1. Description ...........................................................................................2
1
GU320B Controller Operation Manual
1. Description
GU320B Genset intelligent controller is adopted high performance computer chip,
can modify the control procedure and protection parameters of generator, which
incorporated kinds of functions, such as measure, control, protection, three remote,
and programmable management. It fully meets the auto control requirements of
different kinds of Genset for generator user and or special assembly factory.
The controller measure and display all output electric parameters for generator, and
rpm, oil pressure, coolant temperature, DC source voltage and running hours for engine,
and the voltage and current adopted true RMS measure to make sure data accuracy.
Optional kinds of preset PT-sensor, and can custom parameters by corresponding software.
Buttons on control panel are used for selecting control modes, starting the running
procedure, displaying data, and modifying the parameters of running and protection.
LED indicators are used for indicating the operation mode of controller and the
running status of Genset, and LCD displays each measuring parameter and status.
The controller is closely combined by panel and powder coated steel enclosure,
and the panel is die-casting by flame-retarded and high strength plastic. All
connections of controller are connected by pin-like and locked up terminal, easier
and more convenient to connect, move, maintain and replace the device.
This manual only suitable for GU320B generator intelligent controller, user must
carefully see manual first.
NOTE: the controller enclosure must be grounded; well low impedance grounded
can reduce the impact from the processes of surge and transient of the electric
power system to the meter.
2
GU320B Controller Operation Manual
2. The Outline Dimensional Drawings and wirings of Controller
2.1 Following Details:
3
GU320B Controller Operation Manual
2.2 Connecting Terminals:
NOTE: Pin No. D19 is reserved for measurement input, the measurable signal is
0~5VDC or 4~20mA or resistance signal, preset to measure resistance signal, if
required change propose in advance for hardware change.
4
L1
L2
G Load
L3 (3P&N)
N
F1 F2 F3
1 2 3 4 5 6 7 8
2.3 Typical Wiring Diagram:
GU320B
+CI485=RS485
+CI232=RS232
5
RS-CONNECTOR
DC power Source
(12/24VDC) RL1 RL2 RL3 RL4 RL5 RL6
WL
27 28 29 9 12 10 11 13 14 15 16 20 21 22 23 24 17 18 19 25 26
GU320B Controller Operation Manual
F4 F5
(2A) (16A)
Charger
T-sensor
Fuel sensor
P-sensor
Temp switch
E stop
Remote start signal
Fuel Crank
LCD with 128×64 lattice can display multi-lines data information in the same time
and add background-light function that operator can clearly read information
whenever at day or night. After pressing any button the background-light can auto
turn off in a certain time.
LCD displays and control buttons provide a friendly operation interface for operator,
convenient to read information and set running parameter.
6
GU320B Controller Operation Manual
7
GU320B Controller Operation Manual
4. Installation Guide
4.1 The dimensional drawing of install hatch on panel, showing as above attached.
The controller is fixed by 4 special mounting fittings. The shock-proof
equipment must be installed if the enclosure that installed on controller is
directly installed on Genet body or other heavy vibrant device.
4.2 Please see above 2.3 Typical Wiring Diagram or attached drawing for
wiring connecting.
4.3 The installations of P-sensor and T-sensor for engine:
Use Terminal
P-sensor D17 D19 D17 D18
T-sensor D18
Fuel sensor D19 GU320B CONTROLLER
Sensor Com .Port Battery cathode(shell)
8
GU320B Controller Operation Manual
4.4 Kinds of typical connection methods for generator winding.
Series star, 3-phase 4 wires Parallel star, 3-phase 4 wires
L1
L1
N N
L3 L3 L2
L2
L1
L1
L3 L3 L2
L2
L1
L L
L3 L2
N
N
L2
L3
9
GU320B Controller Operation Manual
4.5 Typical input connection for corresponding voltage and current
connected to different kinds of generator winding.
