You are on page 1of 11

PUBLIC SWIMMING

POOL HALLS
Creating an ideal indoor climate for
sportsmen and wellness fans.

Of course
liant!
ErP-comp
Good air ensures Save energy
a good atmosphere! costs!
The quality of the air decides The costs of water, energy and
whether a guests become regular maintenance for the operation of
customers or wether they will go an indoor swimming pool are
to visit the competition. If it is too rising year by year. Any opportu-
humid, too cold or too draughty, nity to make savings has to be
you will certainly not see him used to keep entrance fees
again. Air quality is one of the stable. The use of highly efficient
most important customer loyalty technology reduces the energy
parameters in swimming pool halls. demand significantly.

Protect the fabric Avoid health


of the building! risks!
Poor heat insulation in con- The process of water treatment
junction with a poorly designed can lead to a concentration of
vapour barrier is the most disinfection by-products in the air
common cause of potential of the swimming pool hall. These
damage due to the temperature can be removed from the
falling below the dew point on swimming pool hall by a ventila-
the inside of the building tion system in combination with
envelope of a swimming pool well-designed air distribution.
hall.

The air quality is key


WHY AIR QUALITY IS SO IMPORTANT IN THE SWIMMING POOL HALL TEMPERATURE AND HEAT REQUIREMENT
Modern wellness and leisure pools offer the swimming pool hall temperature and device is always required. The selection The pool water temperature of a sports Surface temperature efficient recuperator reduces this heat
guests much more than just an opportu- humidity level and the volume of outside of a highly efficient dehumidification unit pool is usually 26-28°C and that of a Temperature of furnishings, equipment requirement.
nity for swimming. Water attractions, air required for dehumidification. The is crucial in order to keep down the wellness pool 28-32°C. The room air and room-enclosing surfaces. A tempera- 3. Evaporation heat requirement: Heat
such as slides or white water channels, minimum volume of outside air stipulated operating costs in a swimming pool hall. temperature is usually designed to be ture difference is perceived as uncomfort- requirement for compensation of the
as well as complete waterscapes for by VDI 2089 must be complied with. 2 K higher than the water temperature. able by the bather and can lead tofalling heat loss resulting from the evapora-
children, offer recreational fun for the below the due point. tion of the pool water. The amount of
whole family. Outside of the pool there Besides the comfort needs of the bather, The temperature and the air humidity in heat required for this evaporation is
are lounge areas to rest and relax. The protection of the structure of the the swimming pool hall contribute greatly The heat requirement of a swimming extracted to a level of 90% from the
associated long length of stay of the buildings is of enormous importance. to the well-being of the bather. The pool hall is determined by three variables: water and 10% from the air and has to
guest also outside the pool increases the Well-thought-out air distribution ensures absolute water content plays an essential 1. Transmission heat loss: The quantity of be covered by a customer-provided
requirements for the pool hall air. that all parts of the swimming pool hall role in the swimming pool hall. Here, a heat which is required to compensate heating installation or a heat pump
remain supplied with air. As a result, the value of 14.3 g of water per kg of air for the heat loss through the building integrated into the dehumidification
Due to the constant evaporation of the formation of moist spots is prevented - should not be exceeded permanently as envelope. High-quality insulation unit. In addition there is the amount of
pool water and in order to satisfy the ensuring that the dew point of compo- long as the absolute water content of the reduces this heat requirement. heat which is required to replenish the
comfort criteria, indoor pool dehumidifi- nents is not reached. Regardless of the outside air is < 9 g/kg. This value represents 2. Ventilation heat requirement: Heat quantity of water that has evaporated
cation systems are used. Modern control intensity of use and type of swimming the humidity limit of an undressed person. quantity needed for warming the and heat it up to the pool water
systems ensure continuous adjustment of pool hall, 24-hour operation of the HVAC outside air up to the temperature of temperature.
the swimming pool hall. A highly

2 Public swimming pool halls | 2019/08/EN | Subject to technical modifications. © Menerga GmbH | www.menerga.com Public swimming pool halls | 2019/08/EN | Subject to technical modifications. © Menerga GmbH | www.menerga.com 3
Indoor swimming pool dehumidification Ventilation in swimming pool halls
REQUIREMENTS OF SPECIFIC TYPES OF INDOOR SWIMMING POOLS BASIC PRINCIPLES OF AIR DISTRIBUTION
The pool surface area and depth, as well is designed for bathing and stand-by dehumidification and thus the size of the The air distribution system in a swim- the hall make an important contribution supply and return air at all operating
as the type of pool use, are decisive for mode in accordance with VDI 2089 respective dehumidification unit can be ming pool hall performs several tasks. to the comfort of the bathers. The air points. The position of the air outlet at
the evaporation of the water at the pool sheet 1. A higher amount of evapora- selected. The main task is to discharge the moist inlet, in particular, must be arranged the top of the swimming pool hall is
surface. Another important influencing tion by existing water attractions is also return air from the hall and feed it to the such that the common area is draught- selected in such a way that an air-side
variable is the partial pressure difference taken into account. dehumidification unit. At the same time, free for bathers. The supply air helps to short circuit between the supply air and
between the saturated vapour pressure the drier supply air is fed from the generate an air flow that ensures air return air is ruled out.
at the pool water temperature and the The determination of the amount of air bottom up into the swimming pool hall circulation in all areas of the swimming
partial pressure of the water vapour of required during bathing activities based through the duct system, normally via air pool hall. The successful performance of
the swimming pool hall air. With these on ... and outside air, results in the outlets in the area of the windows. The this task mainly depends on whether the
factors, the evaporating water mass flow amount of outside air required for position of the air inlets and outlets in fans provide a constant quantity of

