DIGSI 5 Basics

Exercises i3D
www.siemens.com/poweracademy Copyright © Siemens AG 2013. All rights reserved.
Exercises –SIPROTEC 5 / DIGSI 5

SIPROTEC 5 / DIGSI 5 Basic Course

Exercise 1 - Design of 220 kV Feeder


Exercise 2 - Handling of SIPROTEC 5

Copyright © Siemens AG 2013. All rights reserved.


Exercise 3 - Online Configurator for SIPROTEC 5
Exercise 4 - DIGSI 5 Offline Design of SLD and SIP5-Devices
Exercise 5 - DIGSI 5 Offline – Implementation of Control Functions
Exercise 6 - DIGSI 5 Offline – Design of Display Pages
Exercise 7 - DIGSI 5 Offline – Implementation of Protection Functions
Exercise 8 - DIGSI 5 Online Operation with SIPROTEC 5
Exercise 9 - DIGSI 5 Offline – Logic Function Charts (CFC): Local Key switch => Flashing LEDs
Exercise 10 - DIGSI 5 Offline – Logic Function Charts (CFC): F-Key => Change the setting group
Exercise 11 - DIGSI 5 Offline - Display Power Flow and SF6 Loss
Exercise 12 - DIGSI 5 Offline – Expansion of Function Points
Exercise 13 - DIGSI 5 Offline – Import/ Export of Parameters
Exercise 14 - DIGSI 5 - Simple Goose Communication SIP5-SIP5

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 2 Siemens Power Academy TD
00_Exercises
Exercises –SIPROTEC 5 / DIGSI 5

SIPROTEC 5 / DIGSI 5 System Course

Exercise 21 - DIGSI 5 Offline – Expansion of Project with SIPROTEC 4

Copyright © Siemens AG 2013. All rights reserved.


Exercise 22 - DIGSI 5 Offline – Bay Interlocking D01 and D02
Exercise 23 - DIGSI 5 Offline – Station Interlocking between SIP5 and SIP4
Exercise 24 - DIGSI 5 Offline – Automatic Settings Group Change
Exercise 25 - DIGSI 5 Offline – DIGSI 5 - Simple Busbar Protection
Exercise 26 - DIGSI 5 Offline – DIGSI 5 and SICAM PAS
Exercise 27 - DIGSI 5 Online - Test Suite
Exercise 28 - DIGSI 5 Online - Expert Mode

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 3 Siemens Power Academy TD
00_Exercises
Exercise 1 – Design of 220 kV Feeder SIPROTEC 5

1. Design the scope of Binary inputs and outputs, the number of VTs and CTs and the number of
protection functions. How many interfaces do you need for the Siprotec 5 devices stipulated
for of the 220 kV SLD Feeder =D01 and =D02 ?
2. Which type of communication interfaces do you need, which type of Display and control keys
and how many LED are necessary? Use the Customer Specification.

Copyright © Siemens AG 2013. All rights reserved.


3. Enter the scope of Interfaces and functions in the table for Line 1 and Bus Coupler

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 4 Siemens Power Academy TD
00_Exercises
Exercise 1 – Design of SIP 5 for 220 kV Feeder
Scope of Line 1 =D01

high Com- key


=D01 BI BO standard fast speed power CT VT Interface LED Display switch Housing
Scope of Siprotec 5 (n x el / n x
(n) (n) (n) (n) (n) (n) (n) (nxn/ nxs) (n) op) (n) (w / s / l ) (y / n) (f/s)

SIP 5 Device 32 l i f

Switching Device 6 12 15 13 2 Remarks: n - number

Copyright © Siemens AG 2013. All rights reserved.


n x p - number of
Alarms 5 5 protection CT

status informations 2 2 3p x 1s - protection senitive CT

CT interfaces 8p n x m - number of measurement CT


n x el - number of electrical
VT interfaces 8 Interfaces
n x op - number of optical
Protection Interface 1p Interfaces

1el w - without display


s / l - small / large
IEC 61 850 Interface 1el display
serial Control Center y / n - yes / no
Interface 1op key swich

Sum 19 15 13 2 0 0 8p 8 f / s - flush / surface mounting


Length of Pimary Network Function
Power Supply (V) 48 Line (km) Starpoint Points
Protection functions
(ANSI) 50 51 51N 87L 21 50BF 79 25 500

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 5 Siemens Power Academy TD
00_Exercises
Exercise 1 – Design of SIP 5 for 220 kV Feeder
Scope of Busbar Coupler =D02

high Com- key


=D02 BI BO standard fast speed power CT VT Interface LED Display switch Housing
Scope of Siprotec 5 (n x el / n x
(n) (n) (n) (n) (n) (n) (n) (nxn/ nxs) (n) op) (n) (w / s / l ) (y / n) (f/s)

SIP 5 Device 32 l i f

Switching Device Remarks: n - number

Copyright © Siemens AG 2013. All rights reserved.


n x p - number of
Alarms protection CT

status informations 3p x 1s - protection senitive CT

CT interfaces n x m - number of measurement CT


n x el - number of electrical
VT interfaces Interfaces
n x op - number of optical
Protection Interface Interfaces

w - without display
s / l - small / large
IEC 61 850 Interface display
serial Control Center y / n - yes / no
Interface key swich

Sum 19 f / s - flush / surface mounting


Pimary Network Function
Power Supply (V) Starpoint Points
Protection functions
(ANSI) 50 51 51N 87L 21 50BF 79

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 7 Siemens Power Academy TD
00_Exercises
Exercise 2 – Handling of SIPROTEC 5

Ex 2a) Mechanical Handling of SIPROTEC 5 with SIP 5 modularly Suitcase model


Teamwork in four groups of trainee
• Remove and pluck in the VT terminal blocks from the SIP 5

• Remove and pluck in the I/O terminal blocks from the SIP 5

Copyright © Siemens AG 2013. All rights reserved.


• Remove and pluck in the Communication Interfaces
• Change the Battery
• Expand the SIP5-Basic device with an expansion module

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 10 Siemens Power Academy TD
00_Exercises
Exercise 2 – Handling of SIPROTEC 5

Ex 2b) Operational Handling of SIPROTEC 5 with the SIP5 Test model

 Open the Operational log list and get the last information:

-…………..

Copyright © Siemens AG 2013. All rights reserved.


 Open the last Fault log list

 Open the user log list 1

 Open the Operational measurement values list of line 1

 Get the Serial Number and the Order Number of SIP5 device
(=>Menu=>Test & Diagnostics=>Device Information)
and write down the Order code and save it in a Word-file under C:Temp

Serial number: BM……………………………………

Order Code: 7SL86-………………………………………………………………………..

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 11 Siemens Power Academy TD
00_Exercises
Exercise 2 – Handling of SIPROTEC 5

Ex 2b) Operational Handling of SIPROTEC 5 with the SIP5 Test model

 Open the Operational log list and get the last information:

-…………..

Copyright © Siemens AG 2013. All rights reserved.


 Open the last Fault log list

 Open the user log list 1

 Open the Operational measurement values list of line 1

 Get the Serial Number and the Order Number of SIP5 device
(=>Menu=>Test & Diagnostics=>Device Information)
and write down the Order code and save it in a Word-file under C:Temp

Serial number: BM 120 1000xx

Order Code:

7SL86 – DAAA -AA0 - 0AAAA0 - AZ1212 - 23111A - EBA000 - 000AA0 - CB1BA2 - CB1

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 12 Siemens Power Academy TD
00_Exercises
Exercise 2 – Handling of SIPROTEC 5

Ex 2c) Operational handling of SIPROTEC 5 with the SIP5 Test model

 Change the IP for DIGSI 5-interface J of SIP 5:

IP 192.168.001.x (x=111;121; 131; 151; 161; 171)

Copyright © Siemens AG 2013. All rights reserved.


Sub Net 255.255.255.0

(Menu=> Communication=> J: On broad Ethernet=> Cannel 1=> IP setting=> Change=Enter confirm ID: 222 222
=> press Enter => press OK for Confirm Forces device restart=> Enter IP address=> press Enter => press right
Arrow bottom for Escape four times => select Confirm => press OK => SIP 5 restarted )

Ex 2d) Operational handling of SIPROTEC 5 with the PA Test model

 Execute a local Command CB of SIP5 device

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 13 Siemens Power Academy TD
00_Exercises
Exercise 3 – Online Configurator for SIPROTEC 5

Internet: Link: http://www.energy.siemens.com/hq/en/automation/power-transmission-


distribution/protection/siprotec5/configurator.htm
Ex 3a)
• Create the Order Number of the Relay =D01 like Specification with the Online-
Configutator => Result? Compare with the Device PA Test model.

Copyright © Siemens AG 2013. All rights reserved.


Short Code:……
Long Code:………………………………………………………………………………..

Ex 3b)
• Create the Order Number for Spare part only for the Basic-Device =D01 like Specification but with
the minimum of function points. => Result?
Function Points:……
Short Code:……
Long Code:………………………………………………………………………………..

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 14 Siemens Power Academy TD
00_Exercises
Exercise 3 – Online Configurator for SIPROTEC 5

Ex 3c)
• Create the Order Number for Spare part only for the Expansion-Module =D01 like Specification
Short Code:……
Long Code:………………………………………………………………………………..

Copyright © Siemens AG 2013. All rights reserved.


Ex 3d)
• Create the Order Number of Communication-Module IEC 61 850 FO
Short Code:……
Long Code:………………………………………………………………………………..

