time curve and historical curve have two display mode:
Direction Horizontal horizontal and vertical.)
First View View AII Press to enter next setting.

Bg Color Black First View


Brightness 10 First view will be displayed when the instrument starts.
Ex, if choose bar (bar graph), the first view is bar graph when restart.
Direction Horizontal
All view, bar, real time curve, historical curve and function view are available.
First View View AII

Group Group1 Group Display


Channel 01 02 03 4 groups in total. 1~6 channels can be selected at the same time, these channels can be
Color grouped together to create a channel group. After setting, the group will show in real time
curve page.
Exit

Group Group1 Channel


Channel 01 02 03 Select channels to group and select curve color of channel group. 1~6 channels can be
selected at the same time. After setting, the group and curve color will show in curve page.
Color
Exit

Group Group1 Exit


Channel 01 02 03 Press EN and “Save the configuration?” will pop up. Choose Yes to save and No to deny.
Color Press EN to confirm choice.
Exit

23
ARC900 Operation Manual OP900.1.1.7.R5ENG
8.3 Input Configuration Settings
Login 2 0 1 0 -11 -1 8 1 4 :0 3 : 4 3

Password Input
In running mode, press & EN to login password.
Password 000000

Press or to move cursor, press or to set value (Initial password: 000000).


Exit Press EN to enter next setting.
D10110126-0 10/11/10 [ 1 0 1 1 0 1 1 0]

EN

Group 1 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3

System Display Input Configuration


to move cursor to choose Input, press EN to enter input configuration
Input Output
Report Alarm Press or
Report
Comm
Print
About
and press to exit.
Press to enter next setting.
Cfg File Exit

EN

Channel 1 Channel
Disable □ Choose channel number which corresponds to input terminal for parameter setting.
Tag ADP9000 Press to enter next setting.
Unit mmH2O

Channel 1
Channel Disable
Disable 
Press or to move cursor and or to choose. If √, it means this channel
Tag ADP9000 is closed, the measurement interface will not be displayed.
Unit mmH2O Press to enter next setting.

Channel 1 Tag Display


Disable □ Display the name of this channel, it can be modified.
Tag ADP9000
Unit mmH2O

Channel 1 Engineering Unit


Disable □ Press or to move cursor, press or to choose engineering unit,
Tag ADP9000 press EN to confirm.
Unit mmH2O
Available units: km3/h, t/h, L/h, kg/h, m3/h, Nm3/h, kNm3/h, oC, F, bar, mbar, mmH2O,
mmHg, Pa, kPa, MPa, mA, A, mv, mg/L, g/L, Kg/m3, m/min, m/s etc. You can also press
"EN" key to set units which the recorder doesn’t have.
Press to enter next setting.

Channel Type Current Channel Type


Signal Type 4 -20mA Select corresponding input signal types. Including current, voltage, resistance, TC, RTD,
Precision 2 ordinary vacuum, sub-vacuum, square root, simulate etc.
Signal scale 4.00- 20.00
Press to enter next setting.

24
ARC900 Operation Manual OP900.1.1.7.R5ENG

Channel Type Current Signal Type


Signal Type 4 -20mA Signal type will change if input channel type is selected. E.g., if channel type is current,
signal type will automatically change to current, such as 4-20mA.
Precision 2
Press or can choose 0-20 mA, 0-10 mA or 4-20mA+
Signal scale 4.00- 20.00
Note: If choose 4-20mA +, the actual acceptable signal value is 3-21mA. The
corresponding value of 3-21mA can be seen on display interface.

Channel Type Current Decimal Point(0~3)


Signal Type 4 -20mA Decimal places: 0~3, Decimal places are related to range setting.
The smaller the value is, the greater the range can be set.
Precision 2
For example, if decimal place is set to 0, range can be set from -9999 to 30000.
Signal scale 4.00- 20.00 If decimal place is set to 3, range can be set from -9.999 to 30.000

Channel Type Current Signal Scale


Signal Type 4 -20mA Press or to move cursor, press EN to modify signal scale. Generally, signal
Precision 2 scale does not need to be modified. This scale varies with Signal Type.
Press to enter the next setting.
Signal scale 4.00- 20.00

View scale 0.00- 100.0 View Scale


Adjust(k×+b) 1.00 0.00 Set the corresponding view scale value of signal scale.
Burnout ―.―― E.g.: 4-20mA corresponds to the value of 0~100, so you should input 0.00~100.0 in view
scale.
Filter 0.0 sec

Adjust (k×+b)
View scale 4.00- 20.00
When the input signal value has error, it can be fine-tuned.
Adjust(k×+b) 1.00 0.00 Adjustment formula: Display value = Measured value × K + B, K value defaults to 1. B
Burnout ―.―― value defaults to 0.
Suppose: After input 4 mA, display value should be 0 but shows 1, so B value can be set to
Filter 0.0 sec -1, the display value will change to 0.

View scale 4.00- 20.00 Burnout


Adjust(k×+b) 1.00 0.00 Press or to move cursor, press or to choose burnout type, and press
Burnout ―.―― EN to confirm. Press to enter next setting.
Filter 0.0 sec E.g.: When signal is not connected or break off, if burnout is ―.――, the interface will
show ―.――.

