You are on page 1of 1

Level : prizemje Space : 2

Transmission heat loss calculation


Heat losses directly to the exterior
Code Building Ak (mІ) Uk (W/mІK) ek Ak·Uk·ek
Element (W/K)
W2 Outer Wall 1 5.50 0.70 1.000 3.85
O1 Reg. Glass 1.54 2.3 1.000 3.54
(Wood.Frame)
O1 Reg. Glass 1.54 2.3 1.000 3.54
(Wood.Frame)
O1 Reg. Glass 1.54 2.3 1.000 3.54
(Wood.Frame)
W7 Outer Wall 10 1.13 0.35 1.000 0.40
Total of building elements Sk Ak·Uk·ek W/K 14.87
Code Thermal bridge Шk (W/mK) lk (m) ek Шk·lk·ek (W/K)
O1- L- 5 0.550 1.40 1.000 0.77
O1- L- 5 0.550 1.40 1.000 0.77
O1- L- 5 0.550 1.40 1.000 0.77
O1- L- 5 0.550 1.40 1.000 0.77
O1- L- 5 0.550 1.40 1.000 0.77
O1- L- 5 0.550 1.40 1.000 0.77
W2- H - 10 (50%) 0.225 3.75 1.000 0.84
W2- H - 10 (50%) 0.225 3.75 1.000 0.84
Total of thermal bridges Sk Psik·lk·ek W/K 6.31
Total heat loss coefficient directly to the exterior Ht,ie = Sk Ak·Uk·ek + Sk Psik·lk·ek 21.18
Heat losses through unheated spaces
Code Building Ak (mІ) Uk (W/mІK) bu Ak·Uk·bu
Element (W/K)
F1 Floor 1 14.18 0.35 0.263 1.31
Total of building elements Sk Ak·Uk·bu W/K 1.31
Code Thermal bridge Шk (W/mK) lk (m) bu Шk·lk·bu (W/K)
Total of thermal bridges Sk Psik·lk·bu W/K 6.31
Total heat loss coefficient through unheated spaces Ht,iue = Sk Ak·Uk·bu + Sk Psik·lk·bu 1.31
Heat losses through the ground
Calculation of B Ag (mІ) P (m) B'=2·Ag/P (m)

Code Building Uk (W/mІK) Uequiv,k Ak (mІ) Ak·Uequiv,k


Element (W/mІK) (W/K)
Total of equivalent building elements Sk Ak·Uequiv,k W/K 0.00
Correction factors fg1 fg2 Gw fg1·fg2·Gw
1.45
Total heat loss coefficient through the ground Ht,ig = (Sk Ak·Uequiv,k)·fg1·fg2·Gw 0.00
Heat losses to spaces heated at different temperatures
Code Building fij Ak (mІ) Uk (W/mІK) fij·Ak·Uk (W/K)
Element
Total heat loss coefficient through spaces at different temperature Ht,ij = Sk fij·Ak·Uk 0.00
Total transmission heat loss coefficient Ht,i = Ht,ie + Ht,iue + Ht,ig + Ht,ij W/K 22.49
Temperature data
Design external temperature иe °C -18
Design internal temperature иint,i °C 20
Design temperature difference иint,i-иe °C 38
Total transmission heat loss Phit,i = Ht,i·(tint,i - te) W 854
Increment % 20
Total design transmission heat loss with increment 1025

Ventilation heat loss calculation


Room internal volumeиe Vi m3 42.54
Outdoor Temperatureиint,i иe °C -18
Internal temperatureиint,i-иe иint,i °C 20
Minimum hygienic air exchange rate nmin,i 1/h 0.5
Minimum hygienic air flow rate Vmin,i m3/h 21.27
Air exchange rate/hour at 50 Pa (n50) n50 1/h 5
Shielding coefficient e 0.02

You might also like