Professional Documents
Culture Documents
January 2006
Special Instruction
i02484974 This Special Instruction provides the following
information for G3500B Engines:
Installation and Initial Start-Up
Procedure for G3516B and • Requirements for the electrical system
G3520B Engines • Proper welding practices
SMCS Code: 1000 • Grounding procedures
Generator Set • Required service tools
G3516B (S/N: ZBB1-Up; CME1-Up;
ZBC1-Up; CSC1-Up) • Electrical components and electronic components
G3520B (S/N: CWD1-Up; GZP1-Up)
• Wiring connections and the corresponding
Power Module functions that are available to the customer
PMG3516 (S/N: CFD1-Up)
Engine • Initial start-up procedures
G3516B (S/N: CEY1-Up; 7EZ1-Up)
G3520B (S/N: BGW1-Up) • Governor adjustment procedures
Reference: Information from the following sources
Table of Contents will be needed for this Special Instruction:
1
Requirements for the Electrical • Rubber couplings may connect the steel piping of
the cooling system and the radiator. This causes
System the piping and the radiator to be electrically
isolated. Ensure that the piping and the radiator are
All of the wiring must conform to all of the codes that
continuously grounded to the cylinder block. Use
are applicable to the site. When you route the wiring,
ground straps that bypass the rubber couplings.
avoid acute bends and sharp edges. To protect the
wiring harnesses, route the harnesses through metal
conduit. A liquid tight conduit is recommended. Use • Ensure that all grounds are secure and free of
corrosion.
proper support and alignment in order to avoid strain
on the conduit.
Proper Welding Procedures
The engine control system requires a clean 24
VDC power supply. The maximum allowable AC Proper welding procedures are necessary in order to
ripple voltage is 150 millivolts AC peak to peak. For avoid damage to electronic controls. Perform welding
the wiring, the maximum allowable voltage drop on the engine according to the following procedure.
is 1 VDC from the power supply to an Electronic
Control Module (ECM) or to an actuator. The power 1. Set the engine control to the “STOP” mode.
supply must be capable of supplying 20 amperes of
continuous power. 2. Turn OFF the fuel supply to the engine.
The power supply for the engine control system must 3. Disconnect the negative terminal from the battery.
be separate from the power supply for the starting
motor. 4. Disconnect the engine’s electronic components
from the wiring harnesses: ECM, throttle actuator,
actuator for the turbocharger compressor’s
Grounding Practices bypass, fuel metering valve, and sensors.
Proper grounding is necessary for optimum engine
5. Protect the wiring harnesses from welding debris
performance and reliability. Improper grounding will
and/or from welding spatter.
result in electrical current paths that are uncontrolled
and unreliable.
NOTICE
Uncontrolled electrical circuit paths can result in Do NOT use electrical components (ECM or ECM
damage to main bearings, to crankshaft bearing sensors) or electronic component grounding points
journal surfaces, and to aluminum components. for grounding the welder.
Uncontrolled electrical circuit paths can also cause
electrical activity that may degrade the engine
electronics and communications. 6. Connect the welder’s ground cable directly to
the engine component that will be welded. Place
the clamp as close as possible to the weld in
• For the starting motor, do not attach the battery order to reduce the possibility of welding current
negative terminal to the cylinder block.
damage to the engine bearings, to the electrical
components, and to other engine components.
• Use an electrical ground strap to connect all
metal cases that contain electrical components or
7. Use standard welding procedures to weld the
electronic components to the cylinder block.
materials together.
• Do not connect the negative terminal from the
electrical power supply directly to the cylinder Service Tools
block. Connect the negative terminal from the
electrical power supply to the negative terminal “−” The tools that are listed in Table 1 are required
on the engine mounted junction box. in order to enable a service technician to perform
the electrical installation procedures and the initial
• Ground the cylinder block with a ground strap that start-up.
is furnished by the customer. Connect this ground
strap to the ground plane. The Caterpillar Electronic Technician (ET) is designed
to run on a personal computer.
