You are on page 1of 11

Modeling a Large-Scale Historic Aquifer Test:

Insight into the Hydrogeology of a Regional


Fault Zone
by Daniel R. Hadley1 , Daniel B. Abrams2 , and George S. Roadcap2

Abstract
Faults can act as flow barriers or conduits to groundwater flow by introducing heterogeneity in permeability. We examine the
hydrogeology of the Sandwich Fault Zone, a 137 km long zone of high-angle faults in northern Illinois, using a large-scale historic
aquifer test. The fault zone is poorly understood at depth due to the majority of the faults being buried by glacial deposits and its
near-vertical orientation which limits geologic sampling across faults. The aquifer test—perhaps one of the largest in terms of overall
withdrawal in North American history—was conducted in 1942 at a facility adjacent to the fault zone. More than 34,000 m3 /day
was pumped for 37 days from nine multiaquifer wells open to the stratified Cambrian-Ordovician sandstone aquifer system. We
modeled the aquifer test using a transient MODFLOW-USG model and simulated pumping wells with the CLN package. We tested
numerous fault core/damage zone conceptualizations and calibrated to drawdown values recorded at production and observation
wells. Our analysis indicates that the fault zone is a low-permeability feature that inhibits lateral movement of groundwater and that
there is at least an order of magnitude decrease in horizontal hydraulic conductivity in the fault core compared to the undeformed
sandstone. Large head declines have occurred north of the fault zone (over 300 m since predevelopment conditions) and modifying
fault zone parameters significantly affects calibration to regional drawdown on a decadal scale. The flow-barrier behavior of the
fault zone has important implications for future groundwater availability in this highly stressed region.

Introduction Fault zones typically consist of an inner fault


Faults affect groundwater movement in the shallow core surrounded by a damage zone, both of which
crust by introducing variations in permeability. Faults have distinct hydrologic regimes (Caine et al. 1996;
can act as groundwater flow barriers, conduits, or com- Faulkner et al. 2010; Bense et al. 2013). Fault cores are
plex barrier-conduit systems depending on the geologic where most strain is accommodated and can consist of
material, the type and amount of deformation, and sec- cataclasite or gouge at the slip surface which can impede
ondary processes such as mineralization. Understanding groundwater flow normal to the fault, whereas damage
the hydrogeology of fault zones thus has important impli- zones accommodate strain through fracturing and are areas
cations for analyzing groundwater flow patterns (Bense where preferential vertical flow may occur (Bense and van
and van Balen 2003; Minor and Hudson 2006; Mayer Balen 2003; Minor and Hudson 2006; Caine and Minor
et al. 2007; Bense et al. 2008; Burbey 2008) and for eval- 2009; Ball et al. 2010). However, for unlithified and
uation of regional groundwater supplies (Bredehoeft et al. lithified siliciclastics (e.g., sandstones), strain is typically
1992; Marler and Ge 2003; Roques et al. 2014). accommodated by the formation of deformation bands (as
opposed to discrete slip surfaces or fractures) where grain
sliding and rotation occur, thus reducing permeability
1
Corresponding author: University of Illinois, Illinois State (Antonellini and Aydin 1994; Shipton and Cowie 2001;
Water Survey, 2204 Griffith Drive, Champaign, IL 61820; (217)
300-0402; drhadley@illinois.edu
Fossen et al. 2007).
2
University of Illinois, Illinois State Water Survey, 2204 Griffith Many studies on the hydrogeology of fault zones take
Drive, Champaign, IL 61820; dbabrams@illinois.edu; roadcap@ place on the outcrop scale at individual faults or inves-
illinois.edu tigate fault zones at shallow depths (<100 m). Various
Article impact statement: Modeling a large-scale historic
aquifer test determined the hydraulic conductivity of a deep vertical
approaches include using field-measured permeability at
fault zone in a multiaquifer system. outcrops (Rawling et al. 2001; Caine and Minor 2009),
Received January 2019, accepted July 2019. permeability measured from boreholes and cores drilled
© 2019, National Ground Water Association. through fault zones (Shipton et al. 2002; Nieto Camargo
doi: 10.1111/gwat.12922 and Jensen 2012), geophysical surveys to infer structure

NGWA.org Vol. 58, No. 3–Groundwater–May-June 2020 (pages 453–463) 453


Figure 1. (A) Map of hydrostratigraphic units at the bedrock surface and the Sandwich Fault Zone in northern Illinois. Dark
blue contours indicate static drawdown in the Cambrian-Ordovician sandstone system from pre-development conditions
(1863) to 2014. Additional static level decline has occurred since then (to over 300 m) at local areas within the center of the
cone of depression in Will County. Red inset box indicates study area. (B) Map of the study area showing the location of the
production and observation wells used in the Arsenal Test and contours of the top elevation of the St. Peter sandstone (m
above mean sea level) indicating the variable offset at the fault zone.

