You are on page 1of 18

The Babcock & Wilcox Company

Chapter 20
Economizers and Air Heaters

Economizers and air heaters perform a key func- Increasingly stringent environmental regulations
tion in providing high overall boiler thermal efficiency limiting nitrogen oxides (NOx) and sulfur dioxide (SO2)
by recovering the low level (i.e., low temperature) en- emissions can also affect economizer and air heater
ergy from the flue gas before it is exhausted to the design. Selective catalytic reduction (SCR) systems for
atmosphere. For each 40F (22C) that the flue gas is NOx control operate within an optimal flue gas tem-
cooled by an economizer or air heater in a conven- perature range, and the arrangement and/or opera-
tional boiler, the overall boiler efficiency increases by tion of the economizer may need to be modified accord-
approximately 1% (Fig. 1). Economizers recover the ingly. In the United States (U.S.), there has been a
energy by heating the boiler feedwater; air heaters substantial increase in the use of low-sulfur Powder
heat the combustion air. Air heating also enhances the River Basin (PRB) coal to reduce SO2 emissions. How-
combustion of many fuels and is critical for pulverized ever, PRB coal ash has high fouling and plugging
coal firing to dry the fuel and ensure stable ignition. characteristics that prohibit extended surface econo-
In contrast to the furnace waterwalls, superheater mizers and require the use of sootblowers throughout
and reheater, economizers and air heaters require a the boiler.
large amount of heat transfer surface per unit of heat
recovered. This is because of the relatively small dif-
ference between the flue gas temperature and the tem- Economizers
perature of either the feedwater or the combustion air. Economizers are basically tubular heat transfer
Use and arrangement of the economizer and/or air surfaces used to preheat boiler feedwater before it
heater depend upon the particular fuel, application, enters the steam drum (recirculating units) or furnace
boiler operating pressure, power cycle, and overall surfaces (once-through units). The term economizer
minimum cost configuration. comes from early use of such heat exchangers to re-
duce operating costs or economize on fuel by recover-
ing extra energy from the flue gas. Economizers also
reduce the potential of thermal shock and strong wa-
ter temperature fluctuations as the feedwater enters
the drum or waterwalls. Fig. 2 shows an economizer
location on a coal-fired boiler. The economizer is typi-
cally the last water-cooled heat transfer surface up-
stream of the air heater. (See chapter frontispiece.)

Economizer surface types


Bare tube
The most common and reliable economizer design
is the bare tube, in-line, crossflow type. (See Fig. 3a.)
When coal is fired, the flyash creates a high fouling
and erosive environment. The bare tube, in-line ar-
rangement minimizes the likelihood of erosion and
trapping of ash as compared to a staggered arrange-
ment shown in Fig. 3b. It is also the easiest geometry
to be kept clean by sootblowers. However, these ben-
Fig. 1 Approximate unit efficiency increase due to an economizer and efits must be evaluated against the possible larger
air heater in conventional boilers. weight, volume and cost of this arrangement.

Steam 41 / Economizers and Air Heaters 20-1


The Babcock & Wilcox Company

Steam Platen Secondary Secondary Reheat


Drum Superheater Superheater Superheater

Attemperator

Primary
Superheater

Economizer

Furnace
SCR

Gas
Outlet

Air Heater

Fig. 4 Longitudinal fins, staggered tube arrangement. (Fin width


exaggerated for clarity.)

Extended surfaces
Forced Draft Primary Air
Pulverizer Fan Fan To reduce capital costs, most boiler manufacturers
Fig. 2 Economizer and air heater locations in a typical coal-fired boiler. have built economizers with a variety of fin types to
enhance the controlling gas-side heat transfer rate.
Fins are inexpensive parts which can reduce the over-
all size and cost of an economizer. However, success-
ful application is very sensitive to the flue gas envi-
ronment. Surface cleanability is a key concern. In
selected boilers, such as PRB coal-fired units, extended
surface economizers are not recommended because of
the peculiar flyash characteristics.
Stud fins Stud fins have worked reasonably well in
gas-fired boilers. However, stud finned economizers
can have higher gas-side pressure drop than a com-
parable unit with helically-finned tubes. Studded fins
have performed poorly in coal-fired boilers because of
high erosion, loss of heat transfer, increased pressure
loss and plugging resulting from flyash deposits.
Longitudinal fins Longitudinally-finned tubes in
staggered crossflow arrangements, shown in Fig. 4,
have also not performed well over long operating pe-
riods. Excessive plugging and erosion in coal-fired
boilers have resulted in the replacement of many of
these economizers. In oil- and gas-fired boilers, cracks
have occurred at the points where the fins terminate.
These cracks have propagated into the tube wall and
caused tube failures in some applications. Plugging
with flyash can also be a problem (tight spaces).