G
L2
L
1
-
N
,
L
2
-
N
,
L
3
-
N
L3 Measure and display data:
N 3-phase phase voltage
3-phase line voltage L1-L2,L2-L3,L3-L1
3-phase current L1 L2 L3
F1 F2 F3 Frequency Hz
3-phase apparent power AL1 AL2 AL3 ∑A
3-phase power and total power PL1 PL2 PL3 ∑P
1 2 3 4 5 6 7 8 3-phase reactive power and total reactive power QL1 QL2 QL3 ∑Q
3-phase power factor PFL1 PFL2 PFL3
GU320B Active energy(KWhr) ∑E
Reactive energy(KVArhr) ∑E
G
L2
L3
G
L2
10
GU320B Controller Operation Manual
Biangle, 1-phase 2 wires
L
G
L2
P
LQ
1LA
P1L
LQ1
2LA
F1 F2
Active power ∑P
2L
∑Q
2
Reactive power
1 2 3 4 5 6 7 8
Apparent power ∑A
Power factor P
Active energy (KWhr) ∑ E
GU320B Reactive energy (KVArhr) ∑ E
Operation Description
Continuously press “AUTO” button (2s above), the
LED above the button lights up, controller then
running in “AUTO” mode.
11
GU320B Controller Operation Manual
5.2 The Process of Start Control:
Operation Description
When controller running in AUTO status and remote
start input signal is active, or in MAN status press
“START” button, controller begins start procedure,
START LED flash.
When remote start signal is active, the start delay will be enabled and begin to
counting. During the period of counting, if the remote start signal is inactive, start
delay will stop counting immediately, controller stop start procedure, and return to
original status after finishing the counting of fail to stop.
During cranking or idle, if the remote start input signal is inactive, controller stop the
following start procedure immediately and control output by closing all relays, then
stop the start process, and return to original “READY” status after finishing the
counting of fail to stop.
NOTE: During crank, engine ignition, when the output frequency of alternator is
reaches to preset frequency, start motor disconnect power. Or the start motor is
disconnected power by one of the following reasons:
a. The magnetic pickup device which mounted on engine flywheel detects that
the frequency reach to preset frequency.
b. The output voltage of alternator is reaches to 80% rating voltage;
c. The low oil pressure switch of engine is open.
12
GU320B Controller Operation Manual
5.3 The Process of Fail to Start and Restart:
Operation Description
During the period of crank time counting, engine can
CRK-RST
not ignite, controller will not output starting signal
during crank rest. LCD flashing FAIL TO START. 15
Once crank rest time out, controller will attempt to CRANK
restart engine again. 2
Above start phenomena repeat again and again until engine successful ignition and or reach
the preset crank times. If any stop failures occur during start process, controller stops control
output immediately, until failure eliminated and reset, then it can be operated again.
Operation Description
When above start phenomena repeat again and again
ALARM
and over the preset crank times, controller will stop
START FAILURE
control output, LCD display:
NOTE:
Operation Description
When the remote start input signal is inactive,
COOL
cooling delay begins count down, cut off running
300
signal. (idle delay not at zero)and then LCD display:
When cooling delay time out, controller switch off
STOP
fuel solenoid valve immediately, the counter for fail
20
to stop begins count down, then LCD display:
When fail to stop time out and if engine still running, ALARM
controller will sent out an alarm, LCD display: STOP FAILURE
If during allowed fail to stop delay engine stop
READY
running, LCD display:
When the remote start input signal is inactive, cooling delay begins counting,
during the period, if remote start input signal is active again, cooling delay stop
counting immediately, controller enter into safe monitor each parameter again,
recover auto running status if normal.
13
GU320B Controller Operation Manual
5.6 The Control Process of MAN Stop:
Operation Description
When Genset in normal running, in “MAN” mode
continuously press “STOP/RESET” button one time,
controller begins cooling delay stop process, which
same as auto stop. Press “STOP/RESET” button
again, controller switch off fuel solenoid valve
immediately, Genset start stop.