Filter (0~9.9s)
View scale 4.00- 20.00
Set filter response. The higher the value that the more stable. On the contrary, the display
Adjust(k×+b) 1.00 0.00 is faster.
Burnout ―.―― E.g.: When filter parameters is 1.0 second, previous collected data is S0=10mA, current
collected data is S1=5mA. Filter parameter is set to f = 1, then (f * S0 + S1) / (1 + f) = 7.5mA.
Filter 0.0 sec

25
ARC900 Operation Manual OP900.1.1.7.R5ENG

Cut 0.0% Low Cutoff (0~9.9%)


Copy 01 Set low cutoff value, range: 0-9.9%. When input signal is less than this value, it will be
cutoff automatically, the displayed value is the lower limit of range.
Exit

Cut 0.0% Copy 01


Copy 01 Press or to move cursor, press or to copy parameters from other
Exit channels.
After copying, the parameters of current channel are the same as the parameters of
source-channel.

Cut 0.0% Exit


Copy 01 Press EN and “save the configuration?” will pop up. Choose Yes to save and No to deny.
Exit Press EN to confirm choice.

8.4 Output Configuration Settings


Login 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3

Password Input
In running mode, press & EN to login password.
Password 000000

Press or to move cursor, press or to set value (Initial password: 000000).


Exit Press EN to enter next setting.
D10110126-0 10/11/10 [ 1 0 1 1 0 1 1 0]

EN

Group 1 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3

Output Configuration
System Display
Input Output Press or to move cursor to choose Output, press EN to output configuration,
Report Alarm
Report Print and press to exit.
Comm About
Press to enter next setting.
Cfg File Exit

EN

Channel 01 Channel
Adjust(k×+b) 1.00 0.00 E.g.: Choose the corresponding 4-20mA output of channel 1.
Exit Press to enter next setting.

Channel 01 Adjust (k×+b)


Adjust(k×+b) 1.00 0.00 If output current isn’t accurate, it can be adjusted.
Exit E.g.: If original channel scale is 0~100℃, and current scale is 26℃, theoretical output
current is 8.16mA, actual output current is 8mA, you can modify b to 0.16, and output
current will turn to be 8.16mA.

26
ARC900 Operation Manual OP900.1.1.7.R5ENG

Channel 01 Exit
Adjust(k×+b) 1.00 0.00 Press EN and “save the configuration?” will pop up. Choose Yes to save and No to deny.
Exit Press EN to confirm choice.

8.5 Record Configuration Settings


Login 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3

Password Input
In running mode, press & EN to login password.
Password 000000

Press or to move cursor, press or to set value (Initial password: 000000).


Exit Press EN to enter next setting.
D10110126-0 10/11/10 [ 1 0 1 1 0 1 1 0]

EN

Group 1 2 0 1 0 -11 -1 8 1 4 :0 3 : 4 3

System Display
Record Configuration
Input
Report
Output
Alarm
Press or to move cursor to choose Record, press EN to enter Record
Report Print Configuration, and press to exit record configuration.
Comm About
Press to enter next setting.
Cfg File Exit

EN

Record Mode Cyclic Record Mode


Rcd Type Real Circular and non-circular are available.
Cyclic: When the last record file in the instrument is full, it will continue to record from the
Rcd Interval 1 sec
first paper, on the basis of replacing the old file by the new file to record historical data
Auto Backup □ circularly.
Acyclic: When the last record file is full, it stops recording automatically.

Record Mode Cyclic Record Type


Rcd Type Real Four types: real-time value, average value, minimum value and maximum value.
Rcd Interval 1 sec
Auto Backup □

Record Interval
Optional time (1s, 2s, 5s, 10s, 30s, 1min, 2min, 5min, 10min and 30 min).
Record Mode Cyclic
The larger the optional time set, the longer the record time will be.
Rcd Type Real Channel 1, record interval: 1s, record time: 80 days. Record interval: 2s, record time:
Rcd Interval 1 sec 160days. Record interval: 10s, record time: 2 years&2 months. Record interval: 1 min,
record time: 13 years&2 months. Record interval: 2 min, record time: 26 years&4 months.
Auto Backup □ Record interval: 5 min, record time: 66 years. 16 Channels, record interval: 1s, 2s, 10s, 1m,
2m and 5m, corresponding time: 5 days, 10 days, 50 days, 300 days, 1 year&6 months, 4
years.

Record Mode Cyclic Auto Backup


Rcd Type Real Every day at 00:00, the instrument will automatically back up historical data to SD card.
Rcd Interval 1 sec Press or to move cursor, press EN to choose, and √ means auto backup.
Auto Backup  Press to enter next setting.

27
ARC900 Operation Manual OP900.1.1.7.R5ENG

Trigger Event Power on


Trigger Event
Available to set data storage type, the trigger includes manual, alarm, relay, switch, timer,
Purge record
power on.
Exit 1. Manual: start/stop the data storage records manually in storage interface. 2. Alarm:
when alarm occurs in channel, it starts recording data storage; when alarm ends, it stops
recording. 3. Relay: when corresponding relay alarm occurs in channel, it starts data
storage records; at the end of the relay alarm, it stops recording. 4. Switch: the instrument
with external switchgear, it will implement data storage records when switch on and stop
when switch off. 5. Timer: timing cycle is fixed at 24 hours, set start time and end time for
the instrument so that it can only implement data storage records at the setting time.
6. Power on: after the instrument is powered on to start, it will automatically create new file
and start recording data.

Trigger Event Power on Purge Record


Purge record Clear historical data, total accumulation, accumulative reports, alarm list and power-down
record in the instrument memory except system log.
Exit

Trigger Event Power on Exit


Purge record Press EN and “save the configuration?” will pop up. Choose Yes to save and No to deny.
Exit Press EN to confirm choice.

