FusionModule1000A40 Prefabricated All-in-One Data

Center
V200R003C00
Product Description (IT, 380 V)

Issue 02
Date 2018-11-30

HUAWEI TECHNOLOGIES CO., LTD.


Copyright © Huawei Technologies Co., Ltd. 2018. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions

and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.


Address: Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China
Website: http://e.huawei.com

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. i


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) About This Document

About This Document

Purpose
This document describes the FusionModule1000A prefabricated all-in-one data center
solution (FusionModule1000 for short) in terms of its overview, typical application scenarios,
product architecture, and key technical specifications, helping readers to systematically
understand the FusionModule1000.

Intended Audience
This document is intended for:
 Sales engineers
 Technical support engineers
 System engineers

Symbol Conventions
The symbols that may be found in this document are defined as follows.

Symbol Remarks

Indicates an imminently hazardous situation which, if


not avoided, will result in serious injury or death.

Indicates a potentially hazardous situation which, if not


avoided, could result in serious injury or death.

Indicates a potentially hazardous situation which, if not


avoided, may result in minor or moderate injury.

Indicates a potentially hazardous situation which, if not


avoided, could result in equipment damage, data loss,
performance deterioration, or unanticipated results.
NOTICE is used to address practices not related to
personal injury.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. ii


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) About This Document

Symbol Remarks

Calls attention to important information, best practices


and tips.
NOTE is used to address information not related to
personal injury, equipment damage, and environment
deterioration.

Change History
Changes between document issues are cumulative. The latest document issue contains all the
changes made in earlier issues.

Issue 02 (2018-11-30)
Updated IT cabinet parameters.

Issue 01 (2017-06-30)
This issue is the first official release.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. iii


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) Contents

Contents

About This Document .................................................................................................................... ii


1 Overview......................................................................................................................................... 1
1.1 Positioning .................................................................................................................................................................... 1
1.2 Benefits ......................................................................................................................................................................... 2

2 Typical Application Scenarios and Typical Configuration .................................................. 4


2.1 Application Scenarios of the Container Data Center .................................................................................................... 4
2.2 Typical configuration .................................................................................................................................................... 6

3 System Architecture...................................................................................................................... 9
3.1 Container Structural System ......................................................................................................................................... 9
3.1.1 Container ................................................................................................................................................................... 9
3.1.2 Container Interior Layout ........................................................................................................................................ 12
3.1.3 Components Inside the Container ............................................................................................................................ 15
3.1.4 External Container Ports .......................................................................................................................................... 20
3.2 Power Supply and Distribution System ...................................................................................................................... 21
3.2.1 Overview ................................................................................................................................................................. 21
3.2.2 Integrated UPS ......................................................................................................................................................... 26
3.2.3 Battery Switch Box .................................................................................................................................................. 29
3.2.4 Static Transfer Switch (STS) ................................................................................................................................... 30
3.2.5 rPDU ........................................................................................................................................................................ 31
3.2.6 Battery Cabinet (Optional)....................................................................................................................................... 32
3.2.7 Battery Pack ............................................................................................................................................................. 32
3.3 Cooling System........................................................................................................................................................... 33
3.3.1 Overview ................................................................................................................................................................. 33
3.3.2 Composition............................................................................................................................................................. 34
3.3.2.1 Indoor Unit ........................................................................................................................................................... 34
3.3.2.2 Ports ...................................................................................................................................................................... 36
3.3.2.3 Operating Environment Specifications ................................................................................................................. 36
3.3.2.4 Technical Specifications ....................................................................................................................................... 37
3.3.2.5 Outdoor Unit ......................................................................................................................................................... 39
3.3.3 Low-Temperature Component ................................................................................................................................. 41
3.4 Management System ................................................................................................................................................... 43
3.4.1 Overview ................................................................................................................................................................. 45

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. iv


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) Contents

3.4.2 ECC800 ................................................................................................................................................................... 46


3.4.3 Independent Deployment AI/DI Unit....................................................................................................................... 52
3.4.4 Smart ETH Gateway ................................................................................................................................................ 53
3.4.5 Access Actuator ....................................................................................................................................................... 55
3.4.6 AC Actuator ............................................................................................................................................................. 58
3.4.7 WiFi Converter ........................................................................................................................................................ 61
3.4.8 IP Camera ................................................................................................................................................................ 63
3.4.9 Water Sensor ............................................................................................................................................................ 67
3.4.10 Pad ......................................................................................................................................................................... 68
3.4.11 Rack Environment Unit (Optional) ........................................................................................................................ 69
3.4.12 Cabinet Access Control System (Optional) ........................................................................................................... 70
3.4.13 Intelligent Battery Monitoring System (Optional) ................................................................................................. 71
3.4.14 External Camera (optional) .................................................................................................................................... 74
3.5 Fire Extinguishing System .......................................................................................................................................... 77
3.5.1 Overview ................................................................................................................................................................. 77
3.5.2 CE Fire Extinguishing System ................................................................................................................................. 80
3.5.2.1 Extinguishant Control Panel ................................................................................................................................. 80
3.5.2.2 Heptafluoropropane Fire Extinguisher ................................................................................................................. 81
3.5.3 Standard Fire Extinguishing System ........................................................................................................................ 83
3.5.3.1 Fire Alarm Control Panel ...................................................................................................................................... 83
3.5.3.2 Heptafluoropropane Fire Extinguisher ................................................................................................................. 84
3.5.4 VESDA (Optional)................................................................................................................................................... 85
3.6 Surge Protection and Grounding ................................................................................................................................. 87
3.6.1 Surge Protection....................................................................................................................................................... 87
3.6.2 Grounding ................................................................................................................................................................ 87
3.7 Integrated Cabling ...................................................................................................................................................... 88

4 Key Technical Specifications .................................................................................................... 90


A Acronyms and Abbreviations .................................................................................................. 94

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. v


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 1 Overview

1 Overview

1.1 Positioning
Huawei has developed the FusionModule1000, a green data center solution, based on a
thorough study on the reform and impact of the cloud computing to traditional data centers
and the practical experience of dozens of global cloud computing centers. The solution
features a flexible, hybrid, and modular design to help customers construct green
infrastructure adapting to cloud computing.
The FusionModule1000, foundation for cloud computing in enterprise data centers, integrates
power distribution, monitoring, cooling, racks, cable routing, and fire extinguishing. It is
characterized by good waterproof and quakeproof performances. The FusionModule1000
helps enterprise telecom operators and Internet operators to rapidly deploy data centers and
has unique advantages in the fields of disaster relief, military affairs, oil exploitation, survey,
and enterprise data for its availability in outdoor environments.
The FusionModule1000, located at the bottom layer of a data center, provides basic physical
construction for all services in the data center.

Figure 1-1 Data center architecture

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 1


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 1 Overview

1.2 Benefits
The FusionModule1000 is a small-capacity prefabricated all-in-one data center that integrates
the container mechanical structure, power supply and distribution system, cooling system,
management system, fire extinguishing system, integrated cabling system, and server cabinets.
It features high security and reliability, rapid deployment, low cost, high efficiency, and
intelligent management.

High Security and Reliability


 The design of two porches prevents sand from entering the equipment compartment
when doors are open during maintenance, ensuring that the FusionModule1000 applies
to various harsh environments.
 The container is properly grounded and resists electromagnetic interference. Its
electromagnetic compatibility (EMC) meets Class A requirements specified in the
CISPR22/EN55022 standard.
 The data center uses International Organization for Standardization (ISO) standard 668
containers which provides IP65 protection (IP55 by default; IP65 available by changing
the dustproof module at the air vent) as the containers feature mature welding
technologies and are well sealed to be waterproof and dustproof.
 Thanks to special coating for the container, the container passes the 1440-hour UL salt
spray test, equivalent to a service life longer than 25 years. Based on corrosion
definitions in ISO12944-2 and service life evaluation rules in ISO12944-1, a 720-hour
salt spray test in the C4-High environment is equivalent to more than 15 years of service
life, and the 1440-hour salt spray test is equivalent to 25 years of service life.
 The bullet-proof function can be provided for the container if required. The container
passes the 10 m rifle test as it is armed with 4.2 mm bullet-proof steel plates on its sides
and 2.4 mm bullet-proof steel plates on the top.
 The container works well at low ambient temperatures (–40°C to +45°C) and normal
temperatures (–20°C to +55°C).
 The container meets NEBS zone 3 antiseismic requirements, and equipment supports
shock absorption.
 Product design complies with the TIA-942 standard.
 The intelligent access control system and mechanical locks provide multifold security
protection and meets class 3 theftproof requirements in EN 1627–EN 1630.
 The container interior is decorated with B1 fire-resistant materials, the enclosure
structure uses the high-density A1 fire-resistant rock wool material, and the exterior is
coated with the customized flame-retardant paint, providing fire resistance duration of
120 minutes as stipulated by UL.
 The fire extinguishing system is reliable, clean, insulating, and environment-friendly, and
can put out a fire efficiently and safely without damaging CT devices, thereby ensuring
high device availability. The extinguishant is Heptafluoropropane. The fire extinguishing
system complies with China's CCC certification in the standard version and the EU's CE
certification in the CE version. Copper fluoride (NOVEC1230) can also be used if
required in the CE version.

Rapid Deployment
 Streamlined manufacturing, professional division of labor, and good work conditions
ensure that modules and products of the FusionModule1000 are produced efficiently
with strict quality control. The standard manufacturing period is six to eight weeks.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 2


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 1 Overview

 Infrastructures such as cooling equipment, power supply equipment, and racks are
factory-installed. You only need to provide network cables, power cables, and water
pipes onsite for commissioning.
 System commissioning is completed in factories, and therefore onsite deployment and
equipment room commissioning take less than one week.
 The container can be easily relocated as it can be transported on level-3 roads and
applies to various scenarios such as dynamic data service deployment, military affairs,
disaster relief, and field operations.

Cost-Effectiveness and High Energy Efficiency


 The container integrates the cabinets, cooling, power distribution, monitoring, security,
and other facilities that are pre-installed in the factory. The FusionModule1000 is
pre-commissioned and put into trial run before delivery. Customers can inspect and try
the product in the factory.
 Civil engineering is simple when the FusionModule1000 is deployed outdoors. It starts
to work after being installed on a concrete podium or platform and connected to a
humidifier, water supply, mains power supply, and network.
 Mature delivery mode, modular structure, and low-cost transportation of the container
ensure fast deployment of the FusionModule1000, and simple and convenient expansion
and upgrade.
 The FusionModule1000 is energy-efficient. The hot and cold aisles are separated in the
equipment compartment to ensure high cooling efficiency.

Intelligent Management
 Manages infrastructure of the FusionModule1000 in a central manner.
 Supports O&M using a mobile app and remote unattended operation. Full WiFi coverage
is realized inside the container using a WiFi converter. WiFi coverage outside the
container is realized using a customer router gateway (optional).
 Monitors equipment effectively in real time.
 Monitors environments in real time to identify potential risks.
 Provides various methods of collecting and analyzing power consumption data to realize
precision energy efficiency analysis. Such data is fundamental to improving the power
usage effectiveness (PUE). You can customize the data collection and analysis methods.
 Provides a robust security mechanism to protect equipment and ensures a proper
environment.
 Provides standard Simple Network Management Protocol (SNMP) ports to communicate
with third-party network management systems (NMSs).

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 3


FusionModule1000A40 Prefabricated All-in-One Data
Center 2 Typical Application Scenarios and Typical
Product Overview (IT, 380 V) Configuration

2 Typical Application Scenarios and Typical


Configuration

2.1 Application Scenarios of the Container Data Center


The FusionModule1000 is a prefabricated container data center, and integrates the
uninterruptible power system (UPS), air conditioner, and cabinets. It can be put into operation
immediately after connecting to the tap water, power supply and network.
The FusionModule1000 is focused on fast deployment of outdoor small-size IT equipment
rooms for carriers and enterprises. It can integrate standard and nonstandard mainstream IT
equipment, supports the 1.2 m cabinet layout, and can be easily relocated.

Table 2-1 Typical application scenarios of the FusionModule1000


IT Equipment Energy Government Large Others
Room Industry Enterprise
 Equipment  Distributed  Distributed  Primarily  Distributed
room single-contai single-contai for private single-contai
construction ner ner use ner
and deployment deployment  Mobile fast deployment
modernizati  Areas such  Diverse deployment  Suburban
on as environment areas
 High
 Distributed wilderness, s such as the without
reliability
and mobile mineries, seaside, class equipment
single-contai and deserts industrial rooms
ner parks,
deployment campuses,
and urban
areas

Distributed and mobile single-container deployment applies to equipment room construction


or modernization.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 4


FusionModule1000A40 Prefabricated All-in-One Data
Center 2 Typical Application Scenarios and Typical
Product Overview (IT, 380 V) Configuration

Figure 2-1 Mobile FusionModule1000

The FusionModule1000 must not be transported with the IT equipment, power modules, and batteries
installed.

The FusionModule1000 can be deployed as a small integrated data center (IDC) for
enterprises in diverse environments such as the seaside, industrial parks, campuses, urban, and
suburban areas to meet specific application requirements such as business blowout and
capacity expansion.
The FusionModule1000 is most preferred when a data center must be quickly constructed and
deployed due to urgent service requirements.

Figure 2-2 Application in an enterprise park

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 5


FusionModule1000A40 Prefabricated All-in-One Data
Center 2 Typical Application Scenarios and Typical
Product Overview (IT, 380 V) Configuration

The FusionModule1000 supports distributed single-container deployment in outdoor areas


such as wilderness, mineries, and deserts to meet application requirements of the energy
industry.

Figure 2-3 FusionModule1000 in harsh outdoor environments

2.2 Typical configuration


A typical 40 ft IT solution provides a capacity of 42 kW, and can house a maximum of 10
cabinets.

