SKILL 5 TEST A TIMER RELAY

Procedure Overview
In this procedure, you will test and operation of a timer relay with out-of-
circuit testing procedures. To do this, you will insert faults into the relay coil
and contacts using the FaultPro Computer-Based Fault Insertion Software.

 1. Lockout/tagout the main power circuit breaker.


 2. Make sure that a USB cable is connected between the 990-MC1F and the PC.
 3. Start up the FaultPro software and login using your ID number and password.
 The Student Options window will open.
 4. Open the Class folder, if required.
 5. Open the LAP 2: Systems Troubleshooting option.
 6. Select any skill from the list.
 7. Click the Single Fault Mode button.
 The Single Fault Mode window will open.

L11152-AB01UEN-E1-S05, REV. A INTRODUCTION TO TROUBLESHOOTING S05-1


Copyright © 2015 Amatrol, Inc.
SKILL 5 TEST A TIMER RELAY

 8. Perform the following out-of-circuit test on the timer relay.


 Measure the resistance of both the N.O. and N.C. contacts of the Timer Relay,
as shown in figure 5-1, and record your measurements.
 Resistance:
Timed N.O. Contacts (15 to 18) ____________________________ (Ohms)
Instantaneous N.O. Contacts (25 to 28) ______________________ (Ohms)
Timed N.C. Contacts (15 to 16) ____________________________ (Ohms)
Instantaneous N.C. Contacts (25 to 26) ______________________ (Ohms)
Contact Status _______________________________________ (Good/Bad)

TIMED N.O. CONTACT


TIMED
N.C.
CONTACT

AMPROBE 30XR-A

NON
MIN MAX CONTACT HOLD
VOLTAGE

V 600 OFF 600 V


200 200
20 20
2 2
200m 200m
200

20M 2m

2M 20m
200k 200m
20k 10 A
2k 10 A
200 200m
A
1.5V 9V
2m 20m
BATT 200
BATT 1.5V CAT 600V
mA A CAT 300V
BATT 9V
COM V
200mA
MAX
10A FUSED

MAX
10A MAX 600V
FUSED 600V

Figure 5-1. Out-of-Circuit Test of Timed N.O. Contacts


 The resistance of the N.O. contacts should be infinite. The resistance of the
N.C. contacts should be at or near zero. This timer relay’s contacts are good.

L11152-AB01UEN-E1-S05, REV. A INTRODUCTION TO TROUBLESHOOTING S05-2


Copyright © 2015 Amatrol, Inc.
SKILL 5 TEST A TIMER RELAY

NOTE
Just like control relays, some timer relays use a coil to control the contacts.
The coil on this type of timer can be tested for continuity. However, the 990-
MC1F Timer Relay uses a transistor device to control its contacts. It is not
practical to test the transistor device out of circuit.

 9. Perform the following substeps to insert a fault into the timer relay in the
single fault mode and test it.
A. Type 11 in the Enter Fault Field and press Enter to activate Fault 11.
Fault 11 is an open in the timed N.C. contacts of the timer relay.
B. Again measure the resistance of the timed N.C. contacts terminals 15 to
16.
Resistance:

Timed N.C. contacts (15 to 16) __________________________ (Ohms)

Contact Status ____________________________________ (Good/Bad)


You should measure infinite resistance. This means the contact is not
operating correctly because the contacts are open before the timer has
been activated.

NOTE
Many timer relays have a manual override (just like standard relays) that
allow you to test the contacts without applying power to the coil. However, the
multifunction timer used on the 990-MC1F has no manual override. Therefore,
you must apply power to the coil to check whether the contacts properly
function.

L11152-AB01UEN-E1-S05, REV. A INTRODUCTION TO TROUBLESHOOTING S05-3


Copyright © 2015 Amatrol, Inc.
SKILL 5 TEST A TIMER RELAY

C. Connect the timer coil to DC power (A1 to +24, A2 to -), as shown in


figure 5-2.
This will apply power to the coil when the circuit breaker is turned on.

Figure 5-2. Timer Relay Coil Connect to Power

D. Set the time delay for 1 second and set the mode for on-delay (A).
E. Remove the lockout/tagout from the circuit breaker.
F. Turn on the circuit breaker.
This will apply power to the timer coil. After the 1 second delay, the
contact should change states.
G. Again measure the resistance of the timed N.C. contact terminals 15 to 16.
Resistance:
Timed N.C. Contacts (15 to 16) __________________________ (Ohms)
Contact Status ____________________________________ (Good/Bad)
This time you should again measure infinite resistance. This indicates that the
contact is open and is bad. It did not switch states after the timer timed out.
H. Turn off the circuit breaker.
I. Disconnect the timer coil from DC power.
 10. Click the Clear Fault button to clear the fault.
 11. Click the Exit button to leave the Single Fault Mode.
 12. Exit the FaultPro software.
 13. If this is your last activity of the day, return the lockout/tagout equipment to
your instructor. If not, continue.