You are on page 1of 10

ZONE BASED PROTECTION FOR LOW VOLTAGE SYSTEMS;

ZONE SELECTIVE INTERLOCKING, BUS DIFFERENTIAL AND THE


SINGLE PROCESSOR CONCEPT
Copyright Material IEEE
Paper No ICPS-08-23

Marcelo Valdes, PE Paul Hamer, PE Tom Papallo


IEEE Senior Member IEEE Fellow GE Industrial and Consumer
GE Industrial and Consumer Chevron Plainville, CT
Plainville, CT Richmond, CA Tom.Papallo@GE.com
Marcelo.Valdes@GE.com PaulHamer@Chevron.com

Radoslaw Narel Bill Premerlani, PHD


GE consumer and Industrial GE Research
Plainville, CT Niskayuna, NY
Radoslaw.Narel@GE.com Bill.Premerlani@CRD.GE.com

Abstract - Time based coordination and protection is the circuits are processed every ½ cycle at a central. Commands
normal basis for coordinating low voltage power distribution to trip or open a circuit breaker are issued at the end of each
systems. Enhancements, such as zone selective interlocking such data processing cycle simultaneously to the start of the
and bus differential protection, may be used to accelerate next processing cycle. Hence, multiple algorithms can process
protective devices. However, these improvements may be the same synchronized data and optimize their overall
costly, difficult to implement, and may not function as expected performance. For further elaboration on the system
using commonly available technology. Nevertheless, the architecture the reader is encouraged to read reference 1 “The
potential benefit of fault clearing speed and selectivity are more Single-Processor Concept for Protection and Control of Circuit
valued in today’s arc-flash and reliability conscious Breakers in Low-Voltage Switchgear”[1].
environment than ever before. The writers shall discuss some Current transformers used in the referenced implementation
issues associated with these traditional improvements, pitfalls of single processor concept are not traditional ANSI relay class
to avoid and, more effective ways to implement zone-based transformers. These current transformers are referred to as
protection to achieve fast fault protection while maintaining sensors and have secondary currents below one ampere.
complete selectivity for a broad range of fault magnitudes, Their characteristics are incorporated and compensated in the
system configurations and load types. algorithms as required to achieved required accuracy.

Index terms - Selectivity, coordination, zone-selective- II. BACKGROUND


interlocking, bus differential, motor contribution, Single- A. Impact of Clearing Speed on Protection
Processor-Concept, directional overcurrent protection.
Incident arc flash energy is an accepted way of measuring
I. INTRODUCTION damaging heat energy radiated from an arc in air during an
Low voltage power distribution systems must deliver reliable arcing fault event. IEEE 1584-2004[2] provides formulas to
power within constraints of cost and size using available estimate arcing current and incident heat energy over a range
technology. Protective devices must be selected and adjusted of working distances under a variety of conditions. The guide
to operate selectively, reliably and as quickly as possible. defines arcing current as a function of available voltage and
Protection has traditionally been coordinated by ensuring that bolted fault current (Ibf), and the gap between the current
carrying conductors. The calculated arcing current is less than
for any specific value of fault or overload current the
downstream device closer to the over current is faster than the the bolted fault current. Fig. 1 demonstrates the relationship of
upstream device further away from the overcurrent. This time- arcing current to bolted fault current as a percent at three
based coordination can achieve good system selectivity. different voltages for a conductor gap of 32 mm. A 480V arcing
However, it does this at the cost of the upstream overcurrent – current varies from 43% to 56% available short circuit current
protective-device’s speed. In a large power system, important for available short circuit current values of 20kA to 100kA.
main devices can be significantly delayed to allow layers of % of Ibf
load side devices to clear selectively. To improve upon time 80% 600V
based coordination two well known methods can be used: 70% 480V
zone-selective-interlocking, and differential protection. 208V
60%
This paper will briefly review the effect of clearing speed on 50%
arc flash energy, and how zone selective interlocking and
40%
differential protection can improve device speed. There are
limitations, and risks of improper operation for these methods 30%
that will also be discussed, as well as how to mitigate those 20%
risks using the “Single-Processor-Concept”[1]. 10%
Within this paper the expression, “algorithms are run 0%
100