• Use a separate ground strap to ground the battery
negative terminal for the control system to the Cat ET can display the following information:
ground plane.
• Parameters
• Diagnostic codes
2
• Event codes
• Engine configuration
• Status of the monitoring system
Cat ET can perform the following functions:
Connecting Cat ET
The engine’s battery supplies the communication
adapter with 24 VDC. Use the following procedure to
connect Cat ET to the engine’s control system.
3
For 20 cylinder engines, if Cat ET displays
“Duplicate Type on data link. Unable to Service”,
check the harness code for the slave ECM.
Terminal Box
Note: The terminal box is designed to remain
mounted on the engine. The mounting hardware
includes isolators. Do not move the terminal box to a
remote location. Moving the terminal box could result
in wiring problems and in reduction of the service life
of the components inside the terminal box.
g01088745
Illustration 1
(1) PC
(2) 196-0055 Serial Cable or the 160-0141 Serial Cable
(3) 171-4401 Communication Adapter II
(4) 207-6845 Adapter Cable
(5) 7X-1414 Data Link Cable
4. Connect cable (4) to communication adapter (3). The ECM is inside the terminal box. This terminal
box provides the point of termination for all of the
5. Connect cable (4) to cable (5). wiring that is related to the engine’s sensors and for
the ignition system. The terminal box’s components
6. Connect cable (5) to the service tool connector on are identified in Illustrations 3 and 4.
the engine mounted terminal box.
4
g01089034
Illustration 3
The connectors on the terminal box connect the Electronic Control Module (ECM) to various engine controls, sensors, actuators, etc.
(1) Emergency stop button (7) Connectors J12/P12 for the harness (12) Connectors J5/P5 for the harness to
(2) Connectors J16/P16 for the harness to the analog sensors the Integrated temperature sensing
to the fuel metering valve (8) Connectors J11/P11 for the harness module
(3) This connector is not used. to the detonation sensors (13) This connector is not used.
(4) Connectors J14/P14 for the wiring to (9) Connectors J10/P10 for the harness (14) Connectors J9/P9 for the wiring to
the starting motor to the speed/timing sensor, to the the customer’s connections
(5) Connectors J13/P13 for the wiring to throttle actuator, and to the oxygen
the gas shutoff valve buffer (if equipped)
(6) Service tool connector J23 for the (10) 168-2028 Wiring Harness
Cat ET (11) Harness to the ignition transformers
5
Some of the wiring connections are required. Some of
the wiring connections are optional. The connections
that are required are identified in Table 2. The
connections that are optional are identified in Table 3.
g01076361
Illustration 4
Components inside the terminal box
(15) Electronic Control Module (ECM)
(16) ECM connector P2
(17) ECM connector P1
(18) Ground strap for the ECM
(19) P50 connector for calibration of the speed/timing sensor
(20) 16 amp circuit breaker for the engine
(21) 6 amp circuit breaker for the switched +Battery
Customer’s Wiring
To properly wire the engine for the requirements of
the specific application, the customer must be aware
of several inputs and outputs that are associated with
the ECM. The following list includes some examples
of the inputs and outputs:
• Emergency stop
• Electrical power supply for the control system
• Start-up and shutdown
• Engine speed and governing
• Status of engine operation
Interconnect wiring harnesses that are supplied
by the factory include the wiring for most of the
customer’s inputs and outputs. Each wiring harness
has a 47-pin connector. The 47-pin connector on the
harness mates with the J9 connector on the bottom
of the terminal box. The terminals on the 47-pin
connector and the corresponding wires are identified
in Illustration 5.
6
g01088445
Illustration 5
47-pin connector J9
Table 2
47-pin connector J9
Connections that are Required
Terminal Description Interconnect Wiring Harness Functions and Comments
B Input for Emergency Stop C256B-BK These inputs must be connected
together in order to run the
h C256C-BK engine. When these inputs are
disconnected, the emergency
stop shutdown will be activated.