Table 2-2 Typical configuration

Type System Composition

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 6


FusionModule1000A40 Prefabricated All-in-One Data
Center 2 Typical Application Scenarios and Typical
Product Overview (IT, 380 V) Configuration

Type System Composition

Structural system  2 N scenario without iBAT: raised floor, seven 42 U IT cabinets


(six with H x W x D dimensions of 2000 mm x 600 mm x 1200 mm
and one with H x W x D dimensions of 2000 mm x 600 mm x 1100
mm)
 2 N scenario with iBAT: raised floor, six 42 U IT cabinets with H x
W x D dimensions of 2000 mm x 600 mm x 1200 mm
 N+X scenario without iBAT: raised floor, eight 42 U IT cabinets
(six with H x W x D dimensions of 2000 mm x 600 mm x 1200 mm
and two with H x W x D dimensions of 2000 mm x 600 mm x 1100
mm)
 N+X scenario with iBAT: raised floor, seven 42 U IT cabinets (six
with H x W x D dimensions of 2000 mm x 600 mm x 1200 mm and
one with H x W x D dimensions of 2000 mm x 600 mm x 1100
mm)
Raised floor, seven 42 U IT cabinets (six with dimensions of 2000 mm
x 600 mm x 1200 mm and one with dimensions of 2000 mm x 600 mm
x 1100 mm)
Container-level low-temperature component assembly (configured
when the temperature is below 0°C.)
Power supply  2 N scenario without iBAT: integrated UPS, rPDU, STS, battery
and distribution switch box, 9 Ah battery pack
system  2 N scenario with iBAT: integrated UPS, rPDU, STS, 40 Ah battery
pack
 N+X scenario without iBAT: integrated UPS, rPDU, battery switch
box, 9 Ah battery pack
 N+X scenario with iBAT: integrated UPS, rPDU, 40 Ah battery
pack
Integrated UPS, rPDU, STS(Static Transfer Switch), battery switch
box, 40 Ah battery pack
Cooling Low 25 kW half-sized variable frequency air cooled air conditioner with the
system tempe outdoor unit, remote temperature and humidity sensor,
rature low-temperature component (configured when the temperature is in the
range of –40°C to –20°C)
None
Norm 25 kW variable frequency air-cooled air conditioner with the outdoor
al unit for a half-sized container, remote T/H sensor
tempe 21 kW variable frequency air-cooled air conditioner with the outdoor
rature unit for a half-sized container, remote T/H sensor
Fire CE Extinguishant control panel, smoke detector, heat detector, fire alarm
extingui versio bell, horn strobe, emergency light, external horn strobe, extinguishant
shing n abort button, warning signs, electrical actuator, pneumatic switch, fire
system nozzle, fire cylinder, and VESDA (optional)

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 7


FusionModule1000A40 Prefabricated All-in-One Data
Center 2 Typical Application Scenarios and Typical
Product Overview (IT, 380 V) Configuration

Type System Composition

Standa Fire alarm control panel, smoke detector, heat fire detector, fire alarm
rd sounder, fire alarm horn/strobe, emergency light, external fire alarm
Versio horn/strobe, emergency start/abort switch, gas release indicator, fire
n nozzle, fire cylinder, and VESDA (optional)
Monitoring ECC800, independent deployment AI/DI unit, smart ETH gateway,
system access actuator, AC actuator, WiFi converter, water sensor, pad,
camera, emergency door release, reader, door status sensor, magnetic
lock, rack environment unit (optional), cabinet access control device
(optional), iBAT (optional), and external camera (optional).
ECC800, independent deployment AI/DI unit, smart ETH gateway,
access actuator, AC actuator, WiFi converter, water sensor, pad,
camera, emergency door release, reader, door status sensor, magnetic
lock, rack environment unit (optional), cabinet access control device
(optional), and external camera (optional).

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 8


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

3 System Architecture

3.1 Container Structural System


3.1.1 Container
Container Appearance
The dimensions and corner pieces of the container comply with the ISO668 standard. The
container exterior can be made of aluminum grilles or Eterpan panels.

Figure 3-1 Appearance 1

(1) End door (for maintaining outdoor units) (2) Lock rod
(3) Ventilation window for the outdoor unit compartment (4) Container feeder window

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 9


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-2 Appearance 2

(1) External fire alarm horn strobe (2) Emergency door (3) Air inlet window
release button
(4) Device installation (5) Air outlet window (6) End door (main
door/emergency door entrance)
(7) Card reader (8) Container ground point (9) Fire control box

Thermal Insulation Structure


The container is furnished with a thermal insulation layer composed of steel plates, rock wool
(density: 120 kg/m3), and color steel plates. The heat transfer coefficient of the container is
equal to or less than 0.4 W/(m2 x K).

Container Door
900 mm wide fire door:
 The door resists fire for 90 min typically and up to 120 min if special treatment is
applied.
 The door is protected to IP65.
 The door uses a WK03 class theftproof structure.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 10


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

 The door is 900 mm wide (net) and 2250 mm high (net). It opens in and out rightwards
(the hinge is on the right side of the door), with a door handle outside and a pushrod
structure inside.
 The door closer allows the door to open to an angle of at least 120°, and it stops the door
at the maximum position to keep the door open.
 When the door is open, the door, door frame, and mechanical parts can withstand the
door weight and will not misshape permanently within 48 hours with a static load of 15
kilograms at any part.
 The fire door uses rubber strips with a framework and composite adhesive to ensure the
waterproof performance.
1200 mm wide fire door:
 The door is used for moving equipment in or out and can be opened only inwards.
 The door resists fire for 90 min typically and up to 120 min if special treatment is
applied.
 The door is protected to IP65.
 The door uses a WK03 class theftproof structure.
 The door is 1200 mm wide (net) and 2250 mm high (net). It opens in rightwards (the
hinge is on the right side of the door), with a pushrod structure inside.
 The door closer allows the door to open to an angle of at least 120°, and it stops the door
at the maximum position to keep the door open.
 When the door is open, the door, door frame, and mechanical parts can withstand the
door weight and will not misshape permanently within 48 hours with a static load of 15
kilograms at any part.
 The fire door uses rubber strips with a framework and composite adhesive to ensure the
waterproof performance.

Container Specifications
Table 3-1 lists the container specifications.

Table 3-1 Container Specifications


Item Specifications

Dimensions 40 ft standard ISO shipping container (8 ft × 9.5 ft × 40 ft): 2896 mm x


(H x W x D) 2438 mm x 12192 mm
Container The heat transfer coefficient of the container is equal to or less than 0.4
heat W/(m2 x K).
insulation
performance
Cabling Power cables and signal cables are routed separately.
Protection IP55/IP65 (optional)
level
Installation Directly installed on the ground.
mode NOTE
The container can also be installed on a concrete platform, with four 300 mm high
steel bases connected to the concrete platform using M16 bolts.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 11


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Item Specifications

Weight Empty container (excluding servers): 12,000 kg; fully-loaded container: <
25,000 kg
Typical IT cabinet dimensions (H x W x D): 2000 mm x 600 mm x 1200 mm/1100
cabinet mm
capacity IT cabinet dimensions (H x W x D): 2000 mm x 600 mm x 1200 mm/1100
mm
Reliability  The intelligent access control system and mechanical locks provide
multifold security protection and meets class 3 theftproof requirements
in EN 1627–EN 1630.
 The access control system can be configured with permission at
different levels to monitor door status and generate alarms.
 Standard container air vents feature good security and ventilation
designs.
 Ground busbars are installed in the container for internal equipment
and the container itself. Surge protection measures are provided for
power ports and network ports to ensure the safety of the data center.
 Real-time video surveillance is implemented for the protected area.
 The container can withstand the 30 m/s wind speed when it is in
operation.
 The container meets NEBS zone 3 antiseismic requirements.
 The container can be used for 25 years in standard coating.
 Fireproof performance: The burning behavior of decorative materials
complies with the Code for Fire Prevention in Design of Interior
Decoration of Buildings (GB50222-95) of China. The materials can
withstand fire for 120 minutes.
 Thermal insulation performance: The heat transfer coefficient of the
container is equal to or less than 0.4 W/(m2 x K).
 Waterproof and dustproof performance: All external ports are protected
to IP55 (weather-tightness test) of the GB4208/IEC529 standard and
can be protected to IP65 if required.
 Corrosion resistance in salt spray: The container uses weathering steel
and surface treatment and passes the 1440-hour cyclic salt spray test.
 Anti-mould performance: The container passes the 24 hours x 28 days
mould growth test.
 Bullet-proof performance (optional): The container passes the 10 m
rifle test.

3.1.2 Container Interior Layout


In the container, the hot aisle is 500 mm wide, the cold aisle is 860 mm wide, and the long
aisle is 650 mm wide in the container. Cabinets can slide 200 mm backward or forward to
flexibly expand the cold or hot aisle to facilitate O&M.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 12


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

2N Scenario
Figure 3-3 and Figure 3-4 show the interior layout of the container.

Figure 3-3 Internal layout in the 2N scenario without the iBAT

(1) Air conditioner (2) Low temperature component (3) IT (4) Integrated
outdoor units for air conditioners Cabinets UPS
(5) Cold aisle (6) Entrance room (7) Fire (8) Battery
cylinder cabinet
(9) Air conditioner (10) Hot aisle
indoor units

Figure 3-4 Internal layout in the 2N scenario with the iBAT

(1) Air conditioner (2) Low temperature component (3) IT (4) Battery
outdoor units for air conditioners Cabinets cabinet
(5) Integrated UPS (6) Cold aisle (7) Entrance (8) Fire
room cylinder
(9) Air conditioner (10) Hot aisle
indoor units

The low-temperature component is deployed for air conditioners when the temperature is in the range of
–40°C to –20°C. When the temperature is below 0°C, the low-temperature component assembly at the
container level should be deployed.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 13


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

N+X Scenario
Figure 3-5 and Figure 3-6 show the interior layout of the container.

Figure 3-5 Internal layout in the N+X scenario without the iBAT

(1) Air conditioner (2) Low temperature component (3) IT (4) Battery
outdoor units for air conditioners Cabinets cabinet
(5) Cold aisle (6) Entrance room (7) Fire (8) Integrated
cylinder UPS
(9) Air conditioner (10) Hot aisle
indoor units

Figure 3-6 Internal layout in the N+X scenario with the iBAT

(1) Air conditioner (2) Low temperature component (3) IT (4) Battery
outdoor units for air conditioners Cabinets cabinet
(5) Integrated UPS (6) Cold aisle (7) Entrance (8) Fire
room cylinder
(9) Air conditioner (10) Hot aisle
indoor units

The low-temperature component is deployed for air conditioners when the temperature is in the range of
–40°C to –20°C. When the temperature is below 0°C, the low-temperature component assembly at the
container level should be deployed.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 14


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

3.1.3 Components Inside the Container


Overhead Cable Tray
 Cable trays are classified into strong-current cable trays and weak-current cable trays.
Cable trays are reserved for optical fibers.
 Cable trays are assembled by section steel. Cable trays are separate from cabinets and
compatible with different cabinet arrangements.
 Aluminum guide rails are deployed along the length side of the container and secured to
the C-shaped beams at the top of the container. Cable trays are secured to the aluminum
guide rails using sliding nuts.

Figure 3-7 Overhead cable tray

Suspended Ceiling
 Cold and hot aisles are isolated by a suspended ceiling to prevent mixture of cold and hot
air.
 The aisle sealing plates are separate from cabinets and secured to the aluminum guide
rails at the top of the container.
 The sealing plates for the suspending ceiling of the long aisle are hinged and can be
easily opened when overhead cables need to be maintained.
 The suspended ceilings of the hot and cold aisles are assembled by three sealing plates.
The sealing plates on both sides can be removed when there is a need to maintain cables.
 The hot aisle door is a glass sliding door that is installed before transportation.

Cabinet
A cabinet used in the data center complies with the International Electrotechnical Commission
(IEC) 60297-1 standard and provides stable installation space for servers, thereby ensuring
safe operation of servers.
The cabinets have the uniform dimensions and provide front and rear ventilation channels.
Figure 3-8 shows the cabinet exterior. Table 3-2 lists its technical specifications.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 15


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-8 Cabinet exterior

An IT cabinet has the following features:


 The ventilation rate of the front and rear doors is greater than or equal to 70%.
 An rPDU can be vertically installed at the rear of the cabinet.
 The position of each U is marked on the vertical mounting bars.
 The front and rear doors are locked and can be unlocked only with dedicated keys.
 The customized cabinet supports a door status sensor and electronic access control.

Table 3-2 Cabinet technical specifications

Item Specifications

Outline dimensions  2000 mm x 600 mm x 1200 mm


(H x W x D)  2000 mm x 600 mm x 1100 mm
Color Black
Materials High-intensity class A carbon cold rolled steel sheet and zinc-coated
steel sheet
Ventilation channel Front and rear ventilation channels

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 16


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Item Specifications

Installation space  42 U
 The distance between the front and rear mounting bars can be
adjusted for every 25 mm.
− For a 1200 mm deep cabinet: The maximum depth for
installing devices inside the cabinet is 750 mm and can be
extended to 850 mm by adjusting the mounting bars.
− For a 1100 mm deep cabinet: The maximum depth for
installing devices inside the cabinet is 700 mm and can be
extended to 750 mm by adjusting the mounting bars.
− If the depth of the equipment exceeds the specifications, the
cabinet needs to be customized by raising RM requirements.
 Positions behind the cabinet are reserved for installing two
rPDUs.
Installation mode Supports installation on a base and raised floor.
Door opening mode The front door is a single door, and the rear door is a double one.
Weight of an empty  The weight of a 2000 mm x 600 mm x 1100 mm cabinet is 110
cabinet kg.
 2000 mm x 600 mm x 1200 mm; weight: 130 kg
(The weight of an empty cabinet includes the weight of the front and
rear doors.)
Protection level IP20

Aisle Sliding Door


There are cold and hot aisles between cabinets in the equipment zone of the container. The
sliding door seals an aisle to form aisle containment (hot aisle containment by default).
The top of the aisle sliding door is secured to the sealing plates of the suspended ceiling, and a
damper is installed at the bottom of the sliding door to prevent the door from swaying during
transportation or movement.
The sliding door is 2046 mm high and 755 mm wide.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 17


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-9 Aisle sliding door

(1) Sliding door guide rail (2) Glass door panel (3) Damper

Cabinet Base
In scenarios without shock absorption:
 Cabinets cannot be transported with servers installed.
 Cabinets are raised for 250 mm high and secured to sliding bases, which are anchored to
the steel floor using self-drilling tapping screws.
 Due to the limitation of space inside the container, when installing or maintaining
devices that are more than 850 mm deep in a cabinet, you need to slide the cabinet to
expand the maintenance space. By adjusting the sliding bases, cabinets can slide by 200
mm backward or forward to flexibly expand the cold or hot aisle to facilitate O&M.
 To prevent the cabinets from sliding during container transportation, each cabinet sliding
base has transport fasteners installed respectively on the front and rear. After the
container is installed and secured, the transport fasteners need to be removed.
 Cabinet sliding bases can be used for cabinets that are 1100 mm and 1200 mm deep. The
bases can be 1100 mm or 1200 mm deep.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 18


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-10 Cabinet sliding base without shock absorption

(1) Fixed supportive leg (2) Sliding platform (3) Transport fastener

In scenarios with shock absorption:


 Cabinets can be transported with servers installed.
 Four steel shock absorbers are deployed at the bottom of a cabinet. They can collaborate
with positioning kits to limit the movement of the cabinet.
 Due to the limitation of space inside the container, when installing or maintaining
devices that are more than 850 mm deep in a cabinet, you need to slide the cabinet to
expand the maintenance space. By adjusting the sliding bases, cabinets can slide by 200
mm backward or forward to flexibly expand the cold or hot aisle to facilitate O&M.
 To prevent the cabinets from sliding during container transportation, each cabinet sliding
base has transport fasteners installed respectively on the front and rear. After the
container is installed and secured, the transport fasteners need to be removed.
 Cabinet sliding bases with shock absorption can be used for cabinets that are 1100 mm
and 1200 mm deep. The bases can be 1100 mm or 1200 mm deep.

