Introduction
The purpose of this report is to find a solution for block D2 column KZ 2-D which is casted with less
amount of rebar than the one indicated in the drawing. The design reinforcement value for this
column is 24Φ24 + 4Φ32. However, mistake was done on site and the contractor casted the
indicated column with reinforcement value of 20 Φ 20.
Figure 1 location of KZ 2 -D
2. Anchorage Length
The diameter 24 bars can be lapped at this stage of construction and anchor the bars
inside the water proofing slab.