simultaneously” will be used. In the context of the “Single-


20

30

40

50

60

70

80

90

Processor-Concept”, this statement means that algorithms are Ibf


executed within the same ½ power cycle. In the Fig. 1. Arcing Current as Function of Prospective Fault
implementation of the “Single Processor Concept” referenced Current, 32 mm Gap, Arc in Box Formula.[2]
current, voltage, status and commands for all equipment
• 25,000 x .85 = 21,250A (85% to account for arcing current
The relationship of arcing current to available bolted fault variance from known bolted currents)[2]
current also varies depending on the gap between electrodes. Hence, in a system with a significant value of prospective
The electrodes represent the current carrying conductors. Fig. short circuit fault current we see that current through the main
2 shows that the relationship can range from 65% at 20,000A device for an arcing fault on the main bus may be less than
available and a 13mm gap to 43% with 100,000A available and 22,000. If, this is a 4000A bus, the arcing fault current could fall
a 32mm gap. within the tolerance of a 5X pick rating for the main circuit
Protective device reaction speed must be considered in breaker and below 50% the current limiting threshold of a
relation to the arcing current present during an arcing fault 4000A Class L fuse. A main circuit breaker may not consider
event. Fig. 1 and 2 demonstrate that the arcing current can be this a short-time fault and a 4000A fuse would not be operating
a variable percent of the prospective fault current based on in its current limiting range.
multiple parameters identified in the IEEE 1584 guide. The Additional arcing current variance could be introduced by
IEEE guide is based on a series of tests performed under incorrect utility information or conservative assumptions in the
specific laboratory conditions. The standard states that two short circuit current calculations that result in higher calculated
values of arcing current be used to identify protective device fault values than available. The impedance of conductor
operating speed, and resultant arcing energy; the calculated terminations and protective devices, for example, will introduce
arcing-current, and 85% of that value. In the opinion of the impedance not normally taken into account during short circuit
authors, more variance is possible because these formulas are calculations. Traditional fault current calculations to identify the
based on calibrated bolted fault currents and very specific required rating of equipment and components must be
electrode geometry. Additional unaccounted variance could be conservative by making sure any error results in higher, not
caused by system impedance not considered in short circuit lower, calculated fault currents. When calculating arc flash
calculations such as connections, distribution equipment incident energy, the more dangerous level of energy may
impedance and protective device impedance. Additional happen with, either, lower or higher arcing fault values. While
variations in the geometry of the conductors involved in the higher arcing current will cause higher incident energy per
arcing event that differ from those used in the laboratory could cycle, lower arcing fault current values may result in slower
create differences between actual and predicted arcing protective device operating times that will increase incident
currents. No generally accepted method exists to account for energy.
this variance at this time, however, conservative use of the The potential for low arcing currents could add significant risk
calculation should, probably, consider additional variance in to an arc flash event. Any device, whether fuses or circuit
arcing current and in incident energy around the values breakers, that depends on high current values to operate
predicted by the model. quickly can operate differently from expected if arcing currents
are lower than expected. For large low-voltage-power circuit
breakers even short time pick up points set to achieve
selectivity with the required short time characteristics of loads
in the system may be set above potential arcing currents.
III. TRADITIONAL ENHANCEMENTS, CONCERNS
A. Impact of Arc Flash Current on Short Time Pick Up
Fig. 3 is the relationship of calculated energy vs. time in
cycles, for a HRG 480 V system with a 32 mm electrode gap
and an 18-inch working distance. As the graph indicates a
2
clearing time that exceeds 22 cycles will result in ~ 40cal/cm .
Above this level, no level of PPE is suitable.
Fig 2. Arching Current as a Function of Prospective Fault
Current, at 480 V, HRG, for Various Electrode Gaps. [2]

Other considerations are the sources of fault current, the


direction, and path of each fault current contribution. A bus with
significant available short circuit current may have a portion of
that current come from motor contribution. These various
considerations mean the arcing fault current through the main
may be surprisingly small. Consider a 62kA, 4,000A low Fig. 3. Incident Energy as Function of Clearing Time in Cycles,
voltage switchgear bus with an estimated 10,000A of motor 480V, HRG, 32mm, 18”, 52kA Ibf, Arc in Box.[2]
contribution through feeders, and estimated 52,000A of
transformer contribution through the main circuit breaker. The In this example the main circuit breaker set with a short time
potential arcing current flowing through the main over-current pick up of 5x nominal will have a short time pick up band of
device may be estimated for 480V switchgear: 18,000 to 22,000A. Though it may not be common for a large
• 62,000 –10,000 = 52,000A (transformer contribution only) main circuit breaker to be set this high, such settings may
• 52,000 x .48 = 25,000A (.48 is from graph in fig. 2) result from similar settings in large feeders and allowances for
high inrush currents. The 21,250A three-phase arcing fault
CURRENT IN AM PERES X 1000 AT 480 VOLTS
current calculated raises the possibility the circuit breaker may 1000
900
800
.5 .6 .8 1 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 100 2 3 4 5 6 7 8 9 1000 2 3 4 5 6 7 8 9 10000
1000
900
800

clear at its long-time delay instead of the faster short-time 700


600
500
700
600
500
400 400

delay. Even if this device is part of a zone interlocking scheme, 300 300

if the current does not exceed the short time pick up, the
200 200

device will not operate within the short time band. 100
90
80
70
60
100
90
80
70
60