Figure 3-11 Cabinet sliding base with shock absorption

(1) Steel shock absorber (2) Sliding platform (3) Transport fastener

Raised Floor
A raised calcium sulphate ESD floor is installed in the cold aisle. The floor is coated with the
PVC ESD veneer that is dustproof and easy to clean. An aluminum ventilated floor is installed
in the hot aisle.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 19


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

 The raised floor is 210 mm high.


 The raised floor consists of flooring, supports, beams, and conductive rubber pads.
 The floor does not dislocate or deform after long range transportation, and is easy to
assemble and maintain.
 The support can be adjusted in height, and are galvanized to provide efficient
anti-corrosion and moistureproof performance.
 The compression strength of both the raised floor and floor supports is greater than 1500
kg/m2.

Figure 3-12 Raised floor

(1) Calcium sulphate ESD floor (2) Support

3.1.4 External Container Ports


End connectors are used at container exterior ports designed for routing power cables, optical
fibers, and network cables on the container exterior. Sealing modules are used at the ports
designed for routing refrigerant pipes and water pipes. All ports provide good water tightness
and thermal insulation performance and meet equipment compartment weathering
requirements. Pipe ports feature an anti-backflow design to meet diverse configuration
requirements. Fire extinguishing devices on the container exterior meet sealing conditions.
A power PDB is deployed on the left side of the container to connect input power cables on
the container exterior. The design avoids the need to route power cables into the container and
simplifies cable connection.

Figure 3-13 Power PDB (left view)

(1) Signal cable feeder window (2) Power cable feeder window (3) Power PDB

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 20


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-14 shows the ports reserved for the humidifier water refill pipe and condensate
drainpipe.

Figure 3-14 Positions of the reserved ports

(1) Port reserved for the humidifier water refill (2) Port reserved for the condensate
pipe drainpipe

The port reserved for the humidifier water refill pipe is a 1 inch ball valve with internal threads. The port
reserved for the condensate drainpipe is a DN25 PP-R pipe port.

3.2 Power Supply and Distribution System


3.2.1 Overview
The IT solution includes two scenarios: 2N and N+X.

N+X Scenario
In the N+1 scenario, the total power of IT equipment is 52 kW, and the power backup time is
7.5 minutes for IT equipment if no iBAT is configured and 15 minutes if the iBAT is
configured. The power supply and distribution system provides power separately for power
and IT equipment, and supports 25 kW variable frequency air-cooled air conditioners, fire

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 21


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

extinguishing devices, lights, ECC800, and other auxiliary devices inside a half-sized
container.
The power supply and distribution system mainly consists of the integrated UPS, battery pack
or batteries (if iBAT is configured), and rPDU.
 Two 380 V/400 V/415 V AC inputs, three phases, four wires, and PE
 One integrated UPS supplies power to IT loads, air conditioners, fire extinguishing
devices.
 The integrated UPS has three built-in 40 kVA power modules (2+1 backup). The battery
pack or batteries (if iBAT is configured) are installed inside the battery cabinet.

Figure 3-15 System conceptual diagram (without iBAT)

Figure 3-16 System conceptual diagram (with iBAT)

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 22


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-17 Power supply and distribution device layout (without iBAT)

(1) Integrated UPS (2) Battery cabinet


(3) Power PDB

Figure 3-18 Power supply and distribution device layout (with iBAT)

(1) Battery cabinet (2) Integrated UPS


(3) Power PDB

2N Scenario
In the 2N scenario, the total power of IT equipment is 52 kW, and the power backup time is
10 minutes for IT equipment if no iBAT is configured and 15 minutes if the iBAT is

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 23


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

configured. The power supply and distribution system provides power separately for power
and IT equipment, and supports 25 kW variable frequency air-cooled air conditioners, fire
extinguishing devices, lights, ECC800, and other auxiliary devices inside a half-sized
container.
In the 2N scenario, the power supply and distribution system mainly consists of the integrated
UPS, battery pack or batteries (if iBAT is configured), static transfer switch (STS), and rPDU.
 Two 380 V/400 V/415 V AC inputs, three phases, four wires, and PE.
 Two integrated UPSs supply power to IT loads and air conditioners.
 The integrated UPS has two built-in 40 kVA power modules. The battery pack or
batteries (if iBAT is configured) are installed inside the battery cabinet.
 The STS supplies power to fire extinguishing devices with single input.

Figure 3-19 System conceptual diagram (without iBAT)

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 24


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-20 System conceptual diagram (with iBAT)

Figure 3-21 Power supply and distribution device layout (without iBAT)

(1) Battery cabinet (2) Integrated UPS


(3) Power PDB

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 25


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-22 Power supply and distribution device layout (with iBAT)

(1) Battery cabinet (2) Integrated UPS


(3) Power PDB

3.2.2 Integrated UPS


The integrated UPS has the following features:
 Uses a unified architecture, and provides reliable quality, comprehensive functions, and
consistent appearance.
 The automatic transfer switch (ATS), molded case circuit breaker (MCCB), IT power
distribution, air conditioner power distribution, lighting power distribution, and UPS are
integrated into one PDC.
Figure 3-23 shows the appearance of an integrated UPS.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 26


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-23 Appearance of an integrated UPS

Table 3-3 lists the configuration specifications of the integrated UPS.

Table 3-3 Configuration specifications of the integrated UPS

Configuration Scenario 2N Scenario N+X

Input mode One 250 A/3P MCCB 250 A/4P ATS


Power distribution circuit UPS input: MCCB 160 A/3P
breakers for UPSs UPS output: MCCB 160 A/3P
Maintenance bypass: MCCB 160 A/3P
Power distribution circuit 40 A/3P x 5
breakers for air conditioner 16 A/1P x 2
boxes
10 A/1P x 7
Power distribution circuit  40 A/1P x 18 x 2
breakers for IT equipment  63 A/1P x 6 x 2
Dimensions (H x W x D) 2000 mm x 600 mm x 1100 mm

An integrated UPS works when the input power is 380 V, 400 V, or 415 V, and features
redundancy, high reliability, high efficiency, environment friendliness, high flexibility, and
intelligent and simple operations.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 27


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Table 3-4 lists the technical specifications of the integrated UPS.

Table 3-4 Technical specifications of the integrated UPS

Category Item Specifications

Input Input system Three phases


Rated input voltage 380 V, 400 V, or 415 V AC, three-phase,
four-wire, and PE
Input voltage range 80–280 V AC (phase voltage) (When the input
voltage ranges from 80 V AC to 176 V AC,
loads are linearly derated.)
Input frequency range 40–70 Hz
Input power factor > 0.99 (full load); > 0.98 (50% load)
Rated input current Air-cooled 1: 250 A; air-cooled 2: 400 A;
air-cooled 3: 125 A
Output Rated voltage 380 V, 400 V, or 415 V AC, three-phase,
four-wire, and PE
Total harmonic THD ≤ 1%
distortion (THD)
(linear load)
Total harmonic THD ≤ 4%
distortion (THD)
(non-linear load)
Power factor 1
Maximum peak factor 3:1 (in compliance with IEC 62040-3 standard)
for loads
Overload capability 60 min (105%–110% load)
10 min (111%–125% load)
1 min (125%–150% load)
Battery Number of batteries 30 to 40 12 V batteries (32 batteries by default)
Derated by 6% when 30 batteries are used
Battery string sharing Battery string is shared inside the same rack by
default.
Charge voltage Equalized charging voltage: 2.35 V/cell; float
charging voltage: 2.25 V/cell
The maximum battery capacity is 3,000 Ah.
The charging current is limited based on the
battery capacity.
System Display LCD + LED
System efficiency ≥ 96%

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 28


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Category Item Specifications

Current equalization < 5% (in parallel mode)


Number of combined In a micro module, cabinets do not need to be
cabinets combined.
Cable connection Routed in and out from the top
Noise At atmospheric pressure (25ºC)
 25% load: 54 dB
 50% load: 58 dB
 75% load: 61 dB
 100% load: 65 dB
Others Maintenance mode Maintained from the front or rear
Surge protection Level C SPD

ATS (Optional)
Table 3-5 lists the specifications of an ATS.

Table 3-5 ATS specifications


Item Specifications

Input voltage range 187–264 V AC (phase voltage)


Input frequency 40–70 Hz
range

3.2.3 Battery Switch Box


The battery switch box is used for power-off maintenance of a single battery string.
The battery switch box provides dual inputs, and provides dual three-route outputs through 63
A/3P circuit breakers. Each 63 A/3P circuit breaker controls one 9 Ah or 7 Ah battery string
with two battery packs.

Table 3-6 Technical specifications of a battery switch box

Item Specifications

Rated operating voltage 384–480 V DC


Number of inputs Two inputs from 25 mm2 cables
Output switch Dual three-route outputs: 3 x 63 A/3P MCB
+ 3 x 63 A/3P MCB
Protection level IP20 (front)

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 29


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Item Specifications

Cabling mode Routed in and out from the rear


Box dimensions 3 U high, installed in a 19-inch rack

3.2.4 Static Transfer Switch (STS)


The STS is used to supply power to fire extinguishing devices. Figure 3-24 shows its
appearance, and Table 3-7 lists its specifications.

Figure 3-24 Appearance

Table 3-7 Parameter


Item Specifications

Input Input source Dual route


Input mode 1Φ+N+PE
Rated voltage 220 V AC/230 V AC
Rated frequency 50 Hz/60 Hz
Voltage range 150–300 V AC
Frequency range Rated frequency±5 Hz
Total harmonic < 10%
distortion
Output Power factor 0.75–1.0 (overexcited or underexcited)
Overload 125%, 30 min
capability
Efficiency (100% 99%
linear load)
Switch Number of poles Two
Automatic < 6 ms (typical); < 11 ms (maximum)
transfer time

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 30


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Item Specifications

Environm Operating 0–40°C


ent temperature
parameter
s Storage –40°C to +70°C
temperature
Relative humidity 5%–95% RH (non-condensing)
Altitude 3000 m
Mechanic Dimensions (H x 44 mm x 430 mm x 250 mm
al W x D)
specificat
ions Weight 4.5 kg (standard)/5 kg (with optional components)

3.2.5 rPDU
Full height rPDU and Half height rPDU show the appearance of rPDUs.
Full height rPDU shows an rPDU.

The figure is for reference only. The actual product prevails.

Figure 3-25 Full height rPDU

Figure 3-26 Half height rPDU

Below tables list the rPDU specifications.

Table 3-8 rPDU specifications

Model Output Port

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 31


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Model Output Port

PDU2000-32-1PH-9/3-B1 IEC320 9 x C13 + 3 x C19


PDU2000-32-1PH-20/2-B1 IEC320 20 x C13 + 2 x C19

Table 3-9 rPDU specifications

Model Output Port

PDU2000-40-2PH-20_4-B1 IEC320 20 x C13 + 2 x C19

3.2.6 Battery Cabinet (Optional)


A battery cabinet provides space for installing batteries and routing battery cables for the
FusionModule1000A, and is mainly used in scenarios when the iBAT is configured.
A battery cabinet is configured with forty 12 V 40 Ah batteries, and has a 160 A MCCB.

Table 3-10 Battery cabinet technical specifications

Parameter Technical Specifications

External dimensions (H x W x D) 2000 mm x 600 mm x 1100 mm


Color Black
Material High-intensity class A carbon cold rolled
steel plate and zinc-coated steel plate
Air channel Front and rear air channels
Installation space 42 U available space
Weight 180 kg (excluding batteries)
Static load 1500 kg
Dynamic load 1000 kg
Protection level IP20

3.2.7 Battery Pack


 In the 2N scenario, six 9 Ah battery strings are configured (each battery string containing
two battery packs) to provide a power backup time of 10 minutes.
 In the N+X scenario, four 9 Ah battery strings are configured (each battery string
containing two battery packs) to provide a power backup time of 7.5 minutes.
The FusionModule1000 is configured with six 9 Ah battery strings (each battery string
containing two battery packs) to provide a power backup time of 10 minutes.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 32


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-27 Battery pack

Table 3-11 Battery pack specifications

Battery Pack Dimensions (H x W x D) Weight


Specifications

9 Ah 130 mm x 430 mm x 685 69 kg


mm

3.3 Cooling System


3.3.1 Overview
Half-sized variable frequency air-cooled air conditioners are used in the cooling system. The
air conditioners and cabinets form contained cold (hot) aisles to isolate hot air from cold air.
Air flows in from the rear and out of the front. Air conditioners cool hot air from servers and
generate cold air for servers. The features are as follows:
 Air conditioners are deployed close to heat sources and provides horizontal airflow. This
mechanism shortens the air supply distance, reduces airflow pressure loss, and
minimizes cold air leakage during air supply, thereby improving the cooling efficiency.
 Teamwork control ensures that air conditioners work in reasonable mode to improve
efficiency.
 Precision air conditioners with constant temperature and humidity and those with cooling
only can collaborate to dynamically control the temperature and humidity inside the
container.
Figure 3-28 shows the conceptual diagram of the cooling system.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 33


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-28 Cooling system conceptual diagram

Figure 3-29 shows the layout of cooling components.