By-products which find their way into


the swimming pool hall air are formed
during the cleaning and disinfection of
the pool water. A further task of the air
distribution system is to actively prevent
© Bädergesellschaft Lünen mbH
a concentration of these substances.

In general, 4 to 5 air changes per hour

© Therme Lasko
have proven effective for the fulfilment
© City of Rijeka

of all tasks.

Kantrida Rijeka, Croatia Lippebad Lunen, Germany Lasko Thermal Baths, Slovenia
SPORTS POOL LEISURE POOL ADVENTURE POOL
Focus on training, 50-metre lanes. Combination of sport and leisure, Strong orientation on leisure activities, many
Competition venue with stands. 25-metre lanes. water attractions, slides, etc.
Temperature: 26/28°C (water/air) Temperature: 28/30°C (water/air) Temperature: 28/30°C (water/air)
Roof can be opened First public passive house swimming pool Connection to the outdoor pool

Supply air Return air

Utility room
© Helmuth Rier

© Klaus Bauer
© Europapark

RA OA

Terme di merano, Italy Hotel Bell Rock in Rust, Germany Hotel Edelweiss in Wagrain, Austria SA EA

SALTWATER POOL HOTEL POOL HEALTH SPA Example of an optimal air distribution
system based on a recuperative system.
Brine water promotes health. Wellness and relaxation. Swimming pool, e.g. for health treatments.
Introduction of the air on the window
Temperature: 30/32°C (water/air) Temperature: 28/30°C (water/air) Temperature: 28/30°C (water/air) facades, extraction at the top. The amount
Very corrosive air Wellness oasis in the Europa Park in Rust First hotel passive house swimming pool of supply and return air is constant.

4 Public swimming pool halls | 2019/08/EN | Subject to technical modifications. © Menerga GmbH | www.menerga.com Public swimming pool halls | 2019/08/EN | Subject to technical modifications. © Menerga GmbH | www.menerga.com 5
Ecodesign Directive
ERP ALSO APPLIES TO VENTILATION UNITS IN SWIMMING POOL HALLS IMPORTANT STANDARDS AND DIRECTIVES

European Directive 2009/125/EC (ErP or ventilation plants were established in Another decisive factor for compliance BUILDINGS HVAC TA-Lärm
"Ecodesign Directive") provides a EU Regulation 1253/2014, which came with the requirements of the Ecodesign Technical Instructions on Noise Abatement
European legal guideline for the estab- into force in 2014. Besides the basic Directive is the power consumption of Energy Conservation Act (EnEG) Machinery Directive 2006/42/EC
lishment of requirements for the requirements for the design of the the fans. If this exceeds a reference Law on saving energy in buildings German Sustainable Building Council -
environmentally friendly design of ventilation unit, efficiency criteria are value, the device may not be placed on Ecodesign Directive 2009/125/EC Leaflet 60.07
energy-related products and came into being formulated in two steps for the market within the EU. Renewable Energies Heat Act Maintenance of Technical Installations in
effect in October 2009. The objective of 1 January 2016 and - with increased (EEWärmeG) Directive 2004/108/EC Swimming Pools, leaflet of the German
this directive is to provide minimum requirements - 1 January 2018. Particu- The objective of the ecodesign require- Law for the promotion of renewable Electromagnetic Compatibility Society for Bathing.
requirements regarding the energy lar focus is on the efficiency of the heat ments for ventilation systems is to energies in the heat sector
efficiency of various product groups recovery system according to the rules increase the primary energy savings of Pressure Equipment Directive 97/23/EC German Study Group of Public and
which fall under the category of of EN 308. These rules describe the test this product group to 60% before 2025 Energy-saving Regulation (EnEV) Municipal Administration for Machines
energy-related products and therefore method in order to determine the relative to 2010. Regulation on energy-saving thermal EN 378 and Electrical Facilities in Buildings -
drive inefficient products from the Single efficiency of all heat exchanger insulation and energy-saving installation Safety and Environmental HVAC Plant Construction Directive
European Market in order to achieve the systems and ensure cross-system engineering for buildings Requirements for Refrigeration Systems Scope of application: public buildings
European climate protection targets. The comparability. and Heat Pumps
requirements for the ecodesign of DIN V 18599 DIN EN 13053
Calculation of the energy needs, delive- DIN EN 13779 Rating and performance for air handling
red energy and primary energy for Mechanical Ventilation and Air-Conditio- units, components and sections
heating, cooling, ventilation, domestic ning of Non-Residential Buildings
hot water and lighting of buildings DIN EN 13501 Part 1 (May 2007)
DIN EN 15251 Fire classification of construction
KOK Directives Input Parameters for the Room Climate products and building elements
Recognised basis and benchmark for the for the Design and Assessment of the
planning and construction of public Energy Efficiency of Buildings DIN EN 1886
swimming pool halls Air handling units - Mechanical Perfor-
DIN EN 12599 mance
Regulation on the Construction and Testing and Measuring methods for the
Operation of Places of Public Assembly Operation of Installed HVAC Plants VDI 3803
(VStättVO) Central Air Conditioning Systems –
Ordinance on the construction and VDI 2089 Structural and technical principles (VDI
operation of public assembly places Building Services in Swimming Baths; ventilation code of practice)
(among other things open-air swimming Sheet 1 = Indoor pools,
pools with fencing, swimming pool halls Sheet 2 = Efficient Use of Energy and DIN EN 1751 ( January 1999)
with a volume > 200 people) Water Air terminal devices

