InteliLite NT ®

Operator Guide
Operator Interface AMF9

G EN-SET CONTROL BUTTONS


POSITION BUTTON DESCRIPTION

START button. Works in MAN mode only. Press this button to initiate the
1
start sequence of the engine.

STOP button. Works in MAN mode only. Press this button to initiate the stop
sequence of the gen-set. Repeated pressing or holding the button for more
2
than 2s will cancel current phase of stop sequence (like ramping the power
down or cooling) and next phase will continue.
FAULT RESET button. Use this button to acknowledge alarms and
deactivate the horn output. Inactive alarms will disappear immediately and
3
status of active alarms will be changed to "confirmed" so they will disappear
as soon as their reasons dismiss.

HORN RESET button. Use this button to deactivate the horn output without
4
acknowledging the alarms.

MODE LEFT button. Use this button to change the mode. The button works
only if the main screen with the indicator of currently selected mode is
displayed.
5
NOTE:
This button will not work if the controller mode is forced by one of binary
inputs Remote OFF, Remote MAN, Remote AUT, Remote TEST.

IL-NT Operator Guide


©ComAp 2
MODE RIGHT button. Use this button to change the mode. The button works
only if the main screen with the indicator of currently selected mode is
displayed.
6
NOTE:
This button will not work if the controller mode is forced by one of binary
inputs Remote OFF, Remote MAN, Remote AUT, Remote TEST.
GCB button. Works in MAN mode only. Press this button to open or close
7 the GCB manually. Note that certain conditions must be valid otherwise GCB
closing is blocked.
MCB button. Works in MAN mode only. Press this button to open or close
the MCB manually.
8 CAUTION!
You can disconnect the load from the mains supply with this button! Be sure
you know well what you are about to do!

GEN-SET OPERATION INDICATORS


POSITION INDICATOR DESCRIPTION
Gen-set failure. Red LED starts flashing when gen-set failure occurs. After FAULT
9 RESET button is pressed, goes to steady light (if an alarm is still active) or is off (if no
alarm is active).
Gen-set voltage OK. Green LED is on if the generator voltage is present and within
limits.
10 NOTE:
The limits for the generator voltage and frequency are given by setpoints in the Gener
Protect group.
GCB ON. Green LED is on, if GCB is closed. It is driven by GCB CLOSE/OPEN
11
output (AMF 8/9) or by GCB feedback signal (AMF 20/25).
MCB ON. Green LED is on, if MCB is closed. It is driven by MCB CLOSE/OPEN
12
output (AMF 8/9) or by MCB feedback signal (AMF 20/25).
13 Mains voltage OK. Green LED is on, if mains is present and within limits.
EN
Mains failure. Red LED starts blinking when the mains failure is detected and after
14 the gen-set has started and connected to the load it lights permanently until the mains
failure disappears.

DISPLAY AND CONTROL BUTTONS


POSITION BUTTON DESCRIPTION
15 Graphic B/W display, 128x64 pixels

PAGE button. Use this button to switch over display pages. See Display
16
Screens and Pages Structure chapter below this table for more details.

17 UP button. Use this button to move up or increase a value.

18 DOWN button. Use this button to move down or decrease a value.

ENTER button. Use this button to finish editing a setpoint or moving right in
19
the history page.

IL-NT Operator Guide


©ComAp 3
Display Screens and Pages Structure
The displayed information is structured into "pages" and "screens". Use PAGE button to switch over
the pages.

1. The page Measurement consists of screens which display measured values like voltages,
current, oil pressure etc., computed values like i.e. gen-set power, statistic data and the alarm
list on the last screen.
2. The page Setpoints contains all setpoints organized to groups and also a special group for
entering password.
3. The page History log shows the history log in the order that the last record is displayed first.

