f = 0.3 + (9.8/B)^0.

5
Corner Column

At DL(Kpa) LL SL Occ Type


R 14.44 3.5 1 1.64 0
3 14.44 4 2.4 0 1
2 14.44 4 2.4 0 1
1 14.44 4 2.4 0 1

Edge Column

At DL(Kpa) LL SL Occ Type


R 28.88 3.5 1 1.64 0
3 28.88 4 2.4 0 1
2 28.88 4 2.4 0 1
1 28.88 4 2.4 0 1

Middle Column

At DL(Kpa) LL SL Occ Type


R 57.76 3.5 1 1.64 0
3 57.76 4 2.4 0 1
2 57.76 4 2.4 0 1
1 57.76 4 2.4 0 1
LL cumulative (kn)
DL at floor (kn) DL cumulative(Kn) f Cum Area, At SL 0 1
50.54 50.54 1 14.44 23.6816 14.44
57.76 108.3 1 14.44 23.6816 14.44 34.656
57.76 166.06 0.882524832 28.88 23.6816 14.44 61.16956
57.76 223.82 0.775629534 43.32 23.6816 14.44 80.64065

DL at floor (kn) DL cumulative(Kn) f Cum Area, At SL 0 1


101.08 101.08 1 28.88 47.3632 28.88
115.52 216.6 1 14.44 47.3632 28.88 34.656
115.52 332.12 0.775629534 43.32 47.3632 28.88 80.64065
115.52 447.64 0.668421053 72.2 47.3632 28.88 115.824

DL at floor (kn) DL cumulative(Kn) f Cum Area, At SL 0 1


202.16 202.16 1 57.76 94.7264 57.76
231.04 433.2 1 14.44 94.7264 57.76 34.656
231.04 664.24 0.668421053 72.2 94.7264 57.76 115.824
231.04 895.28 0.574604839 129.96 94.7264 57.76 179.2215

Column self-weight calculation

WEIGHT Height
Level SECTION NUMBER
(kg/m) (m)
Roof W 150X30 4 30 3.6
3rd W 150X30 4 30 3.6
Corner Column
2nd W 150X37 4 37 3.6
Corner Column

1st W 150X37 4 37 4
Roof W 150X30 20 30 3.6
3rd W 150X30 20 30 3.6
Edge Column
2nd W 200X52 20 52 3.6
1st
W 200X52 20 52 4
Roof W 200X52 25 52 3.6
3 rd W 200X52 25 52 3.6
Middle Column
2nd W 250X73 25 73 3.6
1st W 250X73 25 73 4
TOTAL

Beam self-weight calculation

Total
WEIGHT Weight
SECTION NUMBER weight
(kg/m) (kg)
(kg)
W 310 X 21 12 21 159.6 1915.2
W 310 X 28 138 28 213 29394
ROOF
W 360 X 45 12 45 342 4104
W 460 X 68 30 68 517 15510
W 310 X 24 12 24 182.4 2188.8
W 310 X 39 138 39 296.4 40903.2
3rd
W 410 X 67 12 67 509.2 6110.4
W 530 X 92 30 92 699.2 20976
W 310 X 24 12 24 182.4 2188.8
W 310 X 39 138 39 296.4 40903.2
2nd
W 410 X 67 12 67 509.2 6110.4
W 530 X 92 30 92 699.2 20976
W 310 X 24 12 24 182.4 2188.8
W 310 X 39 138 39 296.4 40903.2
1st
W 410 X 67 12 67 509.2 6110.4
W 530 X 92 30 92 699.2 20976
Total
Cf= 1.25D + 1.5 LL
Total LL cumulative Total Cf Section Cr
38.1216 123.462 W 150X30 540
72.7776 253.422 W 150X30 540
99.2911611650299 373.203951456287 W 150X37 600
118.762251364376 484.18281420547 W 150X37 600

Total LL cumulative Total Cf Section Cr


76.2432 246.924 W 150X30 540
110.8992 463.524 W 150X30 540
156.883851364376 694.28481420547 W 200X52 1210
192.0672 911.544 W 200X52 1210

Total LL cumulative Total Cf Section Cr


152.4864 493.848 W 200X52 1300
187.1424 883.728 W 200X52 1300
268.3104 1331.748 W 250X73 2150
331.707947810152 1757.55493476269 W 250X73 2150

Weight (kg) Total weight (kg) Weight (KN)