8.6 Alarm Configuration Settings


Login 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3

Password Input
In running mode, press & EN to login password.
Password 000000

Press or to move cursor, press or to set value (Initial password: 000000).


Exit Press EN to enter next setting.
D10110126-0 10/11/10 [ 1 0 1 1 0 1 1 0]

EN

Group 1 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3

Alarm Configuration
System Display
Input Output
Press or to move cursor to choose Alarm, press EN to enter alarm
Report Alarm

Report Print configuration, and press to exit alarm configuration.


Comm About
Press to enter next setting.
Cfg File Exit

EN

Channel 1 Alarm Channel


Relay Delay 1 sec Press or to move cursor, press or to choose alarm channel.
Hysteresis 0.00 Press to enter next setting.
I Aim Time 1 sec

Channel 1 Relay Delay(0~10s)


Relay Delay 1 sec Press or to move cursor, press or to choose relay delay time. (Relay
Hysteresis 0.00 delay time after alarm occurs).
Press to enter next setting.
I Aim Time 1 sec

28
ARC900 Operation Manual OP900.1.1.7.R5ENG

Channel 1 Hysteresis(0~300)
Relay Delay 1 sec Hysteresis range of H/L’s eliminating alarm. Suppose choose H alarm, alarm value is set to
25, hysteresis is set to 1, when the project is greater than 25, alarm occurred. When the
Hysteresis 0.00
project is less than 24, then eliminate alarm. Suppose choose L alarm, alarm value is set to
I Aim Time 1 sec 25 and hysteresis is set to 1, when the project is less than 25, alarm occurred. When the
project is greater than 26, then eliminate alarm.

Channel 1 I Alm. Time


Relay Delay 1 sec Increase alarm interval time. It’s set for I alarm of alarm type. Setting range: 0 ~ 32 seconds.
Suppose I Alarm value is 25, time is 3S, if time is up to 25 in 3 seconds, alarm will occur.
Hysteresis 0.00
I Aim Time 1 sec

D Alm Time 1sec D Alm. Time(0~32s)


Alarm Type OFF Decrease alarm interval time. It’s set for D alarm of alarm type. Setting range: 0 ~ 32
seconds.
Alarm Value 0.00
Suppose D Alarm value is 25, time is 3S, if it is down to 25 in 3 seconds, alarm will occur.
Relay OFF

D Alm Time 1sec Alarm Type


Alarm Type OFF Optional alarm types: H(High alarm), L(Low alarm), I(Increase alarm), D(Decrease alarm).
Alarm Value 0.00
Relay OFF

D Alm Time 1sec Alarm Value


Alarm Type OFF Set alarm value.
Alarm Value 0.00
Relay OFF

D Alm Time 1sec Relay


Alarm Type OFF Corresponding relay output of alarm. 24 channels in total. When multiple alarms use the
same relay output, and use the logic output.
Alarm Value 0.00
Relay OFF

Exit Exit
Press EN and “save the configuration?” will pop up. Choose Yes to save and No to deny.
Press EN to confirm.

29
ARC900 Operation Manual OP900.1.1.7.R5ENG
8.7 Report Configuration Settings
Login 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3

Password Input
In running mode, press & EN to login password.
Password 000000

Press or to move cursor, press or to set value (Initial password: 000000).


Exit Press EN to enter the next setting.
D10110126-0 10/11/10 [ 1 0 1 1 0 1 1 0]

EN

Group 1 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3

System Display
Report Configuration
Input
Report
Output
Alarm
Press or to move cursor to choose Report, press EN to enter statement
Report Print configuration, and press to exit.
Comm About
Press to enter the next setting.
Cfg File Exit

EN

Precision 1 Decimal Point(0~2)


Settle Time 23 hour Set the decimal digits of the accumulation value of all channels in the instrument reports.
Shift Nun 2
Tag A

Precision 1 Settle Time(00~23 Hr)


Settle Time 23 hour From the settlement time to the next settlement time point, it can be regarded as the
Shift Nun 2 accumulation per day since the startup of the accumulation function.

Tag A

Precision 1 Shift No.


Settle Time 23 hour The number of shift report per day, and the input range: 2~5.
Shift Nun 2

Tag A

Precision 1 Tag
Settle Time 23 hour Display tag. Tag name can be set according to the actual situation. After setting, it can be
seen in accumulative reports of the function screen.
Shift Nun 2

Tag A

From 00.30 Start Time


To 08.30 Start time of every class, 24-hour clock.

30
ARC900 Operation Manual OP900.1.1.7.R5ENG
From 00.30 End Time
To 08.30 End time varies with start time.

Channel 01 Channel
Enable OFF Press or to move cursor, press or to choose about-to-open totalizer
Initial 0.00 channel. Press to enter next setting.
Multiple 1.00

Channel 01 Enable
Enable OFF Press or to move cursor, press or to choose “OFF” or “ON”.
Initial 0.00 Press to enter next setting.
Multiple 1.00

Channel 01 Initial
Enable OFF Set initial value of accumulation, after setting you need to click clear accumulation so that
desktop will show the initial value you set.
Initial 0.00
Multiple 1.00

Channel 01 Multiple
Enable OFF Default value: 1. Multiple can be modified according to actual situation.
Initial 0.00
Multiple 1.00

Clr Accu Clear Accumulation


Exit Clear the accumulation of current channel.