An emergency shutdown initiates
the following events:
The fuel is immediately turned
off.
7
(Table 2, contd)
47-pin connector J9
Connections that are Required
Terminal Description Interconnect Wiring Harness Functions and Comments
I Input for the Desired Engine Speed M170-WH An input for the desired engine
“+” speed is required. The input can
be either 0 to 5 VDC or 4 to 20
J Return for the Desired Engine M170-BK mA.
Speed “−”
Terminals “I” and “J” are used to
provide a 0 to 5 volt DC input for
the desired engine speed.
8
(Table 2, contd)
47-pin connector J9
Connections that are Required
Terminal Description Interconnect Wiring Harness Functions and Comments
Y Input for the “AUTO” Mode P614C-RD If these inputs are not wired
correctly, the ECM will activate a
d Input for the “STOP” Mode P613C-BK diagnostic code.
Z Input for the “START” Mode P615C-RD
If these inputs are controlled by
the customer’s equipment, the
transitions between the inputs
must occur within 1/10 second.
9
(Table 2, contd)
47-pin connector J9
Connections that are Required
Terminal Description Interconnect Wiring Harness Functions and Comments
T Input for Engine Stop M010-WH This input is not
recommended for normal
shutdown.
Table 3
47-pin connector J9
Connections that are Optional
Terminal Description Interconnect Wiring Harness Functions and Comments
A Fused 24 Volt DC Output P600D-RD This connection provides a fused
24 VDC power supply for the
customer. The electrical power
is provided by the ECM.
10
(Table 3, contd)
H Output for the 5 Volt DC Desired M170-RD An input for the desired engine
Engine Speed speed is required. The input can
be either 0 to 5 volt DC or 4 to 20
mA. The method for the desired
speed input must be selected
with Cat ET.
If a potentiometer is used to
provide the 0 to 5 volt DC input
for desired engine speed, this
terminal provides +5 VDC for the
potentiometer. The +5 VDC is
created by the ECM.
K “+” Input for the 4 to 20 mA Desired M500-WH An input for the desired engine
Speed Signal “+” speed is required. The input can
be either 0 to 5 volt DC or 4 to 20
P “-” Input for the 4 to 20 mA Desired M500-BK mA. The method for the desired
Speed Signal “−” speed input must be selected
with Cat ET.
The 4 to 20 mA is an optional
method for providing the desired
engine speed input.
The 4 to 20 mA input is an
isolated input. The “+” input must
be in the same circuit as the “-”
input.
11
(Table 3, contd)
M Output for Engine Failure P698C-WH The ECM will activate this output
when the ECM causes the
engine to be shut down.
12
(Table 3, contd)
X Input from the Generator Output S990-WH This input is active only on
Power Sensor 50 Hz generators. This input
must be connected for 50 Hz
applications. The ECM will
activate a diagnostic code if this
input is not connected for 50 Hz
applications.
This connection is provided in
order to connect a wattmeter.
The signal from the wattmeter
is used to prevent the
turbochargers from surging.
13
Wiring for the Emergency Stop Circuit
The emergency stop buttons must be properly wired
in order to immediately stop the engine in case of an
emergency situation. An emergency stop button is
provided on the engine mounted terminal box.
NOTICE
Emergency shutoff controls are for EMERGENCY
use ONLY. DO NOT use emergency shutoff devices
or controls for normal stopping procedure.
g01088576
Illustration 6
Schematic diagram for the emergency stop circuit inside the terminal box
14
g01088581
Illustration 7
Schematic diagram for an emergency stop circuit with an emergency stop button that is supplied by the customer
Wiring for the Gas Shutoff Valve (GSOV) The GSOV is controlled by the customer’s
equipment. In this case, the circuit for the engine’s
The GSOV must be energize-to-run. The GSOV control system must be a complete path. The circuit
may be supplied by the customer or by Caterpillar. must include a resistor. Otherwise, an open circuit
Usually, the GSOV is installed when the piping for diagnostic code will be activated and the engine will
the fuel is installed at the site. The GSOV may be not start. Refer to Illustration 8 for an example of this
controlled by the engine’s control system or by the type of installation.
customer’s equipment. The GSOV is also called the
fuel control relay.