(Ball et al. 2010), or detailed study of fault geometries a crystalline-rock aquifer and observed changes in vertical
and modeling of fracture networks (Jourde et al. 2002; flow pathways under pumping and ambient conditions.
Minor and Hudson 2006). These studies determine varia- The purpose of this study is to present an analysis
tions in permeability for various fault components to infer of a large-scale aquifer test (referred to as the Arsenal
groundwater flow conditions on a larger scale. Test) conducted adjacent to a vertical fault system
A growing number of studies have used field within the highly stressed Cambrian-Ordovician sandstone
hydrogeological approaches (e.g., slug testing, aquifer aquifer system in northeastern Illinois. To the authors’
testing, and mapping of heads), analytical modeling, or knowledge, this is perhaps one of the largest confined
numerical modeling, to understand the effect of fault aquifer tests in North American history in terms of
zones on local and regional groundwater flow (see Bense overall withdrawal. The magnitude of withdrawals and
et al. 2013 for a complete review). For example, Marler orientation of the pumping wells provides a unique
and Ge (2003) studied the permeability of the Elkhorn opportunity to study a faulted multiaquifer system at a
Fault Zone in Colorado using slug testing at boreholes considerable depth (>450 m) on a regional scale (tens
across the trace of the fault and simulated flow using of kilometers). We analyze the test both analytically and
two-dimensional numerical modeling. Ball et al. (2010) numerically to determine hydraulic conductivity for 22 km
expanded upon Marler and Ge’s study by incorporating along the length of the fault zone and use our results to
geophysical surveys to map heads across the fault zone update a regional groundwater model that simulates over
and the structure of the fault zone at depth. Both 150 years of withdrawals. We then discuss implications
studies indicate a complex conduit-barrier behavior of of our updated fault zone conceptualization for long-term
the fault zone at a local scale (tens of meters). Mayer groundwater availability.
et al. (2007) estimated conductance for a section of the
Mission Creek Fault Zone in California, which offsets
unconsolidated conglomerates and debris fan deposits, by Geology and Hydrogeology of the Study Area
calibrating a numerical groundwater model to historic The Cambrian-Ordovician (CO) sandstone aquifer
head observations. Burbey (2008) utilized a 62-day system underlies all of northern Illinois and extends into
aquifer test to infer the influence of a small (5 m wide) Wisconsin, southeastern Minnesota, and eastern Iowa. It
fault zone within a thick alluvial aquifer in Nevada. has been a principal groundwater source for municipal
Medeiros et al. (2010) also utilized pump tests to infer and industrial supplies in northeastern Illinois since
hydraulic conductivity across deformation bands within the 1860s. The CO sandstone system consists of the
a shallow sandstone aquifer, but did not detect a strong St. Peter sandstone and underlying Ironton-Galesville
flow barrier despite large differences between host rock sandstone, which are overlain by thick sequences of
and deformed rock permeabilities measured at the outcrop carbonates, shales, and glacial deposits and thus have
scale. More recently, Roques et al. (2014) conducted a limited direct recharge (Figure 1A). Since predevelopment
63-day aquifer test in a highly permeable fault zone within conditions, over 300 m of static head decline has occurred

454 D.R. Hadley et al. Groundwater 58, no. 3: 453–463 NGWA.org


in the sandstone system at the center of the cone of the sandstone aquifers in the center of the cone (Abrams
depression in Will County (Figure 1A; Abrams et al. et al. 2018b). Communities and industries are expected
2015). Drawdowns are minimal or nonexistent in north- to increase withdrawals and to drill additional sandstone
central Illinois because the St. Peter sandstone is exposed wells, many of which will be located near or within the
at the land surface or bedrock surface (allowing for greater fault zone as development continues in western Will and
recharge) and there is less demand (Figure 1A). eastern Kendall Counties. Given that the fault zone is
The Sandwich Fault Zone, a 137 km long zone of buried by glacial deposits for most of its length and limited
parallel and en echelon faults that trend northwest to data are available from drilling logs due to the near-
southeast across northern Illinois (Figure 1A), affects vertical orientation of individual faults, understanding the
groundwater flow locally and regionally. As mapped structure and geometry of the fault zone, and thus the
by Kolata et al. (1978), the fault zone is typically 0.8 hydrogeology, is extremely difficult. The Arsenal Test
to 3.2 km wide and is upthrown to the southwest for provides a unique opportunity to gain insight into the
most of its extent. The fault zone has a maximum hydrogeology of a poorly understood fault system that
displacement of 240 m near its midpoint in DeKalb has significant influence on groundwater availability in a
County but displacement is much less at the ends of the confined aquifer system.
fault zone. In Will County the fault zone has variable
displacement ranging from 0 to 45 m and is typically
upthrown to the northeast (Figure 1B). The fault zone
is characterized by high-angle normal to vertical faults
Arsenal Aquifer Test
that bound horst and graben structures (Kolata et al. Between 1940 and 1942 the Joliet Arsenal (JA) in
1978; Nelson 1995), but reverse faulting has also been Will County, a World War II munitions manufacturing
observed in borehole cuttings, outcrops, and within quarry facility, drilled nine multiaquifer wells open to both
pits (Kolata et al. 1978). The age of the fault zone is the St. Peter and Ironton-Galesville sandstones (Table 1).
constrained stratigraphically by Silurian bedrock units and The wells were drilled to similar depth (around 490 m),
Pleistocene glacial deposits. Movement likely occurred in diameter (46 cm at the bottom) and had the same
multiple episodes of deformation during the late Paleozoic length of casing and open interval. Wells were evenly
(Nelson 1995), possibly coincident with the Ancestral spaced by 762 m in the north-south direction and had
Rockies tectonic event (Marshak et al. 2003). variable spacing (610-762 m) in the east-west direction
The fault zone affects heads in the St. Peter and (Figure 1B). The northernmost well (JA-10) is located less
Ironton-Galesville sandstones most notably in Kendall than 2 km away from the main trace of the fault zone.
County, where there is enough displacement to completely In 1942 the facility, with assistance from engineers
offset the sandstones (i.e., sandstone units are not laterally at the Illinois State Water Survey, conducted a large-
continuous) and there is a large contrast in demands on scale aquifer test to determine whether the sandstone
either side of the fault zone. Both Roadcap et al. (2013) aquifers could provide enough water to satisfy demands
and Abrams et al. (2015) observed sandstone heads that at the height of production. Around 34,500 m3 /day was
were several hundred feet higher on the upthrown side pumped from the production wells for 37 days. Drilling
(southwest side) in Kendall County, indicating that the of JA-4 was completed several days after the start of the
fault zone acts as a flow barrier. Roadcap et al. (2013) production test and some wells were turned off for several
modeled the Sandwich fault zone as a low horizontal days due to difficulties with the turbine pumps, resulting
hydraulic conductivity (K h ) zone of 3 × 10−5 m/day in withdrawals that varied for each well throughout
compared to a K h of 1.5 m/day for the undeformed the duration of the test (Figure 2A). Due to drilling
sandstone units. The fault zone has also been modeled as difficulties, JA-5 was only finished in the St. Peter, was
a no-flow barrier in contouring models of the sandstone never put into production, and served as an observation
system (Abrams et al. 2018b). Most recently, the fault well during the test. JA-8 ran prior to the start of the test
zone has been modeled as a broad region using a and during the recovery phase because it served as the
K h of 0.76 m/day (Mannix et al. 2018; Abrams et al. plant’s drinking water source at the time.
2018a). In all cases, there was little constraint on K h , Water levels and withdrawal rates were recorded daily
which was determined through the regional calibration at the production wells during the 37-day test. Overall
process. drawdowns at the production wells ranged from 68 to
Understanding the influence of the fault zone on 95 m (Table 1, Figure 2B). Observations of recovery were
regional and local groundwater flow has important also recorded for 25 days at each of the production wells
implications for long-term water availability in the CO and at JA-5. Several wells, notably JA-6 and JA-9, had
system. The St. Peter and Ironton-Galesville sandstones pumping events during the recovery phase (Figure 2B).
are heavily utilized in Kane, Will, and Kendall Counties Drawdown was also recorded at sandstone wells in the
which has led to partial and complete desaturation of towns of Wilmington (9 km to the south), Minooka
the St. Peter sandstone in some areas, prompting drillers (12 km to the northwest), and at Braidwood (15 km to the
to install wells only open to the underlying Ironton- southwest) (Figure 1B). Two of these far-field wells were
Galesville sandstone (Abrams et al. 2015; Mannix et al. multiaquifer sandstone wells and two were only open to
2018). This has led to increased head separation between the St. Peter (Table 1).