VDI 2050, Sheet 1-5 LüAr - Ventilation Plant Directive VDI 6022
Planning and Holistic View of Buildings Directive on the technical fire safety Hygiene Requirements for ventilation
and Technical Building Equipment requirements for ventilation systems and air-conditioning systems and units

HVAC Directive 01
IMPORTANT LABELS General Requirements for HVAC Systems,
issued by the German Association of
Ventilation and Air-Conditioning Equip-
ment Manufacturers (Registered
Association)

RLT-TÜV-01
ErP Directive EUROVENT HVAC A+, A, B Test Guideline of TÜV-Süd for
Device complies with Certification Programmes Certification of Efficiency and
Directive 2009/125/EC for Cooling and Air-Conditioning Quality of an HVAC System
Energy Efficiency
Products

6 Public swimming pool halls | 2019/08/EN | Subject to technical modifications. © Menerga GmbH | www.menerga.com Public swimming pool halls | 2019/08/EN | Subject to technical modifications. © Menerga GmbH | www.menerga.com 7
Design Parameters
FOR PUBLIC SWIMMING POOL HALLS
Important Design Parameters In the case of suction through the Monitor the chemical room
Pool surface, pool depth building's roof: The distance of the air
Water temperature intake to be at least 50% above the Maintenance
Air temperature and humidity maximum snow depth Also keep in Provide monitoring with automatic test
Type and number of attractions mind: signals
Operating hours - Main weather direction Schedule maintenance framework
Type of use - Fallen leaves agreements at fixed intervals as well
- Sound (see table on the right) as measures for energy optimisation
Design Choose the position of the exhaust air Inspection twice a year
Provide for multiple use of the air duct such that air is not blown out Inspections must be documented in
Operate wet areas in low pressure below parts of the buildings (roof) the log book
compared to dry areas Check the fire protection concept!
Air distribution system must ensure air Provide smoke detectors in supply and
Immission guide during at night
exchange in the swimming pool hall return air duct in order to turn off the day
values according to
system in the event of fire automati-
TA Lärm
Planning cally 600 am - 1000 am
1000 pm - 600 pm
Early examination of building statics According to VDI 2089, weight-loaded
and possible access openings overpressure relief valves must be Industrial areas 70 dB(A) 70 dB(A)
When setting up the device and provided in order to protect the duct
Industrial estates 65 dB(A) 50 dB(A)
planning the channels, take the system.
minimum space for maintenance work Adjustment depending on the room
Rural and 60 dB(A) 45 dB(A)
into account temperature and room humidity, or mixed areas
Exhaust air channel: Air lines for the alternatively depending on the room General residential 55 dB(A) 40 dB(A)
dehumidification unit as short as possi- temperature and pool temperature areas
ble Only exceed absolute humidity in the Exclusively 50 dB(A) 35 dB(A)
residential areas
Cleaning opportunity and discharge for hall of 14.3 g/kg if OA humidity
Spa areas, 45 dB(A) 35 dB(A)
any penetrated water exceeds >9 g/kg
hospitals etc.
Inspection opening at chamber or Reduction of the minimum external
channel volume flow from 30% to 15% is
Exhaust air passage: Ensuring the permissible if the pool water trihalo-
removal of any water that has entered methanes are permanently <0.020 Terme di merano, Merano
mg/l Photo: Helmuth Rier
Rel. field
Attraction Technical Data
amplification
Design parameters Recreational pools 28 - 32 °C Volume flows Attractions:
(Standard parameters, can be varied at Wading pools 32 °C Entrance area 5 m3/hm2 Overview of the parameters of the No. of nozzles Flow rate Flow rate
the request of the operator) Exercise pools 32 °C
Single changing rooms 15 m3/hm2 relative field amplification according to per system water water
Therapy pools 36 °C
Group changing rooms 20 m3/hm2 VDI 2089 Sheet 1. Jet stream canal 6 to 8 80 to 100 - 30
Room temperature Whirlpools 36 °C
Supervisory rooms 25 m3/hm2
Water mushroom - 40 to 50 - 5
Swimming pool hall 30 - 34 °C Warm bubble pools 36 °C
First aid rooms 25 m3/hm2 Detailed instructions for the calculation
Changing rooms 22 - 28 °C Warm pools 35 °C
WCs (per seat) 100 m³/h according to VDI 2089 are available on Counter-current system 1 to 2 20 to 50 - 20
Showers 26 - 34 °C Cold pools 15 °C
Showers (per shower) 220 m3/h request from your sales partner. Neck shower - 30 to 60 - 6
Sanitary area 26 - 34 °C Floor jet - 50 to 100 - 4
Staff rooms 22 - 26 °C Surface temperatures
Bubble geyser - - 200 to 300 3
Entrance area > 20° C Surface type
Adjoining areas > 20° C Surfaces of seat and lying areas 30° to 39° C Geyser - 50 to 70 - 3
Stairwells > 18° C Surfaces of the floor in the barefoot area 22° to 30° C Children's slide - 60 - 3
Heating surfaces in the barefoot area without protection against contact <50° C Massage area - 10 to 20 - 4
Pool water temperature Heating surfaces in the barefoot area with protection against contact any
Recess for relaxing - - 40 to 50 2
Swimming pools 28° C
Diving pools 28° C For further information and parameters, see VDI 2089 Sheets 1 and 2. Sitting area - - 40 to 50 2