Clr Accu Exit


Exit Press EN and “save the configuration?” will pop up, choose Yes to save and No to deny.
Press EN to confirm.

31
ARC900 Operation Manual OP900.1.1.7.R5ENG
8.8 Print Configuration Settings
Login 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3

Password Input
Password 000000
In running mode, press & EN to login password.
Press or to move cursor, press or to set value. (Initial password: 000000).
Exit Press EN to enter next setting.
D10110126-0 10/11/10 [ 1 0 1 1 0 1 1 0]

EN

Group 1 2 0 1 0 -11 -1 8 1 4 :0 3 : 4 3

System Display
Print Configuration
Input
Report
Output
Alarm
Press or to move cursor to choose Print, press EN to enter Print Configuration,
Report Print and press to exist.
Comm About
Press to enter next setting.
Cfg File Exit

EN

Key Prin Key Print


□Timing Print After choose Key Print, press or to print.
Print Interval 00 H 00 M
Exit

□Key Print Timing Print


Timing Print After choose Timing Print, the default print time is 00:00:00.
It prints real-time data and totalizer regularly according to print intervals.
Print Interval 00 H 00 M
Exit

□ Key Print Print Interval


□Timing Print After choose Timing Print, press or to move cursor to Print Interval.
Print Interval 00 H 00 M Press or to set the print interval time you need.
Exit

□ Key Print Exit


□ Timing Print
Press EN and “save the configuration?” will pop up, choose Yes to save and No to deny.
Exit Press EN to confirm.

32
ARC900 Operation Manual OP900.1.1.7.R5ENG
8.9 Communication Configuration Settings
Login 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3

Password Input
In running mode, press & EN to login password.
Password 000000
Press or to move cursor, press or to set value (Initial password: 000000).
Exit Press EN to enter next setting.
D10110126-0 10/11/10 [ 1 0 1 1 0 1 1 0]

EN

Group 1 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3

System Display Communication Configuration


Input Output
Report Alarm Press or to move cursor to choose Comm., press EN to enter Communication
Report
Comm
Print
About
Configuration, and press to exit.
Press to enter next setting.
Cfg File Exit

EN

Address 001 Address(0~247)


Byte Swap 1-2 3-4 Press or to move cursor, press or to choose address.
Baudrate 9600 Press to enter next setting.
Parity None

Address 001 Byte Swap


Byte Swap 1-2 3-4 Optional: 1-2 3-4, 2-1 4-3, 3-4 1-2, 4-3 2-1. It’s used in communication. Suppose byte is set
to 2-1 4-3, reading is 4E 02 00 01, if byte is set to 1-2 3-4, reading is 02 4E 01 00. For
Baudrate 9600 details, please refer to page 33. Default: 2-1 4-3.
Parity None

Address 001 Baud Rate


Byte Swap 1-2 3-4 Optional: 1200 / 2400 / 4800 / 9600 / 19200 / 38400 / 57600 / 115200. Default value: 9600.
Baudrate 9600 Press or to move cursor, press or to choose baud rate, and press EN
Parity None to confirm. Press to enter next setting.

Address 001 Parity


Byte Swap 1-2 3-4 Optional: no parity, odd parity, even parity. Default value: no check.
Baudrate 9600 Press or to move cursor, press or to choose parity.
Parity None Press to enter next setting.

Exit Exit
Press EN and “save the configuration?” will pop up. Choose Yes to save and No to deny.
Press EN to confirm.

33
ARC900 Operation Manual OP900.1.1.7.R5ENG
8.10 About
Login 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3

Password Input
Password 000000
In running mode, press & EN to login password.
Press or to move cursor, press or to set value (Initial password: 000000).
Exit
Press EN to enter next setting
D10110126-0 10/11/10 [ 1 0 1 1 0 1 1 0]

EN

Group 1 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3

System Display
System Information
Input
Report
Output
Alarm
Press or to move cursor to choose About, press EN to enter About, and
Report Print press to exit.
Comm About
Press to enter next setting.
Cfg File Exit

EN

Socket1:Anglong Input:8 System Information


Socket2:Anglong Input:8 Blue Font (Socket1: Analog Input 8) is meter innate AD info.; Black Font (Socket2: Analog
Accumulation&Report Input 8) is ex-AD info.. If both disaccord, which means AD board has breakdown.
Serial port comm

USB port System Information


SD card System Info. Is for checking the functions you purchased are the same as you want. You
Relay:6 can not modify the system info.
Exit Press or to move cursor to Exit, and press EN to exit.

8.11 Configuration File Settings


Login 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3

Password Input
In running mode, press & EN to login password.
Password 000000
Press or to move cursor, press or to set value (Initial password: 000000).
Exit Press EN to enter next setting.
D10110126-0 10/11/10 [ 1 0 1 1 0 1 1 0]

EN

Group 1 2 0 1 0 -11 -1 8 1 4 :0 3 : 4 3

System Display
System Configuration
to move cursor to choose Cfg File, Press EN to enter Report
Input Output
Report Alarm
Press or
Report Print
Configuration, and press to exit.
Comm About

Press to enter next setting.


Cfg File Exit

EN

34
ARC900 Operation Manual OP900.1.1.7.R5ENG
Device SD Card Press or to move cursor,press or to choose to save the export file in U
File Name CFG000.RCZ disk or SD card, file name can be modified, then the export file will display with this file
Export Cfg name. After setting, press or to move cursor to choose export configuration, press
EN to export configuration. If finished, “export complete” will hint in the lower left corner.

