Procedure Overview
In this procedure, you will select a DMM to use for a given application.
Be sure to observe the IEC 1010 category and the voltage rating when making
your selection.
1. Perform the following substeps to select a meter to use for the following
application.
Application: Testing the feeder circuit voltage to a 480 VAC, three-phase
motor.
AVAILABLE DMMs
DMM No. IEC 1010 Category Voltage Rating
1 CAT II 600 VAC
2 CAT III 1000 VAC
3 CAT I 600 VAC
__________________________________________________ (Yes/No)
You should find that the selected DMM has sufficient voltage rating.
Therefore, DMM 2 should be used for this application.
NOTE
Depending on the size of motor, a CAT IV meter may need to be used.
AVAILABLE DMMs
DMM No. IEC 1010 Category Voltage Rating
1 CAT II 1000 VAC
2 CAT II 600 VAC
3 CAT I 600 VAC
4 CAT IV 1000 VAC
AVAILABLE DMMs
DMM No. IEC 1010 Category Voltage Rating
1 CAT II 750 VAC
2 CAT IV 1000 VAC
3 CAT I 600 VAC
VAC
V COM