108 432
108 432
2
133.2 532.8
2

148 592
108 2160
108 2160
12.224
187.2 3744
208 4160
187.2 4680
187.2 4680
23.23
262.8 6570
292 7300
37.45 KN

Weight (KN)

51

70

70

70

261 KN
Roof Floors
Dead Load (kPa) 3.50 4.00
Live Load (kPa) 1.00 2.40
Snow Load (kPa) 1.64 0.00
Exterior wall DL 1.00 1.00

Length (m) 46.00


Width (m) 46.00
Cladding (m) 0.00
Area(m2) 2116.00
Perimeter (m) 184.00
Total Height (m) 14.80

First Floor Height (m) 4.00

Typical Floor Height (m) 3.60


No. stories 4.00
span (m) 7.60

Seiemic Load Combination: DL+E+0.5LL+0.25S


St Area (m2) DL (kPa)
Roof 2116.00 3.50
3rd 2116.00 4.00
2nd 2116.00 4.00
1st 2116.00 4.00

Vancauver Design spectra


Sa (0.2) Sa (0.5) Sa (1.0)
0.848 0.751 0.425

Equivalent Static Force Procedure

Calculating S(Ta)
S(Ta) = F(0.5)Sa(0.5) for T = 0.5s FROM TABLE
S(Ta) = F(1.0)Sa(1.0) for T = 1.0s F(0.5)
1
S(Ta) = F(0.5)Sa(0.5)
S(Ta) = F(1.0)Sa(1.0)

Interpolation

S(Ta) = 0.751 - {(0.751-0.425)/(1.0-0.5)}* (0.56

Importance Factor(Office
Rd Ro
building)
1 4 1.5

V= S(Ta)*Mv * IE * W / Rd* Ro
4306.37061333333

Vmin = S(2.0) * Mv * IE * W/ Rd* Ro


1554.40624666667
Base shear , V (KN)
Vmax = 2 * S(0.2) * IE * W/ 3*Rd* Ro
3419.29
or
Vmax = S(0.5) * IE * W/ 3*Rd* Ro
4542.25327333333

Noth - South Dircetion EBF design


STOREY hi (m) Wi
roof 14.8 8653.13
3rd 11.2 9181.77
2nd 7.6 9227.37
1st 4 9227.37

Link Design

P V H
408.047467787443 408.047467787443 3.6
327.657547045975 735.705014833418 3.6
223.443266143623 959.148280977041 3.6
117.601719022959 1076.75 4
Outside beam

v'p v=1.3RyV'p L
381.15 545.0445 7.6
449.44361 642.7043623 7.6
585.29394 836.9703342 7.6

Brace

Cf(BEAM) Degree cos (Degree)


1150.6495 28.6 -0.947437818956758
1356.82032041111 28.6 -0.947437818956758
1590.24363498 31.2 0.976778300832261

Column(with brace)
Ag(LINK) Ce Cgravity
2525 695.069375 154
3696 1017.4164 415
5474 1332.987425 735

Column(with link)
Ce=1.3RyV'p Cg total
381.15 154 535.15
449.44361 415 864.44361
585.29394 735 1320.29394

OR
v=1.3RyV'p e(m) Mpr (V * 0.5)
381.15 0.5 190.575
449.44361 0.5 224.721805
585.29394 0.5 292.64697
Building Information, Location Vancouver, Site class -C, This accidental torsional effect & the notional load are neglected.

Snow load Calcutation


S = Is [ Ss (Cb Cw Cs Ca ) + Sr ]
Is = 1.0
Ss = 1.8
Cb = 0.8
Cw = 1.0

Cs = 1.0

Ca =1.0
Sr = 0.2
S=1.64

SL(kPa) 25% Total DL/Floor (KN) Total SL/Floor (KN) Cladding (KN)
0.41 7406 867.56 319.2
0 8464 0 638.4
0 8464 0 684
0 8464 0 684

Sa (2.0) Sa (5.0) Sa (10.0) PGA


0.257 0.08 0.029 0.369

Procedure

F(1.0) Sa (0.5) Sa (1.0)


1 0.751 0.425
Ta
0.751 0.5
0.425 1

(Ta) = 0.751 - {(0.751-0.425)/(1.0-0.5)}* (0.56-0.5) = 0.712

W (kN) Mv Ta= 0.025hn 2Ta

36289.64 1 0.37 0.74

4307

wihi V v*wixi sum WiHi


128066.324 4307 551581657.468 337939.64
102835.824 4307 442913893.968 337939.64
70128.012 4307 302041347.684 337939.64
36909.48 4307 158969130.36 337939.64
337939.64

