Professional Documents
Culture Documents
Abstract - Time based coordination and protection is the circuits are processed every ½ cycle at a central. Commands
normal basis for coordinating low voltage power distribution to trip or open a circuit breaker are issued at the end of each
systems. Enhancements, such as zone selective interlocking such data processing cycle simultaneously to the start of the
and bus differential protection, may be used to accelerate next processing cycle. Hence, multiple algorithms can process
protective devices. However, these improvements may be the same synchronized data and optimize their overall
costly, difficult to implement, and may not function as expected performance. For further elaboration on the system
using commonly available technology. Nevertheless, the architecture the reader is encouraged to read reference 1 “The
potential benefit of fault clearing speed and selectivity are more Single-Processor Concept for Protection and Control of Circuit
valued in today’s arc-flash and reliability conscious Breakers in Low-Voltage Switchgear”[1].
environment than ever before. The writers shall discuss some Current transformers used in the referenced implementation
issues associated with these traditional improvements, pitfalls of single processor concept are not traditional ANSI relay class
to avoid and, more effective ways to implement zone-based transformers. These current transformers are referred to as
protection to achieve fast fault protection while maintaining sensors and have secondary currents below one ampere.
complete selectivity for a broad range of fault magnitudes, Their characteristics are incorporated and compensated in the
system configurations and load types. algorithms as required to achieved required accuracy.
30
40
50
60
70
80
90
delay. Even if this device is part of a zone interlocking scheme, 300 300
if the current does not exceed the short time pick up, the
200 200
device will not operate within the short time band. 100
90
80
70
60
100
90
80
70
60
30
50
40
30
TI ME IN SECONDS
TI ME IN SECONDS
5 5
4 4
3
Main operating 3
Direction Matters 1
.9
.8
1
.9
.8
.7 .7
.6 .6
.5
Main operating .5
.3
.02
.03
.02
allows the device to send a signal to the next upstream circuit .01 .01
senses current that exceeds its short time pick up level. If that Fig 5. ZSI Effect On Upper CB in 2 CB Scheme
circuit breaker also receives a blocking signal, it will operate at
a programmed delay. If it does not receive a blocking signal, it Let us consider a situation as shown on the one line in Fig. 6.
will operate at its minimum time delay. In the system shown an 800A frame CB is feeding an MCC
with four 100Hp motors. Each motor has full load current of
current of 146.3A amperes and a locked rotor current of 863A
(5.9 x FLA). The motors will start individually during expected
operation of the system the 800A CB is set above 125% of the
motor bank’s full load current – 732A (146.3A x 4 x 1.25). The
short time pick up of the circuit breaker is set to clear 125% of
3 motors FLA + 125% of one motor’s starting current ((146.3A
x 3 + 146.3 x 5.9) x 1.25), 1624A.
Δ θ = ang ( I α ) − ang ( I β )
(2)
Where I is the phase current in the circuit being considered
and 'T is the angular difference.
. The angular difference is checked to determine if the
currents are in the same direction, defined as “in, 1”, or in the
opposite direction, defined as “out, 0”. The logic can handle
significant angular error because the expected angular
difference is 180 degrees for opposing currents. If the angular
difference is between + 60 degrees from 180, the currents are
considered to be in opposite directions.
However, since this is a partial differential algorithm
additional consideration must be given to feeders, to determine Fig 14. Fault Contribution to Fault Ahead of Main
if the fault is in the zone or fed through the zone. To that end
only the current of any feeders that are in short time pick up In a single-processor-based system, data from the present
are considered. If the current through the feeder is determined may be compared to past data. This allows a comparison of
to exceed 10X (a value that should be above potential motor pre-fault voltage to pre and post-fault current to be made after
contribution) then the fault is determined to be downstream of any current in excess of the pick up threshold is detected.
the feeder. If the current is under 10X and above the feeder’s Comparing the phase angle of fault current with the phase
short time pick-up then direction of the feeder’s fault current is angle of pre-fault current, and looking for the reversal will
determined to properly locate the fault. detect a reverse current fault. A pre-fault voltage phasor
To determine the relative direction of a faulted feeder’s maybe continuously calculated and discarded when it is
current it must also be compared to a reference phasor that updated. When current exceeding fault magnitude is
represents the “in” current for the respective faulted partial exceeded, the voltage phasor from a predetermined number of
differential zone. The phasor representing each phase current cycles back would be used as a reference. Reversal would be
for every faulted feeder fed by the faulted partial differential indicated by a 180-degree shift as well as any additional lag
zone is compared looking for a difference in direction that is the fault conditions would introduce. Post fault phase voltage
180 + 60. If the difference is found then the feeder is would be an unreliable source of information as voltage may
conducting current towards a downstream fault, if the angular collapse considerably during fault conditions. In a case of
difference is outside of this range then the feeder is conducting complete voltage collapse the small remaining voltage would
be the bus IR drop that is always in phase with current and • Short time – Directional zone interlocking between mains
would not yield the information required. Hence, the algorithm and ties
implemented in equation (3) will detect current reversal. • Short time - Directional zone selective interlocking at
150 ≤ ang( I ) − α ≤ 250
D D
(3) And
feeders with zones above them
(I ) ≥ ( P
phase current periodically to determine fault current.
