You are on page 1of 1

Height correction factor е 1.

00
Infiltration air flow rate Vinf,i m3/h 8.51
Selected value for calculation Vi m3/h 21.27
Design ventilation heat loss coefficient Hv,i W/K 7.23
Temperature difference иint-иe °C 38
Design ventilation heat loss Цv,i W 274.8 274.8

Calculation of heating-up capacity


Reheat factor fRH W/mІ 23
Floor area Ai mІ 14.18
Heating-up capacity ЦRH,i W 0.00 0.00

Total design heat load


Total heat load ЦHL,i W 1300

Level : prizemje Space : 3

Transmission heat loss calculation


Heat losses directly to the exterior
Code Building Ak (mІ) Uk (W/mІK) ek Ak·Uk·ek
Element (W/K)
W2 Outer Wall 1 1.22 0.70 1.000 0.85
W7 Outer Wall 10 0.13 0.35 1.000 0.05
W2 Outer Wall 1 1.31 0.70 1.000 0.92
O1 Reg. Glass 3.68 2.3 1.000 8.46
(Wood.Frame)
W7 Outer Wall 10 0.56 0.35 1.000 0.20
W21.000 0.94
W7 Outer Wall 10 0.15 0.35 1.000 0.05
W2 Outer Wall 1 7.02 0.70 1.000 4.91
W7 Outer Wall 10 0.78 0.35 1.000 0.27
W2 Outer Wall 1 5.26 0.70 1.000 3.68
W7 Outer Wall 10 0.59 0.35 1.000 0.21
Total of building elements Sk Ak·Uk·ek W/K 20.54
Code Thermal bridge Шk (W/mK) lk (m) ek Шk·lk·ek (W/K)
W2- H - 10 (50%) 0.225 0.45 1.000 0.10
W2- H - 10 (50%) 0.225 0.45 1.000 0.10
W2- H - 10 (50%) 0.225 1.85 1.000 0.42
W2- H - 10 (50%) 0.225 1.85 1.000 0.42
W2- H - 10 (50%) 0.225 0.50 1.000 0.11
W2- H - 10 (50%) 0.225 0.50 1.000 0.11
W2- H - 10 (50%) 0.225 2.60 1.000 0.59
W2- H - 10 (50%) 0.225 2.60 1.000 0.59
W2- H - 10 (50%) 0.225 1.95 1.000 0.44
W2- H - 10 (50%) 0.225 1.95 1.000 0.44
Total of thermal bridges Sk Psik·lk·ek W/K 3.31
Total heat loss coefficient directly to the exterior Ht,ie = Sk Ak·Uk·ek + Sk Psik·lk·ek 23.85
Heat losses through unheated spaces
Code Building Ak (mІ) Uk (W/mІK) bu Ak·Uk·bu
Element (W/K)
F1 Floor 1 14.05 0.35 0.263 1.29
Total of building elements Sk Ak·Uk·bu W/K 1.29
Code Thermal bridge Шk (W/mK) lk (m) bu Шk·lk·bu (W/K)
Total of thermal bridges Sk Psik·lk·bu W/K 3.31
Total heat loss coefficient through unheated spaces Ht,iue = Sk Ak·Uk·bu + Sk Psik·lk·bu 1.29
Heat losses through the ground
Calculation of B Ag (mІ) P (m) B'=2·Ag/P (m)

Code Building Uk (W/mІK) Uequiv,k Ak (mІ) Ak·Uequiv,k


Element (W/mІK) (W/K)
Total of equivalent building elements Sk Ak·Uequiv,k W/K 0.00