Ex 3e)
• Create the Order Number of DIGSI 5 Premium with SIGRA for 5 licenses
Short Code:……
Long Code:………………………………………………………………………………..

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 16 Siemens Power Academy TD
00_Exercises
Exercise 3 – Online Configurator for SIPROTEC 5

Ex 3f)
• Create the Order Number of CT-Terminal for Protection with sensitive Ground current

Short Code: ……….

Long Code: ……….

Copyright © Siemens AG 2013. All rights reserved.


Ex 3g)
• Create the Order Number of CT-Terminal for Measurements

Short Code: ……….

Long Code: ………..

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 18 Siemens Power Academy TD
00_Exercises
Exercise 4 – DIGSI 5 Offline Design of SLD

1. Create a new project and rename it to “SIP5_basic_DD_MM_JJ” and save it to C:Temp


2. Select the symbol standard IEC
3. Design a single bus bar line feeder by using a template (e.g. Double busbar line feeder), change it like SLD
feeder “=D01”. The max. of size should be 13x7 quadrates
a) Open the “Single-line configuration”
b) Move the template “Double-BB-Line Feeder” from the Libraries in the SLD-drawing
c) Delete BB2, QB2 and BE2

Copyright © Siemens AG 2013. All rights reserved.


d) Connect QB9 with BE1 (by holding the left mouse key)
e) Insert “Disconnector”, “Grounding” and “3phase VT YY-delta” from the Libraries, rotate and connect them
f) f)Set the parameters of current transformer BC1 (800/1A) and voltage transformer BA1 and BA 11 (220kV/110V)
g) Rename the components of SLD like specified
h) Enter the line parameter and the length of Line
4. Add a device using “Add new device”. Enter the MLFB-long code: (7SL86 – DAAA -AA0 - 0AAAA0 - AZ1212 -
23111A - EBA000 - 000AA0 - CB1BA2 - CB1) from the Configuration-tool with copy and paste, (or the short
code: P1C3001) and verify it.
5. Select the Application Template (DIFF/DIS Basic).
6. Rename the device in the properties of 7SJ86 in “=D01 Line 1” and delete or add the necessary numbers of
protection functions in the Function Group FG* ”Line 1” according specification.
7. Add new Function Groups (FG*) for Disconnector- and Ground- Switches from the libraries in the device Line 1
and rename them.
8. Clarification of Attention-Signs
9. Settings of CT and VTs
10. Connect primary equipment to the device (CT-BC1 to FG* CB and to FG* Line1, VT-BA1 to FG* Line1 and FG
CB, VT-BA11 to FG CB (synchro) and synchronize the settings.
11. Link the commands and status from the FGs to the CB QA1, Disconnectors-QB1/QB9 and Ground Switches
QC1, QC2 and QC9
12. Set the IP address of “Line 1“ =D01 * FG – Function Group

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 20 Siemens Power Academy TD
00_Exercises
Exercise 4 DIGSI 5 Offline Design of SLD

1. Create a new project and rename it to “SIP5_basic” save it to C:Temp

2. Select the symbol standard IEC

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 21 Siemens Power Academy TD
00_Exercises
Exercise 4 DIGSI 5 Offline Design of SLD

3. Design a single bus bar line feeder by using a template (e.g. Double busbar line feeder),
change it like SLD feeder “=D01”. The max. of size should be 13x7 quadrates.
a) Open the “Single-line configuration” , b) Move the template
“Double-BB-Line Feeder”
from the Libraries “Protection Template" into the
SLD-drawing

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 22 Siemens Power Academy TD
00_Exercises
Exercise 4 DIGSI 5 Offline Design of SLD

3. Design a single bus bar line feeder by using a template (e.g. Double busbar line feeder),
change it like SLD feeder “=D01”. The max. of size should be 13x7 quadrates
c) Delete BB2, QB2 and BE2 , d) Connect QB9 with BE1 (by holding the left
mouse key)

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 24 Siemens Power Academy TD
00_Exercises
Exercise 4 DIGSI 5 Offline Design of SLD

3. Design a single bus bar line feeder by using a template (e.g. Double busbar line feeder),
change it like SLD feeder “=D01” The max. of size should be 13x7 quadrates.
e) Insert “Disconnector”, Grounding and 3-Phase-VT YY from the Libraries,
rotate and connect them , f) Set the data of
current transformers
BC1 (800/1A) and
voltage transformers BA1

Copyright © Siemens AG 2013. All rights reserved.


and BA 11 (220kV/110V)

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 25 Siemens Power Academy TD
00_Exercises
Exercise 4 DIGSI 5 Offline Design of SLD

3. Design a single bus bar line feeder by using a


template (e.g. Double busbar line feeder), change
it like SLD feeder “=D01”.
The max. of size should be 13x7 quadrates

g) Rename the components of SLD like specified

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 26 Siemens Power Academy TD
00_Exercises
Exercise 4 DIGSI 5 Offline Design of Device

4) Add a device using “Add new device”. Enter the MLFB-long code:
(7SL86-DAAA-AA0-0AAAA0-AZ1212-23111A-EBA000-000AA0-CB1BA2-CB1) from the
Configuration tool with copy and paste, (or the short code: P1C3001) and verify it.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 28 Siemens Power Academy TD
00_Exercises
Exercise 4 DIGSI 5 Offline Design of Device

4) If You have a online Internet access you can use a better Option:
Add a device using “Add new device”. Enter the Short code:(P1C3001) and verify it.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 29 Siemens Power Academy TD
00_Exercises
Exercise 4 DIGSI 5 Offline Design of Device

5) Select the Application Template (DIFF/DIS Basic).

Copyright © Siemens AG 2013. All rights reserved.


V02.01

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 30 Siemens Power Academy TD
00_Exercises
Exercise 4 DIGSI 5 Offline Design of Device

6) Rename the device in the properties of 7SL86 in “=D01 Line 1” and delete or add the necessary
numbers of protection functions in the Function Group FG ”Line 1” according specification.
Delete or add the necessary numbers of circuit breaker functions in the Function Group
FG ” Circuit Breaker 1 ” like specified.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 31 Siemens Power Academy TD
00_Exercises
Exercise 4 DIGSI 5 Offline Design of Device

6) Rename the device in the properties of 7SL86 in


“=D01 Line 1” and delete or add the necessary
numbers of protection functions in the Function
Group FG ”Line 1” according to specification.
Delete or add the necessary numbers of circuit
breaker functions in the Function Group

Copyright © Siemens AG 2013. All rights reserved.


FG ” Circuit Breaker 1 ” like specified.

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 32 Siemens Power Academy TD
00_Exercises
Exercise 4 DIGSI 5 Offline Design of Device

7) Add new Function Group (FG) for Disconnector- and Ground- Switches from the libraries in
the device Line 1 and rename it.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 33 Siemens Power Academy TD
00_Exercises
Exercise 4 DIGSI 5 Offline Connections to Device

8a) Clarification the Attention-Sign for Hardware and protocols.


What is missing? Get the information!

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 34 Siemens Power Academy TD
00_Exercises
Exercise 4 DIGSI 5 Offline Design of Device

8b) Clarification the Attention-Sign for Hardware and protocols.


Parameterize the “Interface E” Channel 1 as a Protection Interface for 2 devices, Channel 2 for
IEC 103 and after then press the button “check consistency”.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 35 Siemens Power Academy TD
00_Exercises
Exercise 4 DIGSI 5 Offline Design of Device

9) Settings of CT and VTs


9a) Add a 3phase voltage “Meas. Point V-3ph 2” in device D01 and clarify the Attention-Signs

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 38 Siemens Power Academy TD
00_Exercises
Exercise 4 DIGSI 5 Offline Design of Device

9b) Route the new Voltage-Measuring Point to the Expansion module 1 and link this VT
to FG Circuit Breaker 1

Copyright © Siemens AG 2013. All rights reserved.


VN

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 39 Siemens Power Academy TD
00_Exercises
Exercise 4 DIGSI 5 Offline Design of Device

9c) Enter the Rating of Current Transformer, the site of neutral point and the error factors
of CT diagram.

Copyright © Siemens AG 2013. All rights reserved.


for 5P30 24 VA
see Manual page 253

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 40 Siemens Power Academy TD
00_Exercises
Exercise 4 DIGSI 5 Offline Design of Device

9d) Enter the Rating of Voltage Transformers.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 41 Siemens Power Academy TD
00_Exercises
Exercise 4 DIGSI 5 Offline Design of Device

9e) Enter the Rated Value for 100%, of CT and VTs the kind of Primary Starpoint and the length of the
OH-Line for the FG Line 1.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 42 Siemens Power Academy TD
00_Exercises
Exercise 4 DIGSI 5 Offline Design of Device

9f) Enter the Rated Value for 100%, of CT and VTs for the FG Circuit breaker 1.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 43 Siemens Power Academy TD
00_Exercises
Exercise 4 DIGSI 5 Offline Communication Configuration

12) Set the IP address of “Line 1“ =D01 like your device on the table
Port J to 192.168.001.x (x=111/ 121/ 131/ 151/ 161/ 171) and the subnet mask
to 255.255.255.0

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 46 Siemens Power Academy TD
00_Exercises
Exercise 5a
DIGSI 5 Offline – Implementation of Control Functions

1) Allocate the position of switches in the “Information Routing” window:

BB disconnector QB1 to BI 1.7 (OH) and BI 1.8(CH) BI 7 and BI 8


Circuit breaker (CB) QA1 to BI 2.1 (OH) and BI 2.2 (CH) BI 9 and BI 10
Ground switch QC1 to BI 3.1 (OH) and BI 3.2 (CH) BI 12 and BI 13
Ground switch QC2 to BI 3.3 (OH) and BI 3.4 (CH) BI 14 and BI 15
Line disconnector QB9 to BI 3.5 (OH) and BI 3.6 (CH) BI 16 and BI 17
Ground switch QC9 to BI 3.7 (OH) and BI 3.8 (CH) BI 18 and BI 19

Copyright © Siemens AG 2013. All rights reserved.