Figure 3-29 Layout of cooling components

(1) Heating belt cable hole (2) Heating belt cable-routing board
(3) Air conditioner outdoor unit (4) Air conditioner indoor unit

The heating belt should be equipped for low temperature scenarios.

3.3.2 Composition
3.3.2.1 Indoor Unit

Appearance
Figure 3-30 shows the indoor unit of a NetCol5000-A cooled in-row precision air conditioner.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 34


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-30 Indoor unit

Components
The indoor unit consists of a compressor, oil separator, fan, heat exchanger, one-way-valve,
filter dryer, sight glass, electric heater (optional), electrode humidifier (optional), electronic
expansion valve, water pump (optional), display panel, and other components.
 Compressor
The DC variable-frequency compressor provides the cooling capacity ranging from 20%
to 100% to meet load requirements.
 Oil separator
It is an oil-gas separator which separates the lubricant brought out due to exhaustion of
the compressor and brings back the separated lubricant to the compressor.
 Fan
The EC fan implements stepless speed adjustment.
 Heat exchanger
The efficient finned evaporator, an important part in the refrigerating system, absorbs
heat from indoor air to ensure that the indoor temperature and humidity meet
requirements.
 Electronic expansion valve
The flow regulator uses a miniature controller to control the operation of the step motor,
thereby changing the pass-through area of the valve to regulate the flow of refrigerant.
 One-way valve
The one-way valve efficiently controls backflow of gas or liquid.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 35


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

 Filter dryer
The filter dryer absorbs moisture from the refrigerant pipes and filters out foreign
matters, which reduces the component damage probability and improves operating
efficiency and reliability of components.
 Sight glass
The sight glass allows users to observe the refrigerant flow and the content of gas and
liquid for easy maintenance and optimization.
 Electric heater
The PTC heater features quick start, large heating capacity, and even heat dissipation. It
has multiple protection mechanisms to ensure the secure and stable running of the
equipment.
 Electrode humidifier
The electrode humidifier provides stepless adjustment of humidification capacity and
precise control of indoor humidity.
 Water pump
The water pump provides power for top drainage with 4 m.
 Display panel
The 7-inch display panel with the true-color touchscreen provides user interfaces for
query, setting, monitoring, and maintenance.

3.3.2.2 Ports
Table 3-12 shows the physical ports on the NetCol5000-A in-row precision air conditioner.

Table 3-12 Port description

Item Specifications

Refrigerant liquid pipe Copper pipe, external diameter 5/8 inch, pressure resistance ≥
4.5 MPa, soldering
Refrigerant gas pipe Copper pipe, external diameter 3/4 inch, pressure resistance ≥
4.5 MPa, soldering
Humidifier water inlet Reserved port: BSPP 1/2 in.; thread connection
pipe
Top drainpipe Reserved interface: 1/2 inch reserved copper tube
Bottom drainpipe Reserved port: threaded port for copper pipe with a diameter
of 5/8 in

3.3.2.3 Operating Environment Specifications


Table 3-13 describes the operating environment specifications of the NetCol5000-A in-row
precision air conditioner.

Table 3-13 Operating environment specifications


Item Specifications

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 36


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Item Specifications

Operating 18–45°C
temperature
Operating 20%–80% RH
humidity
Storage –40°C to +70°C
temperature
Storage humidity 5%–95% RH (non-condensing)
Applicable  Work with NetCol500-A026 (including a low-temperature
outdoor component): –40°C to +45°C
temperature  Work with NetCol500-A026: –20°C to +55°C
Heating capacity 4 kW
Humidifier 1.5 kg/h
capacity
Protection level  Indoor unit: IP20
 Outdoor unit: IPX5
Installation mode Installed on an ESD floor or rack
Piping and Route pipes and cables from the top or bottom
cabling
Altitude 0–1000 m, derating at above 1000 m, max. 4000 m. For detailed
derating data, contact Huawei technical support.

Table 3-14 Humidifier inlet water quality requirements


Item Requirement Unit

Hydrogen ion 7–8.5 pH


Conductivity at 20°C (σ20)a 125–1250 µS/cm
a: If σ20 is less than 125 µS/cm, it takes a longer time for the humidifier to generate vapor
for the first time. If σ20 is greater than 1250 µS/cm, the humidifier service life is affected.

3.3.2.4 Technical Specifications


Table 3-15 and Table 3-16 describe the technical specifications of the NetCol5000-A in-row
precision air conditioner.

Table 3-15 Generic specifications


Item Specifications

Cooling mode Air cooled

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 37


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Item Specifications

Refrigerant R410A
Air supply mode Horizontal flow
Dimensions (H x W x D) 2000 mm x 300 mm x 1100 mm (cabinet dimensions)
Certification REACH, RoHS, CE

Table 3-16 Optional specifications

Item NetCol5000-A025H412D2 NetCol5000-A025H412D2


0020E1 E120E1

Power supply Dual power supplies Dual power supplies


Cooling capacity 25 kW
Air volume 5000 m3/h
Current 20 A 30 A
Power system Supports the 380–415 V, 3PH+N+PE, 50/60 Hz power
system, and applies to scenarios where the voltage range is
342–457 V and frequency range is 47–63 Hz.
Voltage tolerance Rated voltage±10%
If the upstream voltage fluctuation exceeds this range, add a
voltage stabilizer; otherwise, the air conditioner will
frequently generate alarms and fail to work
Frequency tolerance Rated frequency±3 Hz
Heating function No 4 kW
Humidification function No 1.5 kg/h
Piping Route pipes from the top or Route pipes from the top or
bottom bottom
Condensate pump Yes Yes
Pump lift 4m 4m
In the preceding table, No indicates that the corresponding model does not provide the
function.
Cooling capacity test conditions: dry bulb temperature at air return vent: 37.8°C; wet bulb
temperature at air return vent: 20.8°C; condensing temperature: 45°C

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 38


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

3.3.2.5 Outdoor Unit

Appearance
Figure 3-31 shows the model and appearance of the NetCol500 outdoor unit.

Figure 3-31 NetCol500 appearance

Product Composition
Figure 3-32 shows the composition of the NetCol500 outdoor unit.

Figure 3-32 Composition of the NetCol500 outdoor unit

(1) Fan (2) Rack (3) Fan drive

Specifications
Figure 3-33 shows the dimensions of the NetCol500.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 39


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-33 Dimensions of the NetCol500

Table 3-17 lists the technical specifications of the NetCol500 outdoor unit.

Table 3-17 Technical specifications of the NetCol500 outdoor unit

Product Model NetCol500-A0265S11E0

Power system 380–480 V AC, 3 Ph/N/PE, 50 Hz/60 Hz (for a


unit with a low-temperature component, the
power system is 380–415 V AC, 3 Ph/N/PE, 50
Hz/60 Hz)
Voltage tolerancea Rated voltage±10%
Frequency tolerance Rated frequency±3 Hz
Maximum current 2.5 A
Air volume 12,000 m3/h
Number of fans 1
Dimensions H x W1 (W2) x D 620 mm x 1120 (985) mm x 1094 mm
Liquid pipe outer diameter 5/8 in (15.9 mm)
Gas pipe outer diameter 3/4 inch (19.1 mm)
Net weight 132 kg
Certification RoHS, REACH, CE
Operating temperature Depends on the indoor unit. For details, see the
product overview in the indoor unit user
manual.
Storage temperature –40°C to +70°C
Storage humidity 5%–95% RH (non-condensing)

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 40


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Product Model NetCol500-A0265S11E0

Altitude 0–1000 m: normal use; above 1000 m: derating.


For derating details, see the product overview in
the indoor unit user manual delivered with the
equipment.
a: If the upstream voltage may fluctuate outside the voltage tolerance, add a voltage
stabilizer; otherwise, the air conditioner may fail to run properly due to frequent alarms.

Outdoor unit installation environments are classified as follows based on the harshness:
 Class A (controlled environment): indoor environments where the ambient temperature and humidity
are controlled, including rooms where people live
 Class B (uncontrollable environment): indoor environments where the ambient temperature and
humidity are not controlled or general outdoor environments with simple shielding measures where
the humidity sometimes reaches 100%
 Class C (harsh environment): marine environments within 3.7 km from the coast or outdoor land
environments with simple shielding measures within 1.2 km from a pollution source
 Class D (marine environment): environments within 500 m from the coast

The NetCol500-A026 cannot be used in class D environments.

3.3.3 Low-Temperature Component


Working Principle
When the outdoor temperature is below the operating temperature lower limit specified for the
product, the condensing pressure of the system for the outdoor unit condenser with natural
cooling may still below the safe operating pressure of the compressor. A low-temperature
component is required to address this issue.
The low-temperature component intelligently controls the condensing pressure to ensure that
the equipment can work safely and reliably at an outdoor ambient temperature as low as
–40ºC. When detecting that the outdoor condensing pressure is low, the pressure stabilizing
valve automatically opens to bypass hot gas to the liquid storage tank, thereby ensuring that
the condensing pressure stays in the range for safe and reliable operation. When detecting that
the condensing pressure exceeds the threshold, the pressure stabilizing valve automatically
closes the bypass.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 41


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-34 Low-temperature component

(1) Safety valve (2) Liquid line port 1 (3) Liquid line port 2
(4) Condensing pressure control valve (5) Gas pipe port 1 (6) Gas pipe port 2

A low-temperature component is mandatory when the outdoor ambient temperature may drop
below –20ºC.

Table 3-18 Low-temperature component specifications

Item Specifications

Heater box power supply 220 V AC to 240 V AC, 1 P, 50 Hz/60 Hz


Heater box voltage tolerance Rated voltage±10%
Heater box frequency tolerance Rated frequency±3 Hz
Refrigerant R410A
Liquid pipe outer diameter 5/8 inch (15.9 mm)
Gas pipe outer diameter 7/8 inch (22.3 mm)
Dimensions (H x W x D) 944 mm x 632 mm x 507 mm (with
packing)
828 mm x 470 mm x 300 mm (without
packing)
Expansion bolt hole M12x60
Storage temperature –40°C to +70°C
Storage humidity 5%–95% RH (non-condensing)
Maximum operating pressure 4.35 MPa

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 42


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

3.4 Management System


The FusionModule1000 uses the ECC800 for local monitoring by default, and the NetEco can
be configured.

Table 3-19 NetEco configuration scenario


Function ECC800 NetEco Remarks

Client authorization 6 PCS Basic license. One  A single


license manages up container can
to 25 smart nodes, contain 14 smart
and a maximum of nodes.
20 licenses can be  The number of
configured. smart nodes
applies to the
standard
configuration.
Optional license, N/A
subject to
on-demand
configuration.
Work order No Yes N/A
management
Energy efficiency Yes Yes N/A
management
Capacity No Yes N/A
management
SNMP northbound Yes Yes N/A
device alarm
SNMP northbound Yes Yes N/A
device data
monitoring
Mobile app O&M Yes Yes N/A
NE data and alarm Yes Yes N/A
monitoring
Access management Yes Yes N/A
Intelligent lighting Yes Yes N/A
View presetting Yes No (manually drag) N/A
Adaptive software ECC800 NetEco N/A
version V100R001C20 V600R007C80 and
later

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 43


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Function ECC800 NetEco Remarks

Configuration Standard Optional: N/A


principle configuration  Single-container
deployment:
advise the
customer not to
configure.
 Multiple-contain
er deployment:
advise the
customer to
configure for
managing
multiple sites
through one port.
Hardware N/A  LAN switch: The It is recommended
configuration number of that the NetEco
connected ports hardware be
depends on the deployed in the
number of customer's
connected monitoring room to
ECC800s. It facilitate central
usually occupies monitoring of
1 U space. distributed sites.
 Server: It is If the NetEco is
configured for deployed inside the
the NetEco and container, it
usually occupies occupies space for
2 U space. server cabinets. It is
 1 U cabling recommended that
space the NetEco be
deployed under the
ECC800 in the A1
cabinet.

NetEco V600R007C80 or a later version is applicable to the FusionModule1000. The iManager NetEco
configurator can be used for configuration.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 44


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-35 Monitoring network diagram

 The VESDA, rack environment unit, and hydrogen controller are optional components.
 Common card readers are configured for the access control system by default, and they should be
used at an ambient temperature ranging from –40°C to +85°C. Customized three-in-one fingerprint
and card readers with keypads are also supported, and they should be used at an ambient temperature
ranging from –10°C to +55°C. The three-in-one card readers cannot be used outdoors when the
ambient temperature is below –10°C or exceeds 55°C.
 The camera uses an SD card with a capacity of 64 GB for storage by default, and supports 7x24
recording at 720P/512K. A video management device (VCN500) should be configured if there is a
need of longer-time storage, management, and configuration of external cameras.

3.4.1 Overview
The management system includes the management software NetEco (optional) and
management hardware ECC800 and provides the following linkage features:

Hydrogen Linkage
If the hydrogen sensor and hydrogen controller are configured, the hydrogen controller
controls the hydrogen exhaust fan.

Fire Linkage
The ECC800 monitors the fire control panel onsite. Upon detecting a gas release alarm, the
ECC800 issues a release command to the air conditioners in the FusionModule1000 so that
they will shut down.

For the sake of safety, this function is disabled by default.

Component Layout
Figure 3-36 shows the management system component layout diagram.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 45


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-36 Layout of management components

(1) Cameras (2) Rack-A1 cabinet (3) Smart ETH gateway


(4) Access actuator (5) Pad (6) WiFi converter
(7) AC actuator

The ECC800 and independent deployment AI/DI unit are deployed in the Rack-A1 cabinet.