15
g01088630
Illustration 9
The GSOV is controlled by the engine’s control system.
16
If the generator is equipped with the EMCP II+,
information on the engine load is provided via the
Cat data link. The wiring is installed at the factory. No
additional connections are needed.
g01088638
Illustration 10
The GSOV is controlled by the engine’s control system.
The GSOV is connected via a harness that is provided by the
customer.
17
For details on these parameters, refer to Systems
Operation, Testing and Adjusting, RENR2268,
“Electronic Control System Parameters”.
g01088656
Illustration 11
Schematic of the power sensor’s input
For the actual wiring, refer to the generator’s schematic diagram. The potentiometer is optional. For further information, refer to Troubleshooting,
“Ganerator Output Power Sensor - Calibrate”.
18
Inputs for the Engine’s Mode of Operation
The engine has four modes of operation. The mode
of operation is determined by three inputs on the J9
connector. The valid configurations of the inputs are
described in Table 4.
Table 4
Valid Configurations of the Terminals for Selection of the Engine’s Mode of Operation
Terminal “Y” Terminal “Z” Terminal “d”
“OFF/RESET” Mode No(1) No No
“AUTO” Mode Yes(2) No No
“START” Mode Yes Yes No
“START” Mode No Yes No
“STOP” Mode No No Yes
(1) The “No” indicates that the terminal is not connected to terminal “C” or to terminal “D”.
(2) The “Yes” indicates that the terminal is connected to terminal “C” or to terminal “D”.
Configurations that are not shown in Table 4 will Initial Start-Up Procedure for
activate a diagnostic code. Engines that are Equipped with
The transition between inputs must occur within 1/10 Oxygen Feedback
second. If the transitions do not occur within 1/10
second, a diagnostic code will be activated. Ensure that all of these factors are in proper
working condition prior to the initial start-up: engine
“OFF/RESET” Mode installation, driven equipment, all of the related
hardware, and electrical connections. Failure to
When none of the inputs are connected, the engine perform the commissioning procedure could result in
is in the “OFF/RESET” mode. The ECM is off. Any unsatisfactory operation.
active diagnostic codes are cleared.
Perform the following procedure for the initial start-up
“AUTO” Mode and for start-up after major maintenance and/or after
repair.
When terminal “Y” is connected to terminal “C” or to
terminal “O”, the engine is in the “AUTO” mode. The 1. Verify that the connections between the engine’s
ECM is in standby. control system and the customer’s equipment are
connected properly.
The engine start sequence will be initiated when
terminal “Z” is connected to terminal “C” or to terminal 2. Connect Cat ET to the service tool connector.
“O”. When terminal “Z” is disconnected, the shutdown Refer to “Connecting the Caterpillar Electronic
sequence will be initiated. In the “AUTO” mode, Technician”.
terminal “Z” is used to control both the engine start
sequence and the shutdown sequence. 3. Set the engine control to the STOP mode. Test
each emergency stop button before the engine is
“START” Mode started in order to verify that the engine’s control
system generates an E264 event code.
The engine start sequence will begin when terminal
“Z” is connected to terminal “C” or to terminal “O”. After the operation of each emergency stop
has been verified, set the engine control to the
“STOP” Mode OFF/RESET mode.
The shutdown sequence will begin when terminal “Z” Note: Some of the generator’s protective devices
is disconnected from terminal “C” or from terminal can only be checked prior to start-up.
“O” and terminal “d” is connected to terminal “C” or to
terminal “O”. The shutdown sequence is followed by 4. Check the generator’s protective devices for
a cooldown period. proper operation.