NGWA.org D.R. Hadley et al. Groundwater 58, no. 3: 453–463 455


Table 1
List of Wells, Well Parameters, and Drawdown Associated with the Arsenal Test

Observed Drawdown Skin Factor


Well Name Well Depth (m) Open Interval Well Type at End of Test (m) Adjustment

JA-1 487 SP-IG PW 74 4


JA-2 491 SP-IG PW 83 7.5
JA-3 486 SP-IG PW 81 4.5
JA-4 471 SP-IG PW 89 7
JA-5 285 SP OW 31 -
JA-6 504 SP-IG PW 68 −2.5
JA-7 504 SP-IG PW 77 −1
JA-8 496 SP-IG PW 83 7
JA-9 489 SP-IG PW 95 8
JA-10 479 SP-IG PW 82 6.5
Wilmington 1 216 SP OW 6.7 -
Wilmington 2 477 SP-IG OW 6.1 -
Minooka 2 189 SP OW 1.2 -
Braidwood 1 502 SP-IG OW 0.8 -

JA, Joliet Arsenal; SP, St. Peter; IG-Ironton-Galesville; PW, Pumping Well; OW, Observation Well

Figure 2. (A) Withdrawals from production wells during the Arsenal Test. Note that several wells turned off during the test,
most notably JA-1 and JA-2. Small withdrawals during the recovery phase (after day 37) were not recorded. The withdrawal
rate for JA-8 during the recovery phase was estimated. (B) Recorded heads at the production wells and nearby observation
well (JA-5). Note the small pumping events during the recovery phase.

Modeling Methods and extends into southern Wisconsin, eastern Iowa, and
western Indiana. For a complete description of model
Illinois Groundwater Flow Model parameters, boundary conditions, and hydrostratigraphic
We used a transient 21-layer MODFLOW model units, see Abrams et al. (2018a).
of the CO aquifer system already developed for long- The St. Peter and Ironton-Galesville sandstones are
term water supply planning purposes as a base model to represented in the regional model with a K h of 1.5 m/day
simulate the Arsenal Test. This regional model (known and a vertical hydraulic conductivity (K v ) of 0.18 m/day.
as the Illinois Groundwater Flow Model) consists of 12 Multiaquifer wells throughout the model domain are
bedrock layers and 9 unconsolidated layers on a 762 m simulated with high K v zones in the aquitards that separate
grid and simulates annual stress periods from 1863- the sandstone units (following Mandle and Kontis 1992)
present, as well as the impacts of future demands. The and utilize the Time Variant Materials package available
regional model covers the northern two-thirds of Illinois in Groundwater Vistas 6.0 (Rumbaugh and Rumbaugh

456 D.R. Hadley et al. Groundwater 58, no. 3: 453–463 NGWA.org


2010) to simulate the correct timing of aquifer connections
historically (Mannix et al. 2018). The regional model
is calibrated to modern pumping conditions (post-1963)
because there are limited pumping and water level records
prior to that. Calibrating to modern pumping conditions,
however, introduces two complications: (1) open intervals
of wells have changed through time (Mannix et al. 2018),
and (2) sandstone units are actively being dewatered.
Simulating the Arsenal Test within the regional model
removes these two degrees of freedom since almost all
production wells within the study area at the time of the
test were open to all CO units and the JA wells remained
fully saturated (no specific yield) during the test, allowing
us to build greater confidence in the model results near
the fault zone.