The longer clearing time could result in a significant level of 50


40

30
50
40

30

incident arc flash energy, well above HRC4 (hazard risk 20 20

category 4). A 4000A class-L fuse with a current limiting 10


9
8
10
9
8

threshold around 55,000A would not improve the situation. 7


6
7
6

TI ME IN SECONDS

TI ME IN SECONDS
5 5
4 4

3
Main operating 3

B. Zone Selective Interlocking and Motor Contribution: 2


as back up
2

Direction Matters 1
.9
.8
1
.9
.8
.7 .7
.6 .6
.5
Main operating .5

In zone-selective-interlocking (ZSI), several levels of circuit .4

.3 for in zone fault


.4

.3

breakers operate selectively at their minimum time delay for in- .2 .2

zone short-time faults. For a series of circuit breakers as .1


.09
.08
.07
.1
.09
.08
.07

shown in Fig. 4 communication is enabled that allows devices .06


.05
.04
.06
.05
.04

to receive blocking signals from downstream devices and also .03

.02
.03

.02

allows the device to send a signal to the next upstream circuit .01 .01

breaker. The signal is generated when the circuit breaker .5 .6 .8 1 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 100 2 3

CURRENT IN AM PERES X 1000 AT 480 VOLTS


4 5 6 7 8 9 1000 2 3 4 5 6 7 8 9 10000

senses current that exceeds its short time pick up level. If that Fig 5. ZSI Effect On Upper CB in 2 CB Scheme
circuit breaker also receives a blocking signal, it will operate at
a programmed delay. If it does not receive a blocking signal, it Let us consider a situation as shown on the one line in Fig. 6.
will operate at its minimum time delay. In the system shown an 800A frame CB is feeding an MCC
with four 100Hp motors. Each motor has full load current of
current of 146.3A amperes and a locked rotor current of 863A
(5.9 x FLA). The motors will start individually during expected
operation of the system the 800A CB is set above 125% of the
motor bank’s full load current – 732A (146.3A x 4 x 1.25). The
short time pick up of the circuit breaker is set to clear 125% of
3 motors FLA + 125% of one motor’s starting current ((146.3A
x 3 + 146.3 x 5.9) x 1.25), 1624A.

Fig 4. Three Level Zone-Selective-Interlocking System.

Zone interlocking depends on feeder circuit breakers sensing


in-zone fault current and sending blocking signal to the mains
and ties. The time-current-curve in Fig. 5 demonstrates the
effect of zone selective interlocking on short time operation of
two circuit breakers. If current flows through the feeder to a
fault in its zone then the blocking signal will cause the main CB
to operate at its set delay above the feeder’s clearing time.
This ensures fast operation of the feeder while maintaining the
main as a back up if the fault current also exceeds the main’s
short-time pick-up. If the fault occurs on the main bus, the
feeder will not see it and the main will operate at its faster time Fig 6. Bus Fault With Source and Motor Contribution
delay and clear in less than 100 milliseconds.
Fig. 7(a) is the time current curve for the feeder, the main
(operating in the zone interlocked mode) and the motor load.
The motor load is shown with a 10 second starting inrush for
one motor with the other three running at full load.
C. ZSI Applications in Multiple Source Systems With
Ties: Selectivity or Protection
In distribution systems with tie circuit breakers, ZSI schemes
may be configured two different ways; with a selective tie, or
with fast mains. Fig. 8(a) demonstrates the general (may vary
by manufacturer) configuration for a selective tie and Fig. 8(b)
for fast mains. Both of these schemes result in a compromise
between selectivity and fast protection.

Fig. 7(a). Feeder set for MCC load, 1 motor start

Fig. 7(b) demonstrates the same circuit under bus fault


conditions and the MCC’s contribution of fault current for 0.1- Fig 8(a). Zone-Selective Interlocking With Selective Tie
.05 second. The motor contribution is enough to initiate short
time timing in the feeder circuit breaker and hence the feeder In the selective tie configuration, the feeder circuit breakers
circuit breaker will issue an interlocking signal to the main on both sides of the tie interlock with the tie. The tie then
causing it to operate at a delayed time band. The main is now interlocks with both mains. A fault downstream of a feeder will
reacting more slowly for a fault in its zone of protection than properly keep the tie and mains operating at a delayed interval
intended by the system designer. The reverse current caused while the feeder should clear the fault faster. For a fault on
by the motor contribution fools the feeder circuit breaker into either bus, the tie will delay the mains while it separates the
operating as if it is feeding a fault on its load side. The Zone buses. However separating the buses does not clear the fault.
Selective Interlocking, in this case, performs opposite from Whichever bus is faulted remains faulted until the respective
expected. main clears one time delay later. In this scenario the feeders,
tie and mains are coordinated, one time delay is saved, but the
fault can remain energized for two time delays via one source.
The fast main connection interlocks the feeders with the tie
and both main circuit breakers. I this case bus fault will be
seen by all three circuit breakers as a fault within their
respective zones and all three circuit breakers will trip at a
minimum time delay. Fast protection is achieved, however
system reliability is sacrificed.
In an ideal system the main and tie feeding the faulted bus
would clear in minimum time while the other bus remained
connected to its dedicated source.