STOP
The counter for fail to stop begins counting, LCD display:
00:24
When the counting time excesses the time of fail to
ALARM
stop counter, if engine still running, controller will sent
STOP FAILURE
out an alarm, LCD display:
If during allowed fail to stop delay engine stop running.,
READY
LCD display:
5.7 The start and stop processes of engine, which fuel solenoid valve is N. O.
type (difference from N.C. type):
Start control process:
When start running, the fuel relay of controller no action, fuel solenoid valve no
power, means the electromagnet of solenoid valve no action.
Stop control process:
When controller starts at stop control process, output the power of fuel solenoid
valve, fuel solenoid valve take action, engine begins stop. After delay (according to
the setting fail to stop delay) fuel relay breaking, disconnect the power of fuel
solenoid valve.
Other control process same as engine fuel solenoid valve is N. C. type.
5.8 Idle and Preheat function
Select the delay function of idle or preheat through “the delay setting value of idle
or preheat”, can select idle and preheat output base on the relay custom function.
When set value at 0, no delay function. When delay value not set at 0, realizing idle
and preheat function. Idle covers normal open (N.O) type and normal close (N.C)
type, when the both on working is opposition on close and open status. Now we
take N.C for example showing its working principle: when in READY status for idle,
idle relay switch off, controller running start procedure, idle relay takes action at the
same time, start delay time out, fuel relay takes action, when start successful
switch off start motor, in that time idle delay begins count down, when time out, idle
relay switched off. Safety-on delay begins counting, if each parameter in normal
after time out, unit running. Cooling stop delay begins counting and idle relay no
action, after cooling delay time out, idle delay begins count down, idle relay takes
action at the same time, after delay expired performs stop action, after stop switch
off idle relay. When stay at READY status with preheat function, preheat relay is
open, the produce of start delay begins counting, preheat relay takes action at the
same time, crank attempt successful, after safety-on delay unit running, preheat
relay begins counting, when time out preheat relay switched off, cooling delay for
stop, preheat relay no action.
14
GU320B Controller Operation Manual
6. Measure and Display Data
6.1 The Measuring Data for Electric Section
15
GU320B Controller Operation Manual
7. Warning and Shutdown Alarm
7.1 Warning
(NOTE: Warnings are non-critical failure conditions and do not affect the operation of
the generator system, they serve to draw the operators’ attention to an undesirable
condition and remove it to make sure system continuous running. When Warnings
occur, the status indicator light flash, but failure will not be locked and the unit will not
shutdown. Once failure removed warning indicator auto turn off.)
Charge Fail if controller detects that voltage has fallen below the preset “low
battery warning value” from the excitation contact of auxiliary AC charger, LCD
status bar displays “WARN: CHARGE FAILURE”, alarm buzzer sounds.
Battery Low Voltage controller detects that battery voltage has fallen below the
preset “low battery warning value”; LCD status bar displays “WARN: BATTERY LOW”,
alarm buzzer sounds.
Battery High Voltage controller detects that battery voltage has exceeded the preset
“high battery warning value”; LCD status bar displays “WARN: BATTERY HIGH”,
alarm buzzer sounds.
Low Oil Pressure controller detects that the engine oil pressure has fallen below the
preset “low oil pressure warning value” after the safety-on timer has expired, LCD
status bar displays “WARN: LOW OIL PRESS”, “LOW OIL PRESSURE” LED flash,
alarm buzzer sounds.
High Temperature controller detects that engine coolant temperature has
exceeded the preset “high coolant temperature warning value”, LCD status bar
displays “WARN: COOLANT TEMP”, “HIGH TEMPERATURE” LED flash, alarm
buzzer sounds.
Overspeed if the engine exceeds the preset “overspeed warning value”; LCD
status bar displays “WARN: OVER SPEED”, alarm buzzer sounds.
Underspeed if the engine falls below the preset “underspeed warning value”, LCD
status bar displays “WARN: UNDER SPEED”, alarm buzzer sounds.