2) Allocate the Command of switches in the “Information Routing” window.

Circuit breaker (CB) QA1 to BO 1.1(U) for open CB ;BO2 1.2 and BO 1.3 for close CB (X)
BB disconnector QB1 to BO 1.4 (X) and BO 1.5(X) for op/cl
Ground switch QC1 to BO 2.1 (X) and BO 2.2(X) for op/cl
Ground switch QC2 to BO 3.1 (X) and BO 3.2(X) for op/cl
Line disconnector QB9 to BO 3.3 (X) and BO 3.4(X) for op/cl
Ground switch QC9 to BO 3.5 (X) and BO 3.6(X) for op/cl

3a) Enter in the properties of “Control” of Circuit Breaker 1 the SBO* Time Out of 0,5s, the Feedback
Monitor Time of 5s and the release conditions of Control.
3b) Enter in the properties of Circuit Breaker 1 the Output Time of command = 0,5 s.

4a) Enter in the properties of Disconnectors the Output Time of commands = 10 s and
the Types of Switch (disconnector or grounding switch – IEC 61 850).
4b) Enter the Control Mode of Disconnector for the SBO Time Out of 30s, the Feedback Monitor Time of
25s and the release conditions of Control in the Properties of ”Control” of Disconnectors and Ground
Switches
* SBO – Select before operate

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 47 Siemens Power Academy TD
00_Exercises
Exercise 5a
DIGSI 5 Offline – Implementation of Control Functions
1) Allocate the position of switches
in the “Information Routing” window.

QB1 to BI 1.7 (OH) and BI 1.8(CH)


QA1 to BI 2.1 (OH) and BI 2.2 (CH)
QC1 to BI 3.1 (OH) and BI 3.2 (CH)
QC2 to BI 3.3 (OH) and BI 3.4 (CH)
QB9 to BI 3.5 (OH) and BI 3.6 (CH)
QC9 to BI 3.7 (OH) and BI 3.8 (CH)

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 48 Siemens Power Academy TD
00_Exercises
Exercise 5a
DIGSI 5 Offline – Implementation of Control Functions
2) Allocate the Command of switches in the “Information Routing” window.

QA1 to BO 1.1(U) for open CB ;BO2 1.2 and BO 1.3 for close CB (X)
QB1 to BO 1.4 (X) and BO1.5(X) for op/cl
QC1 to BO2.1 (X) and BO2.2(X) for op/cl
QC2 to BO3.1 (X) and BO3.2(X) for op/cl
QB9 to BO3.3 (X) and BO3.4(X) for op/cl
QC9 to BO3.5 (X) and BO3.6(X) for op/cl

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 49 Siemens Power Academy TD
00_Exercises
Exercise 5a
DIGSI 5 Offline – Implementation of Control Functions

3a) Enter in the properties of Circuit Breaker the Output Time of command = 0,5 s.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 50 Siemens Power Academy TD
00_Exercises
Exercise 5a
DIGSI 5 Offline – Implementation of Control Functions

3b) Enter the control mode of Circuit


Breaker 1 for the SBO* time out of
30s, the Feedback Monitor Time of
5s and the release conditions of
Control in the Properties of ”Control”.

Copyright © Siemens AG 2013. All rights reserved.


* SBO – Select before operate

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 51 Siemens Power Academy TD
00_Exercises
Exercise 5a
DIGSI 5 Offline – Implementation of Control Functions

4a) Enter in the properties of Disconnectors the Output Time of commands = 10 s and
the Types of Switch (disconnector or grounding switch – IEC 61 850).

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 52 Siemens Power Academy TD
00_Exercises
Exercise 5a
DIGSI 5 Offline – Implementation of Control Functions
4b) Enter the Control Mode of Disconnector for
the SBO Time Out of 30s, the Feedback
Monitor Time of 25s and the release
conditions of Control in the Properties of
”Control” of Disconnectors and Ground
Switches .

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 53 Siemens Power Academy TD
00_Exercises
Exercise 5b
DIGSI 5 Offline – Implementation of Control Functions

1. Labeling of Information's. Label the following Circuit breaker signals:


trip/open cmd.: ”Trip CB QA1 cmd”
Close command: “Close CB QA1 cmd”
Position: “Pos CB QA1”

Copyright © Siemens AG 2013. All rights reserved.


2. Change the Allocation of F-Keys: Allocate F3 to “Operational Logs”, F4 to “Fault Log” F5 to “Operational
values”.
3. Allocate LEDs: LED10: CB Open, LED11: CB Closed
and Change the color of the LED11 to green
4. Download the parameters into the device via USB-Front-Interface

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 54 Siemens Power Academy TD
00_Exercises
Exercise 5b
DIGSI 5 Offline – Implementation of Control Functions
1) Label the following Circuit breaker signals: Position as “Pos CB QA1”; trip/open cmd. as ”Trip CB QA1 cmd” and
Close command as “Close CB QA1 cmd”

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 55 Siemens Power Academy TD
00_Exercises
Exercise 5b
DIGSI 5 Offline – Implementation of Control Functions
2) Change the Allocation of F-Keys: Allocate F3: Operational Logs, F4: Fault Log F5: Operational values.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 56 Siemens Power Academy TD
00_Exercises
Exercise 5b
DIGSI 5 Offline – Implementation of Control Functions
3) Allocate LED 1.10: CB Open, LED 1.11: CB Closed and Change the color of the LED 1.11 to green.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 57 Siemens Power Academy TD
00_Exercises
Exercise 5b
DIGSI 5 Offline – Implementation of Control Functions
4) Download the parameters into the device via USB-Front-Interface.
Enter the ID: 222 222 and test the settings.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 58 Siemens Power Academy TD
00_Exercises
Exercise 6
DIGSI 5 Offline – Design of Display Pages

1. Go to the single-line configuration (SLC) and create a display page of the bay. Select
the complete bay and use the “Create Display” button
2. Delete the default display page “Bay 1“ and design the Page D01 with moving of
devices.
3. Link the Switching Devices with “Command with feedback” with drag @ drop

Copyright © Siemens AG 2013. All rights reserved.


4. Create a new Measurement page. Add another display page and add all the
measurement values required for this bay. They are available in the signal catalog in
the group “Line 1 –> Operational Values”
5. Save the project, download the parameters via USB into the device and check the
display pages.

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 59 Siemens Power Academy TD
00_Exercises
Exercise 6
DIGSI 5 Offline – Design of Display Pages

1) Go to the single-line configuration (SLC) and create a display page of the bay. Select the complete
SIP5 device and use the “Create Display” button.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 60 Siemens Power Academy TD
00_Exercises
Exercise 6
DIGSI 5 Offline – Design of Display Pages

2) Delete the “Operation Values” page and design the Page =D01 220kV Line 1 with moving of symbols.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 61 Siemens Power Academy TD
00_Exercises
Exercise 6
DIGSI 5 Offline – Design of Display Pages
3) Link the Switching Devices with “Command with feedback” with drag and drop

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 62 Siemens Power Academy TD
00_Exercises
Exercise 6
DIGSI 5 Offline – Design of Display Pages

4) Create a new Measurement page. Add a new display page, rename it to “=D01 Values” and add
all the measurement values required for this bay. They are available in the signal catalogue in
the group “Line 1 –> “Operational Values”

Copyright © Siemens AG 2013. All rights reserved.


5) Save the project, download the parameters via USB into the device and check the display pages

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 63 Siemens Power Academy TD
00_Exercises
Exercise 7a
DIGSI 5 Offline – Implementation of Protection Functions 1/11

Settings of Distance Protection.


1. The parameterization shall be in secondary values (Edit Mode)
2. Adapt the distance settings for the different zones
 Zone Xreach Rph-ph Rph-g t
 Z1 forward 6,2 3,6 7,2 Ohm 0s
 Z1B forward 15 14,4 14,5 Ohm 0s
 Z2 forward 15 14,4 14,5 Ohm 0,3 s

Copyright © Siemens AG 2013. All rights reserved.


 Z3 reverse 0,6 2,4 1,2 Ohm 0,9
 Z4 switched off

3. By mistake you entered 1450 Ohm instead of 14,5 Ohm for Zone 1B.
See how this invalid value is displayed.
4. Check the list of inconsistencies in the Info area and click on a setting inconsistency
to directly jump there
5. Add a setting group and copy the settings from group 1 to group 2
6. Change the Zone 1 setting in setting group 2 from 6.2 Ohm to 62 Ohm and see how
the difference is displayed
7. Switch on Zone 4 directly from the information routing
8. Save the project and download the parameters into the device
9. Save the project and download the parameters into the device via USB Front-
Interface.