Fig. 7(b). MCC Fault Contribution to Main bus Fault – Main


nd
CB Forced to 2 Delay by ZSI Signal From Feeder

This risk can be addressed by setting the feeder’s delay


higher or adjusting the short time pick up higher. In either case,
some desirable protection is compromised. Fig 8(b). Zone-Selective-Interlocking With Fast Mains
In the case of a bus with no low voltage main, the primary D. Zone Selective Interlocking and Faults Ahead of a
medium voltage transformer protective device main may be Main Circuit Breaker
zone interlocked with the feeders. The problem of fault Most low voltage power systems will be fed from a
contribution from motors through feeders is equally valid when transformer via a low voltage main circuit breaker. A fault
the main is on the other side of a transformer, and slower than detection and isolation problem exists when a fault occurs
expected operation of the medium voltage device is also between the low voltage main and the transformer secondary
possible.
terminals. During closed tie operation, with sources in parallel faster operating mode would be preferable because it results
the fault is fed from the other source through the tie and both faster protection as long as selectivity can be provided by an
main circuit breakers (Fig. 14). Knowledge of the magnitude of interaction of the instantaneous and fast short time protection.
current flow is not enough to identify fault location even when a A delay of 20 to 25 milliseconds is sufficient to be selective
ZSI scheme is used. In the selective tie configuration shown in with the clearing time of most molded case circuit breakers
Fig. 8(a) the tie circuit breaker would clear first and properly operating instantaneously that may be fed through that main
isolate the fault from the other source, though not from all device. Minimum time delay available may vary by
motor contribution, and would drop at least one bus manufacturer.
unnecessarily. However, in the fast main configuration shown
in Fig. 8(b) both mains and tie will clear simultaneously, F. Bus differential Protection: Best Zone Protection
unnecessarily disconnecting both buses from their source. Bus differential protection is based on Kirchoff’s node law:
In an ideal situation, the main closest to the fault should “all the currents into a node (bus) must equal all the currents
separate the fault from the other source in minimum time. The exiting a node”. A bus differential algorithm is able to calculate
tie, as well, as the other main should remain closed. A medium fault current subject to the limitations of error in sensing and
voltage device should also operate as quickly as possible signal processing. Medium voltage relays used for this function
separating the fault from its primary source. To accomplish this typically employ a percentage-differential-slope, which adjusts
the fault location must be known. the threshold relative to the magnitude of currents being
E. Zone Selective Interlocking and Instantaneous measured. This method allows the algorithm to compensate for
Protection the non-linear characteristics of iron core current transformers.
However, in low voltage systems, high fault currents combined
To achieve the fastest possible protection and minimum of with small CT ratings may significantly exceed the saturation
cascaded time delays it is desirable to use a feeder circuit level of iron core current transformers making the percent
breaker with an instantaneous characteristic set low enough to slope method impractical for an extended range. At some large
sense arcing currents in the protected circuit. Any circuit current, the error can no longer be compensated.
breaker upstream may be set at a short time band to be
selective with the feeder circuit breaker. Traditionally the short
time band should be position above the clearing time of the
feeder circuit breaker operating instantaneously. With large
stored energy devices instantaneous clearing times are usually
drawn at 3 cycles (50ms). The short time band in the next
device would start above 3 cycles as shown on the left side of
Fig. 9.