Gen High Voltage if controller detects that the output voltage of generator has
exceeded the preset “high voltage warning value”, LCD status bar displays “WARN:
GEN. V HIGH”, alarm buzzer sounds.
Gen Low Voltage if controller detects that the output voltage of generator has fallen
below the preset “low voltage warning value”, LCD status bar displays “WARN: GEN. V
LOW”, alarm buzzer sounds.
Over Current If controller detects that the output current of generator has
exceeded the preset “high current warning value”, LCD status bar displays “WARN:
OVER CURRENT”, alarm buzzer sounds.
Reserve Input If reserve auxiliary input is set as warning input, when input signal is active,
LCD status bar displays “WARN: AUX ALARM”, alarm buzzer sounds.
16
GU320B Controller Operation Manual
7.2 Shutdown Alarm
(NOTE: shutdown failures immediately lock system and stop generator, it only can
operate controller again after removing failures and press rest button to unlock)
Fail to Start if engine does not fire after the preset number of crank attempts has been
made, means fail to start. LCD status bar displays “ALARM: START FAILURE”, “FAIL
TO START” LED lights up, alarm buzzer sounds, failure relay close output.
Fail to Stop if engine does not stop after the stop delay expires. LCD status bar
displays “ALARM: STOP FAILURE”, failure relay close output.
Emergency Stop when emergency stop input signal is active, controller immediately
stops all relay control output except alarm, LCD status bar displays “ALARM: E. STOP”,
“EMERGENCY STOP” LED lights up, alarm buzzer sounds, failure relay close output.
Low Oil Pressure if controller detects that the oil pressure level still falls below oil
pressure alarm value or oil pressure switch is closing after the safety-on timer has expired,
engine stop immediately, LCD status bar displays “ALARM: LOW OIL PRESS”, “LOW
OIL PRESSURE” LED lights up,, alarm buzzer sounds, failure relay close output.
High Temperature controller detects that engine coolant temperature has exceeded
the high coolant temperature alarm value or temperature switch is closing, engine stop
immediately, LCD status bar display “ALARM: COOLANT TEMP”, “HIGH
TEMPERATURE” LED lights up, alarm buzzer sounds, failure relay close output.
Overspeed if controller detects that engine speed exceeds the overspeed alarm value,
engine stop immediately. LCD status bar displays “ALARM: OVER SPEED”,
“OVERSPEED” LED lights up, alarm buzzer sounds, failure relay close output.
Underspeed if controller detects that engine speed falls below the “underspeed
alarm value”, engine stop immediately. LCD status bar displays “ALARM: UBDER
SPEED”, alarm buzzer sounds, failure relay close output.
High Voltage if controller detects that the output voltage of generator has exceeded
the “Gen high voltage alarm value”, engine stop after delay is confirmed, LCD status
bar displays “ALARM: GEN. V HIGH”, alarm buzzer sounds, failure relay close output.
Low Voltage if controller detects that the output voltage of generator has fallen below
the “Gen low voltage alarm value” after the safety-on timer has expired, engine stop after
delay is confirmed, LCD status bar displays “ALARM: GEN. V LOW”, alarm buzzer
sounds, failure relay close output.
Over Current controller detects that the output current of generator has exceeded the
“Gen high current alarm value”, engine stop after delay is confirmed. LCD status bar
displays “ALARM: OVER CURRENT”, alarm buzzer sounds, failure relay close output.
Reserve Input If reserve auxiliary input is set as warning input, when input signal is
active, engine stop immediately, LCD status bar displays “EXT”, LCD failure bar
displays “ALARM: AUX ALARM”, alarm buzzer sounds, failure relay close output.
17
GU320B Controller Operation Manual
NOTE:
The warnings or shutdown alarms of oil pressure and coolant temp switch
signal can be realized by setting No. 3.31 and 3.32 menus, the data detects
from the switches status (on or off) of P-sensor and T-sensor.