Arsenal Test Simulation


The Arsenal Test was simulated in the Illinois
Groundwater Flow Model using MODFLOW-USG (Pan-
day et al. 2013). To accommodate the Arsenal Test, we
inserted additional daily stress periods for the year 1942, Figure 3. Model grid of the study area (762 m grid)
reduced the K v of the Maquoketa Shale by two orders showing the K h zonation of the fault zone (fault core and
of magnitude where it is exposed at the bedrock surface damage zone) and locations of CLN wells (observation and
(Figure 1A) to better reflect historic (pre-1963) conditions production).
that had considerably less aquifer connections via mul-
tiaquifer wells, and then modified fault zone properties.
Given the large width of the fault zone (up to 3.2 km) respectively. A Ss of 1.7 × 10−7 m−1 was determined to
and the unknown geometry of individual faults that com- be the most consistent with observed drawdowns, which
prise the zone, we conceptualized the fault zone within the is higher than a Ss of 7.9 × 10−8 m−1 used previously
St. Peter and Ironton-Galesville sandstones as an inner 1- by Roadcap et al. (2013) and Abrams et al. (2018a),
cell wide fault core surrounded by a 1-cell wide damage but falls at the upper end of Ss ranges used in previous
zone (Figure 3). This is based on low specific capacities regional models of the CO system (Mandle and Kontis
of sandstone wells near the fault (Abrams et al. 2018a) 1992; Meyer et al. 2009; Feinstein et al. 2010).
and the physical properties of faults observed elsewhere All model runs used the Sparse Matrix Solver
(Caine et al. 1996; Shipton and Cowie 2001; Kim et al. Package with the XMD linear solver and Newton-
2004; Caine and Minor 2009; Ball et al. 2010). We tested Raphson nonlinear solver (Niswonger et al. 2011) and
various conceptualizations of the fault zone by varying achieved convergence with a head change criterion for
K h of the damage zone and fault core but only present inner and outer iterations of 1 × 10−5 and 1 × 10−3 m,
results for three scenarios: (1) an unrestricted flow sce- respectively.
nario in which the fault zone is identical to the host
rock, (2) a restricted flow scenario in which the K h of Arsenal Test Calibration
the damage zone is reduced by half and the K h of the We calibrated to daily drawdown values at the
fault core is reduced by an order of magnitude, and (3) wells instead of head, since all of the JA production
a highly-restricted flow scenario in which the K h of the wells remained under confined conditions throughout the
damage zone and fault core are reduced by two orders test, and hence never switched between Ss and specific
of magnitude (Table 2). Varying horizontal and vertical yield conditions. Calibrating to heads would also have
conductivities within the fault zone for other units in the required extensive review of historic withdrawals in the
model was beyond the scope of this study. model. We simulated the production and observation wells
The original regional model is insensitive to changes transiently using the connected linear network (CLN)
in specific storage (Ss). Consequently, we initially package (Panday et al. 2013) (instead of using a high K v
analyzed the Arsenal Test with a Theis solution to ensure zone and the TVM package) to calibrate to drawdown
a reasonable Ss for the sandstones within the study area values at the well as opposed to values in the cell
using: (1) an average pumping rate of 34,500 m3 /day (Figure 3). The JA production wells enter the model
(calculated by averaging all of the withdrawals over the when they were drilled to ensure that the aquifers were
37-day test), (2) a sandstone K h of 1.5 m/day (consistent not connected via the boreholes for the entire history
with Roadcap et al. 2013; Abrams et al. 2018a, 2018b), of the model run. We also adjusted skin factors within
(3) an overall aquifer thickness of 120 m (60 m for each the CLN package (Konikow et al. 2009) to account for
sandstone unit), and (4) observed drawdowns at the head losses within the boreholes of the JA production
Wilmington and Braidwood wells of 6.5 and 0.8 m, wells and only used drawdown observations at the nine

NGWA.org D.R. Hadley et al. Groundwater 58, no. 3: 453–463 457


Table 2
Fault Zone Parameters of the Tested Scenarios

K h Host K h Damage K h Fault


Scenario Fault Zone Conceptualization Rock (m/day) Zone (m/day) Core (m/day)

Unrestricted flow Fault zone same as host rock 1.5 1.5 1.5
Restricted flow Damage zone K h reduced by 1.5 0.76 0.15
half, fault core K h reduced by
order of magnitude
Highly-restricted flow Damage zone and fault core K h 1.5 0.015 0.015
reduced by two orders of
magnitude

production wells on days with either 24 h of pumping and 4B), but had less of an effect at JA wells 1 to 4 and
or 24 h of no pumping. We also used drawdowns at 6 (Figure 4C, 4D, and 4E). JA-10 achieved the best cal-
surrounding municipal wells observed at the end of the test ibration in the restricted flow scenario with a root mean
as calibration targets. Observed drawdown curves were square error (RMSE) of 1.5 m and a regression line slope
compared to our simulated drawdown curves using linear of 0.93 (Figure 5E), whereas in the unrestricted or highly-
regression and by comparing the slopes of the regression restricted flow scenarios there was either not enough or too
lines. much simulated drawdown (Figure 4A) resulting in larger
Recovery observations were recorded graphically at RMSEs and deviations of the regression line (Figure 5D
the time of the test (Figure 2B), but withdrawal rates and 5F). The differences between simulated drawdowns
were not recorded when individual wells turned on and for each of the three scenarios becomes progressively less
off during the recovery phase. Given the unknown rates as the distance between the production wells and the fault
of withdrawals and the short duration of these pumping zone increases (compare hydrographs for JA wells 10 and
events (many of which were less than 12 h), we did 9 versus JA wells 4 and 2 in Figure 4). The far-field
not use these recovery observations as calibration targets. municipal wells were largely unaffected by whether the
Because withdrawal rates were not recorded for JA-8, but fault zone was represented as a flow barrier or not. In all
was noted as always pumping, we calculated the average three scenarios, the mean residual of simulated drawdown
withdrawal rate of JA-8 during the test and applied that for the far-field municipal wells was ≤0.3 m (Table 3).
to the recovery phase (Figure 2A). Skin factors (in addition to fault zone modifications)
were needed to achieve calibration at the JA production
wells and ranged from −2.5 to 8 (Table 1). The negative
Arsenal Test Observations and Model Results skin factor for JA-6 indicates that the well bore skin
The cone of depression formed by the Arsenal Test has a higher K h than the surrounding formation, whereas
reached a peak drawdown of over 90 m at its center positive skin factors indicate that well bore skins have
and extended outward at a distance of greater than lower K h values than the surrounding formation. A
20 km (Video S1). Review of heads, drawdown, and negative skin factor is unsurprising, given that some
recovery observations recorded during and after the test of the JA production wells (including JA-6) were
indicates that the fault zone inhibits horizontal flow in the blasted with nitroglycerine to increase fracturing in the
sandstone units. This is supported by observations that: Ironton Galesville. Skin factor adjustments resulted in
(1) drawdowns at both JA-9 and JA-10 were the same a decrease or increase in the magnitude of simulated
magnitude (or greater) in comparison to drawdown at JA drawdown but did not result in changing the shape
wells 6 to 8 (Table 2) despite lower withdrawals rates of the simulated drawdown curves (Figure S1), whereas
occurring at JA-9 and JA-10 compared to JA wells 6 to changing fault zone parameters did affect the shape
8 (Figure 2A), (2) JA-9 and JA-10 had slower recoveries of the drawdown curves at wells closes to the fault
in comparison to JA-6 and JA-7 while JA-8 continued (Figure 4A and 4B).
to pump during the recovery phase (Figure 2B), and (3) The restricted flow scenario achieved the best overall
in general, recovery occurred more quickly at the wells calibration with an RMSE of 3.37 m and a slope of
further away from the fault zone (JA wells 1-4) compared the regression line nearest to 1 in comparison to the
to the wells closer to the fault zone (JA wells 6-10) other scenarios (Figure 5B). Overall calibration results
(Figure 2B). Full recovery did not occur at the JA wells did not vary greatly between each of the three scenarios,
after 25 days and drawdown continued to occur north of however, due to the limited influence of the fault zone
the fault zone even after this period (Video S1). on drawdowns in the far-field municipal wells and the JA
Modifying the properties of the fault zone signifi- production wells located further away from the fault zone.
cantly affected calibration at production wells closest to While all nine JA wells were very productive at the
the fault zone, most notably at JA-10 and JA-9 (Figure 4A time of drilling, JA-5 (the dedicated St. Peter monitoring