Device SD Card
File Name CFG000.RCZ
Export Cfg

Device SD Card
File Name CFG000.RCZ
Export Cfg

Device SD Card Press or to move cursor, press or to choose to save the export file in U
File Name CFG000.RCZ disk or SD card,
Inport Cfg Press or to choose the file you want to import and press or to
move cursor to choose import configuration, press EN to import configuration. If
finished, “import complete” will hint in the lower left corner.
If you want to set multiple instruments with the same type and the same
configuration, you can only configure one of the instruments to export the
configuration file in this instrument, and the remaining instruments only need to
Device SD Card import the configuration file, which simplifies multi-channel configuration
File Name CFG000.RCZ operation.
Inport Cfg Press or to move cursor to choose import configuration, press EN to confirm.

Device SD Card
File Name CFG000.RCZ
Inport Cfg

Exit Exit
Press or to move cursor to choose Exit, and press EN to confirm.

35
ARC900 Operation Manual OP900.1.1.7.R5ENG
9. Temperature & Pressure Compensation Display Interface and Parameter Settings

9.1 Display Interface


Group 1 2010-11-18 15:15:36

Temperature & Pressure Compensation Display Interface


1 49. 7
m3 /h

Press to enter the next page.


101.00
Type : S aturated S team
Temperature :28 .5 ℃ Pressure :
0 56MP
. a

P ressure Difference :1 .06K P a


Density : 0 . 03kg /m 3

Alias 2016-06-10 15:15:36

C h0 1 % C h02 % C h03 %
Multichannel Display Interface
33 . 2 3 1. 2 2 6.7
2 52 1.2 2
C h0 4
21 .2 2
% C h05
2 1.9 2
% C h06 % Press to enter the next page.
45 . 8 7 3. 5 1 2. 2
5 21 .22 33 21.22 1 02 1.22
C h0 7 % C h08 % C h09 %

88 . 2 1 0. 2 3 1. 1
2 1. 22 1.2 2 2 02 1.22
C h0 1 0 %C h11 % C h12 %

1. 2 8. 7 5 0. 9
2 52 8.2 2 10 021 .2 2 7 72 1.22

Device Name 2010-11-18 15:15:36


CH01
1000.0
CH02
20.0
CH03
5000.0
CH04
450 Bar Graph Display Interface
Press to enter the next page.

-100.0 4.0 500.0 20


350. 2 8. 0 4995. 0 320
mmH20 mA kg/h m 3/h

Group 1 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3

Real-time Curve Display


[30s ec / Div ] Label Mode CH01
100

320. 4
80
C
CH02

60
250. 0 Press to enter the next page.
m3/h
CH03
40

0. 78
20
Mpa
CH04

0
16. 0
Time : 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3 mA

Group 1 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3
[30s ec / Div ] Label Mode
100
CH01

320. 4
Historical Record Curve Display
Press EN and press EN
C
or to modify date, press to confirm; press or
80
CH02

250. 0
to view channel and corresponding historical data.
60

m3/h
CH03
40

20
0. 78
Mpa
Press to enter the next page.
CH04

0
16. 0
Time : 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3 mA

Query 2010-11-18 14:03: 43

Function Interface
!
B ac k up D ata Print D ata Backup R pt Al a rm L i st Press or to view file list, store operation, backup data, print data, shift report,
S D H Y
daily report, monthly report, year report, alarm record, power record, system log.
Sh i f t R p t D a ily R p t Mo n th l y R p t Ye a r R p t
Press EN to enter or backup data, press to exit.
i
Po w e r R e co rd Sys L o g Press to enter the next page.

36
ARC900 Operation Manual OP900.1.1.7.R5ENG
9.2 Configuration parameter Settings
Login 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3

Password Input
In running mode, press & EN at the same time to login password.
Password 000000

Press or to move cursor, press or to set value. (Initial password: 000000)


Exit Press EN to enter next setting.
D10110126-0 10/11/10 [ 1 0 1 1 0 1 1 0]

EN

G ro up 1 2010-11-18 14: 03: 43

Sy s te m In p u t
Flow Configuration
Ou tp u t F lo w
Press or to move cursor to choose Flow, and press EN to enter flow configuration.
Ala rm Dis p la y

Rep o rt Prin t Press , and press EN to exit flow configuration.


Co mm Ab o u t
Press to enter next setting.
Ex it

EN

LOOP LOOP01 Flow Compensation Loop 01


Channel Chnl03 Press or to choose flow compensation loop, 12 compensation channel maximum.
Device Vortex mA
After selected, it will be showed in Temp&Pressure compensation interface.
Press to enter next setting.
Media Steam

LOOP LOOP01 Flow Channel 02


Channel Chnl02 Press or to choose channel, namely choose the channel which you want to
Device Vortex mA
compensate.
Press to enter next setting.
Media Steam

Measuring Device
LOOP LOOP01
Press or to choose measuring device: “None, orifice, vortex Fr, vortex mA”,
Channel Chnl02
Chnl03 among which “vortex Fr” means measuring device is vortex, and its output signal is
Device Horizontal
Vortex mA frequency. “vortex mA” means measuring device is vortex, and its output signal is 4~20mA.
Media Steam Press to enter next setting.