The warnings or shutdown alarms of the oil pressure and coolant temp analog
signal can be realized by setting the parameters range on No. 3.23, 3.24, 3.25
and 3.26 menus, the data measure from the analog input ranges of P-sensor
and T-sensor.
The engine speed general from the frequency of pickup sensor, which
mounted on engine flywheel, if system do not mount pickup sensor, controller
will auto use the output voltage frequency of generator as the parameters of
control and failure protection, for user convenience, some data expressed by
rpm, RPM=HZ*30.
Generator occur failure during running: after occur high temperature, low oil
pressure, overspeed and underspeed, stop immediately no delay. During
cooling delay, for underspeed and low oil pressure, only set idle delay at “0”
so that no idle function can play protection function, or will not play.
8. Parameters Setting
8.1 SYSTEM
NOTE: Require restart working power source to become effective after the
communication address changed.
18
GU320B Controller Operation Manual
8.2 GENERATOR
8.3 ENGINE
Voltage input type: the connection mode of winding that different from engine,
select different winding by menu
1. Series parallel start, 3-phase 4 wires 2. Series parallel angle, 3-phase 3 wires
3. Island angle, 3-phase 4 wires 4. Biangle, 1-phase 2 wires
5. Biangle, 1-phase 3 wires
20
GU320B Controller Operation Manual
NOTE:
When above No. 3.8 set at “0” means H-sensor is not used, engine speed is
set by No. 3.4 (Pair of Poles); when No.3.4 set at “2” running speed is 1500
rpm, when No.3.4 set at “1” running speed is 3000 rpm.
When above No. 3.8 set at “1” means H-sensor is used, the value of No. 3.2
(pickup frequency) set by MAN; engine speed is set by No. 3.1 (rated speed).
When above No. 3.8 set at “1” means H-sensor is used, if the input value of
No. 3.2 (pickup frequency) is auto set by the method of 11.6 (showed as
below), both the value of No. 3.4 (Pair of Poles) and No. 3.1 (rated speed)
must be correctly set.
8.5 The Definitions of P-sensor and T-sensor
For P-sensor and T-sensor, according to below table different No. stand for
different sensor mode, if the used sensor is not listed in the table, through software
write the sensor data into controller, and the sensor mode in the parameters setting
should be selected as “custom” that is listed as the last mode in below table.
Adopting 128×64 lattice LCD can display multi-lines data information at the same
time. And LCD has background-light function, after pressing any button the
background-light can auto turn off in a certain time. Set a different parameter in
every page and according to this setting to control, the main page displays each
parameter and engine measuring data. If no failure occurs, LCD keep displays the
data of main page, when failure occurs, LCD display failure information in status
bar immediately, when not only one failure, LCD just display one of them.
21
GU320B Controller Operation Manual
For parameters setting and modify adopts gradually increase and decrease, when
continuously press increase or decrease button, the single digit changed one by
one, then the tens digit changed after ten single digit changed, follow this logic, and
the hundreds digit changed after ten. Continuously press“ ” 2s can enter into
setting status, can use “ ” and “ ” scroll page up and down at that time. Press
“ ” enter into next submenu, select the required modify item, press “ ” enter
RUN
For example: (setting current transformer rate at 1000 /5, then CT should be set at 200)
Operation Description
23
GU320B Controller Operation Manual
After changing press“ ” to confirm , then <<SETTING/参数设定 >>
press“ ” and “ ” , then LCD display: 1. System
Operation Description
Operation Description
Continuously press “ ” 2s, enter into parameters <<SETTING/参数设定 >>
setting menu, then LCD display: 0.QUIT
24
GU320B Controller Operation Manual
For example: (set controller as online program mode)
Operation Description
The setting and operation method for other parameters are similar to above method.