19
Note: The engine may be difficult to start if the jacket Table 5
water coolant temperature is below 43 °C (110 °F). Configuration Parameters for G3500B Engines
Note: The spark plugs may become fouled with Timing Control
moisture from condensation if the engine is cranked “First Desired Timing”
and the jacket water coolant temperature is below
43 °C (110 °F). “Second Desired Timing”
Air/Fuel Ratio Control
6. Inspect the inlet air system. Make sure that the
system does not leak. Make sure that the system “Fuel Quality”
is free of debris.
“Gas Specific Gravity”
7. Inspect the fuel supply system. Make sure that “Desired Oxygen at Full Load”
the system does not leak. Make sure that the
“Air/Fuel Proportional Gain”
system is free of debris. Blow any debris from the
fuel lines. “Air/Fuel Integral Gain”
Speed Control
8. Connect a properly calibrated emissions analyzer
to the exhaust stack. “Low Idle Speed”
9. Perform the daily inspection and all of the daily “Minimum High Idle Speed”
maintenance procedures that are scheduled in the “Maximum High Idle Speed”
“Maintenance Interval Schedule” section of the
appropriate Operation and Maintenance Manual. “Engine Accel. Rate”
“Desired Speed Input Configuration”
10. Set the engine control to the STOP mode. Use
the “Monitoring System” screen from the “Service” “Governor Type Setting”
drop-down menu on Cat ET to view the default “Engine Speed Droop”
settings of the trip points for the alarms. Adjust
the settings, if necessary. “Governor Proportional Gain”
“Governor Integral Gain”
For the necessary values of the operating
parameters, refer to the applicable Data Sheet “Governor Derivative Gain”
on engine performance in the engine’s Technical “Auxiliary Proportional Governor Gain 1”
Marketing Information (TMI).
“Auxiliary Integral Governor Gain 1”
11. Use the “Configuration” screen from the “Auxiliary Derivative Governor Gain 1”
“Service” drop-down menu on Cat ET to view the
configuration parameters. Start/Stop Control
“Driven Equipment Delay Time”
Note: Use the data from the gas analysis and from
Caterpillar Software, LEKQ6378, “Methane Number “Crank Terminate Speed”
Program” in order to determine the correct settings “Engine Purge Cycle Time”
for the “Fuel Quality” and for the “Gas Specific
Gravity” parameters. “Engine Cooldown Duration”
“Cycle Crank Time”
a. View the parameters that are listed in Table 5.
Program the parameters, if necessary. “Engine Overcrank Time”
“Engine Speed Drop Time”
Incorrect programming of the parameters
may lead to complaints about performance Monitoring and Protection
and/or to engine damage. For descriptions of “High Inlet Air Temp Load Set Point”
the parameters, refer to Systems Operation,
Testing and Adjusting, RENR2268, “Electronic Power Monitoring
Control System Parameters”. “Generator Output Power Sensor Scale Factor”
“Generator Output Power Sensor Offset”
“Generator Output Power Sensor Offset”
“Engine Output Power Configuration”
“Engine Driven Accessory Load Configuration”
20
12. Calibrate the oxygen sensor. Refer to the e. After the electrohydraulic system is primed,
applicable Troubleshooting manual for the oxygen crank the engine and verify that the reading
sensor’s calibration procedure. on the pressure gauge is 1380 ± 70 kPa
(200 ± 10 psi) during cranking.
13. Verify that the fuel supply is OFF.
This is an adequate pressure for attempting
14. Make sure that the pressure for the start-up.
electrohydraulic actuator system is sufficient for
start-up. 15. Turn ON the fuel supply to the engine. Verify that
no gas is leaking. Verify that the gas does not flow
past the GSOV.
Illustration 12
g01088912 • Proper engine oil pressure
Right side view
• No fluid leaks
(1) Dust cap
(2) Sight gauge
• No gas leaks
a. Check the oil level in sight gauge (2). Fill the
tank to the “FULL” mark on the sight gauge. • Proper electrohydraulic oil pressure
Several attempts may be required for the initial
b. Remove dust cap (1) and install a pressure
start-up before air is purged from the fuel lines.
gauge to the pressure fitting.