3.4.2 ECC800
The ECC800 manages the real-time status, alarm information, and configuration information
of devices (including the PDC, air conditioner, AC/DC power system, environment sensors,
lights, access controllers, PDC monitoring units, and fire extinguishing system) inside a
container, and provides a GUI for O&M. It consists of two power supply units (PSUs) and
one ECC800 monitoring module.
Figure 3-37 and Figure 3-38 show an ECC800 controller.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 46


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-37 ECC800 controller (front view)

(1) PSU (2) Status indicator (3) 3G/4G antenna port


(4) FE ports (WAN_1-WAN_2 and (5) AI/DI_1–6 sensor (6) RF_Z antenna port
LAN_1-LAN_2) input ports
(7) SW button (8) DO_1–2 dry (9) RS485 port
contact output (COM1–4/12 V)
(10) Default button (11) USB port (12) ECC800 main
control module

Figure 3-38 ECC800 controller (rear view)

(1) 53.5 V DC_OUT1 (2) 53.5 V DC_OUT2


(3) AC_INPUT1 (4) AC_INPUT2

Specifications
Table 3-20 lists the ECC800 technical specifications.

Table 3-20 ECC800 technical specifications

Item Specifications

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 47


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Item Specifications

Power input  Dual AC input and dual –48 V DC power supply


 Rated voltage: 200–240 V AC/100–120 V AC
 Rated frequency: 50 Hz/60 Hz
 Input current: 6.7 A
Power output  Rated voltage: 53.5 V DC
 Output power of two power supplies: 2000 W (176–300 V AC);
940 W (linear derating at 85–175 V AC)
 Output power of a single power supply: 1000 W (176–300 V
AC); 470 W (linear derating at 85–175 V AC)
 Output current: 14 A
System memory 512 MB
Solid state disk 2 GB and 128 MB of storage space
FE port expansion Two WAN ports, two LAN ports, and 10/100M communications
rate
RS485 serial port  Reserves four RS485 ports with a default communications rate
expansion of 9600 bit/s.
 Each port provides 12 V DC power with a rated current of 450
mA.
AI/DI expansion  Supports six AI/DI ports to connect to smoke sensors, water
(RJ45) sensors, and temperature sensors.
 Each port provides 12 V DC power with a rated current of 85
mA.
DO expansion  Supports two expansion dry contacts with contact point capacity
(RJ45) of 20 W, maximum withstand voltage of 60 V DC, and rated
current of 0.5 A.
 Supports two active DO ports with the output voltage of 12 V
DC and output current of 450 mA.
Wireless Supports wireless communication that complies with
communication IEEE802.15.4.
3G Supports 3G (WCDMA) communication and is compatible with 2G
(GSM) communication. A standard SIM card slot is provided.
NOTE
A SIM card can be used only in sites with signal coverage.

USB Provides a general USB port.


Button  SW: wireless network pairing button
 Default: restores the default IP address

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 48


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Indicators
Table 3-21 describes the indicators on the ECC800 monitoring module.

Table 3-21 Indicators on the ECC800 monitoring module


Indicat Color Name Status Description
or

RUN Green Running status Steady on The power supply is normal, the
indicator program is being loaded, or
WiFi WPS is pairing.
Off The power supply is abnormal.
Blinking at The software runs properly (the
long indicator blinks at 0.5 Hz, on for
intervals 1s and then off for 1s) or the
ECC800 registers with the
NetEco successfully.
Blinking at The ECC800 does not register
short with the NetEco (the indicator
intervals blinks at 4 Hz, on for 0.125s and
then off for 0.125s).
ALM Red Alarm indicator Steady on A system failure alarm is
generated.
Off The system is normal.
3G Green 3G status Steady on The 3G module is powered on.
indicator
Off The 3G module stops running,
or no 3G module is configured.
Blinking at The 3G module succeeds in
long dial-up (the indicator blinks at
intervals 0.5 Hz, on for 1s and then off
for 1s).
Blinking at The 3G module registers with
short the operator network
intervals successfully (the indicator
blinks at 4 Hz, on for 0.125s and
then off for 0.125s).
RF_Z Green Communication Steady on No network parameters exist, or
status indicator a network is to be created.
Blinking at A network is set up, and no
long node access is allowed (the
intervals indicator blinks at 0.5 Hz, on for
1s and then off for 1s).

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 49


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Indicat Color Name Status Description


or

Blinking at A network is set up, and node


super short access is allowed (the indicator
intervals blinks at 10 Hz, on for 0.05s and
then off for 0.05s).

Table 3-22 describes the indicators on the PSU.

Table 3-22 Indicators on the PSU

Indicator Colo Name Status Description


r

Gree Power Steady on The converter has a power input.


n indicator
Off The converter has no power input or
is faulty.
Blinking at The converter is being queried (the
long intervals indicator blinks at 0.5 Hz, on for 1s
and then off for 1s).
Blinking at The converter application program
short intervals is being loaded (the indicator blinks
at 4 Hz, on for 0.125s and then off
for 0.125s).
Yell Alarm Steady on The converter generates a
ow indicator forewarning indicating that power
will be limited due to ambient
overtemperature, or generates a
protection shutdown alarm due to
ambient overtemperature or
undertemperature.
Power input overvoltage or
undervoltage protection
Reverse DC input connection
Slight current imbalance
Output overvoltage
Hibernation
Off The converter generates no
protection alarms.
Blinking at The communication between the
long intervals converter and the outside is
interrupted (the indicator blinks at
0.5 Hz, on for 1s and then off for
1s).

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 50


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Indicator Colo Name Status Description


r

Red Fault Steady on The converter locks out due to


indicator output overvoltage.
The converter delivers no output
due to internal faults.
Off The converter is working properly.

Wireless Network Pairing (SW) and IP Address Reset (Default) Buttons


Table 3-23 describes the wireless network pairing and IP address reset buttons.

Table 3-23 Wireless network pairing and IP address reset buttons

Button Function Operation Description Indicator Status


Name Description

SW Wireless In non-wireless network (802.15.4) The RF_Z indicator


network pairing mode, press and hold down is blinking at super
(802.15.4) the button for 1.2s to 5s to enter the short intervals.
pairing wireless network pairing mode.
In wireless network (802.15.4) The RF_Z indicator
pairing mode, press and hold down is blinking at long
the button for 1.2s to 5s to exit the intervals.
pairing mode; or the system
automatically exits the pairing mode
after 30 minutes without pressing
the button.
Press and hold down the button for The RF_Z indicator
more than 6s to clear network is on.
parameters.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 51


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Button Function Operation Description Indicator Status


Name Description

WiFi pairing In non-WiFi pairing mode, press the  When the system
button button for less than 1.2s to enter the enters the pairing
WiFi pairing mode. mode, the RUN
indicator is
steady on.
 After pairing
succeeds, the
RUN indicator
blinks just as
before WiFi
pairing.
 If pairing does
not succeed in
three minutes, the
RUN indicator
blinks just as
before WiFi
pairing.
Default IP address reset Press and hold down the button for None
3s. Then the IP address for the
ECC800 WAN_1 port will be
restored to the default address
192.168.1.10.

On the WebUI, restoring factory settings by one-click is supported. Click Maintenance >
Configuration File > Restore Factory Settings.
 The monitoring module IP address restores to the default value.
 The video device IP address restores to the default value.
 Configuration parameters of each device restore to default values (except the access control
configuration parameters).
 The container plan view configuration is cleared.
 Alarm parameter configuration restores to default values.
 The NetEco communication parameters restore to default values.
 The container name restores to the default value.
 The WiFi function is disabled.
 The time and time zone restore to default values.

3.4.3 Independent Deployment AI/DI Unit


An independent deployment AI/DI unit provides a maximum of eight AI/DI inputs to collect
AI/DI signals. It can be mounted on a 19-inch rack.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 52


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-39 Ports on an independent deployment AI/DI unit

Table 3-24 Ports on the independent deployment AI/DI unit front panel
Silk Screen Port Description

COM_IN Cascading ports. COM_IN connects to the RS485 port on the ECC800, and
COM_OUT COM_OUT connects to another independent deployment AI/DI unit.

AI/DI_1–AI/ Provide 12 V DC outputs for sensors and are compatible with 4–20 mA
DI_8 current signals, signals from current-based smoke sensors and water
sensors, dry contact signals, and NTC signals.
Pin definition:
3: 12 V DC, 54 mA
6: D-
7: D+
8: GND

3.4.4 Smart ETH Gateway


A smart ETH gateway allows the extension of the 53.5 V DC power supply and FE
communication for the ECC800 and can be flexibly deployed in a FusionModule1000 data
center.

Figure 3-40 Smart ETH gateway

(1) PWR_IN cascading (2) FE_1 cascading signal (3) PoE_1–2 ports
power port port

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 53


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

(4) PoE_3–4 ports (5) 48V_OUT1 power output (6) 48V_OUT2 power
port output port
(7) FE_2 cascading signal (8) PWR_OUT cascading (9) BLINK button
port power port
(10) Status indicator

Specifications
Table 3-25 lists the environmental specifications for a smart ETH gateway.

Table 3-25 Technical specifications for a smart ETH gateway

Item Specifications

Power input PWR_IN D-type power input terminal, for power cascading, input voltage
range: 45–55 V DC
Power output  PWR_OUT D-type power output terminal, for power cascading, output
voltage range: 45–55 V DC
 48V_OUT1 and 48V_OUT2, phoenix terminal, output voltage range:
45–55 V DC
FE port Two FE ports, RJ45 terminal with an indicator, 10/100M communication
rate, for the cascading between smart ETH gateways and the
communication with the upstream computer
PoE port Four PoE ports, RJ45 terminal with an indicator, 10/100M
communications rate, 12 V DC of power output, complying with
IEEE802.3at
BLINK If you press the BLINK button, the RUN indicator blinks intermittently at
button super short intervals (blinking at super short intervals for 0.5s and then off
for 0.5s) for 10 seconds. This indicates that the smart ETH gateway
reports the Media Access Control (MAC) address and equipment serial
number (ESN) to the ECC800.

Indicators
Table 3-26 describes the indicators on a smart ETH gateway.

Table 3-26 Indicators on a smart ETH gateway

Indicat Col Name Status Description


or or

PWR Gree Power input Steady on The power input is normal.


n status indicator
Off There is no power input.
RUN Gree Module Off The power supply is abnormal.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 54


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Indicat Col Name Status Description


or or
n running status Blinking at The smart ETH gateway
indicator long intervals successfully registers with the
ECC800 and the software runs
properly (the indicator blinks at 0.5
Hz, on for 1s and then off for 1s).
Blinking at The smart ETH gateway does not
short intervals register with the ECC800 (the
indicator blinks at 4 Hz, on for
0.125s and then off for 0.125s).
Blinking The indicator blinks at super short
intervals for 0.5s (blinking at 10 Hz,
on for 0.05s and then off for 0.05s)
and then turns off for 0.5s. The
cycle lasts for 10s.
ALM Red Alarm indicator Steady on A system failure alarm is generated.
Off No system alarm is generated.

3.4.5 Access Actuator


The access actuator is the control component for the front door in a modular data center of a
prefabricated all-in-one data center. It connects to the ECC800 controller system over the FE
port, wireless networking (802.15.4), or RS485 port. It opens the magnetic lock by detecting
the card swiping information of the card reader, door open button information, and fire
linkage information. It has access right management, access event recording, and alarm
recording functions.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 55


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-41 Access actuator

(1) 48 V power port (2) PoE port (3) RS485 port COM2
(4) RS485 port COM1 (5) Address DIP switch (6) Status indicator
(7) BLINK button (8) WG_2 Wiegand (9) WG_1 Wiegand interface
interface
(10) AI/DI_2 dry contact (11) AI/DI_1 dry contact (12)
LOCK/GND/GATE/GND/door
status and magnetic lock port

Specifications
Table 3-27 lists the access actuator technical specifications.

Table 3-27 Access actuator technical specifications

Item Specifications

Power input 36–60 V DC input voltage, phoenix terminal


PoE port FE communication, 10/100M communications rate, 12 V DC power
output
Wireless One wireless communication port that complies with IEEE802.15.4,
communicatio mutual backup with FE communication
n
AI/DI port Two AI/DI ports, can connect to the fire alarm and exit button
DO output One 12 V DC power output that controls magnetic locks, phoenix terminal

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 56


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Item Specifications

DI input One DI input port for connecting to the door status switch
RS485 serial Two RS485 ports (one route) with the default communications rate of
port 9600 bit/s, physical port cascading supported (reserved function)
expansion
Wiegand Two Wiegand interfaces, 12 V DC card reader operating power output;
interface two routes of card readers can operate at the same time.
BLINK  Press the button for less than 1 second to start blinking.
button  Hold down the button for 1–5 seconds to search for a network and start
networking.
 Hold down the button for more than 6 seconds to clear network
parameters.
Address DIP 4-pin address DIP switch
switch
E-label Supported

Indicators
Table 3-28 describes the access actuator indicators.

Table 3-28 Access actuator indicator description

Indicat Col Name Status Description


or or

PWR Gree Power input Steady on The power input is normal.


n status indicator
Off There is no power input.
RUN Gree Communication Off The power is abnormal or the board
n status indicator program is loading.
Blinking at The access actuator successfully
long intervals registers with the ECC800 and the
software runs properly (the
indicator blinks at 0.5 Hz, on for 1s
and then off for 1s).
Blinking at The communication is disconnected
short intervals or the access actuator fails to
register with the ECC800 (the
indicator blinks at 4 Hz, on for
0.125s and then off for 0.125s).
Blinking The indicator blinks at super short
intervals for 0.5s (blinking at 10 Hz,
on for 0.05s and then off for 0.05s)
and then turns off for 0.5s. The
cycle lasts for 10s.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 57


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Indicat Col Name Status Description


or or

ALM Red Alarm indicator Steady on A system failure alarm is generated.


Off No system alarm is generated.
RF_Z Gree Wireless Steady on No network parameters exist, or a
n communication network is to be created.
status indicator
Blinking at A network is set up, and no node
long intervals access is allowed (the indicator
blinks at 0.5 Hz, on for 1s and then
off for 1s).
Blinking at A network is set up, and node
super short access is allowed (the indicator
intervals blinks at 10 Hz, on for 0.05s and
then off for 0.05s).
Blinking The access actuator is searching for
intermittently a network (the indicator blinks at
at super short super short intervals for 0.5s and
intervals then turns off for 0.5s).