458 D.R. Hadley et al. Groundwater 58, no. 3: 453–463 NGWA.org


Figure 4. Hydrographs of observed and simulated drawdown for select wells used in the Arsenal Test. Note the different
drawdown scale on JA-5.

well) was the exception. JA-5 was tested prior to the along the fault zone in Ogle County, lends geologic
start of the Arsenal Test and determined to have a very evidence to a reduced permeability within the fault zone.
low specific capacity, and there was also a very subdued Our modeling efforts determined an “effective”
recovery curve at JA-5 following the end of the test hydraulic conductivity (Bense et al. 2013) for the fault
(Figure 2B). Both the pump test and recovery curve zone in Will County, but the specific mechanisms that
suggest the St. Peter is not as transmissive around JA-5 cause reduced flow across the fault zone are unknown.
in comparison to the other production wells or that there Mechanisms could include: (1) the presence of gouge
was an issue with the well such as formation collapse. In within a fault core or series of fault cores (Rawling
all three scenarios, the largest systematic error occurred at et al. 2001; Shipton and Cowie 2001; Caine and Minor
JA-5 (Figure 4F), likely because this local zone of reduced 2009), (2) dissolution and cementation within the core
permeability was not incorporated into the three model or damage zone fracture networks (Eichhubl et al. 2009),
scenarios. We thus left out the results of JA-5 in our or (3) cataclasis in broad deformation bands bounded by
regression analyses. slip planes (Antonellini and Aydin 1994; Shipton et al.
2002; Fossen et al. 2007; Medeiros et al. 2010). Overall
throw along the fault zone is well defined, but there
Discussion and Implications for Groundwater may be many more upthrown and downthrown blocks
Supply within the fault zone than currently mapped, resulting in
Results of our model comparisons support previous complex structural geometries. A geophysical approach
observations (Abrams et al. 2015, 2018a) and modeling could determine some of these specific mechanisms and
efforts (Roadcap et al. 2013) that there is reduced fault structural controls (e.g., Ball et al. 2010). Clay smearing
zone permeability within the St. Peter and Ironton- (Bense and Person 2006; Egholm et al. 2008) could also
Galesville sandstones which limits groundwater flow have a significant influence on groundwater flow in the
across the fault zone. Decreasing the K h of the fault core central portion of the fault zone (Dekalb County) since
by an order of magnitude and the K h of the damage zone there is enough offset to drag the Maquoketa and Eau
by half achieved the best calibration at wells closest to Claire shales to meet the sandstone units.
the fault zone and overall. Sections of brecciated quartzite We analyzed how incorporating the restricted flow
within the St. Peter, observed by the authors at outcrops fault zone conceptualization into the Illinois Groundwater

NGWA.org D.R. Hadley et al. Groundwater 58, no. 3: 453–463 459


Figure 5. Simulated vs. observed daily drawdown values for all production wells (top row) and only JA-10 (bottom row) for
the Arsenal Test. Gray line indicates 1:1 line.

Table 3 mean error, absolute mean error, and RMSE of head


Results of Simulated vs. Observed Drawdown targets in both sandstone units for both 1980 and 2014
Values at the End of the Test for Far-Field (Table 4). We then incorporated our updated Ss and
Municipal Observation Wells Maquoketa Shale K v values (in addition to updating the
fault zone). This changed calibration results only slightly
Simulated Overall (Table 4), indicating that fault zone modifications are
Drawdown (m) more important for CO sandstone calibration within the
Observed cone of depression.
Overall A reduced hydraulic conductivity in the fault zone
Drawdown Un- Highly means less recharge available from southern Will and
(m) restricted Restricted Restricted
Kendall counties to satisfy demands north of the fault
Wilmington 1 6.7 4.9 5.2 5.5 zone. Municipal wells north of the fault zone within
Wilmington 2 6.1 5.2 5.5 5.9 the current cone of depression are at risk of partially
Minooka 2 1.2 2.8 2.6 2.7 desaturating the Ironton-Galesville by 2040 (Mannix et al.
Braidwood 1 0.8 0.9 1.0 1.0 2017). Given the findings in this study, coupled with
Mean Residual 0.3 0.1 −0.1 newly estimated water use demands for the region, this
time frame is likely less. This shortened time frame is
exacerbated by the expectation that new demands will be
Flow Model affects calibration to post-1963 heads in met by wells near or within the fault zone. The properties
the CO sandstones. We compared head targets for the of the fault zone in this multiaquifer sandstone system
years 1980 and 2014 (see Abrams et al. 2015 for a have implications for other areas in similar geologic
description of these measurements) in a zone centered settings if groundwater use occurs near faults and flow
on the modern day cone of depression (Figure 1A) barriers are reached. The flow-barrier behavior of the
that includes the heavy municipal users northeast of Sandwich Fault Zone may also mean a slower recovery
the fault zone and the heavy industrial users south of (e.g., see Marshall et al. 2019) of the CO system if
the fault zone in Will County. Incorporating only the communities are eventually forced to switch to Lake
restricted flow fault zone conceptualization improved Michigan water as groundwater is depleted.