8 Public swimming pool halls | 2019/08/EN | Subject to technical modifications. © Menerga GmbH | www.menerga.com Public swimming pool halls | 2019/08/EN | Subject to technical modifications. © Menerga GmbH | www.menerga.com 9
Make the Right Choice! How it works...
SYSTEM AND COMPONENT SELECTION COUNTER-CURRENT HEAT EXCHANGER VS. HEAT PUMP
EQUIPMENT SELECTION Recuperative: unit with cross-flow heat the design if the dew point is not reached, Device with counter-flow heat Unit with cross-flow heat exchanger and
Recuperative heat recovery systems exchanger and heat pump since the condensate produced by a heat exchanger, without heat pump heat pump
transmit the sensitive energy stored in Combination of recuperator and down- wheel gets into the outside air flow with
the swimming pool hall return air to the stream heat pump. Here, the exhaust air the help of the rotation. This moisture Stand-by mode
outside air. Substances contained in the is further cooled with the help of the recovery increases the absolute water RA OA No requirement for temperature or dehu- RA OA

air are not transmitted from the return air evaporator after the recuperator in content in the supply air and has to be midification, device operates solely in re-
to the outside or supply air. With low OA outside air mode. The sensitive and compensated for with a greater quantity SA EA circulation mode. The aim is air circulation SA EA

with reduced performance of the fans.


K V

temperatures in which water condenses latent energy obtained is transferred to of outside air. The significantly higher fan
out of the return air, this cannot enter the the supply air. The electrical capacity of input power results in higher energy
supply air. Only the quantity of outside air the compressor is transferred to the requirements in addition to the driving
which is necessary for dehumidification is swimming pool hall as additional heat power of the heat wheel. Recirc Air Heating Operation
RA OA RA OA

used. gain through the supply air. That way, a Heating in accordance with requirements
large share of the transmission heat COMPONENTS for each heating coil. The OA and EA
SA EA SA EA

Recuperative: Device with counter-flow requirement is covered and the heating dampers are closed. K V

heat exchanger, without heat pump system can be sized smaller. This solution Pool water condenser
Devices with counter-flow heat exchan- is ideal for energetically refurbished A pool water condenser can
gers achieve the highest-possible heat swimming pool halls. emit heat to the pool water during the Dehumidification at the device with
RA OA
counter-flow heat exchanger accordance with VDI 2089 minimum
recovery rates. Modern control systems transitional period.
Dehumidification of the swimming pool required amount of outdoor air) for
provide the quantity of outside air Regenerative: Device with rotary SA EA
hall air through demand-based mixing of the recirculated air flow. If required:
required for dehumidification continuous- heat exchanger; Heat wheels
outside air (in bathing mode in reheating of the supply air.
ly and consistently. The ventilation heat For regenerative heat recovery via a
requirement is reduced to a mini- rotary heat exchanger, substances from
mum. This solution is ideal for well-insu- the swimming pool hall air can be Dehumidification of the device with
lated swimming pool halls in which the transferred in addition to the sensitive heat pump of untreated recirculation air, heated at
The return air is cooled to below the the condenser and routed into the hall as
RA OA

transmission heat loss is very low. heat. Moisture recovery results due to
dew point in the evaporator of the heat supply air. If necessary, further heating
pump, reinforced by the recuperator. is carried out with the help of heating SA EA