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 64 Siemens Power Academy TD
00_Exercises
Exercise 7a
DIGSI 5 Offline – Implementation of Protection Functions 2/11

1) The parameterization shall be in secondary values (Edit Mode)

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 65 Siemens Power Academy TD
00_Exercises
Exercise 7a
DIGSI 5 Offline – Implementation of Protection Functions 3/11
2) Adapt the distance settings for the different zones
Zone Xreach Rph-ph Rph-g t
Z1 forward 6,2 3,6 7,2 Ohm 0s
Z1B forward 15 14,4 14,5 Ohm 0s
Z2 forward 15 14,4 14,5 Ohm 0,3 s
Z3 reverse 0,6 2,4 1,2 Ohm 0,9
Z4 switched off

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 66 Siemens Power Academy TD
00_Exercises
Exercise 7a
DIGSI 5 Offline – Implementation of Protection Functions 4/11
2) Adapt the distance settings for the different zones

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 67 Siemens Power Academy TD
00_Exercises
Exercise 7a
DIGSI 5 Offline – Implementation of Protection Functions 5/11
3) By mistake you entered 1450 Ohm instead of 14,5 Ohm for Zone 1B.
See how this invalid value is displayed.
4) Check the list of inconsistencies in the Info area and click on a setting inconsistency to directly jump
there

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 68 Siemens Power Academy TD
00_Exercises
Exercise 7a
DIGSI 5 Offline – Implementation of Protection Functions 6/11

5) Add a setting group and copy the settings from group 1 to group 2

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 69 Siemens Power Academy TD
00_Exercises
Exercise 7a
DIGSI 5 Offline – Implementation of Protection Functions 7/11

5) Add a setting group and copy the settings from group 1 to group 2

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 70 Siemens Power Academy TD
00_Exercises
Exercise 7a
DIGSI 5 Offline – Implementation of Protection Functions 8/11

6) Change the Zone 1 setting in setting group 2 from 6.2 Ohm to 62 Ohm and see how
the difference is displayed

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 71 Siemens Power Academy TD
00_Exercises
Exercise 7a
DIGSI 5 Offline – Implementation of Protection Functions 9/11

7) The general pickup of zone 1 shall


appear as a binary trace in the fault
record.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 72 Siemens Power Academy TD
00_Exercises
Exercise 7a
DIGSI 5 Offline – Implementation of Protection Functions 10/11

8) Switch on Zone 4 directly from the information routing

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 73 Siemens Power Academy TD
00_Exercises
Exercise 7a
DIGSI 5 Offline – Implementation of Protection Functions 11/11

9) Save the project and download the parameters into the device via USB Front-Interface.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 74 Siemens Power Academy TD
00_Exercises
Exercise 7b
DIGSI 5 Offline – Implementation of Protection Functions 1/3

Back up Overcurrent Protection


1. The pickup settings of Line 1 shall be
50/51-1 = 1.2 * I/IN (T1) t I> =……
50/51-2 = 2.5 * I/IN (T2) t I>> =0,05

Copyright © Siemens AG 2013. All rights reserved.


2. Find suitable grading times for the application below for 50/51-1 O/C 3-Ph :

Power flow
Substation 1 Substation 2
Line 1 Bus Coupler Line 2 Incoming

BB1 BB2
0,3 s

3. Parameterize the pickup threshold and grading time (operate delay) of Line 1
4. Display the Setting Diagram

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 75 Siemens Power Academy TD
00_Exercises
Exercise 7b
DIGSI 5 Offline – Implementation of Protection Functions 2/3

2. The pickup settings of Line 1 shall be


T1 50/51-1 = 1.2 * I/IN t= …..
T2 50/51-2 = 2.5 * I/IN t= 0,05s

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 76 Siemens Power Academy TD
00_Exercises
Exercise 7b
DIGSI 5 Offline – Implementation of Protection Functions 3/3

5) Display the Setting Diagram

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 77 Siemens Power Academy TD
00_Exercises
Exercise 7c
DIGSI 5 Offline – Implementation of Protection Functions 1/7

1. Reverse Interlocking of Overcurrent Protection


1.1 Add a new stage of “50/51 O/C 3-Ph A1“ function for Line 1
1.2 Go to the information routing of device Line 1 and parameterize the

Copyright © Siemens AG 2013. All rights reserved.


blocking of the 50/51-2 O/C (T3) function.
1.3 The Settings of stage T3 should be 1.2 A Threshold and 0.05s Operate
delay
1.4 The stage shall be blocked, when binary input 1 goes “high”. Use filtering
to reduce the number of displayed information (>Block stage)
Route the “>Block stage” information to the user-defined Lock List 1.
Test the Reverse Interlocking function.
2. Assign function key 8 to „Setting-history log“.
3. Assign BO1 for trip, BO2 and BO3 for open to 3-pole command (in FG Circuit
Breaker). The trip contacts shall be latched (TL*).
4. The general pickup of zone 1 shall appear as a binary trace in the fault
record
* TL – trip latched

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 78 Siemens Power Academy TD
00_Exercises
Exercise 7c
DIGSI 5 Offline – Implementation of Protection Functions 2/7

1.1 Add the new stage of “50/51 O/C 3-Ph A1“ function to Line 1

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 79 Siemens Power Academy TD
00_Exercises
Exercise 7c
DIGSI 5 Offline – Implementation of Protection Functions 3/7

1. Reverse Interlocking diagram of Overcurrent Protection

Power flow

Copyright © Siemens AG 2013. All rights reserved.


Substation 1 Substation 2
Line 1 Bus Coupler Line 2 Incoming

BB1 BB2
BI 1.1 Block (T3) I>>> (T3) t I>>> 0,05s 0,3 s
(T1)t I> 1,2s t I> 0,9,s t I> 0,6,s

pick up pick up

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 80 Siemens Power Academy TD
00_Exercises
Exercise 7c
DIGSI 5 Offline – Implementation of Protection Functions 4/7

1.2 The Settings of stage T3 should be 1.2 A for Threshold and 0.05s for Operate delay

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 81 Siemens Power Academy TD
00_Exercises
Exercise 7c
DIGSI 5 Offline – Implementation of Protection Functions 5/7

1.3 Go to the information routing of device Line 1 and parameterize the blocking of stage 3
(Definite T3) of 50/51 O/C function. The stage shall be blocked, when binary input 1.1 goes “high”.
Use filtering to reduce the number of displayed information (>Block stage)
Route the “>Block stage” information to the user-defined Lock List 1.
Test the Reverse Interlocking function.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 82 Siemens Power Academy TD
00_Exercises
Exercise 7c
DIGSI 5 Offline – Implementation of Protection Functions 6/7

2) Assign Function Key 8 to „Setting-history log“

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 83 Siemens Power Academy TD
00_Exercises
Exercise 7c
DIGSI 5 Offline – Implementation of Protection Functions 7/7

3) Assign BO1 for trip, BO2 and BO3 for


close (in FG Circuit Breaker). The trip
contacts shall be latched (TL*).

Copyright © Siemens AG 2013. All rights reserved.


* TL – trip latched

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 84 Siemens Power Academy TD
00_Exercises
Exercise 8
DIGSI 5 Online Operation with SIPROTEC 5

1. Go online onto the device


2. Read the process information by selecting “Get all data from device”
3. Set the device time to PC time.
4. Check the log files

Copyright © Siemens AG 2013. All rights reserved.


5. Transfer fault records and trigger a test fault record
6. Check the Indications and save a snapshot
7. Check the measurement values and save a snapshot
8. Change settings in your online device

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 85 Siemens Power Academy TD
00_Exercises
Exercise 8
DIGSI 5 Online Operation with SIPROTEC 5

1. Select the =Do1 Line 1 device and “Connect


to device”:

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 86 Siemens Power Academy TD
00_Exercises
Exercise 8
DIGSI 5 Online Operation with SIPROTEC 5

In the folder “Online access” your Online device =D01 will be displayed.
2. Retrieve the process information of the selected the device by double-click on Get all data
from device:

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 87 Siemens Power Academy TD
00_Exercises
Exercise 8
DIGSI 5 Online Operation with SIPROTEC 5

Back up transparency:
To connect to another device in online mode do disconnect the already connected device by the
context menu.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 88 Siemens Power Academy TD
00_Exercises
Exercise 8
DIGSI 5 Online Operation with SIPROTEC 5

3. To change the time double-click on Device information and select the Time information tab.

Copyright © Siemens AG 2013. All rights reserved.


a) Click on Edit time button.

b) To use the PC time click on


the Down arrow.

c) A calendar appears. Here


click on Today button.

d) The change of time is activated by clicking on Set time button. e) Enter 222222 as confirmation ID.
SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 89 Siemens Power Academy TD
00_Exercises
Exercise 8
DIGSI 5 Online Operation with SIPROTEC 5

4. Check the log files in Logs node:

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 90 Siemens Power Academy TD
00_Exercises
Exercise 8
DIGSI 5 Online Operation with SIPROTEC 5

5. Check & read fault records. Trigger a test fault record. Show in SIGRA via the context menu.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 91 Siemens Power Academy TD
00_Exercises
Exercise 8
DIGSI 5 Online Operation with SIPROTEC 5

6. Check the indications:

Copyright © Siemens AG 2013. All rights reserved.


To save the indications, click the Snapshot button in the menu bar. They will be
available in offline mode in the folder Process data, Menu Indication snapshots.

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 92 Siemens Power Academy TD
00_Exercises
Exercise 8
DIGSI 5 Online Operation with SIPROTEC 5

7. Check the measurement values by double-click on Line 1 in the Measurements node.

Copyright © Siemens AG 2013. All rights reserved.


To save the measured values, click the Snapshot button in the menu bar. They will be available in
offline mode in the folder Process data, Menu Measured-value snapshots.
SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 93 Siemens Power Academy TD
00_Exercises
Exercise 8
DIGSI 5 Online Operation with SIPROTEC 5

8. To change settings in the online device open the nodes Expert configuration > Settings > Line 1
and double-click
the function
50/51 OC-3ph 1

Copyright © Siemens AG 2013. All rights reserved.