Measurement Setpoints History log


OFF MAN AUT TEST ! Password No. Reason
>Basic Settings > 0 Switched On
Not ready Engine Params -1 Fault reset
MainsFlt Page Engine Protect Page -2 Emergency Stop
PF 0.00 Page
Gener Protect -3 Wrn RA15 Fail
RPM 0 AutoMains Fail -4 Sprinkler Set
No Timer Extension I/O -5 Config Loaded
0 kW 0 Date/Time 13:02:17 07/08/2008
Enter Page Enter

Generator Gen-set Name Time Date


L1N 0 L1L2 0V >13:02:17 07/08/2008
L1N 0 L1L2 0V >Nominal Power 13:00:46 07/08/2008
L1N 0 L1L2 0V Page 200 kW 13:00:46 07/08/2008
Page
Gen freq 0.0Hz Nomin Current 13:00:45 07/08/2008
350 A 13:00:45 07/08/2008
0 0 0 A CT Ratio 13:00:43 07/08/2008
2000 /5A 0 Switched On

Enter Enter Page Enter

ECU AlarmList Gen-set Name Mode RPM Pwr


>EngOil Press > OFF 0 0
000225 (000E1h) >Nominal Power OFF 0 0
250 200 kW OFF 0 0
Page Page
Nomin Current OFF 0 0
350 A OFF 0 0
CT Ratio OFF 0 0
FC 100 OC 4 FMI 1 2000 /5A 0 Switched On

Enter

AlarmList 1
Emergency Stop

Page

NOTE:
History and Setpoints pages are available only when you choose Engineer interface (not User). See
Controller Information Screen subchapter below.

History Log is not supported in InteliLite MRS 3, 4, 10, 11 and AMF 8, 9, 20.

IL-NT Operator Guide


©ComAp 4
Alarms

AlarmList 3
*MCB Fail Inactive unconfirmed alarm
*Emergency Stop Active unconfirmed alarm
Sd Override
Active confirmed alarm

Browsing ECU Alarms

IL-NT Operator Guide


©ComAp 5
Setpoint Change
OFF MAN AUT TEST ! Password
>Basic Settings
Not ready Engine Params
MainsFlt Page Engine Protect
PF 0.00 Gener Protect
RPM 0 AutoMains Fail
No Timer Extension I/O
0 kW 0 Date/Time
Enter Page

Gen-set Name

>Nominal Power
200 kW
*Nomin Current
350 A
CT Ratio
2000 /5A

Enter Enter Page

Gen-set Name NOTE:


Cannot change setpoint?
>Nominal Power Setpoints marked with an
250 200 kW asterisk are password
*Nomin Current protected. Enter password
350 A as described in the chapter
CT Ratio Entering the Password
2000 /5A below.
Entering the Password
OFF MAN AUT TEST ! >Password
Basic Settings
Not ready Engine Params
MainsFlt Page Engine Protect
PF 0.00 Gener Protect
RPM 0 AutoMains Fail
No Timer Extension I/O
0 kW 0 Date/Time
Enter Page

>EnterPassword

Changepassword

Enter Enter Page

>EnterPassword
NOTE:
0
Lost password? Display the
Changepassword
information screen containing
the serial number and
password decode number as
described in the chapter below
and send them to your local
distributor.

IL-NT Operator Guide


©ComAp 6
Controller Information Screen

OFF MAN AUT TEST ! InteliLite NT


ComAp 2007-2008
Not ready Enter + Page
MainsFlt IL-NT-x.y
PF 0.00 Serial:12345678
RPM 0 SW ver: x.y, x.y
No Timer Appl : AMF25
0 kW 0 Branch: Standard

Page

Languages
>English
Chinese
Enter

Page

User interface:
User
>Engineer
Enter

Serial: 12345678
Pwd. dec.: 1234567890

Page

Display Contrast Adjustment


OFF MAN AUT TEST !

Not ready
MainsFlt
PF 0.00
OFF MAN AUT TEST ! RPM 0
No Timer
Not ready Enter + 0 kW 0
MainsFlt
PF 0.00 OFF MAN AUT TEST !
RPM 0 Enter +
No Timer Not ready
0 kW 0 MainsFlt
PF 0.00
RPM 0
No Timer
0 kW 0

IL-NT Operator Guide


©ComAp 7

You might also like