You are on page 1of 7

Data sheet 3WL1110-2CB32-1AA2

fixed-mounted circuit breaker 3-pole, size I, IEC In=1000A to 690V,


AC50/60Hz Icu=55kA at 500V rear connection horizontal Overcurrent
release ETU 25 LSI protection adjustable 0.4-1 in With manual
operating mechanism with storage with mechanical request without
1st auxiliary release without 2nd auxiliary release 2NO+2NC

Model
Product brand name SENTRON
Product designation ACB
Design of the product IEC 60947-2
Design of the operating mechanism Pushbutton
Type of the driving mechanism Manual operating mechanism with mechanical closing
Type of the driving mechanism / motor drive No

3WL1110-2CB32-1AA2 Subject to change without notice


Page 1/7 05/19/2020 © Copyright Siemens
Design of the overcurrent release ETU25B

General technical data


Number of poles 3
Size of the circuit-breaker 1
Usage category B
circuit-breaker / Design 3WL1110

Voltage
Rated insulation voltage Ui 1 000 V
Operating voltage
● at AC / at 50/60 Hz / rated value 690 V

Protection class
Protection class IP IP20
Protection class IP / on the front IP20
protection function of the overcurrent release LSI

Dissipation
Power loss [W] / for rated value of the current / at AC 33.3 W
/ in hot operating state / per pole

Current
Operating current / at 45 °C / rated value 1 000 A
Continuous current / rated value 1 000 A
Adjustable pick-up value current
● of the current-dependent overload release / 1 000 A
Full-scale value
● of instantaneous short-circuit trip unit / initial 20 000 A
value
● of instantaneous short-circuit trip unit / Full- 20 000 A
scale value

Main circuit
Operating frequency
● 1 / rated value 50 Hz
● 2 / rated value 60 Hz
Operating current
● at 40 °C / rated value 1 000 A
● at 50 °C / rated value 1 000 A
● at 55 °C / rated value 1 000 A
● at 60 °C / rated value 1 000 A
● at 65 °C / rated value 1 000 A
● at 70 °C / rated value 1 000 A

Auxiliary circuit
Number of NC contacts / for auxiliary contacts 2

3WL1110-2CB32-1AA2 Subject to change without notice


Page 2/7 05/19/2020 © Copyright Siemens
Number of NO contacts / for auxiliary contacts 2

Suitability
Suitability for use Plant / motor protection

Adjustable parameters
Adjustable pick-up value current
● of the short-time delayed short-circuit release / 1 250 A
initial value
● of the short-time delayed short-circuit release / 12 000 A
Full-scale value
Adjustable pick-up value current / of the current- 400 A
dependent overload release / initial value

Product details
Product component
● Trip indicator Yes
● Voltage trigger No
● undervoltage release No
Product extension / optional / motor drive Yes

Product function
Product function
● Ground fault protection No
● Phase failure detection Yes

Display and operation


Display version without display

Short circuit
Operational short-circuit current breaking capacity
(Ics)
● at 415 V / rated value 55 kA
● at 500 V / rated value 55 kA
● at 690 V / rated value 42 kA
Maximum short-circuit current breaking capacity (Icu)
● at 415 V / rated value 55 kA
● at 500 V / rated value 55 kA
● at 690 V / rated value 42 kA

Connections
Arrangement of electrical connectors / for main Main connection rear side horizontal
current circuit
Type of electrical connection / for main current circuit busbar connection

Mechanical Design
Height 439.5 mm
Width 320 mm

3WL1110-2CB32-1AA2 Subject to change without notice


Page 3/7 05/19/2020 © Copyright Siemens
Depth 337 mm
Mounting type fixed mounting

Environmental conditions
Ambient temperature / during operation
● minimum -20 °C
● maximum 70 °C
Ambient temperature / during storage
● minimum -40 °C
● maximum 70 °C

Certificates
Reference code
● acc. to DIN EN 61346-2 Q
● acc. to DIN EN 81346-2 Q

General Product Approval Declaration of Test Certificates


Conformity
Special Test Certi- Miscellaneous
ficate

Shipping Approval
CCS / China Classi-
fication Society

other
Environmental Con- Manufacturer De- Confirmation Miscellaneous
firmations claration

Further information
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3WL1110-2CB32-1AA2
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3WL1110-2CB32-1AA2
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3WL1110-2CB32-1AA2
CAx-Online-Generator
http://www.siemens.com/cax
Tender specifications
http://www.siemens.com/specifications

3WL1110-2CB32-1AA2 Subject to change without notice


Page 4/7 05/19/2020 © Copyright Siemens
5.5

275

327.5
10
437

401

275

10
150
123.5

76
270 15 20 60 90 90

300 10 130 45

150 106

210 127

230

55

13
.5
35

139 58

320

3WL1110-2CB32-1AA2 Subject to change without notice


Page 5/7 05/19/2020 © Copyright Siemens
L / L+
L1

L2

L3

-Q

X6.2

X6.4
X6.12
X6.10
-A1 ETU25B

I> S

I >> I

In = 1000A
Ir = 400A-1000A
Isd = 1250A-12000A
Ii = 20000A

-Q1

-S1 -S2

-T1

-T2

-T3

-F5
X6.11
X6.9

X6.1

X6.3
L1

L2

L3

N / L-

L (Long Time Delay / Überlastschutz); S (Short Time Delay / Kurzschlussschutz, kurzzeitverzögert);


I (Instantaneous / Kurzschlussschutz, unverzögert); F5 (Maglatch for trip unit / Auslösemagnet);
S1 - S8 (Auxiliary switch / Hilfsschalter);

3WL1110-2CB32-1AA2 Subject to change without notice


Page 6/7 05/19/2020 © Copyright Siemens
last modified: 05/08/2020

3WL1110-2CB32-1AA2 Subject to change without notice


Page 7/7 05/19/2020 © Copyright Siemens

You might also like