Click on the Edit
settings button

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 94 Siemens Power Academy TD
00_Exercises
Exercise 8
DIGSI 5 Online Operation with SIPROTEC 5

8. Now it is possible to change the settings. Change the parameter Threshold to 1.500 A
and double-click on Load changes
to device. Confirm with 222222.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 95 Siemens Power Academy TD
00_Exercises
Exercise 8
DIGSI 5 Online Operation with SIPROTEC 5

8. Then compare the settings with offline device by clicking on Compare devices in the context menu.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 96 Siemens Power Academy TD
00_Exercises
Exercise 8
DIGSI 5 Online Operation with SIPROTEC 5

8. Click on Update offline configuration in the context menu of the online device.

Copyright © Siemens AG 2013. All rights reserved.


Compare the device again. The list of comparison
should now be empty:

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 97 Siemens Power Academy TD
00_Exercises
Exercise 9
DIGSI 5 Offline – Logic Function Charts (CFC) 1/6

LED flashing when the device is set on local control


When the control key is in LOCAL, all odd LEDs in the expansion module shall
change their status every second.
When the control key is in remote position, the LEDs shall be turned off

Copyright © Siemens AG 2013. All rights reserved.


1. Add a new function chart called “Local” and select the task “event-triggered”
2. Insert a „Blink“ block from the library
3. Change the time settings of the “high“ (TH) and “low“ (TL) inputs according
to the exercise
4. Open the signal catalog and connect the signal “Switching Authority ->
Local“ to the input “Start“. This signal can be found in the folder “General“.
5. Connect all the odd LEDs of the expansion module to the output Q of the
block. The LED signals can be found in the group “Binary IO“
6. Save the project, download the parameters into the device and test the CFC
logic

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 98 Siemens Power Academy TD
00_Exercises
Exercise 9
DIGSI 5 Offline – Logic Function Charts (CFC) 2/6

1) Add a new function chart called “Local” and select the task “event-triggered”

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 99 Siemens Power Academy TD
00_Exercises
Exercise 9
DIGSI 5 Offline – Logic Function Charts (CFC) 3/6

2) Insert a „Blink“ block from the library

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 100 Siemens Power Academy TD
00_Exercises
Exercise 9
DIGSI 5 Offline – Logic Function Charts (CFC) 4/6

3) Change the time settings of the “high“ (TH) and “low“ (TL) inputs according to the exercise

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 101 Siemens Power Academy TD
00_Exercises
Exercise 9
DIGSI 5 Offline – Logic Function Charts (CFC) 5/6

4) Open the signal catalog and connect the signal “Switching Authority -> Local“
to the input “Start“. This signal can be found in the folder “General“.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 102 Siemens Power Academy TD
00_Exercises
Exercise 9
DIGSI 5 Offline – Logic Function Charts (CFC) 6/6

5) Connect all the odd LEDs of the expansion module to the output Q of the
block. The LED signals can be found in the group “Binary IO“
6) Save the project, download the parameters into the device and test the CFC logic

Copyright © Siemens AG 2013. All rights reserved.


10 100 ms
10 100 ms

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 103 Siemens Power Academy TD
00_Exercises
Exercise 10
DIGSI 5 Offline – Logic Function Charts (CFC) 1/11

Change the setting group (SG)


Using of 2 Binary Inputs for changing 4 Setting-Groups between 1 up to 4.

1. Click on “Device Settings“ and select 4 groups. Select “binary input” for Active settings group parameter:
2. Open the matrix, right-click on group “General“

Copyright © Siemens AG 2013. All rights reserved.


Assign for >SG choice bit 1 and bit 2 the binary input 1.2 and 1.3 as “H”
3. Allocate “Act. settings group 1 up to 4 on” to LED 1.5 up to 1.8 as “U”
4. Insert a Integer status (INS) Information in the Information Group “General” and rename it in “No of Setting
Group”
5. Insert the “No of Setting Group” in the display of page =D01 220kV Line 1.
6. Add a new chart (CFC), rename it in “Setting Group” and select “Event-triggered”
for the task of function chart.
7. Select the MOD-Input and enter “3” for the Mode in the properties of this module.
8. Add a “ADD_D”-Module, rename it in “Setting Group” and enter “1” in the properties of 2’th Input.
9. Link the modules and connect the IN1 and IN2 to the “SG choice bit 1 and 2” and connect the Output of
User defined Information “No of Setting Group” and compile the new Chart.
10. Save the project, download the parameters into the device and test this Exercise.

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 104 Siemens Power Academy TD
00_Exercises
Exercise 10
DIGSI 5 Offline – Logic Function Charts (CFC) 2/11

Change the setting group (SG)

SG Bit 1 Bit 2 Bit 3

Copyright © Siemens AG 2013. All rights reserved.


1 0 0 0
2 1 0 0
3 0 1 0
4 1 1 0
5 0 0 1
6 1 0 1
7 0 1 1
8 1 1 1

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 105 Siemens Power Academy TD
00_Exercises
Exercise 10
DIGSI 5 Offline – Logic Function Charts (CFC) 3/11
1. Click on “Device Settings“ and select 4 groups. Select “binary input” for Active settings group parameter:

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 106 Siemens Power Academy TD
00_Exercises
Exercise 10
DIGSI 5 Offline – Logic Function Charts (CFC) 4/11

2. Assign for >SG choice bit 1 and bit 2 the Binary Input 1.2 and 1.3 as “H”

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 107 Siemens Power Academy TD
00_Exercises
Exercise 10
DIGSI 5 Offline – Logic Function Charts (CFC) 5/11

3. Allocate “Act. settings group 1 up to 4 on” to LED 1.5 up to 1.8 as “U”

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 108 Siemens Power Academy TD
00_Exercises
Exercise 10
DIGSI 5 Offline – Logic Function Charts (CFC) 6/11

4. Insert a Integer status (INS) Information in the Information Group “General” and rename it in “No of Setting Group”

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 109 Siemens Power Academy TD
00_Exercises
Exercise 10
DIGSI 5 Offline – Logic Function Charts (CFC) 7/11

5. Insert the “No of Setting Group” in the display


of page =D01 220kV Line 1.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 110 Siemens Power Academy TD
00_Exercises
Exercise 10
DIGSI 5 Offline – Logic Function Charts (CFC) 8/11

6. Add a new chart (CFC), rename it in “Setting Group” and select “Event-triggered”
for the task of function chart.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 111 Siemens Power Academy TD
00_Exercises
Exercise 10
DIGSI 5 Offline – Logic Function Charts (CFC) 9/11

7. Insert a Logic “BOOL_Int” Module in the new chart rename it in “BOOL to Integer” and switch off
the 3’th and 4’th Input of this module in the properties.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 112 Siemens Power Academy TD
00_Exercises
Exercise 10
DIGSI 5 Offline – Logic Function Charts (CFC) 10/11

8. Select the MOD-Input and enter “3” for the Mode in the properties of this module.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 113 Siemens Power Academy TD
00_Exercises
Exercise 10
DIGSI 5 Offline – Logic Function Charts (CFC) 11/11

9. Add a “ADD_D”-Module, rename it in “Setting Group” and enter “1” in the properties of 2’th Input.
Link the modules and connect the IN1 and IN2 to the “SG choice bit 1 and 2” and connect the
Output of User defined Information “No of Setting Group” and compile the new Chart.
10. Save the project, download the parameters into the device and test this Exercise.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 114 Siemens Power Academy TD
00_Exercises
Exercise 11
DIGSI 5 Offline - Display Power Flow and SF6 Loss 1/4

1. Add a new User-defined function block and rename it Process Signal. Add two user defined
signals: Double-point signal for Power Flow Direction and Single-point signal for SF6 Loss. Assign
binary input 4 as Low Active to the SF6 Loss signal.
2. Create a new CFC chart P-Direction for the power flow direction as follows.
3. Create a new dynamic symbol with 4 states in the display and connect it with the P-Direction

Copyright © Siemens AG 2013. All rights reserved.


signal.
4. The SF6 Loss signal can be added directly by drag&drop into the display page.

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 115 Siemens Power Academy TD
00_Exercises
Exercise 11
DIGSI 5 Offline - Display Power Flow and SF6 Loss 2/4

1. Add a new User-defined function block and rename it Process Signal. Add two user defined signals:
Double-point signal for Power Flow Direction and Single-point signal for SF6 Loss. Assign binary
input 4 as Low Active to the SF6 Loss signal.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 116 Siemens Power Academy TD
00_Exercises
Exercise 11
DIGSI 5 Offline - Display Power Flow and SF6 Loss 3/4

2. Create a new CFC chart P-Direction for the power flow direction as follows:

Copyright © Siemens AG 2013. All rights reserved.


0.001
0
16 # 0000

- 0.001

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 117 Siemens Power Academy TD
00_Exercises
Exercise 11
DIGSI 5 Offline - Display Power Flow and SF6 Loss 4/4
3. Insert a new dynamic symbol (with 4 states) onto the display and connect it with the P-Direction
signal.

Copyright © Siemens AG 2013. All rights reserved.


4) SF6 Loss signal can be
added directly by drag&drop
into the display page.