460 D.R. Hadley et al. Groundwater 58, no. 3: 453–463 NGWA.org


Table 4
Calibration Results from the Illinois Groundwater Flow Model for Cambrian-Ordovician Sandstone Water
Levels in 1980 and 2014 (Years of Mass Measurements) Within the Cone of Depression in Will and Kendall
Counties

1980 2014
OFZ RFZ RFZ + Ss OFZ RFZ RFZ + Ss

Ironton Galesville1
Mean error (m) −3.85 0.87 −0.14 −8.36 3.09 −0.92
Absolute mean error (m) 13.12 11.69 12.51 16.29 12.30 13.23
RMSE (m) 17.69 15.36 15.73 19.74 14.96 15.81
St. Peter2
Mean error (m) −8.87 −8.31 −8.35 −23.64 −22.19 −19.93
Absolute mean error (m) 20.54 17.21 18.62 27.50 24.80 24.55
RMSE (m) 24.26 21.19 22.67 31.98 28.76 28.56

OFZ, original fault zone conceptualization; RFZ, restricted flow fault zone conceptualization; RFZ + Ss, restricted flow fault zone conceptualization plus updated Ss
and Maquoketa Shale K v values.
1 n = 62 for 1980, n = 42 for 2014.
2 n = 47 for 1980, n = 16 for 2014.

Conclusions Production wells further from the fault zone, and the
We used a numerical modeling approach to simulate far-field observation wells, were less affected by modi-
a large-scale historic aquifer test that occurred adjacent to fying fault zone properties.
a poorly understood near-vertical fault zone system. The We then analyzed how the restricted flow fault
fault zone system is structurally complex with variable zone conceptualization affects calibration to heads in
the CO sandstone system post-1963, when there is
offset and numerous fault traces bounding upthrown and
considerably more uncertainty in the system because of
downthrown blocks. Observations of head offset and low
multiaquifer wells and desaturated conditions. Updating
specific capacities near the fault zone indicate that the fault
the Illinois Groundwater Flow Model with the restricted
zone is an important structural control on groundwater
flow scenario significantly improved calibration to
movement in the CO sandstone aquifer system.
CO sandstone water levels for years in which mass
The magnitude of groundwater withdrawals and the
measurement of sandstone water levels took place (1980
duration of the Arsenal Test allowed insight into the and 2014). The flow-barrier behavior of the fault zone
hydraulic properties for a large area of the fault zone has important implications for groundwater availability
(>20 km) at a considerable depth (>450 m) for a confined in the highly stressed CO sandstone aquifer system.
multiaquifer sandstone system. We conceptualized the Communities near the fault zone continue to rely on the
fault zone in the sandstone units as a low-permeable fault deep sandstone system despite increasing drawdown, and
core surrounded by a damage zone based on previous are expected to increase withdrawals before alternative
research of deformation bands in faulted sandstones. The supplies can be utilized. Projected desaturation of the
K h of the fault core and damage zone were modified until Ironton-Galesville sandstone may occur sooner than the
the magnitude and shape of the simulated drawdown previously estimated year of 2040 given our updated
curves matched observed records at the production fault zone conceptualization, and many wells could face
wells and at surrounding observation wells. We presented serious issues under pumping conditions by 2030. Results
results from three scenarios: an unrestricted flow scenario, from this study may inform the hydraulic properties of
a restricted flow scenario, and a highly-restricted flow other faulted sandstone aquifers in confined settings and
scenario. help in long-term groundwater management.
Our study determined an effective hydraulic conduc-
tivity for the fault zone and indicates that there is at least
Acknowledgments
an order of magnitude reduction in K h of the fault core
compared to the undeformed sandstones. We achieved This project was funded in part by the Illinois
Department of Natural Resources under the purview of
the best calibration to drawdown levels (overall and at
water supply planning. We thank Chris Langevin, John
wells closest to the fault) under the restricted flow sce-
Quinn, and an anonymous reviewer for their positive and
nario, in which the K h of the undeformed sandstones,
helpful comments that improved this manuscript.
damage zone, and fault core were set to 1.5, 0.76, and
0.15 m/day, respectively. The unrestricted flow scenario
and the highly-restricted flow scenario either allowed too Authors’ Note
much or too little flow across the fault zone to achieve The authors do not have any conflicts of interest or
calibration at the production wells closest to the fault. financial disclosures to report.

