Gas Turbine Measuring and Supervisory Equipment

Description of Auxiliary Systems Combustion Chamber Instrumentation

Refer also to: The following functions are derived from this for
control and monitoring of the gas turbine:
List of Control Settings (SREL) 3.1-2020
P+I Diagram, Gas Turbine 3.1-2600
P+I Diagram, Combustion Chamber 3.1-2602 Natural Gas and Fuel Oil Operation
List of Measuring Instruments 3.1-2620
Equipment List 3.1-2640 – If the gas turbine is running in premix mode and the
relative combustion chamber pressure drop ∆pCCrel
Settings, limits, and measuring ranges of the items of ≤PP.BK.01 (e.g., <1,0% limit value, changeover from
equipment referred to here are given in the List of premix to diffusion mode) for more than 30s, the GT
Measuring Instruments, Equipment List, and List of must be changed over to diffusion mode.
Control Settings (SREL). This description only gives – The changeover from diffusion mode to premix mode
guideline values. may only be enabled if the relative combustion
chamber pressure drop is above limit PP.BK.01. If
∆pCCrel >PP.BK.01 (e.g., >1.1% limit, enable for
Task premix mode), either premix or diffusion mode is
The functions of the measuring instruments and the permitted.
items of the Equipment List associated with the – If the relative combustion chamber pressure drop
combustion chamber system are described in this remains below the limit value PP.BK.01 for more than
document. These measuring instruments are used to 5s at speeds above turbine speed setting S.TURB.70,
The reproduction, transmission or use of this document or

rights created by patent grant or registration of a utility


its content is not permitted without express written authority.
Offenders will be liable for damages. All rights, including

detect the pressure drop across the combustion chamber, the individual alarm “RELATIVE COMBUSTION
combustion process instabilities (known as humming), CHAMBER PRESSURE DROP <MIN” and the group
and flame out. alarm “HYBRID BURNERS FAULTED” are
annunciated.
Pressure Drop across the Combustion
Chamber Monitoring of Measuring Points
model or design, are reserved.

Over time, the gas turbine can sustain wear (for If the sensors at measuring points MBA12CP101 or
example, increased gaps in the combustion chamber hot MBM11CP103 and MBM21CP103 detect that the
gas casing), a possible consequence of which is a measured value violates the respective upper or lower
decline in the amount of air reaching the burners due to limit, changeover from premix to diffusion mode is not
increased gap losses. This in turn can jeopardize stable triggered and the individual alarm “HYBRID BURNER
premix combustion. DATA ACQUISITION FAULTED” and the group alarm
The relative combustion chamber pressure drop can “TRANSMITTER FAULTED” are annunciated. If the
generally be considered an indication of combustion measuring point fault is not rectified after approximately
chamber cooling air and combustion air flows. It is 24 hours, the changeover from premix to diffusion mode
dependent on the combustion chamber geometry, but is made and an interlock activated that prevents
essentially independent of the momentary GT output. The changeover back to premix mode.
relative combustion chamber pressure drop changes as a
result of wear or damage to burner or combustion Flame Monitoring
chamber parts (changes in geometry, changes in flow
path cross-section). Long-term monitoring of the relative Fuel must never be fed to the gas turbine combustion
combustion chamber pressure drop is performed to chambers for an impermissibly long period without
assess the condition of the combustion chamber. combustion taking place. The task of flame monitoring is
to determine whether the fuel is in fact burning in each
The differential pressure across each combustion
combustion chamber, i.e., whether flames are present. If
chamber ∆pCC is measured using differential pressure
this is not the case, the fuel system trips, interrupting the
transducers MBM11CP103 and MBM21CP103; the
supply of fuel.
compressor outlet pressure (gauge) pCII is measured
using pressure transducer MBA12CP101. This pressure The combustion flames are monitored by four flame
transducer is depicted in P+ID 3.1-2600, “Gas Turbine”. detectors per combustion chamber and their associated
These signals are used to calculate the relative analog boards MBM11CR101/MBM21CR101 and
Class: Confidential

combustion chamber pressure drop (in percent): MBM11CR102/MBM21CR102. The output signals of
MBM11CR101-B02 and MBM11CR102-B02 are for
∆pCC rel. = (∆pCC/pCII) * 100 %
natural gas, those of MBM21CR101-B02 and

Siemens AG 3.1-2603-0725/1
Energy Sector 0708EN
Gas Turbine Measuring and Supervisory Equipment
Description of Auxiliary Systems Combustion Chamber Instrumentation

MBM21CR102-B02 are for fuel oil. The radiant energy increase in pressure fluctuation amplitudes and possible
emitted by the flames (UV to IR range) is detected and consequential damage to components of the gas turbine.
passed on to analog boards in the control cabinet for Humming is detected by measuring the amplitudes of
further processing. The two processing units are set such combustion chamber pressure fluctuations using the two
that the lower level of radiant energy emitted by the two dynamic pressure sensors MBM11CP102 and
ignition flames is not registered as a main flame. An MBM21CP102 and evaluating their output signals that lie
alarm is issued if one flame monitor signals “FLAME in a defined frequency range.
OUT”; turbine trip is triggered if both flame monitors of
Monitoring of humming is only activated when the gas
one combustion chamber signal “FLAME OUT”.
turbine is running in the speed range intended for
To avoid service interruptions due to active faults in continuous operation. Monitoring is blocked during
the flame monitors which trigger control functions, the two changeover between NG DM and NG PM.
flame monitors are integrated into the I&C system such
The limits P.BRUMM.03 and P.BRUMM.04 are
that trip is only triggered if both flame monitors signal that
stipulated for the effective value of combustion chamber
flame intensity has dropped below the minimum limit
pressure oscillations; the respective measures to
(“FLAME INTENSITY NOT >MIN”).
eliminate combustion chamber humming are triggered if
they are exceeded.
Burners Triggering occurs if one of the two instruments
The burners depicted in the P+ID are not described in MBM11CP102 or MBM21CP102 indicates that a limit has
been exceeded when monitoring of humming is active. A
The reproduction, transmission or use of this document or

rights created by patent grant or registration of a utility


its content is not permitted without express written authority.
Offenders will be liable for damages. All rights, including

greater detail in this Section. These items are described


in the corresponding manual Sections pertaining to fuel. corresponding fault alarm is annunciated in such cases
that cannot be reset until it has been acknowledged.
If the measure described in the foregoing is not
Monitoring of Humming sufficient to eliminate combustion chamber humming, the
Gas turbines equipped with hybrid burners may load setpoint of the gas turbine is abruptly reduced by the
sustain combustion instabilities manifested as elevated- increment E.LEIST.12 if limit P.BRUMM.04 is exceeded.
model or design, are reserved.

amplitude combustion chamber pressure fluctuations; this The pitch of the inlet guide vanes is not blocked, i.e., pilot
phenomenon is also known as humming and has a control of the IGVs remains active. Rapid changeover
typical frequency range. Humming must be promptly from premix mode to diffusion mode is not performed and
detected and effectively suppressed to prevent a further is not prevented by an interlock.