Energetic examination of recuperative and regenerative heat recovery Outside air with a low moisture con- coils. During swimming pool mode, the
K V

38 38 tent is preheated in the heat exchan- minimum required amount of outdoor air
[°C]

[°C]

38 % % % 38 % % %
Temperatur[°C]

Temperatur[°C]

5% 0% 4400 % 5% 0% 4400 %
%

%
%

%
%%

%%
%%

%%
55%

55%
%

1,14 225 330 1,14 225 330


36 1,14 36 1,14 ger, then mixed with an amount is added as needed.
2200

2200

36 36
1155

1155
1100

1100
Temperatur

Temperatur

% %
34
34 5500 % 34
34 5500 %
32
32 1,1 32
32 1,1
1,16 3
3 % 1,16 3
3 %
6 6600 % 6 6600 %
30
30 Dichte
Dich te feuc
feuchter Luft [kg/m
hter Luft [kg/m³]
³]
%
30
30 Dichte
Dich te feuc
feuchter Luft [kg/m
hter Luft [kg/m³]
³]
%
Outside Air Exhaust Air Mode
28 7700 % 7700 %
EEnn

28
EEnn

28 2 28
2
In the case of rising OA humidity, the
thth

thth
aalplp

aalplp

1,18
26 1,18 % 1,18
26 1,18 %
26 8800 % 26 8800 %
ieie

ieie

RA OA
[k[kJJ

[k[kJJ

RA OA
% % recirc air damper is continuously closed
/k/kgg

/k/kgg

24 24
24 900% 24 900%
]]

]]

9 9
22
22 100 0% % 22
22 100 0% %
as required. During high OA humidity, the
0 0
6644

6644

1,20
1,20 1 1,20
1,20 2
2 1
6622

6622

20 20 EA
6600

6600

SA
20 20 SA EA
flap closes completely, the device opera-
5588

5588
5566

5566

18 18
5544

5544

K V
18 18
5522

5522

tes in outside air-exhaust air mode.


5500

5500

1,22
16 1,2 1,22
16 1,2
4488

4488

16 2 16 2
4466

4466
4444

4444

14 14
4422

4422

14 14
4400

4400
338866

338866

12 1,24
12 12 1,24
12
33

33

1,24 4
4 1,24
3344

3344

10 10 Defrost Mode
3322 00

3322

10 10
33 88

3300 88
22 66

22 66

8 8
8 8 4
4 Recuperative heat exchangers tend to ice
22

22 44

1,26
1,26 1,26
1,26 RA OA RA OA
2244 22

22

6
6 6
6
22 00

2222 00

up if the OA temperatures are low. This is


22 88

22 88

4
4 4
4 Energetic examination of
11

11 66

1,28 1,28
2 1,28 2 1,28 prevented by opening the return
1166 44

11

2 2 recuperative and regenerative SA EA SA EA


11 22

1144 22
11 00

11 00

0 0
0 0 heat recovery (left) and heat air-exhaust air bypass. K V
11

11

-2 1,3
1,30
0 -2 1,3
1,30
0 recovery with heat wheel
88

88

-2 -2
66

66

-4
-4 -4
-4 (right).
44

44

-6 1,3
1,32
21 -6 1,3
1,32
21 The diagram shows that there
22

22

-6 1 -6 1
00 --22

00 --22

-8
-8 -8
-8 is a big difference in the Heat exchanger bypass
1,34
-10 1,34
1,34
-10 1,34 absolute water content
-

-10 -10 RA OA
The proportion of the air guided through
-

-
44

4 4

between the return air and


--66 --88

--66 --88

-12 Luftdruck: 1.013,3


Luftdruck: 1.013,3 hPa
hPa -12 Luftdruck: 1.013,3
Luftdruck: 1.013,3 hPa
hPa
-12 -12
--11
--11

--11
--11

outside air in the case of low the heat exchanger and the bypass can
22
00

22
00

0
0 1
1 2
2 3
3 4
4 5
5 6
6 7
7 8
8 9
9 10
10 11
11 12
12 13
13 14
14 15
15 1616 0
0 1
1 2
2 3
3 4
4 5
5 6
6 7
7 8
8 9
9 10
10 11
11 12
12 13
13 14
14 15
15 1616
Absoluter Wassergehalt
Wassergehalt [g/kg]
[g/kg] Absoluter Wassergehalt
Wassergehalt [g/kg]
[g/kg] OA temperatures. SA EA
Absoluter Absoluter be regulated up to free ventilation.