L vf= H*P/L 0.55Fy*0.9 Aw=Vf*1000/0.55*.09*Fy


7.6 193.285642636157 173.25 1115.64584494174
7.6 348.491849131619 173.25 2011.49696468467
7.6 454.333396252283 173.25 2622.41498558316
7.6 566.71052631579 173.25 3271.05642895117
hs Cf = V * L/hs Section Cr
3.6 1150.6495 W530x123 1230
3.6 1356.82032041111 W530x138 1380
4 1590.24363498 W530x150 1590

Ce(brace) CD+0.5L+0.25S Cf(brace) KL


1214.48550709851 110 1324.48550709851 7518
1432.09432140373 151 1583.09432140373 7518
1628.0497157083 194 1822.0497157083 7717

total Section Zx(mm3) x 10^3 Cr


849.069375 W200X100 1150 2693
1432.4164 W200X100 1150 2693
2067.987425 W200X100 1150 2390

Section Cr Ag ry
W 310 X 74 1640 9480 49.9
W 310 X 74 1640 9480 49.9
W 310 X 74 1640 9480 49.9

Zx (10^3)mm Mf Fy Mf
693 0.4ZFy 385 106.722
1090 0.4ZFy 385 167.86
1590 0.2ZFy 385 244.86
l load are neglected.

Beam (KN) Column (KN) Total weight/Floor (kn)


51 9.37 8653.13
70 9.37 9181.77
70 9.37 9227.37
70 9.37 9227.37
Total 36289.64
S(Ta)=0.56s S(2.0) S(0.2)

0.712 0.257 0.848

F(KN) F/4
1632.18987114977 408.047467787443
1310.6301881839 327.657547045975
893.773064574491 223.443266143623
470.406876091837 117.601719022959

Section w t d h=d-2t Aw= wh


W 250 x 58 8 13.5 252 225 1800
W 250x80 9.4 15.6 257 225.8 2122.52
W 310X97 9.9 15.4 310 279.2 2764.08
W 310X129 13.1 20.6 308 266.8 3495.08
SIZE Cr Area B t 4t
HSS 203X203X13 1530 4240 203 13 52
HSS 203X203X13 1530 4240 203 13 52
HSS 203X203X16 1790 5390 203 16 64

KL KL/ry Zx(10^3) mm
4000 80.1603206412826 1180
4000 80.1603206412826 1180
4000 80.1603206412826 1180

Total Moment Section Mrx(kn-m)


297.297 W250x131 574
392.581805 W250x132 574
537.50697 W250x133 574
v'p=0.55*Aw*385/1000 Zx 3.6Zx/Aw Mp=Zfy 1.6Mp/Vp
381.15 693000 1386 242550000 1018.1818182
449.44361 1090000 1848.7458304 381500000 1358.1236587
585.29394 1590000 2070.8517843 556500000 1521.2868939
740.08319 2160000 2224.8417776 756000000 1634.4108559
Bo= (t-4t) Bo/t < 28.2
151 11.615384615
151 11.615384615
139 8.6875
Noth - South Dircetion Link Moment frame design

STOREY hi Wi wihi
roof 14.8 8653.13 128066.324
3rd 11.2 9227.37 103346.544
2nd 7.6 9227.37 70128.012
1st 4 9227.37 36909.48
338450.36

Link Beam Design ( considering 3 link per floor according to EBF link pass each condition separately)

F P H L
407.431726079417 3.6 7.1

407.431726079417
735.089273125392 3.6 7.1

327.657547045975
958.195364432253 3.6 7.1

223.106091306861
1075.61962301481 4 7.1

117.424258582558

Column Design(with 3 link vp)


Ce=1.3RyV'p For 3 link, Ce*3 Cg Cf= Ce + Cg
448.4097618 1345.2292854 72.0594 1417.2886854
501.5060622 1504.5181866 157.0274 1661.5455866
640.585374 1921.756122 241.9954 2163.751522
714.499071 2143.497213 326.9634 2470.460613

Outside Beam Design like EBF (considering 1 link V'p per floor)
FLOOR v'p v=1.3RyV'p L
Roof 313.57326 448.4097618 7.6
3rd 350.70354 501.5060622 7.6
2nd 447.9618 640.585374 7.6
1st 499.6497 714.499071 7.6

Outside Beam COLUMN Design USING Portal method


Moment Frame Design North sounth direction
100% shear is 4307 KN. Moment frame should be design in
25% of total shear.