Communications Ports
The access actuator provides one DO port (LOCK/GND) and one DI port (GATE/GND).
Table 3-29 lists the LOCK/GND/GATE/GND port pin definitions.

Table 3-29 LOCK/GND/GATE/GND port pin definitions

Item Description

LOCK/GND LOCK 12V_OUT


(control
magnetic GND GND
locks) pin
sequence
GATE/GND GATE DI1
(door status)
pin sequence GND GND

3.4.6 AC Actuator
The AC actuator is used in a container data center to receive infrared signals or upstream
instructions for controlling lights or fans. The AC actuator can connect to the ECC800
controller by wireless networking (802.15.4).

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 58


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-42 AC actuator

(1) AC OUT2 port (2) AC OUT1 port (3) AC IN port


(4) Status indicator (5) BLINK button (6) AI/DI dry contact
(7) COM1–2 RS485 port

Specifications
Table 3-30 lists the AC actuator environmental specifications.

Table 3-30 AC actuator technical specifications

Item Specifications

Power input One AC input, 90–240 V AC


Power output Two AC outputs, 90–240 V AC, maximum current 5 A
Wireless One wireless communication port, complying with IEEE802.15.4
communicatio
n
RS485 port One route of dual RS485 ports, not isolated (reserved)
AI/DI Two AI/DI dry contacts, reserved
detection

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 59


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Item Specifications

BLINK  Press the button for less than 1 second to start blinking.
button  Hold down the button for 1–5 seconds to search for a network and start
networking.
 Hold down the button for more than 6 seconds to clear network
parameters.

Indicators
Table 3-31 describes the indicators on the AC actuator.

Table 3-31 AC actuator indicators

Indicat Col Name Status Description


or or

Power Gree Power status Steady on The power input is normal.


n indicator
Off There is no power input.
RUN Gree Running status Off The power is abnormal or the board
n indicator program is loading.
Blinking at The AC actuator successfully
long intervals registers with the ECC800 and the
software runs properly (the
indicator blinks at 0.5 Hz, on for 1s
and then off for 1s).
Blinking at The communication is disconnected
short intervals or the AC actuator fails to register
with the ECC800 (the indicator
blinks at 4 Hz, on for 0.125s and
then off for 0.125s).
Blinking The indicator blinks at super short
intervals for 0.5s (blinking at 10 Hz,
on for 0.05s and then off for 0.05s)
and then turns off for 0.5s. The
cycle lasts for 10s.
ALM Red Alarm indicator Steady on A system failure alarm is generated.
Off No system alarm is generated.
RF_Z Gree Communication Steady on No network parameters exist, or a
n status indicator network is to be created.
Blinking at A network is set up, and no node
long intervals access is allowed (the indicator
blinks at 0.5 Hz, on for 1s and then
off for 1s).

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 60


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Indicat Col Name Status Description


or or

Blinking at A network is set up, and node


super short access is allowed (the indicator
intervals blinks at 10 Hz, on for 0.05s and
then off for 0.05s).
Blinking The AC actuator is searching for a
intermittently network (the indicator blinks at
at super short super short intervals for 0.5s and
intervals then turns off for 0.5s).

3.4.7 WiFi Converter


The WiFi converter is used in the FusionModule1000 to convert PoE signals into WiFi signals
for communicating with devices such as the pad and mobile phone.

Figure 3-43 WiFi converter

(1) RF_1 antenna port (2) RF_2 antenna port (3) Reset (4) WPS button
(5) Status indicator (6) 48 V power port (7) PoE port

Technical Specifications
Table 3-32 lists the WiFi converter technical specifications.

Table 3-32 WiFi converter technical specifications

Item Specifications

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 61


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Item Specifications

Power input One power input port with the 3-pin Phoenix terminal; input voltage
range: 36–60 V DC
WiFi function  2.4 GHz frequency, two antennas, supporting eight STA connections,
50 m WiFi coverage (no blockage)
 Support the WPS button
PoE port One PoE port, complying with IEEE802.3AT, 25.5 W
Reset button Press and hold down the button for more than 5s to restore the factory
settings of the WiFi converter
WPS button Support fast WiFi access by WPS

WPS function: If you choose Advanced settings > WPS connection on the WLAN of the intelligent
device and press the WPS button on the WiFi converter at the same time, the intelligent device will
quickly connect to the WiFi hotspot of the container.

Indicators
Table 3-33 describes the indicators on the WiFi converter.

Table 3-33 WiFi converter indicators


Indicat Col Name Status Description
or or

RUN Gree Running status Steady on The power supply is normal.


n indicator
Off The power supply is abnormal.
Blinking at The WiFi converter successfully
long intervals registers with the ECC800 and the
software runs properly (the
indicator blinks at 0.5 Hz, on for 1s
and then off for 1s).
Blinking at The WiFi converter fails to register
short intervals with the ECC800 or the
communication is disconnected (the
indicator blinks at 4 Hz, on for
0.125s and then off for 0.125s).
ALM Red Alarm indicator Steady on A system failure alarm is generated.
Off No system alarm is generated.
WiFi Gree WiFi status Steady on The WiFi converter is powered on
n indicator but there is no data communication.
Blinking Data communication is in progress.
WPS Gree WPS mode Off The WPS is normal.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 62


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Indicat Col Name Status Description


or or
n indicator Blinking WPS matching mode. If the
matching fails, the WPS indicator
turns off after blinking for 2
minutes. If the matching is
successful, the WPS indicator turns
off.

3.4.8 IP Camera
An IP camera (IPC) IPC6325 is deployed inside a container. The camera has the following
features:
 Support for the H.265 encoding format and dual-channel 1080p HD video encoding
 Built-in 2.8 mm to 12 mm HD zoom lens, enabling more flexible surveillance
 IP66 waterproof and dustproof rate, ensuring that the camera can run reliably outdoors
for a long time
 IK10 vandal-proof rate, preventing video surveillance interruption due to violent
damages to the camera
 Compliance with the railway industry certification, applicable to trackside scenarios
 A super WDR of 120 dB, ensuring that both foreground and background objects are
clearly identified in environments with sharp light contrast
 Intelligent defogging, enhancing image definition in foggy environments
 Intelligent infrared lamp, automatically adjusting the infrared transmit power and angle
 Five intelligent behavior analysis functions, color classification, human and vehicle
classification
 Super Error Concealment (SEC) to ensure smooth images in case of 20% network packet
loss rate
 Transmission quality diagnosis through Packet Conservation Algorithm for Internet
(iPCA)
 Acousto-optic assisted focus, ensuring higher installation and commissioning efficiency
 An ultra wide operating temperature that ranges from –30°C to +60°C
 An ultra wide operating voltage range of ±25%
 PoE, DC, and AC power supply modes; DC/AC power adapter and PoE in hot standby
mode

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 63


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-44 IPC6325 camera

Table 3-34 lists the IPC6325 camera technical specifications.

Table 3-34 Technical specifications of IPC6325

Parameter Value

Camera Image sensor 1/2.7" 2.0-megapixel progressive scan CMOS


Maximum 1920 (H) x 1080 (V)
image
resolution
Minimum  Multicolor: 0.01 lux (F1.4, AGC ON)
illumination  B/W: 0.004 lux (F1.4 and AGC on)
 B/W (infrared lamp enabled): 0 lux
Maximum 30 m
infrared
radiation
distance
Day/Night Automatic, Multicolor, or B/W (ICR)
mode
Electronic 1/100000s to 1s
shutter speed
Gain control Automatic or manual
WDR 120 dB
Backlight Supported
compensation
(BLC)
Image Automatic or manual
defogging
White balance Automatic/Automatic tracking/Manual/OnePush; support for
scene selection (indoor/outdoor/incandescent lamp/fluorescent
lamp)

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 64


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Parameter Value

Digital noise Self-adaptive to 2D or 3D DNR


reduction
(DNR)
Lens Focal length 2.8 mm to 12 mm manual focus, 4.3x optical zoom
Angle of view  Horizontal: 36°(telephoto) to 106°(pantoscopic)
 Vertical: 20°(telephoto) to 57°(pantoscopic)
Maximum iris F1.4
Automatic iris DC iris
Three-axis Horizontal: 0°to 356°; vertical: 0°to 75°; rotation: 0°to 356°
adjustment
angle
Functio Video H.265/H.264/MJPEG
n encoding
format
Maximum 1920 x 1080
resolution
Frame rate  60 Hz: 1 fps to 30/20 fps
 50 Hz: 1 fps to 25/20 fps
Video bit rate 32 kbit/s to 16 Mbit/s
Multi-channel Support for three channels of streams and dual-channel 1080p
video encoding HD video encoding
Audio G.711a/G.711u/G.726/OPUS
encoding
format
Voice Voice intercom and broadcast
communication
PU access ONVIF Profile S/G, GB/T 28181-2014, Genetec Protocol
protocol v1.00, and Huawei SDK (proprietary)
Network TCP, UDP, IPv4, DHCP, DNS, ICMP, IGMP, HTTP, HTTPS,
protocol SFTP, RTP, RTSP, RTCP, SIP, ARP, TLS, NTP, SNMP
(V1/V2/V3), 802.1x, QoS, and DDNS
Security mode User name and password authentication, 802.1x (MD5
Challenge/EAP-TLS), and HTTPS digital certificate
Media security Stream encryption using the AES128/192/256 encryption
algorithm; support for digital watermark
Intelligent Support for tripwire detection, loitering detection, intrusion
video analysis detection, abandoned object detection, removed object
detection, object color identification, human and vehicle
classification, and metadata backhaul

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 65


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Parameter Value

Motion Support for four motion detection and lens block detection
detection and areas
lens block
detection
Alarm linkage  Alarm source: motion detection alarm/lens block
alarm/alarm input/intelligent analysis alarm
 Alarm linkage: alarm output/preset position
invoking/scanning during parking actions/SD card video
recording/snapshot taking
Interfac Network One RJ45 10/100 Base-T adaptive Ethernet interface
e interface
Communicatio One RS-485 interface
n serial
interface
Alarm interface 1-channel alarm input, 1-channel alarm output
Video interface BNC interface; 1-channel hybrid analog video output through
the CVBS interface
Audio interface Support for 1-channel audio input and 1-channel audio output
through 3.5 mm audio interfaces
Storage One Micro SD card slot that supports SDHC or SDXC cards
interface (maximum capacity: 64 GB)
General Power supply PoE (802.3at/af), 18 V AC to 30 V AC, 18 V DC to 30 V DC,
specific 9 V DC to 15 V DC (non-polarity DC); DC/AC power adapter
ations and PoE in hot standby mode
Power Typical power consumption: 4 W; maximum power
consumption consumption: 10 W
Operating –30°C to +60°C
temperature
Operating 5% RH to 95% RH (noncondensing)
humidity
Surge 4 kV surge protection that meets the IEC 61000-4-5 standard
protection level
Anti-corrosion Compliance with the ISO9223 C4 corrosion resistance
standard and the IEC 60068-2-11 standard
Protection rate IP66 (meeting the IEC 60529 standard)
Vandal-proof IK10 (meeting the IEC 62262 standard)
rate
Railway Compliance with the EN 50121-4 EMC standard and
industry EN50125-3 anti-vibration standard
certification

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 66


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Parameter Value

Weight Net weight: 1 kg; gross weight: 1.4 kg


Physical Φ135 mm x 112.5 mm
dimensions
Packing 260 mm x 195 mm x 148 mm
dimensions

3.4.9 Water Sensor


The water sensor monitors water leaks on the floor in real time. When water intrusion is found,
the water sensor generates an audible alarm and delivers dry contact signals to report the
alarm.

Figure 3-45 Water sensor

Table 3-35 Water sensor technical specifications

Item Specifications

Operating voltage 12 V DC (9–16 V DC)


Signal output under the CLOSED
condition of no liquid detected
Signal output under the OPEN
condition of liquid detected
Insulation resistance > 500 megohms
Operating temperature –20°C to +70°C
Storage temperature –40°C to +85°C (non-condensing)
Protection level IP68
Length of the signal cable 1m
Reliability Failure rate: 8000 fits
Power consumption < 0.2 W

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 67


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

3.4.10 Pad
The pad allows the wireless access from the container data center management system. You
can monitor the equipment in the container data center and environmental parameters in real
time over the APP.

Table 3-36 Structural specifications

Item Specifications

Dimensions (L x 248.5 mm x 150 mm x 8.3 mm


W x H)
Weight 430 g
Touchscreen 9.6-inch, 800X1280, IPS screen 1600 million colors, and capacitive
5-point touch
Chip processor MSM8916, four cores, 4xA53@1.2 GHz
WLAN 802.11a/b/g/n@2.4 GHz&5 GHz
Storage  ROM: 16 GB
 RAM: 2 GB
 Expansion card: micro SD (TF), a maximum of 64 GB supported
Button/Port  Power switch and volume button
 3.5 mm stereo headphones port
 Micro SD card port
 Micro-USB port that supports charging and synchronization with
PC data
Battery  Materials: Li-polymer
 Capacity: 4800 mAh
 Standby time: about 570 hours
 Power adapter charge time: about 5–6 hours
Operating Android 4.4 (KitKat)+Emotion UI 3.0
system

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 68


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

3.4.11 Rack Environment Unit (Optional)


Figure 3-46 Rack environment unit

(1) Ground port (2) 48 V DC power input (3) PoE port (4) COM1/12 V
port port
(5) COM2/12 V (6) COM3 port (7) COM4 port (8) NTC1–3
port
(9) NTC4–6 (10) AI/DI_1 port (11) AI/DI_2 port (12) 12V_1 port
(13) 12V_2 port (14) SW button (15) Status
indicator

Technical Specifications
Table 3-37 lists the technical specifications for the rack environment unit.

Table 3-37 Technical specifications for the rack environment unit

Item Specifications

Power input Phoenix terminal, with input voltage of 36–60 V DC


12 V power Two 12 V DC power outputs with the rated output current of 250 mA
output
PoE port  FE communication with the rate of 10/100M
 12 V DC power output
RS485 serial  Four RS485 ports with a default communications rate of 9600 bit/s
port  Among the four RS485 ports, two support 12 V DC, 400 mA power
expansion output.
 The other two are isolated, with the default communications rate of
9600 bit/s, and do not support power output.
AI/DI input Two active 12 V DC, 200 mA AI/DI input ports
Temperature Provides two RJ45 ports to connect to six temperature sensors, each RJ45
sensor port port connecting to three temperature sensors.
BLINK Provides a BLINK button.
button

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 69


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Indicators
Table 3-38 describes the rack environment unit indicators.