for bus faults the setting is independent of all other settings in
2
RMS RC )2 (4)
the system that may be required for optimum selectivity or
sustaining loads.
Where IRMS could be computed form ½ cycle of current Reverse current protection at the main would function
samples for each phase and PRC is the reverse current independently and would issue a trip signal to the proper circuit
protection setting chosen for the main circuit breaker being breaker when the algorithm is satisfied, including a medium
considered. voltage transformer main if provided. The same algorithm
Once it is determined that a current through the main has would simultaneously block action by the other short time
exceeded the pick up threshold for reverse current pick up, a functions to prevent unnecessary nuisance tripping if other
series of calculations can be run comparing the angular sources can continue to sustain load.
relationship between pre-fault positive-sequence current and All algorithms are able to reliably calculate with as little as
post fault positive-sequence current by referencing both to pre- two half cycles of current data. The combination of the various
fault positive-sequence voltage. If the current is determined to algorithms operating simultaneously can provide identification
have reversed then the fault is ahead of that device. Since this of fault location ahead, within and downstream of a bus in a
reverse current setting need not be considered for forward line up of switchgear with multiple sources and closed ties,
current coordination analysis the pick up level may be quite low regardless of motor contribution magnitude relative to the short
and the delay only as long as required to make a reliable trip time settings of feeder circuit breakers. The minimum
decision. Zone selective interlocking can provide back up sensitivity of a the bus differential algorithm allows fault smaller
levels of protection even in this reverse direction by reversing than the a bus’ current rating to be located and the various
the hierarchy implemented for forward faults. short time algorithms allow faults up to the short circuit rating of
These comparisons plus appropriate error compensation, the equipment, if the circuit breakers allow it, to be detected
cooling and heating algorithms can be used to provide quick and located with 1 cycle of data.
reverse fault protection on any circuit breaker. The application Limitations in range of settings, circuits, and exact detection
is most useful at main circuit breakers to detect reverse-fed and clearing times would depend on the specific
fault current in parallel multiple-source systems or when implementation of the algorithms described and the devices
substantial motor contribution can provide the required current used to implement the system.
to identify a fault. B. Putting it Together
V. SUMMARY The net effect of these implementation on 2500kVA
A. Directionally Sensitive Zone Based Protection substation with a 4000A main and tie, a 1600A feeder and
vacuum CB ahead of the transformer is shown on the time
Based on this set of solutions, available to the protection current curve in Fig. 15. A current limiting molded case circuit
engineer a complete zone based protection system can be breaker located downstream of the 1600A feeder is added for
provided for multiple source, or single source systems with comparison.
large motor loads capable of substantial motor contribution or
with multiple sources operating in parallel. The algorithms
operating simultaneously would be:
• Bus differential protection
• Short time -Reverse current detection at mains
T Papallo & I Purkayastha, IEEE Transactions July/August
2004, pg 932-940. Also presented at IEEE PCIC 2003.
[2] “IEEE Guide for Performing Arc-Flash Hazard
Calculations”, IEEE Standard 1584-2002, Published by
The institute of Electrical and Electronic Engineers, Inc.
NY, NY.
VII. VITA
Paul Hamer (S’70–M’74–SM’89–F’97) received the B.S.E.E
degree from Virginia Polytechnic Institute and State
University, Blacksburg, and the M.S.E.E. degree from Oregon
State University, Corvallis, in 1972 and 1979, respectively. In
1979, he joined Chevron Corporation, where he is currently a
Consulting Engineer, Electrical Machinery and Power
Systems, with Chevron Energy Technology Company,
Richmond, CA. His primary responsibilities include power
system, motor, and generator application and consultation.