10 Public swimming pool halls | 2019/08/EN | Subject to technical modifications. © Menerga GmbH | www.menerga.com Public swimming pool halls | 2019/08/EN | Subject to technical modifications. © Menerga GmbH | www.menerga.com 11
Quality Factors
YOU CAN RECOGNISE A GOOD HVAC DEVICE BY THESE PARAMETERS.
Control and regulation sufficient rigidity in conjunction with a design stage. All components are complete with and algae deposits. During production,
Control and regulation is part of any unit cover designed as sandwich panels. corrosion-resistant coatings or polypro- significantly fewer CO2 emissions are
energy-efficient device. The device can The thermal insulation shell reduces Highest efficiency confirmed pylene panels. This ensures a long produced compared to aluminium.
be connected to BACnet and other heat losses and hence energy con- Menerga is a member of the German lifespan. Furthermore, the weight is five times
systems and can be operated and sumption. Thermal isolation is ensured AHU Manufacturers Association and less.
analysed by remote control and remote by design. This means best possible certified by them and by EUROVENT. Polypropylene recuperator
monitoring (vicomo). avoidance of thermal bridges, and no The basis for this is measurements and Polypropylene (PP) is a thermoplastic
condensation on the outside of the unit. tests which have been created by material which is ideal for use in
Unit structure This is very important when used in the independent institutes such as TÜV or air-conditioning and ventilation techno-
The unit design ensures the durability of swimming pool hall area. DMT. With these we ensure design and logy. It is non-toxic and neutral to
a device, as well as simple, secure production according to standard ground water. Polypropylene possesses
integration. Menerga units are based on Cleaning and maintenance market quality and efficiency criteria. a high level of resistance to many types
a long-lasting, robust frame structure. A unit design according to VDI 6022 of acids, alkalis, salts and solvents and
ensures the high hygiene standard of Extra corrosion design is resistant to corrosion and to ageing.
Thermal insulation HVAC units. This includes the possibility If the swimming pool hall air is particu- The material cannot be metabolised
A good HVAC device is based on a of thorough cleaning of all components, larly corrosive, for instance in the case microbiologically and provides no basis
comprehensive thermal insulation in particular the heat exchanger. This of brine baths, units have to be provi- for the growth of germs or lime scale
concept. It has a solid construction with has to be made possible already at the ded with increased corrosion protection.

Panel Measured values according to EN


with insulation shell

1886
Omega section

M-section with Casing stability D1 (M)


insulation shell
Panel

Air tightness -400 Pa L1 (M)

50 mm Air tightness +700 Pa L1 (M)


Filter bypass leakage F9 (M)
Heat transfer T2
Panel
Thermal bridge factor TB1

Heat exchanger made of polypropylene, fully automated production.

12 Public swimming pool halls | 2019/08/EN | Subject to technical modifications. © Menerga GmbH | www.menerga.com Public swimming pool halls | 2019/08/EN | Subject to technical modifications. © Menerga GmbH | www.menerga.com 13
Comparison of Operating Costs
COMPARISON OF THREE SOLUTIONS FOR DEHUMIDIFICATION

Design conditions
Pool size: 25 x 12.5 m
Pool water temperature: 28° C
Condition of the air in the swimming pool hall: 30 °C/54% r.h.
Swimming pool mode: 8 a.m. - 9 p.m.
Electricity price: EUR 0.165/kWh
Heating price: EUR 0.05/kWh
Air quantity: 15,800 m3/h
Calculation according to VDI 2089.
Specification of all costs in euros

Photo: National
Zwemzentrum de
Tongelreep, Netherlands

80,000 25,000 80,000 25,000 80,000 25,000 80,000 25,000 80,000 25,000 80,000 25,000
Operating costs

22,500 22,500 22,500 22,500 22,500 22,500


Operating costs

70,000 70,000 70,000 70,000 70,000 70,000


20,000 20,000 20,000 20,000 20,000 20,000
60,000 60,000 60,000 60,000 60,000 60,000
12,500

17,500 17,500 17,500 17,500 17,500 17,500


50,000 50,000 50,000 50,000 50,000 50,000
10,600

15,000 15,000 15,000 15,000 15,000 15,000

Maintenance
Investment costs

Investment costs

Investment costs

Investment costs

Investment costs

Investment costs
Maintenance

40,000 12,500 40,000 12,500 40,000 12,500 40,000 12,500 40,000 12,500 40,000 12,500

Maintenance

Maintenance
Operating costs

Operating costs

Operating costs

Operating costs
Maintenance

Maintenance
30,000 10,000 30,000 10,000 30,000 10,000 30,000 10,000 30,000 10,000 30,000 10,000