Table 3-38 Indicator description

Indica Color Name Status Description


tor

PWR Green Power input Steady on The power input is normal.


status
indicator Off There is no power input.

RUN Green Module Off The power is abnormal or the board


running status program is loading.
indicator
Blinking at The software runs properly (the
long indicator blinks at 0.5 Hz, on for 1s
intervals and then off for 1s).
Blinking at PoE communication fails (the
short indicator blinks at 4 Hz, on for
intervals 0.125s and then off for 0.125s).
Blinking The indicator blinks at super short
intervals for 0.5s (blinking at 10 Hz,
on for 0.05s and then off for 0.05s)
and then turns off for 0.5s. The
cycle lasts for 10s.
ALM Red Alarm Steady on A system failure alarm is generated.
indicator
Off No system alarm is generated.

3.4.12 Cabinet Access Control System (Optional)


Cabinet-level access control is available for containers to further improve the data and device
security.
The cabinet access control system has the following features:
 The IC card for the cabinet access control system can be used after being authorized by
using software.
 An IC card can be authorized for one electric lock or for all electric locks.
 Door opening events can be logged in the management system.
 The system displays the status of cabinet doors and locks in real time, and generates
alarms for unauthorized door opening.
 The system supports remote door opening by using the NMS (network management
system).
Figure 3-47 shows a cabinet electronic lock. Table 3-39 lists its technical specifications.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 70


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-47 Cabinet electronic lock

Table 3-39 Technical specifications


Item Specifications

Rated input voltage 12–24 V DC


Rated current 200–300 mA
Lock opening mode By powering on the lock
Available card IC card
Supporting mechanically unlocking Yes

3.4.13 Intelligent Battery Monitoring System (Optional)


The intelligent battery monitoring system consists of a CIM (CIM01C2) and BIMs
(BIM01C3/BIM02C1), and is configured when the iBAT is required.

CIM
The Communication Interface Module (CIM) is an intelligent battery management module
which collects wireless communication data from the downstream BIM groups, collects the
operating data of battery strings, calculates State Of Charge (SOC) and State Of Health (SOH)
of batteries and battery strings, estimates the battery health status, supports battery tripping
management, and uploads data to the MDU/ECC through RS485 or PoE ports.
 Collects battery data detected by the BIM through wireless communication.
 Each CIM can manage a maximum of four battery strings or 300 batteries.
 An external Hall effect sensor is connected to monitor the current of each battery string.
 Calculates the SOC and SOH of batteries and battery strings.
 Accurately identifies weak batteries in a battery string.
 Identifies loose battery terminals and battery terminal overtemperature, and controls
battery switch tripping.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 71


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

 Supports WebUI display, northbound communication over FE and RS485, and a


third-party NMS.
 Supports CIM and BIM online upgrade on an upstream management unit.

If the upgrade package is transmitted to the CIM within 30 minutes, the upgrade is complete. The BIM
upgrade is finished through the CIM backend. The CIM ensures the successful upgrade of the BIM
through retransmitting and flow control.

Figure 3-48 shows the CIM front view, and Figure 3-49 shows the CIM rear view.

Figure 3-48 CIM front view

(1) –48 V 0.5 A port (power (2) PoE port (3) COM_IN port (RS485
input) communication input)
(4) COM_OUT port (RS485 (5) DI and DO ports (6) HALL_1–HALL_8 current
communication output) monitoring ports
(7) RF_Z antenna port (8) BCB_1–BCB_4 (9) BCB_OUT and BCB_IN
ports ports
(10) Networking switch (11) PWR indicator (12) RUN indicator
(13) ALM indicator (14) RF_Z indicator (15) Delivered antenna

Ports support the security mechanism.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 72


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-49 CIM bottom view

(1) Fastener (2) Micro SD card (3) Default button


slot (IP reset)
(4) ADDR dual in-line package (DIP) switch (5) 12 V 2 A port
(RS485 communication address) (power input)

BIM
The BIM (BIM01C3) is a battery monitoring module that supports 12 V power input and
monitors the voltages, internal resistances, and pole temperatures of batteries.
 Monitors the voltages, internal resistances, and pole temperatures of batteries.
 Provides the hibernation function (when it detects that the battery voltage is low, it turns
the battery to low-consumption mode).
 Uploads battery data to CIM through wireless communication.
Figure 3-50 show the front and bottom views of a BIM.

Figure 3-50 BIM front view

(1) RUN/ALM indicator (2) Networking switch

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 73


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

(3) Panel port (4) Fastener

3.4.14 External Camera (optional)


An external camera IPC6211 is deployed outside a container. The camera has the following
features:
 Intelligent infrared lamp power adjustment and a maximum infrared radiation distance of
30 meters
 Built-in motorized zoom and focus lens that supports manual, automatic, OnePush, and
synchronous focus
 An aspect ratio of 9:16
 Region of Interest (ROI) encoding
 Defogging
 Stream smoothing parameter configuration, adaptive bandwidth, MTU configuration,
and QoS configuration
 IP address filtering, stream AES encryption, and 802.1x access authentication
 Quick configuration of ISP and stream packages
 ISP package plan setting
 Ultra wide operating voltage range and ultra wide operating temperature range
 DC, AC, PoE power supply modes
 Dual system backup, ensuring faster upgrade and higher security
Figure 3-51 shows the appearance of IPC6211. Table 3-40 describes its technical
specifications.

Figure 3-51 Appearance of IPC6211

Table 3-40 Technical specifications of IPC6211

Parameter Value

Camera Image sensor 1/2.8" 2.0-megapixel progressive scan CMOS


Effective pixels 1920 (H) x 1080 (V)
Minimum  Multicolor: 0.01 lux (F1.4, AGC ON, 1/30s shutter speed,
illumination and 50 IRE) and 0.007 lux (F1.2, AGC ON, 1/30s shutter
speed, and 50 IRE)
 B/W (infrared lamp enabled): 0 lux

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 74


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Parameter Value

Day/Night Automatic ICR, multicolor, or B/W


mode
Shutter speed 1/16,000s to 1/25 (1/30)s
Gain control Automatic
Backlight Supported
compensation
(BLC)
Wide dynamic Digital WDR
range
White balance Manual/Auto/Indoor/Outdoor/Fixed sodium lamp/Fluorescent
lamp 1/Fluorescent lamp 2/Incandescent lamp/OnePush
Noise Self-adaptive to 2D or 3D DNR
reduction
Defogging Supported
Maximum 30 m
infrared
radiation
distance
Lens Lens type Built-in Φ14 motorized zoom lens with an IR-CUT filter
Focal length 2.8 mm to 12 mm (support for automatic focus)
Iris DC automatic iris; a maximum iris of F1.4
Angle of view Horizontal angle of view: 11.3°to 33.8°
Zoom 4.3x optical zoom
Functio Video H.264 Main Profile/Baseline Profile (support for Profile
n compression switchover) and MJPEG
standard
Video 1920 x 1080, 1280 x 720, 720 x 576, 720 x 480, 352 x 288,
resolution and 352 x 240 (H.264: 30 fps, 25 fps, 1 fps to 20 fps; MJPEG: 1
frame rate fps to 5 fps)
Video bit rate 100 kbit/s to 8 Mbit/s
ROI encoding Supported
Corridor Support for an aspect ratio of 9:16
format
Multi-channel Three types of streams (can encode one channel of primary
video encoding streams and two channels of secondary streams at the same
time); maximum resolution for primary streams: 1080p;
maximum resolution for secondary streams: D1

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 75


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Parameter Value

Stream Four preset stream packages and four customized stream


package packages
ISP package Four preset ISP packages and eight customized ISP packages;
support for daily and monthly ISP package plans
Bit rate type Constants Bit Rate (CBR) or Variable Bit Rate (VBR)
Dynamic bit Supported
rate
Image quality H.264: CBR controlled by streams and VBR controlled by
adjustment stream upper limit (selectable image quality); MJPEG: JPEG
quality (QP) control
IP address IP address filtering by blacklist or whitelist
filtering
Communicatio One RJ-45 10M/100M adaptive Ethernet interface and one
n interface RS-485 interface (PELCO-P/D)
Alarm interface 2-channel alarm input and 2-channel alarm output (phoenix
connector)
Analog video BNC interface (1.0 Vp–p and 75 ohms); 1-channel hybrid
output analog video output through the CVBS interface
Audio G.711a/G.711u/G.726
encoding
format
Audio interface Support for 1-channel audio input and 1-channel audio output
through 3.5 mm audio interfaces
Voice Voice intercom (sound pickup required), voice broadcast, and
communication channel-associated voice
Motion Supported
detection
Privacy mask Supported
Image Vertical, horizontal, or both
mirroring
PU access ONVIF 2.4 and HUAWEI SDK
protocol
Network TCP, UDP, IPv4, DHCP, DNS, ICMP, IGMP, HTTP, HTTPS,
protocol SFTP, RTP, RTSP, RTCP, SIP, ARP, SSL, NTP, SNMP,
802.1x, and QoS
Stream mode Unicast and multicast
Maximum 10 (allows users to obtain a maximum of two channels of
number of 1080p video streams at the same time)
concurrent
login users

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 76


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Parameter Value

Local storage Micro SD card (configured additionally) with a maximum


capacity of 32 GB and at least class 4 speed
Security mode User name and password authentication, 802.1x (MD5
Challenge), and PKI digital certificate
Media security Stream encryption using the AES128/192/256 encryption
algorithm
Data Stream smoothing parameter configuration, adaptive
transmission bandwidth, MTU configuration, and QoS configuration
optimization
Alarm linkage Alarm source: motion detection alarm/lens block
alarm/Boolean value input; linkage target: Boolean value
output
Browser 32-bit Windows XP Internet Explorer 8, 32- or 64-bit
Windows 7 Internet Explorer 8/9/10/11, 32- or 64-bit
Windows 8 Internet Explorer 10/11; 32-bit Internet Explorer
General Power supply 9 V DC to 15 V DC, 18 V DC to 30 V DC, 18 V AC to 30 V
parame AC, PoE 802.3at; power adapter and PoE in hot standby mode
ters
Power Typical power consumption: 9.5 W; maximum power
consumption consumption: 12.5 W
Operating Operating temperature: –40°C to +60°C; relative humidity:
environment 5% RH to 95% RH (noncondensing)
Protection rate IP66
Net weight 1.4 kg
Physical 120 mm x 353.6 mm x 128.1 mm (including the shield)
dimensions (H
x W x D)

3.5 Fire Extinguishing System


3.5.1 Overview
A CE or standard fire extinguishing system can be used. The CE system complies with the
EU's CE certification, and the standard system complies with China's CCC certification.
If the container catches fire, smoke and heat will trigger the smoke detectors and heat
detectors, which will send fire alarm signals to the extinguishant control panel. Upon
receiving the fire alarm signals, the extinguishant control panel counts down and then opens
the solenoid valve on the fire extinguisher so that the fire cylinder discharges extinguishant to
the protection zone. At the same time, the extinguishant control panel automatically reports
alarms.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 77


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-52 shows the conceptual diagram of the CE fire extinguishing system, and Figure
3-53 shows the conceptual diagram of the standard fire extinguishing system.

Figure 3-52 Conceptual diagram of the CE fire extinguishing system

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 78


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-53 Conceptual diagram of the standard fire extinguishing system

Figure 3-54 shows the layout of the fire extinguishing system.

Figure 3-54 Layout of fire extinguishing components

(1) Fire extinguishing pipe and nozzles (2) Heat detector (3) Smoke detector
(4) Indoor horn strobe (5) Fire alarm bell (6) Outdoor horn strobe
(7) Fire control box (8) Fire cylinder

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 79


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

3.5.2 CE Fire Extinguishing System


3.5.2.1 Extinguishant Control Panel
The extinguishant control panel provides the following functions:
 Two zones supported, a third zone configurable
 Serial status connection and timer display
 Programmable for I.S. barriers
 Standard exhaust fan control
 Hold activated indication and disablement indication
 Test mode
 Two first stage sounder outputs
 One second-stage audible and visual alarm output
 First- and second-stage relay contacts
 Auxiliary 24 V DC output
 Monitored manual release input and output
 Monitored release pneumatic switch input
 (Optional) Mode select key switch on the front panel
 (Optional) Manual release on the front panel

Figure 3-55 Extinguishant control panel

Table 3-41 lists the technical specifications of the extinguishant control panel.

Table 3-41 Extinguishant control panel specifications

Item Specifications

Input AC input frequency: ≤ 120 W


AC input voltage and frequency: 230 V AC (tolerance ±10%), 50
Hz

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 80


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Item Specifications

DC backup power voltage: 24 V DC


24 V power output 3A
Capacit Number Three loops. Loops 1 and 2 respectively connect to smoke detectors
y of and heat detectors. Loop 3 is reserved by default.
detection
loops
Number ≤ 24 PCS
of
detectors
connecte
d to each
loop
Output loop current Output loop for the solenoid valve driver: 1 A
limiting Output loops for other drivers: 1 A

The extinguishant control panel is equipped with two 12 V batteries and the required cables.

3.5.2.2 Heptafluoropropane Fire Extinguisher


When the FusionModule1000 catches fire, a lot of smoke is generated and the temperature
rises sharply. The smoke detector and heat detector send fire alarm signals to the
extinguishant control panel, which generates an electrical actuator start voltage to start the
electrical actuator of the fire cylinder. Then the fire cylinder valve is opened, and
extinguishant is released into the protected zone.
Heptafluoropropane (HFC-227ea) is a colorless, odorless, non-conductive, and secondary
pollution-free gas extinguishant. It features cleanness, low toxicity, good electrical insulation,
high fire extinguishing efficiency, zero threat to the ozonosphere (ODP = 0), and short
residual time (ATL = 34Y).

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 81


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-56 Fire extinguisher

Table 3-42 lists the technical specifications of the Heptafluoropropane fire extinguisher.