He has worked on many refining, chemical, and oil production
projects during his career with Chevron. As a member of the
Fig 15. TCC: MCCB, Swgr Feeder and Swgr Bus American Petroleum Institute (API) Subcommittee on
Electrical Equipment, he has contributed to the API standards
The time current curve shows the following devices: for induction and synchronous machines and the API
recommended practice on electrical area classification. He
• 250A molded case current limiting MCCB applied on a bus
represents the API on the National Electrical Code, Code-
with 30kA bolted fault available, 17,100A arcing fault
Making Panel 11, on the subjects of motors, motor circuits,
available at 100%, 14,500 arcing current at 85%
and controllers, and on the technical committee for NFPA
• 1600A LVPCB feeder applied on a system with 65kA total
70E, Standard for Electrical Safety in the Workplace. From
bolted fault current, calculated arcing at feeder load side of
1972 through 1977, he was with Westinghouse Electric
30,500A at 100%, 26,00A at 85%, single source
Corporation, where he was a Service Performance Engineer
• 4000A with 62kA bolted fault current available from one with the Large Generator Department and an Industrial Power
source. 4000A bus is protected with a combination of bus System Engineer and Resident Engineer with the Industry
differential protection set to pick up at 800A and functional Services Division. Mr. Hamer has been an active member of
up to 40,000A, with a delay clearing in 92 ms. A zone the Petroleum and Chemical Industry Committee of the IEEE
selective algorithm keeps the main operating at minimum Industry Applications Society since 1981. He is a Registered
time delay all the way to maximum fault value. Professional Electrical Engineer in the State of California.
In addition the main CB is able to isolate the load side from any
line side fault condition or if a parallel source is provided such Radoslaw Narel graduated from Technical University of
as during a close transition transfer. This function would look Bialystok, Poland in 1996 with MS degree in Computer
like definite time function similar to how 87B is shown in Fig. Science. He started with GE in 1999 in the New Product
15. The reverse protection is not shown on this TCC. Development department. He has worked on multiple power
The feeder protection and main bus protection are fully protection related software / firmware projects. He currently
selective. The MCCB may be fully selective based on its holds position of senior software engineer and leads technical
current limiting capabilities. aspects of a single processor power protection firmware
All calculated arc flash currents downstream of the feeder are project. He is the holder of 3 US and international patents.
interrupted by a device operating instantaneously, the main
bus arcing current is interrupted by devices operating at Tom Papallo graduated from the University of Connecticut in
minimum time band yielding the following energy levels at 1986 with a BS degree and in 1989 with an MS degree, both in
Mechanical Engineering. He started with GE in 1986 in the
480V
New Product Development department. He has also worked on
• Main bus, 62kA Ibf, 32mm, 24”, .092s ==> 7.9cal, HRC2
circuit breaker and electrical distribution system projects for
• Main bus, 62kA Ibf, 32mm, 18”, .092s ==> 12cal, HRC3
several other major manufacturers, returning to GE in 1997. He
• Feeder terminals, 32mm, 18”, .05s ==> 6.5cal, HRC2 is currently the technical lead for a New Product Development
• MCCB bus, 30kA Ibf, 25mm, 18”, .05s ==> 3.8cal, HRC1 project and an adjunct member of the Design Office for the
• MCCB terminals, 25mm, 18”, .017s==> 1.3cal, HRC0 New Product Introduction Department, Plainville, CT. He is the
The above listed arc flash energy values do not reflect the holder of 18 US and international patents has co-authored
result of actual testing of these devices for arc flash three IEEE technical papers.
performance, which would generally result in lower incident
energy values nor do they account for motor contribution Dr. William Premerlani graduated from Rensselaer
decrement which could lower values further. Polytechnic Institute in 1971, 1972, and 1974 with a BS, MS
and Doctor of Engineering in Electric Power Engineering. He
VI. REFERENCES has since worked at GE’s Global Research in Niskayuna, New
[1] “The Single-Processor Concept for Protection and Control York, exploring a wide range of technologies in the fields of
of Circuit Breakers in Low-Voltage Switchgear”, M Valdes, parallel computing, power system protection, and software
development. Dr. Premerlani holds more than 35 patents, and
has co-authored numerous technical papers. His current currently is the Manager of Application Engineering for GE’s
research interest is in phasor measurements and advanced Circuit breaker Business in Plainville Connecticut. Mr. Valdes
protection algorithms. He is a co-author of the popular is past chair of several local IEEE chapters. He is a registered
textbooks: “Object Oriented Modeling and Design” and “Object- Professional Electrical Engineer in California. Mr. Valdes has
Oriented Modeling and Design for Database Applications”. co-authored several technical papers in IEEE forums and has
several patents pending in the field of power systems
Marcelo E. Valdes graduated from Cornell University in 1977 protection.
with a BS in Electrical Engineering. He has held various field
and management positions at General Electric since 1977. He