NGWA.org D.R. Hadley et al. Groundwater 58, no. 3: 453–463 461


Supporting Information Caine, J.S., and S.A. Minor. 2009. Structural and geochemical
characteristics of faulted sediments and inferences on the
Additional supporting information may be found online role of water in deformation, Rio Grande Rift, New Mexico.
in the Supporting Information section at the end of Geological Society of America Bulletin 121, no. 9–10:
the article. Supporting Information is generally not peer 1325–1340. https://doi.org/10.1130/b26164.1
reviewed. Caine, J.S., J.P. Evans, and C.B. Forster. 1996. Fault zone
architecture and permeability structure. Geology 24,
Figure S1 Plot of simulated drawdown at JA-10 under no. 11: 1025–1028. https://doi.org/10.1130/0091-7613
the restricted flow scenario using different skin factors (1996)024<1025:Fzaaps>2.3.Co;2
Egholm, D.L., O.R. Clausen, M. Sandiford, M.B. Kristensen,
for calibration. Note that skin factor adjustments change
and J.A. Korstgard. 2008. The mechanics of clay smearing
the magnitude of drawdown but not the shape of the along faults. Geology 36, no. 10: 787–790. https://doi.org/
drawdown curve. 10.1130/G24975a.1
Video S1 Animation of drawdown and subsequent Eichhubl, P., N.C. Davatzes, and S.P. Becker. 2009. Structural
recovery in the St. Peter sandstone during the Arsenal and diagenetic control of fluid migration and cementation
along the Moab fault, Utah. AAPG Bulletin 93, no. 5:
Test using the restricted flow fault zone conceptualization. 653–681. https://doi.org/10.1306/02180908080
Note that drawdown values are cell values. Actual Faulkner, D.R., C.A.L. Jackson, R.J. Lunn, R.W. Schlische, Z.K.
drawdown at the wells were much greater during the test. Shipton, C.A.J. Wibberley, and M.O. Withjack. 2010. A
review of recent developments concerning the structure,
mechanics and fluid flow properties of fault zones. Journal
References of Structural Geology 32, no. 11: 1557–1575. https://doi
.org/10.1016/j.jsg.2010.06.009
Abrams, D.B., D.H. Mannix, D.R. Hadley, and G.S. Roadcap. Feinstein, D.T., R.J. Hunt, and H.W. Reeves. 2010. Regional
2018a. Groundwater flow models of Illinois: Data, pro- groundwater-flow model of the Lake Michigan Basin in
cesses, model performance, and key results. Illinois State support of Great Lakes Basin water availability and use
Water Survey Contract Report 2019-04. Champaign, Illi- studies. U.S. Geological Survey Scientific Investigations
nois. Report 2010–5109. Reston, Virginia: USGS.
Abrams, D.B., G.S. Roadcap, and D.H. Mannix. 2018b. Fossen, H., R.A. Schultz, Z.K. Shipton, and K. Mair. 2007.
Developing potentiometric surfaces and flow fields with a Deformation bands in sandstone: A review. Journal of the
head-specified MODFLOW model. Groundwater 56, no. 1: Geological Society 164, no. 4: 755–769. https://doi.org/10
8–17. https://doi.org/10.1111/gwat.12540 .1144/0016-76492006-036
Abrams, D.B., D.R. Hadley, D.H. Mannix, G. Roadcap, S.C. Jourde, H., E.A. Flodin, A. Aydin, L.J. Durlofsky, and X.H.
Meyer, K.J. Hlinka, K.L. Rennels, K.R. Bradbury, P.M. Wen. 2002. Computing permeability of fault zones in eolian
Chase, and J.J. Krause. 2015. Changing groundwater levels sandstone from outcrop measurements. AAPG Bulletin 86,
in the sandstone aquifers of northern Illinois and southern no. 7: 1187–1200.
Wisconsin: Impacts on available water supply. Illinois Kim, Y.-S., D.C.P. Peacock, and D.J. Sanderson. 2004. Fault
State Water Survey Contract Report 2015–02. Champaign, damage zones. Journal of Structural Geology 26, no. 3:
Illinois. 503–517. https://doi.org/10.1016/j.jsg.2003.08.002
Antonellini, M., and A. Aydin. 1994. Effect of faulting on Kolata, D.R., T.C. Buschbach, and J.D. Treworgy. 1978. The
fluid-flow in porous sandstones—Petrophysical properties. Sandwich Fault Zone of Northern Illinois. Illinois State
AAPG Bulletin 78, no. 3: 355–377. Geological Survey Circular 505. Urbana, Illinois.
Ball, L.B., S. Ge, J.S. Caine, A. Revil, and A. Jardani. Konikow, L.F., G.Z. Hornberger, K.J. Halford, and R.T. Hanson.
2010. Constraining fault-zone hydrogeology through inte- 2009. Revised Multi-Node Well (MNW2) package for
grated hydrological and geoelectrical analysis. Hydrogeol- MODFLOW ground-water flow model. U.S. Geological
ogy Journal 18, no. 5: 1057–1067. https://doi.org/10.1007/ Survey Techniques and Methods 6-A30. Reston, Virginia:
s10040-010-0587-z USGS.
Bense, V.F., T. Gleeson, S.E. Loveless, O. Bour, and J. Scibek. Mandle, R.J., and A.L. Kontis. 1992. Simulation of regional
2013. Fault zone hydrogeology. Earth-Science Reviews ground-water flow in the Cambrian-Ordovician aquifer
127: 171–192. https://doi.org/10.1016/j.earscirev.2013.09 system in the Northern Midwest, United States. U.S.
.008 Geological Survey Professional Paper 1405-C. Reston,
Bense, V.F., M.A. Person, K. Chaudhary, Y. You, N. Cremer, Virginia: USGS.
and S. Simon. 2008. Thermal anomalies indicate pref- Mannix, D.H., D.B. Abrams, D.R. Hadley, and G.S. Roadcap.
erential flow along faults in unconsolidated sedimentary 2018. Conceptualizing leakage and storage contributions
aquifers. Geophysical Research Letters 35, no. 24: L24406. from long open interval wells in regional deep basin flow
https://doi.org/10.1029/2008GL036017 models. Hydrological Processes 33, no. 2: 271–282. https://
Bense, V.F., and M.A. Person. 2006. Faults as conduit-barrier doi.org/10.1002/hyp.13324
systems to fluid flow in siliciclastic sedimentary aquifers. Mannix, D.H., D.B. Abrams, G.S. Roadcap, D.R. Hadley, and
Water Resources Research 42, no. 5. https://doi.org/10 W.R. Kelly. 2017. Groundwater Depletion in Chicago’s
.1029/2005WR004480 Southwestern Suburbs. Champaign, Illinois: University of
Bense, V., and R. van Balen. 2003. Hydrogeological aspects Illinois at Urbana-Champaign.
of fault zones on various scales in the Roer Valley Marler, J., and S. Ge. 2003. The permeability of the Elkhorn
Rift System. Journal of Geochemical Exploration 78-79: Fault Zone, South Park, Colorado. Ground Water 41,
317–320. https://doi.org/10.1016/S0375-6742(03)00031-1 no. 3: 321–332. https://doi.org/10.1111/j.1745-6584.2003
Bredehoeft, J.D., K. Belitz, and S. Sharp-Hansen. 1992. The .tb02601.x
hydrodynamics of the Big Horn Basin; a study of the role Marshak, S., W.J. Nelson, and J.H. McBride. 2003. Phanerozoic
of faults. AAPG Bulletin 76, no. 4: 530–546. strike-slip faulting in the continental interior platform of
Burbey, T.J. 2008. The influence of geologic structures on the United States: Examples from the Laramide Orogen,
deformation due to ground water withdrawal. Ground Water Midcontinent, and Ancestral Rocky Mountains. Geological
46, no. 2: 202–211. https://doi.org/10.1111/j.1745-6584 Society, London, Special Publications 210, no. 1: 159–184.
.2007.00395.x https://doi.org/10.1144/gsl.sp.2003.210.01.10