Fig. 3 Bare tube economizer arrangements. Fig. 5 Helically-finned tube.

20-2 Steam 41 / Economizers and Air Heaters


The Babcock & Wilcox Company

Helical fins Helically-finned tubes (Fig. 5) have


been successfully applied to some coal-, oil- and gas-
fired units. The fins can be tightly spaced in the case
of gas firing due to the absence of coal flyash or oil
ash. Four fins per inch (1 fin per 6.4 mm), a fin thick-
ness of 0.06 to 0.075 in. (1.5 to 1.9 mm) and a height
of 0.75 in. (19.1 mm) are typical. For 2 in. (51 mm)
outside diameter tubes, these fins provide ten times
the effective area of bare tubes per unit tube length.
If heavy fuel oil or coal is fired, a wider fin spacing
must be used and adequate measures taken to keep
the heating surface as clean as possible. Economizers
in units fired with heavy fuel oil can be designed with
helical fins, spaced at 0.5 in. (13 mm) intervals.
Smaller fin spacings promote plugging with oil ash,
while greater spacings reduce the amount of heating
surface per unit length. Sootblowers are required and
the maximum bank height should not exceed 4 to 5 ft
(1.2 to 1.5 m) to assure reasonable cleanability of the
heating surface. An in-line arrangement also facili-
tates cleaning and provides a lower gas-side resistance. Fig. 7 Baffling of bare tube return bends for finned tube bundles.
Rectangular fins The square or rectangular fins, ar-
ranged perpendicular to the tube axis on in-line tubes
as shown in Fig. 6, have been used occasionally in maximum economical pressure loss. For high ash oil
retrofits. The fin spacing typically varies between 0.5 and coal, gas-side velocities are limited by the erosion
and 1 in. (13 and 25 mm) and the fins are usually potential of the flyash. This erosion potential is pri-
0.125 in. (3.18 mm) thick. There is a vertical slot down marily determined by the percentage of Al2O3, and
the middle because the two halves of the fin are welded SiO2 in the ash, the total ash in the fuel and the gas
to either side of the tube. Most designs are for gas maximum velocity. Experience dictates acceptable flue
velocities below 50 ft/s (15.2 m/s). However, because gas velocities. Fig. 8 provides sample base velocity lim-
of the narrow, deep spaces, plugging with flyash is a its as a function of ash characteristics. Note: PRB coal
danger with such designs. contains ash with low erosion potential. Velocities above
Baffles The tube ends should be fully baffled (Fig. 70 ft/s (21.3 m/s) can typically be allowed for such coals.
7) to minimize flue gas bypass around finned bundles. Further criteria may also be needed. For example,
Such bypass flow can reduce heat transfer, produce a 5 ft/s (1.5 m/s) reduction in the base velocity limit is
excessive casing temperatures, and with coal firing recommended when firing coals with less than 20%
can lead to tube bend erosion because of very high gas volatile matter. In other cases, such as Cyclone boil-
velocities. Baffling is also used with bare tube bundles ers, high flue gas velocities can be used because much
but is not as important as for finned tube bundles. Tube
bend erosion can be alleviated by shielding the bends.
Velocity limits
The ultimate goal of economizer design is to achieve
the necessary heat transfer at minimum cost. A key
design criterion for economizers is the maximum al-
lowable flue gas velocity (defined at the minimum
cross-sectional free flow area in the tube bundle).
Higher velocities provide better heat transfer and re-
duce capital cost. For clean burning fuels, such as gas
and low ash oil, velocities are typically set by the

Fig. 8 Base maximum allowable velocity for pulverized coal-fired


Fig. 6 Rectangular fins, in-line tube arrangement. boiler economizers.