Shear ,V
1076.75

STOREY hi Wi wihi
roof 14.8 8653.13 128066.324
3rd 11.2 9227.37 103346.544
2nd 7.6 9227.37 70128.012
1st 4 9227.37 36909.48
338450.36

Beam Design (Check the design with Prof)

Storey Earthquake Moment Gravity Moment total moment


roof 61 30 91
3rd 172.6 79 251.6
2nd 255.6 79 334.6
1st 504 79 583

Column Design (Check the design with Prof)

STOREY Beam Z r-b-s Fy


roof W 200 X 31 225.765344 350
3rd W 310 X 52 569.121312 350
2nd W 310 X 74 787.44058 350
1st W 310 X 118 1271.884892 350

Location Of Plastic Hinge


STOREY Beam Ag (mm2) Zx (10^3 mm3)
roof W 200 X 31 3970 335
3rd W 310 X 52 6650 837
2nd W 310 X 74 9480 1180
1st W 310 X 118 15000 1950
V v*wixi sum WiHi
4307 551581657.468 338450.36
4307 445113565.008 338450.36
4307 302041347.684 338450.36
4307 158969130.36 338450.36

Vf= H*P/L Vf= H*P/L 0.55*0.9*Fy


206.58510054731 70 173.25
70 173.25
70 173.25
372.721321584706 130 173.25
130 173.25
130 173.25
485.845536895227 165 173.25
165 173.25
165 173.25
605.982886205528 205 173.25
205 173.25
205 173.25

KL(mm) Cr
W 200 X 71 3600 1800
W 200 X 71 3600 1800
W 250 X 89 3600 2530
W 250 X 89 4000 2530

hs Cf = V * L/hs Section
3.6 946.642830466667 W 460 X 128
3.6 1058.7350202 W 460 X 144
3.6 1352.34690066667 W 460 X 177
4 1357.5482349 W 460 X 177
V v*wixi sum WiHi
1076.75 137895414.367 338450.36
1076.75 111278391.252 338450.36
1076.75 75510336.921 338450.36
1076.75 39742282.59 338450.36

section Mr
W 200 X 31 104
W 310 X 52 260
W 310 X 74 366
W 310 X 118 605

Mpr= 1.1 * Ry * Fy * Z r-b-s L 2(x+d/2)


95.611623184 7.6 0.478
241.022875632 7.6 0.651
333.48108563 7.6 0.72
538.643251762 7.6 0.928

d (mm) b t
210 134 10.2
317 167 13.2
310 205 16.3
314 307 18.7
F(KN) F/4
1629.72690431767 407.431726079417
1315.15169612465 328.787924031164
892.424365227444 223.106091306861
469.697034330234 117.424258582558
4307 1076.75

Aw=Vf*1000/0.55*0.9*Fy Section w
404.040404040404 W 200 X 59
404.040404040404 W 200 X 59
404.040404040404 W 200 X 59 9.1
750.36075036075 W 200 X 71
750.36075036075 W 200 X 71
750.36075036075 W 200 X 71 10.2
952.380952380952 W 200 X 86
952.380952380952 W 200 X 86
952.380952380952 W 200 X 86 13
1183.26118326118 W 200 X 100
1183.26118326118 W 200 X 100
1183.26118326118 W 200 X 100 14.5

e Zx(10^3)mm^3 Fy
0.5 803 345
0.5 803 345
0.5 1230 345
0.5 1230 345

Cr
990
1120
1400
1400
F(KN) F/2 (kn)
407.431726079417 203.715863039708
328.787924031164 164.393962015582
223.106091306861 111.553045653431
117.424258582558 58.7121292912792

Lh VhE = 2Mpr/Lh VhG


7.122 26.8496554855378 65
6.949 69.3690820641819 75
6.88 96.9421760552326 75
6.672 161.463804485012 75
354.624718089964 290

w a=0.5b s=0.65d
6.4 67 136.5
7.6 83.5 206.05
9.4 102.5 201.5
11.9 153.5 204.1
t d h=d-2t Aw= wh