3,000
7,500 7,500 7,500 7,500 7,500 7,500
3,000

2,000

2,000
20,000 20,000 20,000 20,000 20,000 20,000
2,000

2,000
71,000

75,000

60,000

17,500

71,000

17,600

75,000

14,100

60,000

24,500
5,000 5,000 5,000 5,000 5,000 5,000
10,000 2,500 10,000 2,500 10,000 2,500 10,000 2,500 10,000 2,500 10,000 2,500

unit with counter-flow heat exchanger unit with cross-flow heat exchanger and heat unit with rotary heat exchanger unit with counter-flow heat exchanger unit with cross-flow heat exchanger and heat unit with rotary heat exchanger
pump pump

SYSTEM COMPARISON: SWIMMING POOL HALL WITH EXCELLENT THERMAL INSULATION SYSTEM COMPARISON: SWIMMING POOL HALL WITH POOR THERMAL INSULATION
Requirement: coverage of ventilation heat requirements Requirement: coverage of ventilation and transmission heat requirements
unit with rotary
450,000 450,000 heat exchanger

400,000 400,000
unit with counter-flow
unit with rotary heat exchanger
350,000 heat exchanger 350,000
unit with cross-flow heat
Accumulated investment, ope- unit with cross-flow heat Accumulated investment, ope- exchanger + heat pump
300,000 exchanger + heat pump 300,000
rating and maintenance costs, rating and maintenance costs,
Period: 15 years unit with counter- Period: 15 years
250,000 flow heat exchanger 250,000

200,000 200,000

150,000 150,000

100,000 100,000

50,000 50,000

0 0
1st 2nd 3rd 4th 5th 6th 7th 8th 9th 10th 11th 12th 13th 14th 15th 1st 2nd 3rd 4th 5th 6th 7th 8th 9th 10th 11th 12th 13th 14th 15th
year year year year year year year year year year year year year year year year year year year year year year year year year year year year year year

14 Public swimming pool halls | 2019/08/EN | Subject to technical modifications. © Menerga GmbH | www.menerga.com Public swimming pool halls | 2019/08/EN | Subject to technical modifications. © Menerga GmbH | www.menerga.com 15
Saving energy with waste water
HEAT RECOVERY FROM WASTE WATER
Not only the waste water in the showers
of the swimming pool hall, but also the
Cleaning phase HOW IT WORKS:
fresh water in the swimming pool to be
Waste water 31° C Waste water Heat recovery from waste water with fully automatic recuperator cleaning.
supplied per visitor offers great energy Condenser Hot water 35° C Condenser

potential for swimming pool halls.

Per visitor, 30 litres of fresh water has to M M The combination of a recuperative Consistent pipe cross-sections ensure - Quantity of flow: 0.8 – 5.4 m3/h
be supplied during standard swimming counter-flow coaxial recuperator with a that flow rates are constant. If the waste - Heat pump system with fully sealed
pool operation. This means that 30 litres heat pump provides the highest possible water is organically contaminated, suction gas-cooled coolant compressor,
of pool water brought up to the right
Cleaning
mounted on vibration dampers

Recuperator

Rekuperator
pellets Compressor heat recovery. The warm waste water bacteria growth and organic sludge
temperature must be exchanged for - Ready-to-connect complete device
Flow Flow flows through the recuperator and then formation will possibly adhere to the
unheated fresh water. Hence, heat quantity
regulation
quantity
regulation through the evaporator of the heat exchange surfaces. These are removed
recovery from waste water is a good Options:
Fresh water10° C pump. In counterflow and physically by the fully automatic cleaning. - Additional prefiltering of the
solution for older swimming pool halls,
separated, the same volume of fresh At regular intervals, cleaning pellets are waste water
including refurbishment cases. The crucial Cleaning
pellets water first passes through the recupera- carried along the waste water paths. - Designed as a safety heat exchanger
point for efficient operation is a continu-
ous accumulation of waste water, for tor, and then through the condenser of - Recuperator bypass
Evaporator Evaporator
instance by using a tank. the heat pump.
Waste water 8° C Waste water

COMPARISON OF OPERATING COSTS FOR FRESH WATER HEATING WITH


WASTE WATER HEAT RECOVERY IN THE CASE OF REFURBISHMENT

Technical data of a swimming pool hall,


1,500 visitors per day

Number of swimmers/day: 1,500


Fresh water quantity/day: 45 m3 250,000
ld
Electricity price: EUR 0.165/kWh 225,000 ts, o
cos
Heating price (gas): EUR 0.05/kWh ting
200,000 era
Op
fresh water temperature: 10 °C
175,000
hot water temperature: 35 °C Savings
fresh water/person 150,000 Cumulative
operating +
under DIN 19643-1: 30 litres 125,000 investment
costs
100,000
Daily operating costs for the necessary 75,000 Costs
fresh water heating Conversion
1. with gas: €65.36/day
50,000 costs, new
Operating
25,000
2. with heat recovery: €18.87/day
Savings: €46.49/day 0
1st year 2nd year 3rd year 4th year 5th year 6th year 7th year 8th year 9th year 10th year