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 118 Siemens Power Academy TD
00_Exercises
Exercise 12
DIGSI 5 Offline – Expansion of Function Points

Imagine the =D01 feeder is a Base-Version without Function Points


and you have to expand this Line 1 - feeder.
• Check the number of Function Points of =D01-Line1 Feeder in your project.
• Get the Serial number (BM) of the Line 1 feeder from the menu of your SIP 5 device.

Copyright © Siemens AG 2013. All rights reserved.


• Use the SIPROTEC 5 Online Configurator for Expasion of Function Points of your device:
-Select your Type of Protection device
- Enter the Serial BM-number
-Select the Expansion Base + 100 function points and the Mode of dispatch
- Get the Order-Number for this Expansion.
4. After Ordering of Expansion of function points you will get a DAF-file.
In the reality you can follow the Instruction for Expansion of functions

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 119 Siemens Power Academy TD
00_Exercises
Exercise 12
DIGSI 5 Offline – Expansion of Function Points

1. Check the number of Function Points of =D01-Line1 Feeder

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 120 Siemens Power Academy TD
00_Exercises
Exercise 12
DIGSI 5 Offline – Expansion of Function Points

2. Get the Serial number (BM) of the Line 1 feeder from the menu of your SIP 5 device.

Copyright © Siemens AG 2013. All rights reserved.


3. Use the SIPROTEC 5 Online Configurator for
Expansion of Function Points of your device:
-Select your Type of Protection device
- Enter the Serial BM-number
-Select the Expansion Base + 100 function points and
the Mode of dispatch
- Get the Order-Number for this Expansion.

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 121 Siemens Power Academy TD
00_Exercises
Exercise 12
DIGSI 5 Offline – Expansion of Function Points
4. After Ordering of Expansion of function points you will get a DAF-file.
In the reality you can follow the Instruction for Expansion of functions, don’t do it in the course.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 122 Siemens Power Academy TD
00_Exercises
Exercise 14a
DIGSI 5 - Simple Goose Communication

Expansion of SLD for a Busbar Coupler

1. Expand the Single Line Diagram for the Bus Coupler by using of a template (“Busbar Coupler Bay”) and change it like
specified SLD feeder “=D02”
a) Open the “Single-line configuration”
b) Move the template “Busbar Coupler Bay” from the Libraries in the SLD-drawing
c) Delete BB1 and change the link of Voltage Transformer QE5 to the BB2
d) Rename the components of SLD like specified in QC11, QC21, QA1, BA21 and BC1.

Copyright © Siemens AG 2013. All rights reserved.


e) Move the BA21 and BC1 in the correct position and link them.
f) Insert “Disconnector”, and “Grounding” from the Libraries, rotate and connect them
g) Set the data of current transformer BC1 (2500/1A) and voltage transformer BA21 and
BA 11 (220kV/110V)
h) Rename the components of SLD like specified

2. Add a device using “Add new device”. Enter the MLFB-long code: (7SL86 – DAAA -AA0 - 0AAAA0 - AZ1212 - 23111A
- EBA000 - 000AA0 - CB1BA2 - CB1) from the Configuration-tool with copy and paste, (or the short code: P1C3001)
and verify it.
3. Select the Application Template (DIFF/DIS Basic).
4. Rename the device in the properties of 7SJ86 in “=D02 Bus Coupler” and delete or add the necessary numbers of
protection functions in the Function Group “Circuit Breaker 1” and “ FG* ”Line 1” according specification.
5. Rename FG “Line 1” into “Bus Coupler”
6. Add new Function Groups (FG) for Disconnector- and Ground- Switches from the libraries in the device D02 and
rename them.
7. Clarify the Attention-Sign.
8. Connect primary equipment to the device (CT-BC1 to FG CB and to FG Bus Coupler, VT-BA21 to FG Bus Coupler and
FG CB, the VT-BA11 (Bay-D01) only to FG CB (V sync 2) and synchronize the settings.
9. Link the commands and status from the FGs to the CB QA1, Disconnectors-QB11/QB21 and Ground Switches QC11,
QC1, QC2 and QC21

* FG- Function Group

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 124 Siemens Power Academy TD
00_Exercises
Exercise 14a
DIGSI 5 - Simple Goose Communication

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 125 Siemens Power Academy TD
00_Exercises
Exercise 14a
DIGSI 5 - Simple Goose Communication
1) Allocate the position of switches in the “Information Routing” window of BC:

BB1 Ground switch QC11 to BI 1.1(OH) and BI 1.2 (CH)


BB1 disconnector QB11 to BI 1.7 (OH) and BI 1.8(CH)
Circuit breaker (CB) QA1 to BI 2.1 (OH) and BI 2.2 (CH)
Line disconnector QB21 to BI 3.1 (OH) and BI 3.2 (CH)
Ground switch QC1 to BI 3.3 (OH) and BI 3.4 (CH)
Ground switch QC2 to BI 3.5 (OH) and BI 3.6 (CH)
Ground switch QC21 to BI 3.7 (OH) and BI 3.8 (CH)

Copyright © Siemens AG 2013. All rights reserved.


2) Enter the control model of Circuit Breaker 1 and the SBO* Time Out, the Feedback Monitor Time (5s) and the interlocking conditions in the
Properties of ”Control”.

3) Enter the Control Model and the SBO* Time Out, the Feedback Monitor Time (15s) and the interlocking conditions in the settings of Properties of
”Control” for Disconnectors and Ground Switches.

4) Allocate the Command of switches in the “Information Routing” window.

Circuit breaker (CB) QA1 to BO1.1 (X) and BO 1.2(X) for op/cl
BB1 Ground switch QC11 to BO 1.3(X) and BO 1.4(X) for op/cl
BB1 disconnector QB11 to BO 1.5 (X) and BO 1.6(X) for op/cl
Ground switch 1 QC1 to BO 2.1 (X) and BO 2.2(X) for op/cl
Ground switch 2 QC2 to BO 3.1 (X) and BO 3.2(X) for op/cl
BB2 disconnector QB21 to BO 3.3 (X) and BO 3.4(X) for op/cl
BB2 ground switch QC21 to BO 3.5(X) and BO 3.6(X) for op/cl

5) Enter in the properties of Circuit Breaker the Output Time of command = 0,5 s.

6) Enter in the properties of Disconnectors the Output Time of commands = 10 s and the Type of Switch (grounding switch or disconnector).
7) Save and download =D02 in your divice (over write =D01) and test it.

* SBO – Select before operate

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 126 Siemens Power Academy TD
00_Exercises
Exercise 14a
DIGSI 5 - Simple Goose Communication

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 127 Siemens Power Academy TD
00_Exercises
Exercise 14b
DIGSI 5 - Simple Goose Communication

Expansion of DIGSI 5 Project for Busbar Coupler

1) Set the IP address of “Line 1“ =D01


Port J to 192.168.001.x (x=111/ 121/ 131/ 151/ 161/ 171)
and the subnet mask to 255.255.255.0
Port F to 192.168.001.x (x=113/ 123/ 133/ 153/ 163/ 173)
and the subnet mask to 255.255.255.0

Copyright © Siemens AG 2013. All rights reserved.


and link the interfaces to the Bus Coupler =D02 and rename the networks.

2) Set the IP address of “Bus Coupler“ =D02


Port J to 192.168.001.x (x=112/ 122/ 132/ 152/ 162/ 172)
and the subnet mask to 255.255.255.0
Port F to 192.168.001.x (x=114/ 124/ 134/ 154/ 164/ 174)
and the subnet mask to 255.255.255.0

3) Set in both devices =D01 and = D02:


a) Select the Time Source 1 to 192.168.1.5 and Time Source 1 to 192.168.1.15
b) Enable SNMP , DCP and RSTP
c) Select IEC 61850-8-1 (Edition 1) as communication protocol

4) Save the project and download the parameters of “Line 1” and “Bus Coupler” into the devices.

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 128 Siemens Power Academy TD
00_Exercises
Exercise 14b
DIGSI 5 - Simple Goose Communication

Expansion of the DIGSI 5 Project for a Busbar Coupler


1) Set the IP address of “Line 1“ =D01
Port J to 192.168.001.x (x=111/ 121/ 131/ 151/ 161/ 171) and the subnet mask to 255.255.255.0
Port F to 192.168.001.x (x=113/ 123/ 133/ 153/163/ 173) and the subnet mask to 255.255.255.0
and link the interfaces to the Bus Coupler =D02,
and rename the networks.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 129 Siemens Power Academy TD
00_Exercises
Exercise 14b
DIGSI 5 - Simple Goose Communication

Expansion of the DIGSI 5 Project for a Busbar Coupler


2) Set the IP address of “Bus Coupler“ =D02
Port J to 192.168.001.x (x=112/ 122/ 132/ 152/ 162/ 172) and the subnet mask to 255.255.255.0
Port F to 192.168.001.x (x=114/ 124/ 134/ 154/ 164/ 174) and the subnet mask to 255.255.255.0

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 130 Siemens Power Academy TD
00_Exercises
Exercise 14b
DIGSI 5 - Simple Goose Communication
3) Set in both devices =D01 and = D02:
a) Select the Time Source 1 to 192.168.1.5 and Time Source 1 to 192.168.1.15
b) Enable SNMP , DCP and RSTP
c) Select IEC 61850-8-1 (Edition 1) as communication protocol
4) Save the project

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 131 Siemens Power Academy TD
00_Exercises
Exercise 14c
DIGSI 5 - Simple Goose Communication 1/7

If the F4 key in device 1 is pressed in both devices =D01 and =D02 LED 4 should change the status.
If the F6 key in device 2 is pressed in both devices LED 6 should change the status.
The GOOSE messages should be logged in a User Log.
1. Establish a network for two devices. GOOSE’ing works only with Ethernet communication modules.
2. In device D01 Line add two User-defined function blocks and rename them to Goose send and Goose

Copyright © Siemens AG 2013. All rights reserved.


receive. Add a user defined signal -> Goose send: Single-point signal F4 LED4. Assign function key 4 as
Toggle and LED 4 for indication.
3. In device D02 BC add two User-defined function blocks and rename them to Goose send and Goose receive.
Add a user defined signal -> Goose send: Single-point signal F6LED6. Assign function key 6 as Toggle and
LED 6 for indication.
4. Set up a GOOSE application and drag & drop F4 LED4 for the source signals in the D01 device and F6 LED6
in the D02 device. For the destination column only Logical Nodes Goose Receive from both devices are
enough to establish a GOOSE connection. The destination signals will be created automatically.
5. New signals appear in the information matrix as the result of the GOOSE assignment. They can be used as
own signals now – rename and assign them to required LEDs. Assign all GOOSE signals into User Log U1.
Device 1.
6. Do the corresponding settings for device 2.
Save and load parameters for both devices. Test the GOOSE communication at the devices.