Steam 41 / Economizers and Air Heaters 20-3


The Babcock & Wilcox Company

less flyash is carried into the convection pass, as much H f = enthalpy of saturated water at economizer
of the ash (> 50%) is collected in the bottom of the boiler outlet pressure
as slag. Particles that enter the boiler furnace are also These economizers can be economical in certain
less erosive. (See Chapter 15.) boilers. They require careful design and must be ori-
For a given tube arrangement and boiler load, the ented so the water flows upward and the outlet is be-
gas velocity depends on the specific volume of flue gas low drum level. This avoids water hammer and exces-
which falls as the flue gas is cooled in the economizer. sive flow instabilities. The enthalpy equation accounts
To maintain the gas velocity, it can be economical to for possible steaming due to flow imbalances and dif-
decrease the free flow gas-side cross-section by select- ferences in individual circuit heat absorptions.
ing a larger tube size in the lower bank of a multiple High-pressure, drum-type units are usually sensi-
bank design. This achieves better heat transfer and tive to feedwater temperatures close to saturation. To
reduces the total heating surface. enhance circulation, feedwater temperature to the
Other types of economizers drum should normally be at least 50F (28C) below
saturation temperature. However, for some applica-
Fig. 9 depicts an industrial boiler with a longflow tions, due to specific design conditions, use of Equa-
economizer, often used in chemical recovery boilers. tion 1 may result in a feedwater temperature slightly
Such heating surfaces consist of vertical, longitudi- greater than 50F (28C) below saturation temperature.
nally-finned (membraned) tubes through which the
feedwater flows upward. The gas flows downward in Performance
pure counterflow, outside the tubes and fins. While
the heat transfer is less efficient than crossflow banks Heat transfer
of tubes, there is minimal gas-side resistance and foul- Bare tubes The equations discussed in Chapter 4
ing products are removed through hoppers at the bot- can be used to evaluate the quantity of surface for an
tom of the enclosure. economizer. For the economizer shown in Fig. 2 with
Steaming economizers the upflow of water and downflow of gas and
nonsteaming conditions, the bundle can be treated as
Steaming economizers are defined as meeting the an ideal counterflow heat exchanger with the follow-
following enthalpy relationships: ing characteristics:
H 2 − H1 ≥ 2
3 (H f − H1 ) (1) 1. bundle log mean temperature difference correction
factor = 1.0,
where 2. heat absorbed by the tube wall enclosures and
heat radiated into the tube banks from various
H2 = enthalpy of fluid leaving economizer (to drum) cavities can generally be neglected,
H1 = enthalpy of fluid (water) entering economizer 3. all of the energy lost by the flue gas is absorbed
by the water, i.e., no casing heat loss,
4. the water-side heat transfer coefficient is typically
in the range of 2000 Btu/h ft2 F (11,357 W/m2 K)
and has only a small overall impact on the econo-
mizer performance, and
5. the effect of gas-side ash deposition can be accounted
for by a cleanliness factor based upon experience.
In general the heat transfer rate is primarily lim-
ited by the gas-side heat transfer for in-line bare tube
bundles. In this case, the overall heat transfer coeffi-
cient (flue gas to feedwater) used in the heat ex-
changer calculation can be approximated by the fol-
lowing relationship:

U = 0.98 ( hc + hr ) kf (2)
where
U = overall heat transfer coefficient, Btu/h ft2 F
(W/m2 K)
h c = gas-side heat transfer coefficient for a bare
tube bundle, Btu/h ft2 F (W/m2 K) (Chapter
4, Equations 60 and 61)
h r = inter-tube radiation heat transfer coefficient,
Btu/h ft2 F (W/m2 K) ≈ 1.0 for coal firing (for
finned tubes hr, is very small and is assumed
to be 0)
kf = surface effectiveness factor = 0.7 for coal, 0.8
Fig. 9 Longflow economizer for a chemical recovery boiler. for oil and 1.0 for gas