Fig. 10. Two Zone Double Ended Substation

Bus differential is most applicable to detection of lower value


higher-impedance faults that may or may not exceed the short
time pick up of large main and tie circuit breakers. As fault
currents increase, a properly zone-interlocked system can
provide similar results as a differential algorithm. Hence a
combination of bus differential protection and properly set zone
selective short time protection can provide a broad range of
selective protection operating in minimum time.
Bus differential protection requires dedicated current
transformers and a dedicated relay. In low voltage applications,
Fig. 9. Traditional ZSI (Left) Above Instantaneous vs. Faster this scheme may be regarded as too costly or complex to
Implementation (right) Overlapping Feeder Instantaneous consider. Furthermore traditional relaying and CTs may not be
able to handle the required dynamic range to maintain
It would be more desirable that the short time delay of the nuisance free tripping for through-faults due to saturation.
second circuit breaker operate faster and still maintain
selectivity with the overlapping instantaneous response of the IV. IMPROVEMENTS & ENHANCEMENTS POSSIBLE
low-voltage-power circuit breaker downstream. The right side A. The “Single-Processor-Concept” and Fault Location
of Fig. 9 shows two circuit breakers with the main device
operating at a faster short-time band that overlaps the The “Single-Processor-Concept”[1] for circuit protection is a
instantaneous band of the feeder. Any zone selectively system where a single processor takes all pertinent system
interlocked circuit breakers further upstream would be information and is able to process it simultaneously for a
selectively operating at the same short-time band. This second complete line up of power distribution equipment. Since all
current and voltage information is synchronized and available cycles would require a forward fed fault from a significant
in one place at the same time, calculations may be made using source, not reverse fed motor contribution.
single simultaneous data samples or RMS values calculated
over time. Which type of data is used depends on what is C. Method for Detection of Current Direction in Faulted
optimal for the algorithm. Systems With Multiple Fault Current Sources: Relative
Direction
To address potential issues created by motor contribution or
closed tie operation with multiple sources the zone selective
interlocking system would need to identify relative fault current
direction. Traditional implementations of zone selective
operations are not able to do this. Sufficient identification of
fault current direction can be achieved in the single processors
system because faults currents can be compared to each
other. Since the intent is to simply identify relative direction, the
exact angle or magnitude is not required, and significant error
can be accommodated without loss of key directional
information.
To address the problem of which side of the tie a fault is
Fig. 11. Simultaneous, Instantaneous Values of Four located an algorithm similar to a partial differential calculation
Waveforms Available Through Simultaneous Sampling may be used. A partial differential calculation uses only the
mains and ties thereby minimizing cumulative error caused by
Fig. 11 demonstrates how four instantaneous (single data many small current transformers associated with the feeders.
samples) values for the four currents in a simple radial system Current direction may be defined as inward (+1) for current
can be used to calculate the differential current for the bus at flowing towards the bus, or outward (-1) for current flowing
every data sample. Proper polarity assignment allows a away from the bus. Fig. 12 demonstrates the left main, and the
differential calculation to be made with every data sample tie flowing towards the bus. This identifies a fault on the main
using current magnitude only. The calculations can be bus. The right bus has one current flowing in, and one current
corrected for expected signal and processing error. Tests have flowing out, hence it is not the faulted bus.
shown that using this method and iron core current
transformers sufficient resolution to detect fault currents
smaller than the rating of the bus being protected can be
achieved. Performing the calculation for a length of time such
as 1 or 1.5 cycles allows sufficient calculations to be made to
confirm, with a high degree of certainty, the magnitude and
location of the fault current.
The single processor concept allows the use of the same
circuit information for a variety of protective and control
algorithms such as bus differential without the need for single
function dedicated devices. Hence, the same hardware
providing normal over-current, ground fault and zone selective
interlocking, can provide bus differential protection Fig. 12. Fault Current Contribution for Left Side Fault
simultaneously.
In the situation where a single feeder circuit breaker goes
B. Combining Bus Differential and Zone Selective
into short time trip pick up timing in addition to the main and
Interlocking: Complete Range Fault Detection
ties the direction of that feeder’s current can also be compared
Limiting the differential calculations to a range where the to the main’s and tie’s current direction. If the current is
measured currents do not exceed 10 times the rated current of determined as inward then the fault is in the bus. If the fault
any CT in the system keeps the calculation within the linear current in the feeder is opposite the current direction in the
range of the transformers. The differential function can be main and tie then the fault is a through-fault fed by the feeder.
complimented by the short-time zone-selective-interlocking Consider the case where two feeders go into simultaneous
scheme. The combination provides fault sensing and location short time-pick up timing, both may be determined to be
information over the complete expected fault range. flowing in the same direction as the main and tie, i.e. inward.
A 4,000 ampere bus with 4,000 amp mains and tie would That indicates the fault is in the bus. If one feeder is flowing
require over 40,000 amperes of fault current through either the inward and the other outward then the fault is on the load side
main or the tie before the bus differential algorithm would be of the one feeder with current flowing opposite all other
suspended. In a situation where the fault is downstream of a excessive currents.
1,600-ampere feeder, fault current through the feeder must The situation where two feeders are both simultaneously
exceed 16,000 amperes for the bus-differential algorithm to be feeding separate faults on their load side is improbable.
disabled. In either or these situations, the current is high However, it would not result in a lack of tripping. The logic can
enough to engage the short time pick up of the circuit breakers identify that neither is flowing in the same inward direction as
required to isolate the fault optimally and, to reach 10X for 1.5 the main and tie and hence both feeders should trip.
The specific method is to consider each zone as a partial motor contribution towards the main bus. The various tests on
differential using only ties and mains. Equation (1) would be the faulted feeders will determine if one feeder is feeding a
used when any CB in the zone is identified as having current in fault in its zone of protection or multiple feeders are conducting
excess of its short time threshold. motor contribution towards a bus fault.
Once the determination is made of what each CB in the zone
Ir = ¦I M − ¦ ( I T * DT ) (1)
is conducting, all the proper circuit breakers can be opened.
Whether it’s one main, a main and a tie, or several sources into
1− p 1− q
a bus including downstream motor contribution, all devices
Where Ir is the residual for the partial differential zone, IM is contributing fault current can be identified. Proper back up
the current for the main, IT is the current for the tie and DT is circuit breakers can be identified and operated if required as
the reference direction unit vector for the tie. The reference unit best suits the fault location, magnitude and system
vector is designated such that if the tie and main current flow configuration at the time of the fault. This can be done in the
towards the bus equation (1) adds the two currents. p and q same time frame that a simple short time calculation can be
are the number of mains and ties feeding the partial differential made for a single circuit breaker.
zone respectively. Ir is compared to a minimum threshold such
as 1.5 times the largest CT in the zone (usually the main). D. Method for Detection of Fault Current Direction Ahead
When Ir exceeds this threshold the fault is in the zone or being of Main Circuit Breakers: Absolute Direction
fed by the zone. Further analysis demonstrates that if the fault were located
In the case that one or more current readings exceed 10X on the line side of a main the algorithm, based on relative
their respective CTs a test is set up to find a large reference direction of current in the source circuit breakers would yield
phasor for each phase current and then all the other currents in inconclusive results. In the case of a fault on a main’s line side
short time pick up are compared to those phasors to determine the fault location would be indeterminate, as neither bus would
relative direction. Once a reference phasor is identified for show the fault located within them. Both buses would show the
each phase, the phasor for current in each phase of every tie and main with current flowing in opposite directions
breaker in the partial differential zone that has exceeded a indicating a through fault. See Fig. 14 for an illustration of this
defined current threshold can be compared. situation. To solve for this situation knowledge of the actual
For each phase, a reference current and angle is calculated - current direction through the main circuit breaker is required.
IE and ang(IE). Whether other fault currents for that phase in the
partial differential zone are same is identified by first computing
the angular difference between a faulted breaker in the zone
and the reference faulted circuit breaker via equation (2).