25
GU320B Controller Operation Manual
10.2 The Communication Connection for CI485
Controller has RS485 COM after add CI485A accessory, following typical wiring diagram:
S w itc h te rm in a l
R S C O N N EC TO R
A
G U 3 2 0 B C o n tro lle r
(D B9)
C I4 8 5 A B (R S 4 8 5 )
S
Controller has RS232 COM after add CI232A accessory, following typical wiring diagram:
R S C O N N EC TO R
(D B9)
C I232A
C a n c o n n e c t se p a ra te ly
M O D EM
PC
The communication interface offers user a route: from which you can get more
information that can not get from panel, the matching software can display all
measured parameters and status information, and can set all parameters. The
controller that has RS485 COM allows 1 communication bus most connect to 247
same series of controllers by wiring connection mode, each device has one and
only ID NO., only can connect to PC or MODEM by matching with another
RS485/RS232 shifter in that time. Following typical wiring diagram:
26
GU320B Controller Operation Manual
C a n c o n n e c t se p a ra te ly
PC
M O D EM
R S485/232
Sw itc h
S
B
A
R c o n n e c t re sista n c e
S
S
B
B
A
A
C I485A
C I485A
C I485A
(D B 9 ) (D B 9 ) (D B 9 )
R S C O N N E C TO R R S C O N N E C TO R R S C O N N E C TO R
G U 320B C o n tro lle r
NOTE: Communication cable used high quality shielded twisted-pair cable, and its
amount length must not exceed 1000m. The anode and cathode of RS485 in each
controller must be correctly connected, and the cable shield only can be grounded
at one side.
27
GU320B Controller Operation Manual
10.3 Communication Protocol
When working, controller adopts 9600 baud rate and MODBUS-RTU
communication protocol, when it is working, computer will send out a string of
instruction to controller and then waiting for the return data string. Modbus protocol
is one kinds of universal language that applied in electronics controller. Using this
protocol, controllers can communication with each other, the controller can
communication with other device through network (such as Ethernet). It has
become a universal industry standard. Using it, the control device that
manufactured by different manufacturer can connect to industry network,
processing concentration monitor.
This protocol defines a message construction that can be identified by controller,
no matter which network it used to communication. If response request from other
device it describes the process that a controller request to access other device and
how to detect error and make a record. It has set up message structure and the
common format of content.
When communicating in Modbus network, this protocol decides each controller
must know their device address, and identify message that send out from address,
and according it to decide take which action. If need respond, controller will create
return massage and send out by Modbus protocol. In other network, the message
that including Modbus protocol will be translated into frame or package structure
that used in network.
Data frames format
28
GU320B Controller Operation Manual
Device Function
Start Bit Data CRC Parity Stop Bit
Address Code
Address code
The address field of message frame including two characters: ASCII or 8 bit RTU.
The possible slave address is 0…247(algorism). The address range of single
device is 1…247. Master select slave by putting the salve address into the address
filed of message. When slave send out response message, it will put itself address
into the response address field, in order to make master know which device send
out response.
Function Code
Data Field
Data field is structured by two hex number set, the range is 00...FF. According to
the network transport mode, it can be structured by 1 pair of ASCII or an RTU
characters.
The message data field sent out from master to slave including additional message:
slave must use this message to implement action that defined by function code.
This including discontinuous register address, the quantity of items will to be
handled, the practical data bytes in the field.
For example, if master requires slave read a set of hold register (function code 03),
the start register and the quantity of register to be read is specified by data field. If
master write a set of slave register (function code 10 hex), then data field specify
start register and the quantity of register to be wrote. Data bytes in data field need
to write into register data.
If no error, data field return from slave including request data. If occur error, this
field will including an exception code, master application can use it to judge the
next action.
In some message, data field can be inexistent (0 length). For example, master
requires slave response communication record (function code 0B, hex), slave do
not require any additional message.
29
GU320B Controller Operation Manual
Error Correction Code(CRC)
Standard Modbus network has two error detection methods. Content in error detect
field depends on the selected detect method.
When selects RTU mode as character frame, error detect field including a 16 bits
value (realized by two 8 bits character). Content in error detect field is detects by
message content processing CRC. CRC field append at the end of the message,
add from low byte to high byte. So the high byte of CRC is the last byte of the send
out message.