20-4 Steam 41 / Economizers and Air Heaters


The Babcock & Wilcox Company

Finned tubes Heat transfer performance of finned


tube economizers can be evaluated in a similar fash-
ion except that appropriate relationships for extended
surfaces should be used. In addition, because the gas-
side heat transfer has been enhanced, the water-side
heat transfer coefficient and tube wall thermal resis-
tance are more significant and must be included in the
evaluation. (See Chapter 4.) As a general guideline,
the overall heat transfer coefficient can be approxi-
mated by the following relationship for most types of
economizer fins:
U = 0.95 ( hg kf ) (3)

where hg is the gas-side heat transfer coefficient for


the heat transfer across finned tube bundles evalu-
ated with the procedures defined in Chapter 4. A cal-
culated example is provided in Chapter 22 for a bare
tube economizer tube bundle.
Gas-side resistance
The gas-side pressure loss across the economizer Fig. 10 Economizer supports – sample waterwall support arrangement.
tube bank can be evaluated using the crossflow cor-
relations presented in Chapter 3. The pressure loss
analyzing the allowable deflection in the tubes and
should be adjusted for the number of tube rows using
tube assemblies. Deflection is important for tube
the correction factors provided. The gas-side resistance
drainability. Figs. 10 through 12 show typical support
across the in-line finned tube banks is approximately
arrangements for bare tube economizers.
1.5 times the resistance of the underlying bare tubes.
Wall or end supports are usually chosen for rela-
Water-side pressure drop tively short spans and require bridge castings or in-
dividual lugs welded or attached to the tube wall en-
The water-side pressure loss can be evaluated us-
closures. (See Fig. 10.) Another possibility exists if en-
ing the procedures in Chapter 3 where the total pres-
closure wall (usually primary superheater circuitry)
sure loss ∆PT is calculated:
headers are present above the economizer (for ex-
ample, Fig. 11).
∆PT = ∆Pf + ∆Pl + ∆Pz (4)
Quarter point stringer supports are used for spans
where exceeding the limits for end supports (Fig. 12). The
stringers are mechanically connected to the economizer
∆Pf = friction pressure loss Ch. 3, Eq. 47 sections, which are held up by ladder type supports.
∆Pl = sum of the local losses Ch. 3, Eq. 52 The supports exposed to hot inlet gases may be made
(entrance, bends and exits)
∆Pz = static head loss Ch. 5, Eq. 10
The design pressure is then evaluated by the sum
of the drum design pressure and the total pressure loss
∆PT rounded up to the nearest 25 psig (172 kPa).
If the calculated water-side pressure drop is exces-
sive, the number of parallel flow paths must be in-
creased. If the flue gas velocity can be increased, the
water-side pressure drop can also be reduced by in-
creasing the tube size, usually in increments of 0.125
in. (3 mm). As indicated in Chapter 3, the dynamic
pressure drop is inversely proportional to the fifth
power of the inside tube diameter.

Economizer support systems


Economizers are located within tube wall enclosures
or within casing walls, depending on gas tempera-
tures. In general, casing enclosures are used at or
below 850F (454C) and inexpensive carbon steel can
be used. If a casing enclosure is used, it must not sup-
port the economizer. However, tube wall enclosures
may be used as supports. Fig. 11 Economizer supports – sample lower waterwall header
The number of support points is determined by arrangement.

Steam 41 / Economizers and Air Heaters 20-5


The Babcock & Wilcox Company

cated inside the gas stream and may receive feedwater


through one or both ends. Regardless of design, it is
necessary to properly seal the inlet pipe where it pen-
etrates the enclosure by using brackets and flexible
seals. The seal becomes especially important in pres-
surized (forced draft) units. Other important consid-
erations are tube leg flexibility, differential expansion
and potential gas temperature imbalances and upsets.
The outlet headers, not to be confused with inter-
mediate or transition headers seen in larger boilers
and stringer supports, receive the heated feedwater
and convey it to the drum or, in the case of once-
through boilers, to the downcomer(s) supplying the
furnace circuitry. Inlet and outlet headers must be
large enough to assure reasonable water flow distri-
bution in the economizer banks. Flow velocities in
headers are typically less than 20 ft/s (6.1 m/s).

