NOTE :-

A = 6 MTR AS PER SITE (1) FIRE PROTECTION WALL SHALL BE 0.25M THICK
HT SIDE HT SIDE AND HEIGHT EQUAL TO THE MAX. HEIGHT OF
B = 12 MTR AS PER SITE TRANSFORMER ABOVE PLINTH LEVEL.
C = 3 MTR. OR HIGHER (2) THE MS CHANNEL SHALL BE IN CEMENT
CONCRETE FOUNDATION IN 1:3:6.
AA= 3 MTR. (3) FENCING SHALL BE EARTHED PROPERLY
TR-1 TR-2 COVERING ALL ROWS ON ALL SIDES.
BB= 3 MTR. (4) CAUTION NOTICE SHOULD BE FIXED ONE
EACH AT FOLLOWING AS A MIN.:
- AT SUITABLE LOCATION NEAR TRANSFORMER
- ON THE GATE.
(5) ALL WORK SHALL BE CARRIED OUT BY
LT SIDE LT SIDE CONTRACTOR AS PER STATUTORY
REQUIREMENT OVER & ABOVE THE DETAILS
FURNISHED IN THIS DRAWING.
GATE GATE (6) FENCING & GATES SHALL BE EARTHED
PROPERLY COVERING ALL RWS ON ALL
SIDES AS PER IS; 3043 & STATUTORY NORMS.
75 MM 10 GAUGE WIRE
MESH TYPE FENCING
75MM SIZE 10 GAUGE
WIRE MESH
ISMC 100
HINGES X =1250MM.
(TYP.)
AS PER STRUCTURE A A Y = 1250MM.
DESIGN XX = 850MM.
FLOOR LEVEL
RCC
25MM ∅ G.I.
PIPE DOOR
PLAN OF TRANSFORMEROF TRANSFORMER
DETAIL OF GATE (NTS) FOUNDATION
ISA 50 75MM SIZE 10 GAUGE 100 X 50 MM MS CAHNNEL (ISMC)
WIRE MESH EMBEDDED IN FOUNDATION
ISMC 100
R0 09.04.2019 ISSUED FOR EXECUTION AMP RVS
NO DATE DESCRIPTION REV. BY CHK. BY
RCC As per FLOOR LEVEL PROJECT:
WATER DISTRIBUTION STATION AT SARKHEJ POLICE STATION OF AMC
structural Design
CLIENT:
AHMEDABAD MUNICIPAL CORPORATION (AMC),AHMEDABAD
ASSOCIATED CONSULTANTS:
SAPIENT TECHNO CONSULTANTS
FENCING DETAIL (NTS) SECTION A-A 701, Rembrandt, Opp. Associated Petrol Pump,
C.G.Road, Ellisbridge, Ahmedabad-380 006
Sapient E-mail :- sapient_ahd@sapient.net.in
TITLE:
TYPICAL G.A. DRG. OF 11KV TRANSFORMER YARD WITH
REMARKS :- FOUNDATION & FENCING DETAILS (AS APPLICABLE)
DRAWN BY : RPD DESIGNED BY : AMP
(1) TRANSFORMER LOCATION SHALL BE AS PER SITE REQUIREMENT.
CHECKED BY : RVS PROJ. NO. :
SCALE : NTS DRG. NO. : AMC/STC/WDS-S/E-05
DATE : 09.04.2019 REVISION : R0