Use RTU mode, message including an error detect field that based on CRC
method. CRC field detects the entire message content.
CRC field covers two bytes, including a 16 bits binary value, which added into
message after calculated by transmission device. Receiver recalculates the
received message CRC and compared with the value in CRC field. If any
difference, there must be some error.
CRC firstly introduces a 16 bit register that all value at “1”, and then processes the
value in the current register for the continuous 8-bits in message. Only 8 bit data in
each character is active for CRC, start bit, stop bit and parity are inactive.
During CRC produce, each 8 bit character will OR with register content respectively,
result moving to LSB (least significant bit), use 0 fill out MSB (most significant bit).
LSB is picked out for detection, if LSB is 1, register OR with the preset value, if
LSB is 0, no action. The whole process will repeat 8 times. After finishing the last
bit (the eighth bit), the next 8-bits will OR with the current value of register
respectively. At last, the value in register is CRC value that after all bytes in
message are processing.
Master Request
01 03 00 38 00 01 XX
30
GU320B Controller Operation Manual
Slave Response
01 03 2 41 24 XX
The algorism integer of hex 4124 is 16676, error correction value is decided by
transmission mode.
33
GU320B Controller Operation Manual
$2039 1 Custom Relay 2
$203A 1 Custom Relay 3
$203B 1 Batt High PreALM V
$203C 1 ALT. Low PreALM V
$203D 1 Voltage Type
$2040 1 V1 Correction
$2041 1 V2 Correction
$2042 1 V3 Correction
$2043 1 I1 Correction
$2044 1 I2 Correction
$2045 1 I3 Correction
$2046 1 Oil pressure Correction
$2047 1 Coolant Correction
$2048 1 Battery voltage Correction
$2049 1 Excitation charging voltage Correction
$204A 1 Fuel level Correction
$204B ――― $205E are P-sensor data table, according to the resistance (0.1Ω)
from small to big, ordered from resistance to corresponding value to resistance.
$205F ――― $2072 are T-sensor data table, according to the resistance (0.1Ω)
from small to big, ordered from resistance to corresponding value to resistance.
$2073 ――― $2086 are Fuel sensor data table, according to the resistance (0.1Ω)
from small to big, ordered from resistance to corresponding value to resistance.
34
GU320B Controller Operation Manual
11. Preparation before Start the Controller
11.1 Make sure controller is fixed well and its install meet ambient requirement.
11.2 Confirm controller all wrings connection meet electric specification and
according with the “typical wiring diagram”, and especially need confirm DC
supply source has correct polarity. Otherwise, it maybe damage controller.
11.3 Controller must be grounded well.
11.4 We suggest external install “E- stop” button, connecting E-stop signal input
terminal to the N. O. contact of “E- stop” button, and another contact connected
to the cathode of battery source.
11.5 Switch on DC working power source, make sure the preset parameters meet
practical condition, such as current rate, H-sensor, P-sensor, T-sensor, etc.
11.6 If H-sensor is electromagnetic mode sensor, must according to below steps to
adjust the speed measuring parameter:
Method 1:
After switch on power source, set controller on MAN operation mode, the key
switch stay at “MAN”. H-sensor input frequency (F) is calculated by the rated speed
and the flywheel tooth, F= tooth * Rate speed / 60, just input this calculated value
to controller directly and finish setting, detailed steps as following:
Operation Description
Controller in ready status: READY
Continuously press “ ” 2s, enter into parameters <<SETTING/参数设定 >>
setting menu, then LCD display: 0.QUIT
35
GU320B Controller Operation Manual
Method 2:
Operation Description
Controller in ready status: READY
Continuously press “ ” 2s, enter into parameters <<SETTING/参数设定 >>
setting menu, then LCD display: 0.QUIT
36
GU320B Controller Operation Manual
13. Troubleshooting
Version:059B081030