14.2 210 181.6 1652.56

17.4 216 181.2 1848.24

20.6 222 181.6 2360.8

23.7 229 181.6 2633.2

Mz Mz Mr
0.4ZFy 110.814 W 200 X 71 246
0.4ZFy 110.814 W 200 X 71 246
0.4ZFy 169.74 W 250 X 89 382
0.2ZFy 84.87 W 250 X 89 382
Vh = VhE + VhG x+d/2 M= Mpr + Vh (x+d/2) Section
91.8496554855378 0.239 117.563690845044 W 310 X 67
144.369082064182 0.3255 288.015011843891 W 310 X 67
171.942176055233 0.36 395.380269009884 W 360 X 122
236.463804485012 0.464 648.362457043046 W 360 X 122
644.624718089964 Cf

c=0.2b b/2 X=a+b/2 d/2


26.8 67 134 105
33.4 83.5 167 158.5
41 102.5 205 155
61.4 153.5 307 157
v'p=0.55*Aw*345/1000 Zx 3.6Zx/Aw Fy Mp=Zfy

313.57326 653000 1422.52021106647 345 225285000

350.70354 803000 1564.08258667706 345 277035000

447.9618 981000 1495.93358183667 345 338445000

499.6497 1150000 1572.23150539268 345 396750000


Mr
297
297
705
705

x+d/2 4*c*t Ar-b-s = Ag - (4*c*t) Zx d-t


239 1093.44 2876.56 335 199.8
325.5 1763.52 4886.48 837 303.8
360 2673.2 6806.8 1180 293.7
464 4592.72 10407.28 1950 295.3
1.6Mp/Vp 3v'p

1149.51128166987 940.71978

1263.90512054712 1052.11062

1208.83521764579 1343.8854

1270.49010536782 1498.9491
2*c*t*(d-t) Zr-b-s = Zx - {2*c*t*(d-t)}
109.234656 225.765344
267.878688 569.121312
392.55942 787.44058
678.115108 1271.884892
Calculating Cg"

Floor DL(Kpa) LL(Kpa) SL(Kpa) Length (m) Width (m)


Roof 3.5 1 1.64 4.3 3.8
3rd 4 2.4 0 4.3 3.8
2nd 4 2.4 0 4.3 3.8
1st 4 2.4 0 4.3 3.8
Area (m2) 1.0DL+0.5LL+0.25SL(Kpa) Total Gravity on Column(KN) Cumulative Cg (KN)
16.34 4.41 72.0594 72.0594
16.34 5.2 84.968 157.0274
16.34 5.2 84.968 241.9954
16.34 5.2 84.968 326.9634
Roof Floors
Dead Load (kPa) 3.50 4.00
Live Load (kPa) 1.00 2.40
Snow Load (kPa) 1.64 0.00
Exterior wall DL 1.00 1.00

Length (m) 46.00

Width (m) 46.00

Cladding (m) 0.00


Area(m2) 2116.00
Perimeter (m) 184.00

Total Height (m) 14.80

First Floor Height (m) 4.00

Typical Floor Height (m) 3.60

No. stories 4.00


span (m) 7.60

Seiemic Load Combination: DL+E+0.5LL+0.25S


St Area (m2) DL (kPa)
Roof 2116.00 3.50
3rd 2116.00 4.00
2nd 2116.00 4.00
1st 2116.00 4.00

Vancauver Design spectra


Sa (0.2) Sa (0.5) Sa (1.0)
0.848 0.751 0.425

Equivalent Static Force Procedure


Calculating S(Ta)
S(Ta) = F(0.5)Sa(0.5) for T = 0.5s FROM TABLE
S(Ta) = F(1.0)Sa(1.0) for T = 1.0s F(0.5)
1

S(Ta) = F(0.5)Sa(0.5)
S(Ta) = F(1.0)Sa(1.0)

Interpolation

S(Ta) = 0.751 - {(0.751-0.425)/(1.0-0.5)}* (0.56-0.

Importance Factor(Office building) Rd Ro

1 4 1.5

V= S(Ta)*Mv * IE * W / Rd* Ro
4306.37061333333

Vmin = S(2.0) * Mv * IE
1554.40624666667
Base shear , V (KN)
Vmax = 2 * S(0.2) * IE
3419.29
or
Vmax = S(0.5) * IE * W
4542.25327333333

Noth - South Dircetion EBF design


STOREY hi (m) Wi
roof 14.8 8653.13
3rd 11.2 9181.77
2nd 7.6 9227.37
1st 4 9227.37
Link Design

P V Number of link
408.047467787443 408.047467787443 3
408.047467787443 3
408.047467787443 3
327.657547045975 735.705014833418 3
735.705014833418 3
735.705014833418 3
223.443266143623 959.148280977041 3
959.148280977041 3
959.148280977041 3
117.601719022959 1076.75 3
1076.75 3
1076.75 3

total number of link 12


Building Information, Location Vancouver, Site class -C, This accidental torsional effect & the notional load are neglected.

