You are on page 1of 4

1 833

Cable Temperature Sensor QAP21.2


for applicatiions up to 180 °C

Use

The cable temperature sensor is used for acquiring high medium temperatures. It is
especially suited for acquiring the medium temperature in flat solar collectors.

Ordering

When ordering, please give type reference of cable temperature sensor and type refer-
ence of the accessories required.

Function

The sensor acquires the medium temperature in the solar panel with its nickel element.
The resistance value of the element changes as a function of the temperature.
It is delivered for further handling by a suitable controller.

CE1N1833en
Building Technologies
2017-12-01
Sensing element Characteristic Accuracy
R [Ω] ∆ϑ [K]

2500 2.0

1833D01

1833D02
1.5

2000 1.0

0.5

1500 0

−0.5

1000 −1.0

−1.5

500 ϑ −2.0 ϑ
−40 −20 0 20 40 60 80 100 120 140 160 180 200 220 240 [°C] −50 0 50 100 150 200 250 [°C]

Legend R Resistance value in Ohm


ϑ Temperature in degrees Celsius
∆ϑ Temperature differential in Kelvin

Mechanical design

The cable temperature sensor consists of a sleeve (6 mm diameter, 50 mm long), sens-


ing element and connecting cable with ferrules.
The sensing element is accommodated in the sleeve which is flat on one side and to
which the connecting cable is attached.
The sensor is not suited for direct immersion in liquid media (without using a protection
pocket).

Accessories (not included with standard delivery)

Name Type reference


Protection pocket, Ms63, PN10, immersion length 100 mm ALT-SB100 1)
1) For other protection pocket accessories, refer to Data Sheet N1194.

Engineering notes

The permissible cable lengths are dependent on the type of controller used. For details,
refer to the Data Sheet of the relevant controller.

Mounting notes

The following mounting choices exist:


On pipes • Up to medium temperatures of 85 °C: with plastic cable tie (supplied by thirds)
• Up to medium temperatures of 220 °C: with stainless steel cable tie (supplied by
thirds)
A: ≤ 85 °C B: ≤ 220 °C
1833Z01

1 1

2 2 2

Indirect immersion With the help of a protection pocket. The inside diameter of the pocket should match
the diameter of the sensor’s sleeve (e.g. 6.1 mm).
The sensor is supplied complete with Mounting Instructions.

2/4

Siemens Cable temperature sensor QAP21.2 CE1N1833en


Building Technologies 2017-12-01
Disposal

The device is considered electrical and electronic equipment for disposal in terms of the
applicable European Directive and may not be disposed of as domestic garbage.
• Dispose of the device via the channels provided for this purpose.
• Comply with all local and currently applicable laws and regulations.

Technical data

Functional data Measurement range −30 ... +180 °C


max. (1-2 h/d) 220 °C
Sensing element LG-Ni 1000
Time constant t63
When fitted to the pipe <20 s
With protection pocket <30 s
Measurement accuracy at 0 °C ±0.4 K (refer to "Function")
Measurement and output Passive
Degree of protection Protection degree of housing IP67 acccording to EN 60529
Protection class III acccording to EN 60730-1
Connections Mechanically Cable tie or protection pocket
(supplied by thirds)
Electrical connections
Connecting cable 2-core, interchangeable, with ferrules
Cable length Approx. 1.5 m
Perm. cable length Refer to "Engineering notes"
EU conformity (CE) A5W00040799 *)
Environmental Ambient temperature
conditions Sensor sleeve −30 ... +180 °C (220 °C for max. 1-2 h/d)
Connecting cable −50 ... +180 °C (220 °C for max. 1-2 h/d)
Environmental The product environmental declaration CE1E1701*) contains data on environmentally
compatibility compatible product design and assessments (RoHS compliance, materials composi-
tion, packaging, environmental benefit, disposal).
Materials Sensor sleeve Stainless steel V4A (1.4571)
Connecting cable Silicon
Packaging (minigrip bag) PVC
Weight Including packaging 0.056 kg
*) The documents can be downloaded from http://siemens.com/bt/download.

3/4

Siemens Cable temperature sensor QAP21.2 CE1N1833en


Building Technologies 2017-12-01
Internal diagram

1833G01
LG-Ni 1000

Dimensions

ø 4,7
QAP21.2
40
ø6

40

1833M01
50 1500

ALT-SB100
G½ A
ø9

13

1833M02
100 13 22

Dimensions in mm

Published by:
Siemens Switzerland Ltd.
Building Technologies Division
International Headquarters
Gubelstrasse 22
6301 Zug
Switzerland
Tel. +41 58-724 24 24 © Siemens Switzerland Ltd 2004