Δ θ = ang ( I α ) − ang ( I β )
(2)
Where I is the phase current in the circuit being considered
and 'T is the angular difference.
. The angular difference is checked to determine if the
currents are in the same direction, defined as “in, 1”, or in the
opposite direction, defined as “out, 0”. The logic can handle
significant angular error because the expected angular
difference is 180 degrees for opposing currents. If the angular
difference is between + 60 degrees from 180, the currents are
considered to be in opposite directions.
However, since this is a partial differential algorithm
additional consideration must be given to feeders, to determine Fig 14. Fault Contribution to Fault Ahead of Main
if the fault is in the zone or fed through the zone. To that end
only the current of any feeders that are in short time pick up In a single-processor-based system, data from the present
are considered. If the current through the feeder is determined may be compared to past data. This allows a comparison of
to exceed 10X (a value that should be above potential motor pre-fault voltage to pre and post-fault current to be made after
contribution) then the fault is determined to be downstream of any current in excess of the pick up threshold is detected.
the feeder. If the current is under 10X and above the feeder’s Comparing the phase angle of fault current with the phase
short time pick-up then direction of the feeder’s fault current is angle of pre-fault current, and looking for the reversal will
determined to properly locate the fault. detect a reverse current fault. A pre-fault voltage phasor
To determine the relative direction of a faulted feeder’s maybe continuously calculated and discarded when it is
current it must also be compared to a reference phasor that updated. When current exceeding fault magnitude is
represents the “in” current for the respective faulted partial exceeded, the voltage phasor from a predetermined number of
differential zone. The phasor representing each phase current cycles back would be used as a reference. Reversal would be
for every faulted feeder fed by the faulted partial differential indicated by a 180-degree shift as well as any additional lag
zone is compared looking for a difference in direction that is the fault conditions would introduce. Post fault phase voltage
180’ + 60’. If the difference is found then the feeder is would be an unreliable source of information as voltage may
conducting current towards a downstream fault, if the angular collapse considerably during fault conditions. In a case of
difference is outside of this range then the feeder is conducting complete voltage collapse the small remaining voltage would
be the bus IR drop that is always in phase with current and • Short time – Directional zone interlocking between mains
would not yield the information required. Hence, the algorithm and ties
implemented in equation (3) will detect current reversal. • Short time - Directional zone selective interlocking at
150 ≤ ang( I ) − α ≤ 250
D D
(3) And
feeders with zones above them