Vibration ties
Vibration ties or tube guides are required on some
Fig. 12 Economizer supports – sample stringer support arrangement. end-supported tube sections. These ties may be needed
if the natural frequencies within the boiler load range are
of stainless steel, while lower grade material is nor- in or near resonance with the vortex shedding frequency.
mally used to support the lower bank which is exposed Stringer tubes are also subject to vibration. This vi-
to reduced gas temperatures. In The Babcock & Wil- bration is magnified by long unsupported stringer tube
cox Company (B&W) designs, stringer tubes also usu- lengths near the large cavity below the convection
ally support other horizontal convection surfaces pass roof.
above the economizer. (See frontispiece.) Bottom sup-
port is sometimes used if the gas temperature leaving Tube geometry, materials and code
the lowest economizer bank is low enough. requirements
Economizer tube diameters typically range between
Bank size 1.75 and 2.5 in. (44.5 and 63.5 mm). Tubes outside this
The bank size is limited by the following constraints: range are sometimes used in retrofits. Smaller tubes are
normally used in once-through, supercritical boilers
1. type of fuel, where water-side pressure drop is less of a consideration.
2. fabrication limits, In these units, tube wall thicknesses are minimized.
3. sootblower range, The ASME Code requires that the design tempera-
4. maximum shipping dimensions, ture for internal boiler pressure parts is at least 700F
5. construction considerations, especially for retrofits, (371C). The calculated mean tube wall temperature
and in economizers seldom reaches this temperature. It
6. maintenance. usually lies 10 to 20F (6 to 11C) above the fluid tem-
Bank depths greater than 6 ft (1.83 m) are rare in perature, which seldom exceeds 650F (343C) along
new boilers, while carefully designed larger banks can any economizer circuit.
be tolerated in retrofits. The minimum tube wall thickness is determined in
accordance with procedures outlined in Chapter 8.
In coal-fired boilers, the side spacing is usually de-
Access requirements termined by the maximum allowable gas velocity and
Cavities around the banks are needed for field weld- gas-side resistance, which are functions of a given tube
ing, tube leg maintenance and sootblower clearance. size. If fins are used, the side and back tube spacings
A sufficient number of access doors must be arranged should permit the fin tips to be at least 0.5 in. (13 mm)
in the enclosure walls to access these cavities. Cavity apart. For bare tubes, a minimum clear spacing of 0.75
access can be provided from the outside through indi- in. (19 mm) is desirable.
vidual doors or from the inside through special open- PRB coal firing usually calls for increased clear side
ings across stringers or collector frames. The minimum spacing to avoid plugging and bridging with flyash
cavity height should be 2 ft (0.6 m) of crawl space. in the horizontal spaces.
The minimum back (vertical) spacing of the tubes
should be no less than 1.25 times the tube outside di-
Headers ameter. Smaller ratios can reduce heat transfer by as
B&W economizer header designs are typically based much as 30%. Ratios larger than 1.25 have relatively
on American Society of Mechanical Engineers (ASME) little effect on heat transfer but increase the gas-side
Code requirements. Inlet headers are frequently lo- resistance and bank depth.