Note: If the engine will not start, use Cat ET to check
c. To fill the hydraulic hoses and lines, crank the
for diagnostic codes and for event codes. Correct
engine and observe the pressure gauge. Do
any active conditions before you attempt to start the
not crank the engine for more than 30 seconds
engine again.
at a time. If necessary, crank the engine
repeatedly in order to achieve a pressure of
17. After the engine is running, test the operation of
1380 ± 70 kPa (200 ± 10 psi).
each emergency stop button.
Note: The ECM will generate event codes and
After each test, reset the emergency stop button
diagnostic codes during this procedure. After the
and set the engine control to the OFF/RESET
electrohydraulic system is filled with oil, use Cat ET
mode. Then restart the engine. After all of the
to clear the codes.
emergency stop buttons have been tested, use
Cat ET to clear the event codes from the ECM.
d. Stop cranking the engine and check the oil level
in sight gauge (2) again. Add oil, if necessary.
Note: Some of the generator’s protective devices
can only be checked during engine operation.
The correct oil level is between the “ADD” and
“FULL” marks on the sight gauge.
18. Check the generator’s protective devices for
proper operation.
21
If the engine is unstable, perform the following If the engine is unstable, adjust the auxiliary
procedure. governor.
a. Record the values for these parameters: 27. Slowly ramp up to 75 percent load.
Note: The engine will now operate in open loop Use an emissions analyzer in order to verify that
mode throughout the entire range of engine loads. the values of emissions meet the requirements
of the site.
23. Slowly ramp up to 25 percent load.
32. Increase the engine load to 105 percent load.
24. Adjust the auxiliary governor.
33. Verify that the engine is operating at 105 percent
25. Slowly ramp up to 50 percent load. Allow the load.
jacket water coolant temperature to reach 75 °C
(167 °F).
22
34. At 105 percent load, adjust the wastegate so 40. Select “Service Procedures” from the “Service”
that the throttle is wide open. Determine the drop-down menu. Select “Air Fuel Ratio Tuning”
throttle’s position by viewing the “Throttle Position” from the selection menu. Set the “Oxygen
parameter on Cat ET. The “Throttle Position” Feedback Enabled Status” to “Enabled”.
parameter should indicate “100”.
Note: The engine is now operating in closed loop
35. Reset the load to 100 percent load. The “Throttle mode.
Position” parameter should indicate between “65”
and “75”. 41. The engine’s operation should not change
in closed loop mode. If the engine operation
36. Check the emissions level. If necessary, adjust changes, change the “Oxygen Feedback Enabled
the “Fuel Quality” parameter. Use the procedure Status” to “Disabled” and perform the necessary
in Test Step 31 in order to obtain the required troubleshooting steps.
emissions.
Note: When the engine is running in closed loop
37. Once the correct emissions are obtained, review mode, the Fuel Correction Factor (FCF) may no
the “Actual Oxygen” and “Desired Oxygen” values. longer be 100 percent. The FCF may adjust in order
These parameters are in status group 9. The to compensate for the fuel quality and for the ambient
engine must still be in the open loop mode. conditions.
If the “Actual Oxygen” is higher than the “Desired 42. Change the engine load to the load that is
Oxygen”, use the following equation. This equation required at the site. Check the emissions level.
is used in order to adjust the set point of the Verify that the emissions meet the requirements
“Desired Oxygen at Full Load” parameter: of the site.
Table 6 43. Record the data from all of the status groups on
Equation for the Calculation of a New Set Point Cat ET. Save the data for future reference.
for “Desired Oxygen at Full Load”
N = ( A - D ) + C Initial Start-Up Procedure for
N is the new “Desired Oxygen at Full Load” value. Engines that are Equipped with
A is the “Actual Oxygen” value. Charge Density
D is the “Desired Oxygen” value. Ensure that all of these factors are in proper condition
C is the current “Desired Oxygen at Full Load” value. prior to the initial start-up: engine installation, driven
equipment, all of the related hardware, and electrical
connections. Failure to perform the commissioning
If the “Actual Oxygen” is lower than the “Desired procedure could result in unsatisfactory operation.