Table 3-42 Heptafluoropropane fire extinguisher specifications

Item Specifications

Dimensions Outer diameter of the steel cylinder: 406 mm


Startup current 0.25 A
Startup voltage 24 V DC
Startup mode Electromagnetic startup
Maximum operating 50°C: 3.4 MPa
pressure
Storage pressure 20°C: 2.5 MPa
Cylinder volume 52 L

The CE-certified fire extinguishing system supports the customized copper fluoride
(NOVEC1230) extinguishant.
Copper fluoride (NOVEC1230) is a new-generation extinguishant that has been favored like
Heptafluoropropane (HFC-227ea) for recent years. Copper fluoride (NOVEC1230) has been
widely proved to be eco-friendly and safe. It can be used to extinguish fire caused by
flammable liquid, gas, and electrical equipment. Physical and chemical actions are combined
during extinguishing. Generally copper fluoride (NOVEC1230) is a colorless and odorless
liquid. It does not contain bromine or chlorine, does no harm to the ozonosphere (ODP = 0),
and resides for a short time in the atmosphere (ATL = 0.014Y).

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 82


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

3.5.3 Standard Fire Extinguishing System


3.5.3.1 Fire Alarm Control Panel
The fire alarm control panel provides the following functions:
 Detects and reports composite fire alarm signals in dual loops. It can be connected to the
emergency start/abort switch, which ensures that the system operation is under control in
case of an emergency or during onsite equipment maintenance. It restarts automatically
after a fault is rectified.
 Provides a port for the gas release confirmation signal (reporting pressure values).
 Generates single fire and double fire alarms; drives the gas release indicator, alarm fire
alarm horn/strobe, and alarm fire alarm sounder.
 Provides an independent output port for the electromagnetic valve driver and supports 3
A, 24 V electromagnetic valve (electric detonator) startup voltage.
 Detects an open circuit fault of the input loop and a short or open circuit of the output
loop (in active output mode).
 Provides intelligent monitoring as well as overcharge and overdischarge protection for
backup batteries.
 Adopts the low-power consumption design, and supports at least 48-hour consecutive
operation with the backup power.
 Provides password lock protection for the keypad to prevent misoperations.

Figure 3-57 Fire alarm control panel

Table 3-43 Fire alarm control panel specifications

Item Specifications

AC input power ≤ 120 W

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 83


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Item Specifications

AC input voltage 220 V AC±20%


DC backup Voltage 24 V DC
power
Electric energy 7.0 Ah
Capacity Number of detection Two loops: one loop connected to the common
loops heat fire detector and the other connected to
the smoke detector
Number of detectors ≤ 20 (common detectors)
connected to each loop
Wire system of the detector loop Two-wire system
Length of the detector loop ≤ 1000 m
Relay contact capacity 7 A, 24 V DC for all relays
Output loop current limiting for the ≤3A
solenoid valve
Output loop current limit for other drivers ≤1A

3.5.3.2 Heptafluoropropane Fire Extinguisher


The fire extinguisher consists of a fire cylinder, pressure announciator, electromagnetic valves,
and other components.
When the FusionModule1000 catches fire, a lot of smoke is generated and the temperature
rises sharply. The smoke detector and heat fire Detector send fire alarm signals to the fire
alarm control panel, which generates a electromagnetic valve start voltage to start the
electromagnetic valve of the fire cylinder. Then the fire cylinder valve is opened, and
extinguishant is released into the protected zone.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 84


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-58 Heptafluoropropane fire extinguisher

Table 3-44 Heptafluoropropane fire extinguisher specifications

Item Specifications

Dimensions Outer diameter of the steel cylinder: 364


mm
Maximum operating pressure 50°C: 3.4 MPa
Storage pressure 20°C: 2.5 MPa
Cylinder volume 70 L
Heptafluoropropane filling density ≤ 1120 kg/m3
Startup current 1.2 A
Startup voltage 24 V DC

3.5.4 VESDA (Optional)


Composition
The VESDA consists of a VLF-250 detection unit and meshed air sampling pipes.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 85


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-59 VESDA

(1) VESDA detection unit (2) Sampling pipes (3) Air sampling pipe plugs

Working Principle
The detection unit includes the suction pump, filter, high-sensitive smoke detector, and
precision electrical analyzer. The air detector of the VESDA can detect fire in the initial phase
and generates alarms at an early time.
The detection unit of the VESDA sucks air samples from the monitored environment through
the air sampling tube to the smoke detector and works out the dust density in the air. If the
dust density exceeds the preset alarm threshold, the VESDA blinks and sends an alarm signal
to the monitoring module.

Features
 High sensitivity
The VESDA features extremely high sensitivity and wide sensitivity adjustment range
(0.005%–20% obs/m). It can detect both potential fire in the early phase and particles
released by the softened insulation layer of an overloaded power cable.
 Precise detection result
The VESDA works in active air sampling mode. The efficient aspirator continuously
sends air samples from the protected area to the detection chamber for analysis. The
detection result and response time are less influenced by air flow compared with a
traditional fire detection method.
 Flexible installation
The VESDA detection unit is compact and easy to install. The air sampling pipes can be
deployed depending on site requirements. The air sampling pipes are made of PVC and
can be installed on or under the ceiling, under the floor, at air return vents of air
conditioners, and in locations that need special protection. For example, the sampling
capillaries can be installed in a cabinet to monitor equipment in the cabinet.
 Easy maintenance
The VESDA is equipped with a special filter that filters air for cleaning the laser
measuring chamber, ensuring that the laser detector has a long lifespan. The filter can be
easily maintained and replaced, and cleaned by blowing air into the air sampling pipes.
Therefore, you do not have to replace any other components.
 Efficient auto-diagnosis system

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 86


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

The VESDA is designed with an efficient auto-diagnosis system for monitoring the
working status of itself, the network, and the air sampling pipes in real time. If a fault is
detected, the system generates an alarm and indicates the fault location for
troubleshooting.

3.6 Surge Protection and Grounding


3.6.1 Surge Protection
Power Ports
 First-level surge protection: A class I SPD with the capacity Imax of at least 100 kA (8/20
µs) should be deployed at the AC power inlet for the container.
 Second-level surge protection: An SPD with the recommended capacity Imax of 60 kA
(8/20 μs) should be deployed at the PDB.
 Third-level surge protection: An SPD with the recommended capacity Iin of 20 kA (8/20
μs) should be deployed at the power input port of the downstream equipment such as the
air conditioner or UPS.

Signal Ports
 Indoor signal ports are protected to 1 kV for common mode.
 Signal ports for routing cables out of the container pass the 3 kA impulse current test.

3.6.2 Grounding
Internal Grounding
The main earthing terminal (MET) is installed in the container and connects to the external
ground grid over ground downleads.
Equipment in the container connects to the ground busbar over ground cables and are
insulated from other metal parts.

Figure 3-60 Internal Grounding Diagram

The actual cable path varies depending on the site.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 87


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

External Grounding
M12 bolt ground points are evenly located on the container exterior. Ensure that the two
diagonal ground points are connected to the ground grid. The FusionModule1000 provides
two external ground points, as shown in Figure 3-61. The ground resistance is within 10
ohms.

Figure 3-61 Container ground points (unit: mm)

3.7 Integrated Cabling


Integrated cabling of the FusionModule1000 involves cable trays and various cables. Cable
trays on the tops of containers are separate from cabinets, and can be moved horizontally
along the width direction on the tops of containers. Strong- and weak-current cables are
routed separately.
Cables of the FusionModule1000 include power cables, monitoring cables, fire extinguishing
cables, signal cables, and ground cables.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 88


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 3 System Architecture

Figure 3-62 Cable routes

(1) L2 signal cables (2) L1 power cables


(3) Mains inlet port (4) Cables for air conditioner indoor and outdoor units

Figure 3-63 Cable routes on cable trays

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 89


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 4 Key Technical Specifications

4 Key Technical Specifications

Table 4-1 lists the key technical specifications of the FusionModule1000.

Table 4-1 Key technical specifications

Item Specifications

Power supply Power input Two 250 A inputs, three-phase four-wire + PE,
and 380 V AC/400 V AC/415 V AC 50 Hz/60 Hz
distribution Two 400 A inputs, three-phase four-wire + PE,
208 V AC/220 V AC/230 V AC 50 Hz/60 Hz
Surge protection Class I, 100 kA (8/20 µs), 20 kA (10/350 µs)
level
Load power  2 N scenario without iBAT: single cabinet
power 4 x 9 kW/Rack + 3 x 6 kW/Rack; total
power ≤ 52 kW
 2 N scenario with iBAT: single cabinet power
6 x 9 kW/Rack; total power ≤ 52 kW
 N+X scenario without iBAT: single cabinet
power 2 x 9 kW/Rack + 6 x 6 kW/Rack; total
power ≤ 52 kW
 N+X scenario with iBAT: single cabinet power
4 x 9 kW/Rack + 3 x 6 kW/Rack; total power ≤
52 kW
Single cabinet power 7 x 6 kW/Rack; total power
≤ 42 kW
Battery backup time  2N scenario without iBAT: 10 min
 2N scenario with iBAT: 15 min
 N+X scenario without iBAT: 7.5 min
 N+X scenario with iBAT: 15 min
10 min
Cooling Cooling capacity 25 kW for each air conditioner, 3+1 mode
21 kW for each air conditioner, 3+1 mode

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 90


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 4 Key Technical Specifications

Item Specifications

Refrigerant R410A
Fire Type Fire extinguishing system with the automatic fire
extinguishing detection and emergency gas release functions
Alarm Audible and visual alarming with automatic
monitoring and detection
Monitoring The analog addressable system releases the
gaseous extinguishant if fire alarms are generated
from dual detector loops.
Extinguishing agent Heptafluoropropane. Copper fluoride
(NOVEC1230) can be used in the CE version if
required.
Monitoring IP camera Dual-resolution IP cameras installed in the
entrance room and long aisles
Management Monitors the temperature and humidity control
functions system, fire detection and control system, access
control system, and cooling system inside the
FusionModule1000 in real time
O&M using the mobile APP, remote unattended
control
(Optional) The NetEco supports monitoring over
emails and Simple Network Management Protocol
(SNMP) short messages.
Allows all backup power sources to be connected
over programmable dry contact ports or fast
Ethernet (FE) ports (FE port for the UPS, RS485
and dry contact ports for the diesel generator)
Structure Dimensions (H x W 40 ft standard ISO shipping container (8 ft × 9.5 ft
x D) × 40 ft): 2896 mm x 2438 mm x 12192 mm
Container heat The heat transfer coefficient of the container is
insulation equal to or less than 0.4 W/(m2 x K).
performance
Integrated cabling Power cables and signal cables are routed
separately.
Protection level IP55/IP65 (optional)
Installation mode Directly installed on the ground
NOTE
The container can be installed on a concrete platform,
with four 300 mm high steel bases connected to the
concrete platform using M16 bolts.

Weight Empty container (excluding servers): 12,000 kg;


fully-loaded container: < 25,000 kg

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 91


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 4 Key Technical Specifications

Item Specifications

Typical cabinet  2 N scenario without iBAT: raised floor, seven


capacity 42 U IT cabinets (six with H x W x D
dimensions of 2000 mm x 600 mm x 1200 mm
and one with H x W x D dimensions of 2000
mm x 600 mm x 1100 mm)
 2 N scenario with iBAT: raised floor, six 42 U
IT cabinets with H x W x D dimensions of
2000 mm x 600 mm x 1200 mm
 N+X scenario without iBAT: raised floor, eight
42 U IT cabinets (six with H x W x D
dimensions of 2000 mm x 600 mm x 1200 mm
and two with H x W x D dimensions of 2000
mm x 600 mm x 1100 mm)
 N+X scenario with iBAT: raised floor, seven
42 U IT cabinets (six with H x W x D
dimensions of 2000 mm x 600 mm x 1200 mm
and one with H x W x D dimensions of 2000
mm x 600 mm x 1100 mm)
Raised floor, seven 42 U IT cabinets (six with
dimensions of 2000 mm x 600 mm x 1200 mm
and one with dimensions of 2000 mm x 600 mm x
1100 mm)
Bullet-proof Performance The container bullet-proof function passed the 10
(optional) m rifle test.
Operating Cold aisle 18–27°C
parameters temperature
Humidity 20%–80% RH
Environmental Altitude –40°C to +55°C
requirements –20°C to +55°C
NOTE
 When the temperature is lower than or equal to
45°C, the cabinet power is not derated and the
derating coefficient is 1.
 When the temperature is 50°C, the cabinet power is
derated and the derating coefficient is 0.89.
 When the temperature is 55°C, the cabinet power is
derated and the derating coefficient is 0.58.

Storage temperature –40°C to +70°C


Ambient humidity 5%–95% RH

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 92


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) 4 Key Technical Specifications

Item Specifications

Altitude 0–4000 m
 The performance is derated when the altitude is
from 1000 m to 4000 m. For the derating
details, contact Huawei technical support.
 The UPS is derated as described in
IEC62040-3 when the altitude is from 1000 m
to 4000 m.
 The PDB and rPDU are derated when the
altitude is 2000–4000 m. For the derating
details, contact Huawei technical support.

 Do not leave the prefabricated data center power off for more than six months. If the data
center will be idle for a long time, power it on and keep it operational for at least two
hours every six months.
 The battery storage temperature must be in the range from –20°C to +40°C.
 Batteries can be stored without power-on for a maximum of 90 days. If the storage period
exceeds 90 days, recharge the batteries promptly.

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 93


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) A Acronyms and Abbreviations

A Acronyms and Abbreviations

A
ATS automatic transfer switch

C
CE Conformite Europende

M
MCB miniature circuit breaker
MCCB molded case circuit breaker

N
NetEco network ecosystem

T
TCP/IP Transmission Control Protocol/Internet Protocol

P
PUE power usage effectiveness

S
SNMP Simple Network Management Protocol

U
UPS uninterruptible power system

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 94


FusionModule1000A40 Prefabricated All-in-One Data
Center
Product Overview (IT, 380 V) A Acronyms and Abbreviations

V
VCN video cloud node

Issue 02 (2018-11-30) Copyright © Huawei Technologies Co., Ltd. 95