• Instantaneous tripping function at feeders able to operate


Where ang(I) is the angle of the positive sequence current while other ZSI functions operate simultaneously
phasor and α is the pre-fault voltage positive sequence phasor. The instantaneous function would be continuously performed
The expected theoretical angle for a forward current would be - in any of several ways in which instantaneous tripping is
0 to 90 degrees for a purely resistive to purely inductive obtained in modern digital trips. If an instantaneous trip
current. A reversal in current would add 180 degrees and because of potential motor contribution to a bus fault or
would range from 180 to 270 degrees. More realistically the separate feeder fault is not desired then the instantaneous
forward angle may be 0 to 60 degrees for resistive to very should be set above the potential maximum motor contribution.
inductive loads. A reversal of 180 degrees would cause the All short time functions, including those for the circuit breaker
angle to shift to 180 to 240 degrees. The above algorithm operating instantaneously can continue to function regardless
should identify a fault shifting from load currents flowing at 30 initiation of the instantaneous trip function as long as the
degrees leading to 70 degrees lagging (-30º < α < 70º). The system is designed to do so.
pre-fault positive-frequency voltage phasor would require The bus differential function is performed independently of all
compensation for any mismatch between sampling rate and other functions and would continue to function as long as no
frequency. That compensation is ignored in the above formula single current exceeded 10 times the rating of any CT within
for sake of simplicity. the zone. Bus differential may be set significantly under the
The algorithm in equation (4) may be performed on each short time pick up level of any main or tie and offers the most
sensitive fault protection. Since bus differential functions only

