You are on page 1of 1

Generator protection with machine differential protection 2 Product introduction

Table 2 - Applications

Easergy P3 Standard Easergy P3 Advanced

Voltage – – –

Feeder P3F30
w.
directional

P3L30
w. line diff. &
P3U30 distance
with
Transformer P3T32
directional
o/c – with
P3U10 P3U20
with voltage differential
protection
Motor P3M32
P3M30 with
differential

Generator P3G32
P3G30 with
differential

Measuring Phase current 1/5A CT (x3) 1/5A CT (x3) 1/5A CT (x3


inputs slot 4)

1A or 5A (x3
slot 8)

Residual current 1/5A CT or 0.2/1A CT 5/1A+1/0.2A CT 5/1A+1/0.2A


CT (slot 8)

5/1A CT (slot 4)

Voltage VT (x1) VT (x4) VT (x4) VT (x4)

Arc-flash sensor input – 0 to 4 point 0 to 4 point


sensor sensor

Digital I/O Input 2 8/10 16 6 to 36 6 to 16

Output 5 + SF 5/8 + SF 8 + SF 10 to 21 + SF 10 to 13 + SF

Analog I/O Input – 0 or 4 2 0 or 4 2

Output – 0 or 4 2 0 or 4 2

Temperature sensor input – 0 or 8 or 122 0 or 8 or 122

Front port USB USB

20 P3G/en M/F006

You might also like