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 132 Siemens Power Academy TD
00_Exercises
Exercise 14
DIGSI 5 - Simple Goose Communication 2/7

1. Establish a network with for the two devices. GOOSE’ing works only with Ethernet communication
modules.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 133 Siemens Power Academy TD
00_Exercises
Exercise 14
DIGSI 5 - Simple Goose Communication 3/7

2. In device D01 Line add two User-defined function blocks and rename them to Goose send and
Goose receive. Add a user defined signal -> Goose send: Single-point signal F4 LED4. Assign
function key 4 as Toggle and LED 4 for indication.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 134 Siemens Power Academy TD
00_Exercises
Exercise 14
DIGSI 5 - Simple Goose Communication 4/7

3. In device D02 BC add two User-defined function blocks and rename them to Goose send and
Goose receive. Add a user defined signal -> Goose send: Single-point signal F6 LED6. Assign
function key 6 as Toggle and LED 6 for indication.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 135 Siemens Power Academy TD
00_Exercises
Exercise 14
DIGSI 5 - Simple Goose Communication 5/7

4. Create a GOOSE application and drag&drop F4LED4 for the source signals in the D01 device and
F6 LED6 in the D02 device. For the destination column only Logical Nodes Goose Receive from both
devices are enough to establish a GOOSE connection. The destination signals will be created
automatically.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 136 Siemens Power Academy TD
00_Exercises
Exercise 14
DIGSI 5 - Simple Goose Communication 6/7
5. New signals appear in the information matrix as the result of the GOOSE assignment. They can be
used as own signals now – rename and assign them to required LEDs. Assign all GOOSE signals into
User Log U1. Device 1:

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 137 Siemens Power Academy TD
00_Exercises
Exercise 14
DIGSI 5 - Simple Goose Communication 7/7

6. Do the corresponding settings for device 2.


Save and load parameters for both devices. Test the GOOSE communication at the devices.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 138 Siemens Power Academy TD
00_Exercises
Exercise 21a
DIGSI 5 Offline – Expansion of Project with SIPROTEC 4

Expansion of Project with SIPROTEC 4


If the F4 key in SIP 5 device 1 is pressed in all devices LED 4 should change the status.
If the F6 key in SIP 5 device 2 is pressed in all devices LED 6 should change the status.
If the F1 key in SIP 4 device 3 is pressed in all devices LED 1 should switch on.
If the F2 key in SIP 4 device 3 is pressed in all devices LED 1 should switch off.

Copyright © Siemens AG 2013. All rights reserved.


The GOOSE messages should be logged in a User Log1.

F4 F6

LED 1 LED 1
LED 4 LED 4
LED 6 LED 6

F1
LED 1
LED 4
LED 6

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 139 Siemens Power Academy TD
00_Exercises
Exercise 21a
DIGSI 5 Offline – Expansion of Project with 7SA631
1) Open the project: “ SIP5_basic” with SIP5-SIP5 Goose communication and rename it in “System SIP4-
SIP5” and save it to C: Temp
2) Copy the SLD of feeder = D01, paste and rename it to =D03. Delete the VT BA11 in the feeder =D03.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 140 Siemens Power Academy TD
00_Exercises
Exercise 21b
DIGSI 5 Offline – Expansion of Project with 7SA631

Step A 1. Preparation of SIPROTEC 4

 Create a new SIP4 Project : “SIP4_SIP5” and rename the folder in “GOOSE Edition 1”
 Insert a 7SA631 Protection device (MLFB: 7SA63112BB017PR7, FW: 4.68)

Copyright © Siemens AG 2013. All rights reserved.


 Insert an electrical EN100 module.
 Change the IP address to: 192.168.1.x (x=2,3, 21,11,12, 22) Subnet mask:
255.255.255.0 and the IED name to “SIP4_D03”.
 Create in the I/O masking a new Information group : ”GOOSE” and insert 3 internal
single points for switching of LED 1 and routing to the Goose-bus and insert 2 external
single points for the Goose signals from IED 01 and IED 02 and route this signals to
LED 4 and 6.
 Create a CFC chart with a RS-flip-flop for controlling of LED 1
 Insert a IEC61850 station and add the IED 03 in the properties of IEC 61850
Substation to the Goose-communication.
 Export the IEC 61850 Substation as a SCD – file under C:Temp

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 141 Siemens Power Academy TD
00_Exercises
Exercise 21b
DIGSI 5 Offline – Expansion of Project with 7SA631

Step B 1. Preparation in DIGSI 5 :

 Select the SIP 5 Project and import the “IEC61850 station.scd” (SIP 4 project) from
C:Temp.
 In the importing windows open “Import contents” “select all” devices and “Create as new
device”.

Copyright © Siemens AG 2013. All rights reserved.


 Open the project: “ SIP5_basic” with SIP5-SIP5 Goose communication and rename it in
“System SIP4-SIP5” and save it to C: Temp
 D01 and D02: Set in the properties of Channel F : DCP, SNMP, SNTP and Homepage
and RSTP and select the Edition 1 of IEC 61850-8-1. Switch the “Homepage Mode” On.
 Select the SIP 5 Project and import the “IEC61850 station.scd” (SIP 4 project) from
C:Temp.
 In the importing windows open “Import contents” “select all” devices and “Create as new
device”.

 Route the IED 03 Goose Information in the Folder “IEC 61850 Communication” to the
Source of “Goose Application” of “Goose connections”
 Save the project and export it as a SCD – file to C: Temp.

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 142 Siemens Power Academy TD
00_Exercises
Exercise 21b
DIGSI 5 Offline – Expansion of Project with 7SA631

Step C 2. Preparation of SIPROTEC 4

 Import the System SIP4-SIP5.SCD file in the IEC61850 substation from C:Temp
• Allocate the external single points of the IED 03 to suitable source information of IED

Copyright © Siemens AG 2013. All rights reserved.


01 and IED 02 in the destination catalog. Save the IEC 61850 Substation
 Save and close the “IEC 61850 Substation” and “update all parameter sets” in the
properties of “IEC Substation”.
 Download the parameter set of IED 03.
 Export the “IEC Substation” as “IEC 61850 Substation_2”.SCD – file under C:Temp

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 143 Siemens Power Academy TD
00_Exercises
Exercise 21b
DIGSI 5 Offline – Expansion of Project with 7SA631

Step D 2. Preparation in DIGSI 5 :

 Select the SIP 5 Project and import the “IEC61850 substation_2.scd” (SIP 4 project)
from C:Temp.

Copyright © Siemens AG 2013. All rights reserved.


 In the importing windows open “Import contents” “select all” devices and “Create as new
device”.
 Allocate the Goose information of IED 03 in the “Goose connection” to the destination log
to the suitable IED 01 and IED 02 signals. Use the filter form searching.
 Save the project and load the configuration of to the devices and test this Exercise.

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 144 Siemens Power Academy TD
00_Exercises
Exercise 21b
DIGSI 5 Offline – Expansion of Project with 7SA631

Step A 1. Preparation of SIPROTEC 4

 Create a new SIP4 Project : “SIP4_SIP5” and rename the folder in “GOOSE Edition 1”

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 145 Siemens Power Academy TD
00_Exercises
Exercise 21b
DIGSI 5 Offline – Expansion of Project with 7SA631
Step A 1. Preparation of SIPROTEC 4

 Insert an electrical EN100 module.


 Change the IP address to: 192.168.1.x for PC01-06 (x=2,3, 21,11,12, 22)
Subnet mask: 255.255.255.0 and the IED name to “SIP4_D03”.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 146 Siemens Power Academy TD
00_Exercises
Exercise 21b
DIGSI 5 Offline – Expansion of Project with 7SA631

Step A 1. Preparation of SIPROTEC 4

 Create in the I/O masking a new Information group : ”GOOSE” and insert 3 internal
single points for switching of LED 1 and routing to the Goose-bus and insert 2
external single points for the Goose signals from IED 01 and IED 02 and route this

Copyright © Siemens AG 2013. All rights reserved.


signals to LED 4 and 6. Noting down the path of routed Goose Information.