Investment costs
Heat recovery device: €44,000
Installation: €20,000

Amortisation of the conversion: 3.7 years

16 Public swimming pool halls | 2019/08/EN | Subject to technical modifications. © Menerga GmbH | www.menerga.com Public swimming pool halls | 2019/08/EN | Subject to technical modifications. © Menerga GmbH | www.menerga.com 17
Energy Costs through Refurbishment Anything else?
EVEN PARTIAL REFURBISHMENT CAN PROVIDE SAVINGS OF 30% SWIMMING POOL HALL AND ADJOINING ROOMS AS INTEGRATED STRUCTURE

Schematic diagram of a public swimming pool

Leasure Wellness Sauna Restaurant Kitchen

Swimming pool device from 1993.


Through adjustments, for example to
the fan technology, the energy Shower Changing room
consumption can be significantly
reduced.

Our device technology is designed for there may be possible faults in terms of with respect to regulation of the plant:
permanent energy-efficient operation. function or technology, but rather the fast From 1994 to 2013 each Menerga unit
Many devices which we installed during pace of progress and the increasing came with an A/B-DDC control system.
the first few years of the company still air-conditioning requirements. Something Since 2009, A-DDC has only been used
are or would be in running order today. that was impossible five years ago is as a replacement, as has B-DDC since
Nevertheless, it pays to check a state-of-the-art today. And may save you 2012. We modify old devices continu-
complete installed system regularly with a good deal of money. Have changes ously and you benefit from the much
respect to optimisation opportunities. turned up in the overall structure? Has a improved technological status, e.g.
CHP plant been incorporated whose communication via BacNet, visualised
A complex system waste heat can be used for heating the remote access, long-term data recording,
such as a dehumidification swimming pool hall? We always lower energy requirements, connection
plant should be checked factor the "big picture" into our of other components which can also be
every five to ten assessment! managed and much more. This pays off
years.The reason for in many ways.
this is not that There is also a good deal A modern public swimming pool consists maintained between 22 and 28 °C so temperature in a restaurant is supposed
that can be optimised The largest amount of energy expenditu- not only of the swimming pool hall, but that the guest neither freezes nor to be between 19 and 26 °C.
re in a ventilation unit is caused by the also of many other areas which place sweats.
fan motors. Currently, we are replacing various requirements on the ventilation Kitchen
V-belts and solvent fan units with EC and air-conditioning. The areas have to Staff and first aid rooms In the kitchen area the room air tempe-
fans in our old devices throughout be considered separately from one The people here tend to be lightly rature should be at least 17 °C and
Germany. This alone saves up to 30% another to a large extent. dressed. The ideal air temperature is bet- preferably not above 26 °C. It should be
energy. ween 22 and 26 °C. borne in mind that a high fat content can
Entrance area occur in the return air, for which an
Contact us today! The business card of a swimming pool Fitness areas encapsulated ventilation unit is required.
hall. If it smells of chloroform here and is In order to avoid putting additional stress
stiflingly hot, it will make a bad impres- on the body during exercise, an air Sauna
sion. Temperature recommendation at temperature of between 18 and 20 °C is Heat can be recovered in the sauna area
least 20 °C. recommended. - however, the supply of fresh air must
also be ensured. Recommended air
Toilets, showers Wellness complex temperature: 22° - 26°C.
In these areas, the bather is lightly In the wellness complex, the people are
dressed. The temperature in the shower mostly lightly dressed, but not wet. Hotel, conference rooms and more
and sanitary rooms should be between Depending on the form of use, the air Currently, leisure oases are being created
26 and 34 °C. temperatures are usually between worldwide with an adjoining hotel,
26° and 30°C. business rooms etc. We also provide the
Changing rooms appropriate air-conditioning for these
In the changing rooms the visitor is Restaurant additional applications.
either lightly dressed or fully dressed. According to the German building
The air temperature in this area is regulations for restaurants, the room air

18 Public swimming pool halls | 2019/08/EN | Subject to technical modifications. © Menerga GmbH | www.menerga.com Public swimming pool halls | 2019/08/EN | Subject to technical modifications. © Menerga GmbH | www.menerga.com 19
Menerga GmbH
Alexanderstraße 69
45472 Mülheim an der Ruhr
Germany

Tel: +49 208 9981- 0


Fax: +49 208 9981-110

info@menerga.com
www.menerga.com

OUR FIELDS OF APPLICATION:


er

n
y
nt

io
r
st
Ce

is
du

ec
ta

In

Pr
Da

ice
en

lo

rv
gi

Po

Se
Hy

You might also like