462 D.R. Hadley et al. Groundwater 58, no. 3: 453–463 NGWA.org


Marshall, S.K., P.G. Cook, A.D. Miller, C.T. Simmons, and Panday, S., C.D. Langevin, R.G. Niswonger, M. Ibaraki, and J.D.
S. Dogramaci. 2019. The effect of undetected barriers Hughes. 2013. MODFLOW–USG version 1: An unstruc-
on groundwater drawdown and recovery. Groundwater. tured grid version of MODFLOW for simulating ground-
https://doi.org/10.1111/gwat.12856 water flow and tightly coupled processes using a control
Mayer, A., W. May, C. Lukkarila, and J. Diehl. 2007. Estimation volume finite difference formulation. U.S. Geological Sur-
of fault-zone conductance by calibration of a regional vey Techniques and Methods 6-A45. Reston, Virginia.
groundwater flow model: Desert Hot Springs, California. Rawling, G.C., L.B. Goodwin, and J.L. Wilson. 2001. Inter-
Hydrogeology Journal 15, no. 6: 1093–1106. https://doi nal architecture, permeability structure, and hydrologic
.org/10.1007/s10040-007-0158-0 significance of contrasting fault-zone types. Geology
Medeiros, W.E., A.F. do Nascimento, F.C.A. da Silva, N. Destro, 29, no. 1: 43–46. https://doi.org/10.1130/0091-7613(2001)
and J.G.A. Demétrio. 2010. Evidence of hydraulic connec- 029<0043:Iapsah>2.0.Co;2
tivity across deformation bands from field pumping tests: Roadcap, G.S., S.C. Meyer, W.R. Kelly, H.A. Wehrmann, and
Two examples from Tucano Basin, NE Brazil. Journal of Y.F. Lin. 2013. Groundwater studies for water supply
Structural Geology 32, no. 11: 1783–1791. https://doi.org/ planning in Kendall County, Illinois. Illinois State Water
10.1016/j.jsg.2009.08.019 Survey Contract Report 2013–05. Champaign, Illinois.
Meyer, S.C., G.S. Roadcap, Y.F. Lin, and D.D. Walker. 2009. Roques, C., O. Bour, L. Aquilina, B. Dewandel, S. Leray,
Kane County water resources investigations: Simulation of J.M. Schroetter, L. Longuevergne, T. Le Borgne,
groundwater flow in Kane County and northeastern Illinois. R. Hochreutener, T. Labasque, N. Lavenant, V. Vergnaud-
Illinois State Water Survey Contract Report 2009–07. Ayraud, and B. Mougin. 2014. Hydrological behavior
Champaign, Illinois. of a deep sub-vertical fault in crystalline basement and
Minor, S.A., and M.R. Hudson. 2006. Regional survey of struc- relationships with surrounding reservoirs. Journal of
tural properties and cementation patterns of fault zones Hydrology 509: 42–54. https://doi.org/10.1016/j.jhydrol
in the northern part of the Albuquerque Basin, New .2013.11.023
Mexico—Implications for ground-water flow. U.S. Geo- Rumbaugh, J.O., and D.B. Rumbaugh. 2010. Groundwater Vistas
logical Survey Professional Paper 1719. Reston, Virginia: 6.0 . Reinholds, Pennsylvania: Environmental Simulations
USGS. Inc.
Nelson, J.W. 1995. Stuctural features in Illinois. Illinois State Shipton, Z.K., J.P. Evans, K.R. Robeson, C.B. Forster, and
Geological Survey Bulletin 100. Champaign, Illinois. S. Snelgrove. 2002. Structural heterogeneity and perme-
Nieto Camargo, J.E., and J.L. Jensen. 2012. Analysis of fault ability in faulted eolian sandstone: Implications for sub-
permeability using mapping and flow modeling, Hickory surface modeling of faults. AAPG Bulletin 86, no. 5:
Sandstone Aquifer, Central Texas. Natural Resources 863–883. https://doi.org/10.1306/61EEDBC0-173E-11D7-
Research 21, no. 3: 395–409. https://doi.org/10.1007/ 8645000102C1865D
s11053-012-9181-5 Shipton, Z.K., and P.A. Cowie. 2001. Damage zone and
Niswonger, R.G., S. Panday, and M. Ibaraki. 2011. MODFLOW- slip-surface evolution over μm to km scales in high-
NWT, A newton formulation for MODFLOW-2005. U.S. porosity Navajo sandstone, Utah. Journal of Structural
Geological Survey Techniques and Methods 6-A37. Reston, Geology 23, no. 12: 1825–1844. https://doi.org/10.1016/
Virginia: USGS. S0191-8141(01)00035-9

NGWA.org D.R. Hadley et al. Groundwater 58, no. 3: 453–463 463

You might also like