Oxygen”, use the following equation in order to
adjust the set point of the Desired Oxygen at Full Perform the following procedure for the initial start-up
Load parameter: and for start-up after major maintenance and/or
repair.
Table 7
Equation for the Calculation of a New Set Point 1. Verify that the connections between the engine’s
for “Desired Oxygen at Full Load” control system and the customer’s equipment are
connected properly.
N = C - ( D - A )
N is the new “Desired Oxygen at Full Load” value. 2. Connect Cat ET to the service tool connector.
Refer to “Connecting Cat ET with the 171-4401
C is the current “Desired Oxygen at Full Load” value.
Communication Adapter II”.
D is the “Desired Oxygen” value.
3. If the information on the generator’s output power
A is the “Actual Oxygen”value.
is provided by a power sensor, check the power
sensor’s offset voltage. Refer to Troubleshooting,
38. Enter the new “Desired Oxygen at Full Load” “Generator Output Power Readings Do Not
value with the Cat ET. Match”. Continue with this procedure after you
have minimized the power sensor’s offset voltage.
39. Review status group 9. Ensure that the “Desired
Oxygen” and the “Actual Oxygen” parameters are 4. Set the engine control to the STOP mode. Test
the same value. each emergency stop button before the engine is
started in order to verify that the engine’s control
system generates a E264 event code.
23
After the operation of each emergency stop 9. Connect a properly calibrated emissions analyzer
has been verified, set the engine control to the to the exhaust stack.
OFF/RESET mode.
10. Perform the daily inspection and all of the daily
Note: Some of the generator’s protective devices maintenance procedures that are scheduled in the
can only be checked prior to start-up. Operation and Maintenance Manual, SEBU7681,
“Maintenance Interval Schedule”.
5. Check the generator’s protective devices for
proper operation. 11. Set the engine control to the STOP mode. Use
the “Monitoring System” screen from the “Service”
6. Turn on the jacket water heater. Verify that the drop-down menu on Cat ET to view the default
heat is set to 45 to 65 °C (113 to 150 °F). settings of the trip points for the alarms. Adjust
the settings, if necessary.
Note: The engine may be difficult to start if the jacket
water coolant temperature is below 43 °C (110 °F). For the necessary values of the operating
parameters, refer to the applicable Data Sheet
Note: The spark plugs may become fouled with on engine performance in the engine’s Technical
moisture from condensation if the engine is cranked Marketing Information (TMI).
and the jacket water coolant temperature is below
43 °C (110 °F). 12. Use the “Configuration” screen from the
“Service” drop-down menu on Cat ET to view the
7. Inspect the inlet air system. Make sure that the configuration parameters.
system does not leak. Make sure that the system
is free of debris. Note: Use the data from the gas analysis and from
Caterpillar Software, LEKQ6378, “Methane Number
8. Inspect the fuel supply system. Make sure that Program” in order to determine the correct settings
the system does not leak. Make sure that the for the “Fuel Quality” and for the “Gas Specific
system is free of debris. Blow any debris from the Gravity” parameters.
fuel lines.
a. View the parameters that are listed in Table 8.
Program the parameters, if necessary.
24
Table 8 13. Turn ON the fuel supply to the engine. Verify that
Configuration Parameters for G3500C Engines
no gas is leaking. Verify that the gas does not flow
past the GSOV.
Timing Control
“First Desired Timing”
“Second Desired Timing”
Unburned gas in the air inlet and exhaust system
Air/Fuel Ratio Control may ignite when the engine is started. Personal
“Fuel Quality” injury and/or damage may result.
“Gas Specific Gravity” Before starting an engine that may contain un-
“Fuel Specific Heat Ratio”
burned gas, purge the unburned gas from the air
inlet and exhaust system. Refer to “Unburned Gas
“Desired Emission Gain Adjustment” - Purge”.