20-6 Steam 41 / Economizers and Air Heaters


The Babcock & Wilcox Company

SCR considerations heaters enhances combustion of all fuels and is


needed for drying and transporting the fuel in pul-
SCR systems are normally located between the verized coal-fired units.
economizer and the air heater. NOx reduction reactions
take place within an optimal temperature range as the
flue gas passes through the catalyst reactor (see Chap- Classification of air heaters
ter 34). Therefore, flue gas temperature entering the Air heaters are classified according to their principle
SCR is critical to system performance. of operation as recuperative or regenerative.
Typical temperature control methods include:
1. Gas bypass The goal is to maintain a minimum Recuperative
gas temperature to the SCR, typically 600F (316C) In a recuperative heat exchanger, heat is trans-
to 650F (343C) for coal-fired applications, over the ferred continuously and directly through stationary,
boiler load range in which the SCR will be oper- solid heat transfer surfaces which separate the hot
ated. This can be achieved by extracting flue gas flow stream from the cold flow stream. The most com-
from a cavity above the economizer or between mon heat transfer surfaces are tubes and parallel
economizer banks, and routing the higher tem- plates. Recuperative heat exchangers function with little
perature gas to a point upstream of the SCR where cross-contamination, or leakage, between streams.
it is mixed with lower temperature gas from the Tubular air heaters In a typical tubular air heater,
economizer outlet. The gas flow through the by- energy is transferred from the hot flue gas flowing
pass flue is controlled by a damper. inside many thin walled tubes to the cold combustion
In retrofits, the bypass gas flow is usually lim- air flowing outside the tubes. The unit consists of a
ited by the available gas-side pressure differen- nest of straight tubes that are roll expanded or welded
tial and maximum allowable gas velocity through into tubesheets and enclosed in a steel casing. The
the bypass flue. Existing physical constraints limit casing serves as the enclosure for the air or gas pass-
the maximum flue size. The increase in flue gas ing outside of the tubes and has both air and gas in-
temperature entering the SCR reduces boiler ef- let and outlet openings. In the vertical type (Fig. 13),
ficiency due to an increase in flue gas tempera- tubes are supported from either the upper or lower
ture leaving the unit. To reduce this loss in boiler tubesheet while the other (floating) tubesheet is free
efficiency, a separate economizer bank can be in- to move as tubes expand within the casing. An expan-
stalled downstream of the SCR or additional air sion joint between the floating tubesheet and casing
heater surface can be added if space is available. provides an air/gas seal. Intermediate baffle plates
2. Water-side bypass Water-side parameters (i.e., parallel to the tubesheets are frequently used to sepa-
mass flow) indirectly control the flue gas tempera- rate the flow paths and eliminate tube damaging flow
ture exiting the economizer by reducing the wa- induced vibration.
ter flow through some of the economizer surface, Carbon steel or low alloy corrosion resistant tube
thus reducing economizer heat absorption. (In- materials are used in the tubes which range from 1.5
stead of a gas-side damper controlling the gas to 4 in. (38 to 102 mm) in diameter and have wall
bypass flow, several control valves regulate wa-
ter flow to the various economizer banks.) Econo-
mizer water outlet temperature should not exceed
certain limits dictated by furnace circulation.
3. Duct burners Special duct burners (usually natu-
ral gas fired) are sometimes used to raise the gas tem-
perature entering the SCR. However, the econom-
ics of natural gas firing must be carefully evaluated.

Air heaters
Air heaters are used in most steam generating
plants to heat the combustion air and enhance the
combustion process. Most frequently, the flue gas is
the source of energy and the air heater serves as a
heat trap to collect and use waste heat from the flue
gas stream. This can increase the overall boiler effi-
ciency by 5 to 10%. Air heaters can also use extrac-
tion steam or other sources of energy depending upon
the particular application. These units are usually em-
ployed to control air and gas temperatures by preheat-
ing air entering the main gas-air heaters.
Air heaters are typically located directly behind the
boiler, as depicted in Fig. 2, where they receive hot flue
gas from the economizer and cold combustion air from
the forced draft fan(s). The hot air produced by air Fig. 13 Vertical type tubular air heater.