(I ) ≥ ( P
phase current periodically to determine fault current.
for bus faults the setting is independent of all other settings in
2
RMS RC )2 (4)
the system that may be required for optimum selectivity or
sustaining loads.
Where IRMS could be computed form ½ cycle of current Reverse current protection at the main would function
samples for each phase and PRC is the reverse current independently and would issue a trip signal to the proper circuit
protection setting chosen for the main circuit breaker being breaker when the algorithm is satisfied, including a medium
considered. voltage transformer main if provided. The same algorithm
Once it is determined that a current through the main has would simultaneously block action by the other short time
exceeded the pick up threshold for reverse current pick up, a functions to prevent unnecessary nuisance tripping if other
series of calculations can be run comparing the angular sources can continue to sustain load.
relationship between pre-fault positive-sequence current and All algorithms are able to reliably calculate with as little as
post fault positive-sequence current by referencing both to pre- two half cycles of current data. The combination of the various
fault positive-sequence voltage. If the current is determined to algorithms operating simultaneously can provide identification
have reversed then the fault is ahead of that device. Since this of fault location ahead, within and downstream of a bus in a
reverse current setting need not be considered for forward line up of switchgear with multiple sources and closed ties,
current coordination analysis the pick up level may be quite low regardless of motor contribution magnitude relative to the short
and the delay only as long as required to make a reliable trip time settings of feeder circuit breakers. The minimum
decision. Zone selective interlocking can provide back up sensitivity of a the bus differential algorithm allows fault smaller
levels of protection even in this reverse direction by reversing than the a bus’ current rating to be located and the various
the hierarchy implemented for forward faults. short time algorithms allow faults up to the short circuit rating of
These comparisons plus appropriate error compensation, the equipment, if the circuit breakers allow it, to be detected
cooling and heating algorithms can be used to provide quick and located with 1 cycle of data.
reverse fault protection on any circuit breaker. The application Limitations in range of settings, circuits, and exact detection
is most useful at main circuit breakers to detect reverse-fed and clearing times would depend on the specific
fault current in parallel multiple-source systems or when implementation of the algorithms described and the devices
substantial motor contribution can provide the required current used to implement the system.
to identify a fault. B. Putting it Together
V. SUMMARY The net effect of these implementation on 2500kVA
A. Directionally Sensitive Zone Based Protection substation with a 4000A main and tie, a 1600A feeder and
vacuum CB ahead of the transformer is shown on the time
Based on this set of solutions, available to the protection current curve in Fig. 15. A current limiting molded case circuit
engineer a complete zone based protection system can be breaker located downstream of the 1600A feeder is added for
provided for multiple source, or single source systems with comparison.
large motor loads capable of substantial motor contribution or
with multiple sources operating in parallel. The algorithms
operating simultaneously would be:
• Bus differential protection
• Short time -Reverse current detection at mains
T Papallo & I Purkayastha, IEEE Transactions July/August
2004, pg 932-940. Also presented at IEEE PCIC 2003.
[2] “IEEE Guide for Performing Arc-Flash Hazard
Calculations”, IEEE Standard 1584-2002, Published by
The institute of Electrical and Electronic Engineers, Inc.
NY, NY.
VII. VITA
Paul Hamer (S’70–M’74–SM’89–F’97) received the B.S.E.E
degree from Virginia Polytechnic Institute and State
University, Blacksburg, and the M.S.E.E. degree from Oregon
State University, Corvallis, in 1972 and 1979, respectively. In
1979, he joined Chevron Corporation, where he is currently a
Consulting Engineer, Electrical Machinery and Power
Systems, with Chevron Energy Technology Company,
Richmond, CA. His primary responsibilities include power
system, motor, and generator application and consultation.
He has worked on many refining, chemical, and oil production
projects during his career with Chevron. As a member of the
Fig 15. TCC: MCCB, Swgr Feeder and Swgr Bus American Petroleum Institute (API) Subcommittee on
Electrical Equipment, he has contributed to the API standards
The time current curve shows the following devices: for induction and synchronous machines and the API
recommended practice on electrical area classification. He
• 250A molded case current limiting MCCB applied on a bus
represents the API on the National Electrical Code, Code-
with 30kA bolted fault available, 17,100A arcing fault
Making Panel 11, on the subjects of motors, motor circuits,
available at 100%, 14,500 arcing current at 85%
and controllers, and on the technical committee for NFPA
• 1600A LVPCB feeder applied on a system with 65kA total
70E, Standard for Electrical Safety in the Workplace. From
bolted fault current, calculated arcing at feeder load side of
1972 through 1977, he was with Westinghouse Electric
30,500A at 100%, 26,00A at 85%, single source
Corporation, where he was a Service Performance Engineer
• 4000A with 62kA bolted fault current available from one with the Large Generator Department and an Industrial Power
source. 4000A bus is protected with a combination of bus System Engineer and Resident Engineer with the Industry
differential protection set to pick up at 800A and functional Services Division. Mr. Hamer has been an active member of
up to 40,000A, with a delay clearing in 92 ms. A zone the Petroleum and Chemical Industry Committee of the IEEE
selective algorithm keeps the main operating at minimum Industry Applications Society since 1981. He is a Registered
time delay all the way to maximum fault value. Professional Electrical Engineer in the State of California.
In addition the main CB is able to isolate the load side from any
line side fault condition or if a parallel source is provided such Radoslaw Narel graduated from Technical University of
as during a close transition transfer. This function would look Bialystok, Poland in 1996 with MS degree in Computer
like definite time function similar to how 87B is shown in Fig. Science. He started with GE in 1999 in the New Product
15. The reverse protection is not shown on this TCC. Development department. He has worked on multiple power
The feeder protection and main bus protection are fully protection related software / firmware projects. He currently
selective. The MCCB may be fully selective based on its holds position of senior software engineer and leads technical
current limiting capabilities. aspects of a single processor power protection firmware
All calculated arc flash currents downstream of the feeder are project. He is the holder of 3 US and international patents.
interrupted by a device operating instantaneously, the main
bus arcing current is interrupted by devices operating at Tom Papallo graduated from the University of Connecticut in
minimum time band yielding the following energy levels at 1986 with a BS degree and in 1989 with an MS degree, both in
Mechanical Engineering. He started with GE in 1986 in the
480V
New Product Development department. He has also worked on
• Main bus, 62kA Ibf, 32mm, 24”, .092s ==> 7.9cal, HRC2
circuit breaker and electrical distribution system projects for
• Main bus, 62kA Ibf, 32mm, 18”, .092s ==> 12cal, HRC3
several other major manufacturers, returning to GE in 1997. He
• Feeder terminals, 32mm, 18”, .05s ==> 6.5cal, HRC2 is currently the technical lead for a New Product Development
• MCCB bus, 30kA Ibf, 25mm, 18”, .05s ==> 3.8cal, HRC1 project and an adjunct member of the Design Office for the
• MCCB terminals, 25mm, 18”, .017s==> 1.3cal, HRC0 New Product Introduction Department, Plainville, CT. He is the
The above listed arc flash energy values do not reflect the holder of 18 US and international patents has co-authored
result of actual testing of these devices for arc flash three IEEE technical papers.
performance, which would generally result in lower incident
energy values nor do they account for motor contribution Dr. William Premerlani graduated from Rensselaer
decrement which could lower values further. Polytechnic Institute in 1971, 1972, and 1974 with a BS, MS
and Doctor of Engineering in Electric Power Engineering. He
VI. REFERENCES has since worked at GE’s Global Research in Niskayuna, New
[1] “The Single-Processor Concept for Protection and Control York, exploring a wide range of technologies in the fields of
of Circuit Breakers in Low-Voltage Switchgear”, M Valdes, parallel computing, power system protection, and software
development. Dr. Premerlani holds more than 35 patents, and
has co-authored numerous technical papers. His current currently is the Manager of Application Engineering for GE’s
research interest is in phasor measurements and advanced Circuit breaker Business in Plainville Connecticut. Mr. Valdes
protection algorithms. He is a co-author of the popular is past chair of several local IEEE chapters. He is a registered
textbooks: “Object Oriented Modeling and Design” and “Object- Professional Electrical Engineer in California. Mr. Valdes has
Oriented Modeling and Design for Database Applications”. co-authored several technical papers in IEEE forums and has
several patents pending in the field of power systems
Marcelo E. Valdes graduated from Cornell University in 1977 protection.
with a BS in Electrical Engineering. He has held various field
and management positions at General Electric since 1977. He

You might also like