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 147 Siemens Power Academy TD
00_Exercises
Exercise 21b
DIGSI 5 Offline – Expansion of Project with 7SA631

Step A 1. Preparation of SIPROTEC 4


 Create a new CFC chart rename it in Goose and use a RS-flip-flop for controlling of
LED 1.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 148 Siemens Power Academy TD
00_Exercises
Exercise 21b
DIGSI 5 Offline – Expansion of Project with 7SA631
Step A 1. Preparation of SIPROTEC 4
 Insert a IEC61850 station and add the IED 03 in the properties of “IEC 61850
Substation” to the Goose-communication.
 Export the IEC 61850 Substation as a SCD – file under C:Temp

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 149 Siemens Power Academy TD
00_Exercises
Exercise 21b
DIGSI 5 Offline – Expansion of Project with 7SA631

Step B 1. Preparation in SIPROTEC 5:


 Open the project: “ SIP5_basic” with SIP5-SIP5 Goose communication and rename it in
“System SIP4-SIP5” and save it to C: Temp
 D01 and D02: Set in the properties of Channel F : DCP, SNMP, SNTP and Homepage
and RSTP and select the Edition 1 of IEC 61850-8-1. Switch the “Homepage Mode” On.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 150 Siemens Power Academy TD
00_Exercises
Exercise 21b
DIGSI 5 Offline – Expansion of Project with 7SA631

Step B 1. Preparation in SIPROTEC 5:


 Select the SIP 5 Project and import the “IEC61850 station.scd” (SIP 4 project) from C:Temp.
 Open “Import contents” in the importing windows, “select all” devices and
“Create as new device”.
System SIP4-SIP 5

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 151 Siemens Power Academy TD
00_Exercises
Exercise 21b
DIGSI 5 Offline – Expansion of Project with 7SA631
Step B 1. Preparation in SIPROTEC 5:
 Route the IED 03 Goose Information in the Folder “IEC 61850 Communication” to the
Source of “Goose Application” of “Goose connections”

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 152 Siemens Power Academy TD
00_Exercises
Exercise 21b
DIGSI 5 Offline – Expansion of Project with 7SA631
Step B 1. Preparation in SIPROTEC 5:
 Allocate the destination Information's of external single points of IED 01 and IED 02 to
the right Source Information of IED 03 (use the filter).

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 153 Siemens Power Academy TD
00_Exercises
Exercise 21b
DIGSI 5 Offline – Expansion of Project with 7SA631
Step B 1. Preparation in SIPROTEC 5:
 Save the project and export it as a SCD – file to C: Temp.

Copyright © Siemens AG 2013. All rights reserved.


System SIP4-SIP 5

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 154 Siemens Power Academy TD
00_Exercises
Exercise 21b
DIGSI 5 Offline – Expansion of Project with 7SA631
Step C 2. Preparation of SIPROTEC 4

 Import the System SIP4-SIP5.SCD file in the IEC61850 substation from C:Temp

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 155 Siemens Power Academy TD
00_Exercises
Exercise 21b
DIGSI 5 Offline – Expansion of Project with 7SA631
Step C 2. Preparation of SIPROTEC 4
 Allocate the external single points of the IED 03 to suitable source information of IED
01 and IED 02 in the destination catalog. Save the IEC 61850 Substation

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 156 Siemens Power Academy TD
00_Exercises
Exercise 21b
DIGSI 5 Offline – Expansion of Project with 7SA631
Step C 2. Preparation of SIPROTEC 4
Save and close the “IEC 61850 Substation” and “update all parameter sets” in the
properties of “IEC Substation”. Download the parameter set of IED 03.
Export the “IEC Substation” as “IEC 61850 Substation_2”.scd – file under C:Temp

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 157 Siemens Power Academy TD
00_Exercises
Exercise 21b
DIGSI 5 Offline – Expansion of Project with 7SA631

Step D 2. Preparation in SIPROTEC 5:

Select the SIP 5 Project and import the “IEC61850 substation_2.scd” (SIP 4 project) from C:Temp.
Open in the importing windows “Import contents” “select all” devices and “Update matching devices”.
System SIP4-SIP 5

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 158 Siemens Power Academy TD
00_Exercises
Exercise 21b
DIGSI 5 Offline – Expansion of Project with 7SA631

Step D 2. Preparation in SIPROTEC 5:


 Allocate the Goose information of IED 03 in the “Goose connection” to the destination log to
the suitable IED 01 and IED 02 signals. Use the filter form searching.
 Save the project and load the configuration of to the devices and test this Exercises.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 159 Siemens Power Academy TD
00_Exercises
Exercise 26
DIGSI 5 and SICAM PAS

1. Open the project: „System SIP4-SIP5” and export it as: “System_SIP4-SIP5_2.scd”


to C: Temp and copy it to the USB-Stick.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 172 Siemens Power Academy TD
00_Exercises
Exercise 26
DIGSI 5 and SICAM PAS

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 173 Siemens Power Academy TD
00_Exercises
Exercise 26
DIGSI 5 and SICAM PAS

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 174 Siemens Power Academy TD
00_Exercises
Exercise 26
DIGSI 5 and SICAM PAS

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 175 Siemens Power Academy TD
00_Exercises
Exercise 26
DIGSI 5 and SICAM PAS

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 176 Siemens Power Academy TD
00_Exercises
Exercise 26
DIGSI 5 and SICAM PAS

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 177 Siemens Power Academy TD
00_Exercises
Exercise 26
DIGSI 5 and SICAM PAS

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 178 Siemens Power Academy TD
00_Exercises
Exercise 27
DIGSI 5 Online Test Suite

Open the project: „SIP5_Basic_E6_V2_01” from C: Temp / master files / SIP5_2_01

a) Remote Control of Switching devices


Control the QB1 of the =D01 Line 1 feeder form remote via DIGSI 5 and check the right

Copyright © Siemens AG 2013. All rights reserved.


switching sequence in the Spontaneous indication responses list.

b) Commissioning Mode
Make the Online test of all Binary Inputs and Outputs as well as of all LEDs independent
of the wiring to the Switchgear with DIGSI 5.

c) Simulation Mode
Test Protection Setting of Overcurrent with DIGSI 5 without Omicron test unit.

SIPROTEC 5/ DIGSI 5 Basic Course


Version: D28_Page 179 Siemens Power Academy TD
00_Exercises
Exercise 27
DIGSI 5 Online Test Suite

a) Remote Control of Switching devices


1) Select the =D01 Line 1 device and 2) Go to the Assigned Online folder of Line 1,
“Connect to device”: start the test suite
and open the “Control function” folder

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 180 Siemens Power Academy TD
00_Exercises
Exercise 27
DIGSI 5 Online Test Suite

a) Remote Control of Switching devices


3) Click on Operate Switching device directly.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 181 Siemens Power Academy TD
00_Exercises
Exercise 27
DIGSI 5 Online Test Suite

a) Remote Control of Switching devices


4) Select close for the “New value” of QB1 , press “Select” and then
“Operate” and change the position of Binary Input BI 6 and 7
for the feedback in time. Check the right switching sequence in
the Spontaneous indication responses list.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 182 Siemens Power Academy TD
00_Exercises
Exercise 27
DIGSI 5 Online Test Suite

b) Commissioning Mode
1) Go to the Assigned Online folder of Line 1, start the “test suite” and open the “Wiring”
folder and “Activate Commissioning Mode”

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 183 Siemens Power Academy TD
00_Exercises
Exercise 27
DIGSI 5 Online Test Suite

b) Commissioning Mode
Go online und start commissioning mode at wiring

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 184 Siemens Power Academy TD
00_Exercises
Exercise 27
DIGSI 5 Online Test Suite

b) Commissioning Mode
2) Test the Binary Inputs and monitor the position of switching devices of Siprotec 5

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 185 Siemens Power Academy TD
00_Exercises
Exercise 27
DIGSI 5 Online Test Suite

b) Commissioning Mode
3) Test the Binary Outupts and monitor the commands of switching devices of Siprotec 5

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 186 Siemens Power Academy TD
00_Exercises
Exercise 27
DIGSI 5 Online Test Suite

b) Commissioning Mode
4) Test the LEDs and monitor the LEDs of Siprotec 5

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 187 Siemens Power Academy TD
00_Exercises
Exercise 27
DIGSI 5 Online Test Suite

c) Simulation Mode
1) Prepare test sequence offline first, step 1 nominal values, set time for step

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 188 Siemens Power Academy TD
00_Exercises
Exercise 27
DIGSI 5 Online Test Suite

c) Simulation Mode
2) Add test steps (step1 may have nominal values)

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 189 Siemens Power Academy TD
00_Exercises
Exercise 27
DIGSI 5 Online Test Suite

c) Simulation Mode
3) Edit next step with
fault situation (e.g.
current 2A, voltage
10V, BI 3 and active for
Commissioning mode)

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 190 Siemens Power Academy TD
00_Exercises
Exercise 27
DIGSI 5 Online Test Suite

c) Simulation Mode
4) Open the folder “analog inputs” and change to simulation mode.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 191 Siemens Power Academy TD
00_Exercises
Exercise 27
DIGSI 5 Online Test Suite

c) Simulation Mode
5) Select simulation sequence 1 and start the simulation mode and monitor the measurements.

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 192 Siemens Power Academy TD
00_Exercises
Exercise 27
DIGSI 5 Online Test Suite

c) Simulation Mode
6) Watch reaction in several protection function (start test sequence always new)

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 193 Siemens Power Academy TD
00_Exercises
Exercise 28
DIGSI 5 Online Expert Mode

Copyright © Siemens AG 2013. All rights reserved.


SIPROTEC 5/ DIGSI 5 Basic Course
Version: D28_Page 194 Siemens Power Academy TD
00_Exercises