LOOP LOOP01 Measuring Medium


Channel Chnl02 Press or to choose measuring medium:”None, steam, water and common gas”.
Device Vortex mA Press to enter next setting.
Media Steam

Multiple 1.0 Totalizer Multiple


Little Fill Chnl02 Press or to move cursor, press EN to change value.
Over Scale 100% Default value: 1. According to the actual situation to modify Multiple.
Shut Fill 0% Press to enter next setting.

37
ARC900 Operation Manual OP900.1.1.7.R5ENG

Multiple 1.0 Little Flow Fill


Little Fill 0% 0% Press or to move cursor, press or to choose little fill, the first
Over Scale 100% percentage is for little flow limit, the second is compensated percentage.
Percentage (%) is for range, if flow rate is lees than the first percentage value, flow totalizer
Shut Fill 0% will compensate as the second setting percentage.
Press to enter next setting.

Multiple 1.0 Over Scale


Little Fill 0% 0% When flow rate is over the upper limit of range, recorder will totalize flow by
Formula [Flow Range × Over Fill Value].
Over Scale 100% Suppose over scale is set as 115% and range set as 20m3/h,actual flow rate is 50m3/h,
Shut Fill 0% then recorder will totalize as [20*115%=23], but the displayed flow rate is still 20m3/h.

Multiple 1.0 Shut Fill


Little Fill 0% 0% Press or to move cursor, press or to choose power down fill. If recorder
is power down suddenly, it will compensate the totalizer lost during shut down.
Over Scale 100%
Compensated totalizer=Shut Fill%×Flow Range×Shut Time
Shut Fill 0%
Press EN to enter next setting

Shut Fill 0% Local Pressure


Local P 0.1013Mpa Press or to move cursor, press or to choose local pressure.
Setting Press EN to enter next setting.
EXIT

Parameter Setting
Shut Fill 0%
Press or to move cursor, press EN to enter parameter setting.
Local P 0.1013Mpa
Press EN to enter next setting.
Setting
EXIT

Cut 0.0% Low Cutoff


Volume Scale:0.00 100.00 Press or to move cursor, press or to choose value.
Volume Unit m3/h Set low cutoff value, range: 0-9.9%. When input signal is less than this value, it will be cutoff
automatically, the display value is the lower limit of range.
Flow Unit t/h
Press EN to enter next setting.

Cut 0.0% Volume Scale


Volume Scale:0.00 100.00 Press or to move cursor, press EN to set volume scale.
Volume Unit m3/h V Press EN to enter next setting.
Flow Unit t/h V

38
ARC900 Operation Manual OP900.1.1.7.R5ENG

Cut 0.0% Volume Unit


Volume Scale:0.00 10.00 Press or to move cursor, press or to choose unit.
Volume Unit m3/h V Press EN to enter next setting.
Flow Unit t/h V

Cut 0.0% Flow Unit


Volume Scale:0.00 100.00 Press or to move cursor, press or to choose unit.” t/h, kg/h” are optional.
Volume Unit m3/h Press EN to enter next setting.
Flow Unit t/h

T Condition Temperature Condition


P Condition Choose temperature input channel.
If input temperature signal in channel 4, choose channel 4 as temperature signal source.
Finish
If temperature is fixed, you can manually set temperature value.
Default temperature unit: oC.

T Condition Pressure Condition


P Condition Choose pressure input channel.
If input pressure in channel 5, choose channel 5 as pressure signal source.
Finish
If pressure is fixed, you can manually set pressure value.
Default pressure unit: Mpa.

Design Temp Finish


Design Pres Press or to move cursor, press EN to confirm that parameter is set.
Finish Press EN to enter flow configuration setting.

Shut Fill 0% EXIT


Local P 0.1013Mpa Press EN and “save the configuration?” will pop up. Choose Yes to save and No to deny.
Setting Press EN to confirm choice.
EXIT

39
ARC900 Operation Manual OP900.1.1.7.R5ENG
Below is an example to illustrate ARC900’s temperature & pressure compensation function among AVF7000, APT8000
and ATT1000. See diagram below:

AVF 7 0 0 0

APT 8 0 0 0 AT T 1 0 0 0

ARC9 0 0

RS4 8 5 / 2 3 2

Co m p u te r

Step 1. Channel
AVF7000’s 4-20mA output to ARC900’s 1st channel.
APT8000 4-20 mA output to ARC900’s 2nd channel.
ATT1000 to ARC900’s 3rd channel.

40
ARC900 Operation Manual OP900.1.1.7.R5ENG
1.1 Channel Wiring Diagram/ Connection

AVF7000’s 4-20mA output to ARC900:

ARC900 Z

mA

AVF7000

APT8000’s 4-20mA output to ARC900:

ARC900 Z

mA

APT8000

ATT1000 and ARC900:

ARC900 X Y Z

PT100

41
ARC900 Operation Manual OP900.1.1.7.R5ENG
Step 2. Input Channel Settings
2.1 Flow Settings

Suppose AVF7000’s flow range is 0~100 m3/h before compensation and 0~300kg/h after compensation, two interfaces
should be set for flow channel: one is flow configuration while other is input configuration.
Here AVF7000’s input signal (like 4-20mA) and flow range 0~100 m3/h (before compensation) need to be set.