Steam 41 / Economizers and Air Heaters 20-7


The Babcock & Wilcox Company

thicknesses of 18 to 11 gauge [0.049 to 0.120 in. (1.24 Cast iron air heaters Cast iron tubular air heaters
to 3.05 mm)]. Larger diameter, heavier gauge tubes are heavy, large and durable. Their use is mainly lim-
are used when the potential for tube plugging and cor- ited to the petrochemical industry, but some are used
rosion exists. Tube arrangement may be in-line or stag- on electric utility units. Cast iron is used because of
gered with the latter being more thermally efficient. its superior corrosion resistance. Rectangular, longi-
Tubular air heaters may be fitted with steam or air tudinally split tubes are assembled from two cast iron
sootblowers to remove ash accumulations from the gas- plates and individual tubes are assembled into air
exposed side of tubing during operation. Permanent heater sections. Air heaters are usually arranged for
water wash piping above gas-side tube banks may a single gas pass and multiple air passes with air flow
also be used off line to soak and wash tube internal inside the tubes. Heat transfer is maximized by fins
or external surfaces. cast into inside and outside tube surfaces.
The most common flow arrangement is counterflow Plate air heaters Plate air heaters transfer heat from
with gas passing vertically through the tubes and air hot gas flowing on one side of a plate to cold air flow-
passing horizontally in one or more passes outside the ing on the opposite side, usually in crossflow. Heaters
tubes. A variety of single and multiple gas and air path consist of stacks of parallel plates. Sealing between air
arrangements are used to accommodate plant layouts. and gas streams at plate edges is accomplished by
Designs frequently include provisions for cold air by- welding or by a combination of gaskets, springs and
pass or hot air recirculation to control cold end corro- external compression of the plate stack. Plate materi-
sion and ash fouling. Modern tubular air heaters are als and spacing can be varied to accommodate oper-
shop assembled into large, transportable modules. ating requirements and fuel types.
Several arrangements are shown in Fig. 14. Steel plate air heaters were some of the earliest types

Fig. 14 Various tubular air heater arrangements.

20-8 Steam 41 / Economizers and Air Heaters


The Babcock & Wilcox Company

used, but their use declined due to plate to plate seal-


ing problems. However, sealing developments have
prompted increased use in industrial and small util-
ity applications. Plate modules may be combined to
make different size air heaters with a variety of flow
path arrangements. A single gas pass, two air pass
plate air heater is shown in Fig. 15. Modern plate units
are somewhat smaller than tubular units for a given
capacity and exhibit minimal air to gas leakage.
Steam coil air heaters Steam coil and water coil re-
cuperative air heaters are widely used in utility steam
generating plants to preheat combustion air. Air pre-
heating reduces the corrosion and plugging potential
in the cold end of the main air heater. Occasionally,
they serve as the only source of preheated combus-
tion air. These heaters consist of banks of small diam-
eter, externally finned tubes arranged horizontally or
vertically in ducts between the combustion air fan and
main air heater. Combustion air, passing in crossflow
outside the tubes, is heated by turbine extraction
steam or feedwater flowing inside the tubes. Ethyl-
ene glycol is sometimes used as the hot fluid to pre-
vent out of service freezing damage.
Regenerative
Regenerative air heaters transfer heat indirectly by
convection as a heat storage medium is periodically
exposed to hot and cold flow streams. A variety of
materials can be used as the medium and periodic
exposure to hot and cold flow streams can be accom-
plished by rotary or valve switching devices. In steam
generating plants, tightly packed bundles of corru- Fig. 15 Single gas pass, two air pass plate air heater.
gated steel plates serve as the storage medium. In these
units either the steel plates, or surface elements, rotate
through air and gas streams, or rotating ducts direct air hot end on top and cold end on bottom. In operation,
and gas streams through stationary surface elements. the rotor is subjected to a temperature differential, hot
Regenerative air heaters are relatively compact and top and cold bottom, causing the rotor to expand and
are the most widely used type for combustion air pre- bow (or distort) upward. This rotor distortion opens
heating in electric utility steam generating plants. gaps between the rotor and stationary parts through
Their most notable operating characteristic is that a which objectionable air-side to gas-side leakage occurs.
small but significant amount of air leaks into the gas Air to gas leakage is controlled by cold-presetting
stream due to the rotary operation. axial and radial seal plates to minimize gaps at the
Ljungström The most common regenerative air hot operating condition (Fig. 19). Note that a signifi-
heater is the Ljungström ® type (Figs. 16 and 17), cant radial gap remains at the hot end which is toler-
which features a cylindrical shell plus a rotor which ated in industrial and small utility boiler air heaters.
is packed with bundles of heating surface elements However, for controlling leakage in larger units the
and is rotated through counterflowing air and gas hot end radial sealing plate is designed to adjust au-
streams. The rotor is enclosed by a stationary hous- tomatically during operation to follow rotor distortion
ing which has ducts at both ends. Air flows through and maintain a minimum seal gap.
one half of the rotor and gas flows through the other Sootblowing devices in the gas outlet are used to
half. Metallic leaf-type seals minimize air to gas leak- direct superheated steam or dry air via nozzles into
age and flow bypass around the rotor. See Fig. 18. the rotor heating surface elements to periodically clean
Bearings in upper and lower beam assemblies support them of fuel residue accumulations during operation.
and guide the rotor at the central shaft. A rotor speed For especially heavy or tenacious deposits, sootblow-
of one to three rpm is provided by a motor driven pin- ers may also be used at the air heater gas inlet.
ion engaging a rotor encircling pinrack. Both vertical Air heaters operating in dirty flue gas streams (coal,
and horizontal shaft designs are used to accommodate oil, waste, biomass, etc.) are also fitted with perma-
various plant air and gas flow schemes. The vertical nent water wash piping for soaking and cleaning
shaft design is more common. heavy heating surface ash accumulations. The wash
The most prevalent flow arrangement has the hot piping is located in the top of the heater above the rotor
gas entering the top of the rotor as cold air enters the with nozzles arranged such that all heating surface
bottom in counterflow fashion, as shown in Fig. 16. elements are exposed to the nozzle spray pattern as
Heaters employing this flow scheme are identified as the rotor turns. Air heaters are normally washed off-

