Power Monitoring Device and Power Quality Recorder SICAM P855

The multifunctional measuring device is used for acquisition, visualization, evaluation


and transmission of electrical measured variables such as alternating current, alternating
voltage, frequency, power, harmonics etc. The acquisition and processing of measured
variables and events are performed according to the IEC 61000-4-30 power quality
measurement standard.

Applications
The measuring device is used in single-phase as well as in three-wire and four-wire
systems (with neutral conductor). The device is applied wherever comprehensive
measure-ment of supply quality is necessary - at power utilities as well as in industry and
trade sectors.

Features
- Comprehensive acquisition of relevant network
www.Elec-Engg.com

parameters for early identification of supply


quality problems.
- Easy operation via integrated web server for
parameterization,diagnosis,evaluation and reporting.
- Manufacturer-independent, comparable measured
values obtained by using the IEC 61000-4-30
standard measurement methods.
- Interoperability is guaranteed by using standard
interfaces and standard protocols (IEC 61850,
Modbus, IEC 60870-5-103) and standard data
(PQDiff, Comtrade).
- Measured value acquisition according to the
IEC 61000-4-30 power quality measurement standard
including flicker
- Automatic PQ reporting according to EN 50160
- Mean value, event and fault recorder functionality
- Data export in the PQDIF and COMTRADE format
- Memory capacity of 2 GB for storage of the recorder
data
- Evaluation of events directly in HTML via the
integrated web server
- Time synchronization
- Via Ethernet: SNTP client
- Via fieldbus
- Internal Real Rime Clock (RTC)
- 4 LEDs for state and system messages

Housing
Dimensions: 96 x 96 x 100 mm (W / H / D)
X Snap-On mounting unit without graphical display
O Panel-mounted instrument with graphical display

Front protection class


X IP20
O IP40
O IP51

Serial communication interfaces


X without
O RS485 - Modbus RTU
O RS485 - IEC 60870-5103 and Modbus RTU

Ethernet communication
O Modbus TCP
X Modbus TCP and IEC 61850 Server

Basis function
The following measurands are collected or calculated
by the device from the measured variables
- True RMS AC voltage and AC current
- 2,048 sampled values, 10 / 12 periods
www.Elec-Engg.com

- Effective value measurement (TRMS) up to 100th


harmonic
- Line frequency
- Active, reactive and apparent power
- Active, reactive and apparent energy
- Power factor and active power factor
- AC voltage and AC current unbalance
- Harmonics of AC voltage and AC current are stored
up to the 40th order for evaluation
- THD (Total Harmonic Distortion) of AC voltage and
- AC current
- Phase angle
- Flicker
Recorder functionality
- Measurand recorder
- Trend recorder
- Fault recorder
- Event recorder

Hersteller/Typ: Siemens/SICAM P855 7KG855