Input 2016-06-10 15:15:36

Ch a n n e l 1

Ta g 01

Un it m3 / h

Ch a n n e l Ty p e C u rre n t
Sig n a l Ty p e 4 2 0 mA
Sig n a l s c a le 4 . 000 2 0. 0 0 0

View s c a le 0 . 00 1 0 0. 0 Pre c is io n 1

Ad ju s t ( KX + b ) 1. 0 0 0. 0 0

Bu rn o u t -.--

C lrAc c u 01 C opy 01 E x it

Note: suppose compensated flow channel is channel 1, the display range in channel 1 will be compensated range. Unit
change to “kg/h” ,View scale change to 0~300.
To set uncompensated range, it has to be achieved by entering “flow configuration→setting” as 2.4. For other channels,
it’s the same way as described here.

2.2 Pressure Channel Settings

Set input type (like 4-20mA) and display range (0~3Mpa).

Note: the default unit for compensated pressure is Mpa, so Mpa range needs to be set.

Input 2016-06-10 15:15:36

Ch a n n e l 2

Ta g 02

Un it MPa

Ch a n n e l Typ e C u rre n t
Sig n a l Ty p e 4 2 0 mA
Sig n a l sca le 4 . 000 2 0. 0 0 0

View sca le 0 . 00 3. 0 Pre c isio n 1

Ad ju s t ( KX + b ) 1. 0 0 0. 0 0

Bu rn o u t -.--

C lrA c c u 01 C opy 01 E x it

42
ARC900 Operation Manual OP900.1.1.7.R5ENG
2.3 Temperature Channel Settings

Set input type (like PT100) and display range (-200~650°C).

Note: the default unit for compensated temperature is °C, so °C range needs to be set.

Input 2016-06-10 15:15:36

Ch a n n e l 3

Ta g 03

Un it ℃
Ch a n n e l Typ e RTD
Sig n a l Typ e PT1 0 0
Sig n a l sca le - 2 0 0. 0 6 5 0. 0

View sc a le -2 0 0. 0 6 5 0. 0 Pre cis io n 1

Ad ju st ( KX + b ) 1. 0 0 0. 0 0

Bu rn o u t -.--

C lrAc c u 01 C opy 01 E x it

2.4 Flow Configuration Settings

Set channels for temp&pressure compensation, pressure, temperature and other parameters.
Method: enter flow configuration and then enter setting. See picture below:

F low 2016-06-10 15:15:36

L OOP L OOP0 1

Ch a n n e l C h n l0 1

De v ice Vo rte x mA

M e d ia Ga s

M u ltip le 1 . 00

L ittle Fill 0% 0%

Ove r Sca le 1 0 0%

Sh u t F ill 0%

L o ca l P 1. 0 0

S et t ing Finis h

43
ARC900 Operation Manual OP900.1.1.7.R5ENG

Setting 2016-06-10 15:15:36

Cut 0. 3%

Volume Scale 0. 0 100 . 0

Volume Unit m3 / h

Flow Unit Kg / h

T Condition Input Channel02 ℃

P Condition Input Channel03 MPa

Finish

After compensated channel interface is set, shift to main interface to display temp&pressure compensation interface.
See picture below:

Group 1 2016-06-10 15:15:36

1 49. 7
K g/h

1 0 1 .0 0
Type: Gas
Temperature : 28 .5 ℃ Pressure :0 . 26MPa

Density : 4.175kg /m3

Temperature 28.5oC: Measured temperature in channel 3.


Pressure 0.26 MPa: Measured pressure in channel2.
4.175kg/m3: compensated density.
49.7 kg/h: The value after temp. & pressure compensation.

44
ARC900 Operation Manual OP900.1.1.7.R5ENG
10. How to Download Data from the Paperless Recorder
1. Ensure FAT32 USB drive format. If not, please set it to FAT32. (Note: Max. USB capacity is 8GB and SD card 4GB)
2. Ensure enough USB drive storage capacity and should be more than recorder’s internal storage memory (Not less
than 4MB).
3. Plug USB drive into USB slot or SD card in front of recorder.
File Name: “Default Format: DAT+’S/N’ (S/N is editable)
Report Name: “Default Format: RPT+’S/N’(S/N is editable).
It will create a data file in USB drive or SD card (e.g.: DAT001.RDZ).
The data will be automatically saved in the file. During data transfer, do not plug out USB drive or SD card, otherwise
paperless recorder will not work normally. If abnormality occurs, plug out USB drive or SD card and follow step 1 & step
2 as above.
After USB drive plug-in, shift to “Backup Data” to check progress of exported data.
Fu n c t io n 2 0 1 0 -11 -1 8 1 4 : 0 3 : 4 3

FILE
Choose Backup
Press or to move cursor, choose Backup Data, and press EN to enter.
FileList St o r e o p Backup Data Print Data

S D H Y

Shi f t R pt D a il y R p t Monthly Rpt Year Rpt

! i
Alarm Record Power Record Sys Log

Backup Content Sys Log Backup Content


FileNameRPTM000.CSV Press or to move cursor, press or to choose backup content. Including
Backup(USB) all history files, single history file, alarm list, power record, system log, shift report, daily
report, monthly report, year report.
Backup(SD)
Press EN to confirm. Press to enter next setting.

Backup Content Sys Log File Name


FileNameRPTM000.CSV Press or to move cursor, and press EN to modify file name.
Backup(USB) Press to enter next setting.
Backup(SD)

Backup Content Sys Log Backup USB


Choose to use USB for data back-up.
FileNameRPTM000.CSV
You can check backup progress below. If finished, “Backup Complete” will hint in the lower
Backup(USB) left of screen.

Backup Content Sys Log Backup SD


FileNameRPTM000.CSV Choose to use SD card for data back-up.
Backup(USB) You can check backup progress below. If finished, “Backup Complete” will hint in the lower
Backup(SD) left of screen.