Snow load Calcutation

S = Is [ Ss (Cb Cw Cs Ca ) + Sr ]

Is = 1.0
Ss = 1.8

Cb = 0.8

Cw = 1.0

Cs = 1.0

Ca =1.0

Sr = 0.2
S=1.64

SL(kPa) 25% Total DL/Floor (KN) Total SL/Floor (KN) Cladding (KN)
0.41 7406 867.56 319.2
0 8464 0 638.4
0 8464 0 684
0 8464 0 684

Sa (2.0) Sa (5.0) Sa (10.0) PGA


0.257 0.08 0.029 0.369

ce Procedure
F(1.0) Sa (0.5) Sa (1.0)
1 0.751 0.425

Ta
0.751 0.5
0.425 1

(Ta) = 0.751 - {(0.751-0.425)/(1.0-0.5)}* (0.56-0.5) = 0.712

W (kN) Mv Ta= 0.025hn 2Ta

36289.64 1 0.37 0.74

4307

wihi V v*wixi sum WiHi


128066.324 4307 551581657.468 337939.64
102835.824 4307 442913893.968 337939.64
70128.012 4307 302041347.684 337939.64
36909.48 4307 158969130.36 337939.64
337939.64
Average link Shear on each link, p H L
136.015822595814 136.015822595814 1.2 1
136.015822595814 272.031645191629 1.2 1
136.015822595814 408.047467787443 1.2 1
245.235004944473 653.282472731916 1.2 1
245.235004944473 898.517477676388 1.2 1
245.235004944473 1143.75248262086 1.2 1
319.716093659014 1463.46857627987 1.2 1
319.716093659014 1783.18466993889 1.2 1
319.716093659014 2102.9007635979 1.2 1
358.916666666667 2461.81743026457 1.33 1
358.916666666667 2820.73409693124 1.33 1
358.916666666667 3179.6507635979 1.33 1

17323.4036692144
average shear on link 1443.61697243454 1.2 1
tional load are neglected.

Beam (KN) Column (KN) Total weight/Floor (kn)


51 9.37 8653.13
70 9.37 9181.77
70 9.37 9227.37
70 9.37 9227.37
Total 36289.64
S(Ta)=0.56s S(2.0) S(0.2)

0.712 0.257 0.848

F(KN) F/4
1632.18987115 408.04746778744
1310.63018818 327.65754704598
893.773064574 223.44326614362
470.406876092 117.60171902296
vf= H*P/L 0.55Fy*0.9 Aw=Vf*1000/0.55*.09*Fy Section w t d
163.218987115 173.25 942.100935728583 W 250 x 58 8 13.5 252
326.43797423 173.25 1884.20187145717
489.656961345 173.25 2826.30280718575
783.938967278 173.25 4524.90024403058 W 250x80 9.4 15.6 257
1078.22097321 173.25 6223.49768087541
1372.50297915 173.25 7922.09511772025
1756.16229154 173.25 10136.5788833238 W 310X97 9.9 15.4 310
2139.82160393 173.25 12351.0626489274
2523.48091632 173.25 14565.5464145309
3274.21718225 173.25 18898.8004747583 W 310X129 13.1 20.6 308
3751.57634892 173.25 21654.1203400782
4228.93551559 173.25 24409.440205398

1732.34036692 173.25 9999.07859694916 W 690 X 240 16.8 27.4 701


h=d-2t Aw= wh v'p=0.55*Aw*385/1000 Zx 3.6Zx/Aw Mp=Zfy 1.6Mp/Vp
225 1800 381.15 693000 1386 242550000 1018.182

225.8 2122.52 449.44361 1090000 1848.7458304 381500000 1358.124

279.2 2764.08 585.29394 1590000 2070.8517843 556500000 1521.287

266.8 3495.08 740.08319 2160000 2224.8417776 756000000 1634.411

646.2 10856.16 2298.79188 8430000 2795.4635893 2950500000 2053.6