“Air/Fuel Proportional Gain”
“Air/Fuel Integral Gain”
14. Start the engine.
25
• “Governor Derivative Gain” 25. Verify that the NOx emissions are above the
desired full load setting.
b. Set the values for the “Governor Proportional
Gain”, “Governor Integral Gain”, and “Governor 26. Slowly ramp up to 100 percent load. Verify that
Derivative Gain” parameters to zero. the engine is stable.
c. Adjust the “Fuel Quality” parameter until the If the engine is unstable, adjust the primary
engine becomes stable and the exhaust governor.
oxygen is approximately four percent. Verify
that the exhaust port temperatures are below 27. Verify that the value of the “Generator Real kW”
the setpoint for a warning. parameter is within one percent of the generator’s
output power.
d. Adjust the primary governor. Refer to “Adjusting
the Governor”. 28. Adjust the “Desired Emission Gain Adjustment”
parameter in order to obtain the values of
18. Select the “Information” drop-down menu in order emissions that are required at the site.
to view the status parameters. Review the values
of the status groups on Cat ET. Verify that the • To lean the air/fuel mixture, decrease the gain
pumps for the cooling system are operating. Verify adjustment.
that the cooling system temperatures and the
cooling system pressures are within the correct • To richen the air/fuel mixture, increase the gain
operating ranges. adjustment.
19. Close the main circuit breaker for the generator in A small change in the “Desired Emission Gain
order to engage the generator. Adjustment” causes a large change in the actual
exhaust emissions. For example, an adjustment of
Note: When the engine load exceeds 25 percent, one percent in the parameter’s value will result in a
the air/fuel ratio control will operate in the feedback change of 20 to 40 ppm in the actual level of NOx.
mode.
When you adjust the exhaust emissions, make a
20. Slowly ramp the load up to 30 percent. small change in the value of the gain. Wait until
the system stabilizes. Check the emissions again.
Note: When the air/fuel ratio control is in the Repeat the process until the desired emissions
feedback mode, the Fuel Correction Factor (FCF) level is achieved.
may no longer be 100 percent. The ECM may adjust
the FCF in order to compensate for the fuel quality Use the emissions analyzer in order to verify that
and for the ambient conditions. the values of emissions meet the requirements
of the site.
21. Set the “Desired Emission Gain Adjustment” to a
value of “100”. 29. Record the data from all of the status groups on
Cat ET. Save the data for future reference.
22. Verify that the value of the “Generator Real kW”
parameter in Status Group 1 is within one percent
of the generator’s output power.
Adjusting the Governor
The response of the throttle actuator can be adjusted
If the reading on Cat ET is not within one
with Cat ET. Use Cat ET to change these three
percent of the generator’s output power, refer
parameters:
to Troubleshooting, “Generator Output Power
Readings Do Not Match”.
• Proportional Gain
When the value of the “Generator Real kW”
parameter is within one percent of the generator’s • Integral Gain
output power, continue with this procedure.
• Derivative Gain
23. Slowly ramp up to 50 percent load. Allow the
For details on these parameters, refer to Systems
jacket water coolant temperature to reach 75 °C
Operation/Testing and Adjusting, “Electronic Control
(167 °F). System Parameters”.
24. Slowly ramp up to 70 percent load. Verify that the
The default values should be sufficient for initial
engine is stable. start-up. However, the values may not provide
optimum performance.
If the engine is unstable, adjust the primary
governor.
26
These adjustments are provided in order to obtain
optimum responses to changes in the engine’s load
and in the engine’s speed. The adjustments also
provide stability during steady state operation.
27
g01017541
Illustration 14
The increased width of the line for the actuator voltage indicates
that the throttle actuator is more active as the derivative gain
increases.
(Y) Actuator voltage
(X) Time in seconds
• Emergency stop
• Engine overspeed
• The engine control is set to the STOP mode and
the gas shutoff valve does not close.
©2006 Caterpillar
All Rights Reserved Printed in U.S.A.