45
ARC900 Operation Manual OP900.1.1.7.R5ENG
11. Application of Data Analysis Software
1. Insert USB drive into computer and if you need to permanently save data, please copy the data to hard drive of
computer.

2. Run “DMR.exe”, click “Open historical data”. Check the pictures:

11.1 Historical Graph

11.2 Circular Display Curve

46
ARC900 Operation Manual OP900.1.1.7.R5ENG
12. Communication Address
12.1 Modbus Communication Wiring Diagram

ARC900

A B L N

X24

X13 X14 X15 X16 X17 X18 X19 X20 X21 X22 X23

Y24

Y13 Y14 Y15 Y16 Y17 Y18 Y19 Y20 Y21 Y22 Y23

Resistance(120Ω) Z24

Z13 Z14 Z15 Z16 Z17 Z18 Z19 Z20 Z21 Z22 Z23

RS485A
( RS485A )

RS485B X12
( RS485B ) X1 X2 X3 X4 X5 X6 X7 X8 X9 X10 X 11

GND Y12

Y1 Y4 Y6 Y7 Y8 Y9 Y10 Y 11
( GND ) Y2 Y3 Y5

Z12

Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8 Z9 Z10 Z 11

Moudbs module

ARC900 outdoor type


A L I A PA N E L

Group 1 2015-12- 10 15:15:36


Ch01 m3/h Ch02 C

887. 5 30. 2
6521.22 6589.25
CH03 Kg/h CH04 mA

52. 8 18. 0
528.22 105.25

Resistance(120Ω)
RS485A
( RS485A )
RS485B 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
R R P1 P1 P
1A 1B 1C 3A 3B 3C 5A 5B 5C 7A 7B 7C 9A 9B 9C 11 11 11 P2 P
P2 P
P3 P
A B C R1 R1 R3 R3 R5 R5 R7 R7 R9 R9 11 11 + - + - + -
P3
( RS485B )
2A 2B 2C 4A 4B 4C 6A 6B 6C 8A 8B 8C 10 10 10 12 12 12 R R R R
A B C A B C R2 R2 R4 R4 R6 R6 R8 R8 10 10 12 12 D+ D- RA TB G
GND 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72
( GND )

Moudbs module

47
ARC900 Operation Manual OP900.1.1.7.R5ENG
12.2 Modbus Communication Address

ALIA PANEL Modbus Communication

Channel Data Type Address Function Code Initial Address Register Size
Real-time data Short 0000
Channel 1 Real-time data 32 bytes float 0064
Totalizer ulong 00C8
Real-time data Short 0001
Channel 2 Real-time data 32 bytes float 0066
Totalizer ulong 00CA
Real-time data Short 0002
Channel 3 Real-time data 32 bytes float 0068
Totalizer ulong 00CC
Real-time data Short 0003
Channel 4 Real-time data 32 bytes float 006A
Totalizer ulong 00CE
Real-time data Short 0004
Channel 5 Real-time data 32 bytes float 006C
Totalizer ulong 00D0
Real-time data Short 0005
Channel 6 Real-time data 32 bytes float 006E
Totalizer ulong 00D2
Real-time data Short 0006
Channel 7 Real-time data 32 bytes float 0070
Totalizer ulong 00D4
Real-time data Short 0007
Channel 8 Real-time data 32 bytes float 0072
Totalizer ulong 00D6
01 04 0002
Real-time data Short 0008
Channel 9 Real-time data 32 bytes float 0074
Totalizer ulong 00D8
Real-time data Short 0009
Channel 10 Real-time data 32 bytes float 0076
Totalizer ulong 00DA
Real-time data Short 000A
Channel 11 Real-time data 32 bytes float 0078
Totalizer ulong 00DC
Real-time data Short 000B
Channel 12 Real-time data 32 bytes float 007A
Totalizer ulong 00DE
Real-time data Short 000C
Channel 13 Real-time data 32 bytes float 007C
Totalizer ulong 00E0
Real-time data Short 000D
Channel 14 Real-time data 32 bytes float 007E
Totalizer ulong 00E2
Real-time data Short 000E
Channel 15 Real-time data 32 bytes float 0080
Totalizer ulong 00E4
Real-time data Short 000F
Channel 16 Real-time data 32 bytes float 0082
Totalizer ulong 00E6

48
ARC900 Operation Manual OP900.1.1.7.R5ENG
12.3 Modbus Illustration
Firstly, set related parameters such as baud rate, parity bit, stop bit .etc. Secondly, choose the same setting value in the
Communication software interface (Start bit is 1, data bit is 8 and stop bit is 1. Those are certain.)
Register data readings support swap-byte function, 4 alternatives given below are for you to choose: 1-2 3-4、 2-1 4-3、
3-4 1-2、4-3 2-1. The default order is 2-1 4-3.
1. Instruction Programming Rule
E.g. If the totalizer of Channel 1 is to be seen, set the meters to 2-1 4-3 default order to get the data storage from
register. And refer to table 1, enter below instructions:
01 04 75F8 0002 EA36
Device Address Function Code Initial Address Register Size CRC Check Cod (PC software generates
automatically)
2. Instruction Receiving Format
E.g. If the above instructions are sent, the instruction codes can be as follows:
01 04 04 4E 02 00 00 4D6C
Device Address Function Code Bytes Length 2 1 4 3 CRC Check

Consequently, the totalizer is 00004E02.