Steam 41 / Economizers and Air Heaters 20-9


The Babcock & Wilcox Company

Fig. 16 Ljungström-type air heater.

line as the rotor is turned via an auxiliary drive. Air


heater washing through sootblowers may also be done
with appropriate piping and valves.
Rothemühle The Rothemühle®-type regenerative
air heater uses stationary surface elements and rotat-
ing ducts (Fig. 20). The surface elements are supported
and contained within a stationary cylindrical shell
called the stator. On both sides of the stator, a double
wing symmetrical hood rotates synchronously on a
common vertical shaft. The central shaft is supported
by bearings within the stator and the hoods are driven
slowly by a pinion which engages a pinrack encircling
the lower hood. Stationary housings surround the
hoods. Heat is transferred as flow streams are directed
through the heating surface in counterflow fashion,
one flow stream inside the hoods and the other outside.
Either air or gas may pass through the hoods. However,
air is more common because it requires less fan power.
Rothemühle air heater stators distort in a manner
similar to Ljungström rotors. Special sealing systems
mounted to rotating hoods at the interface with the sta-
tor are used to control leakage. Both preset and auto-
mated seal systems are used. Sealing at the rotating hood
to stationary duct interface is maintained by a ring of
spring-backed cast iron seal shoes and a rotating race.
Sootblowers mounted to the outside of rotating
hoods are employed on cold and hot ends as fuels dic-
Fig. 17 Air heater service project at a midwest U.S. power plant. tate. Water wash piping both inside the hoods (rotat-

20-10 Steam 41 / Economizers and Air Heaters


The Babcock & Wilcox Company

Radial Leaf Seal Cold Condition Hot Operation

Sealing Surface Automatic Radial Seal


Adjuster or Actuator Plate Drive

Radial Sealing Plate Radial


Seal Plate

Axial
Seal
Plate
Cold End Radial Seal Plate Axial Seal
Fig. 19 Cross-section through air heater rotor and seal plates.

ment. Heavy gauge, open profile elements are used for


corrosion resistance and cleanability. Practically all cold
layer elements are low alloy corrosion resistant steel or,
Circumferential
when high corrosion potential exists, porcelain enamel
Bypass Seal coated steel. Hot and intermediate surface layers are
Sealing Surface Adjuster
more compact than cold layers and use thinner plates.
Fig. 21 illustrates several heating surface element pro-
Radial Leaf Seal
files and air heater surface arrangements.
Axial Sealing Plate

Axial Leaf Seal


Fig. 18 Ljungström-type air heater seals.

ing piping) and outside the hoods (stationary piping)


assures complete coverage of the heating surface.
Special sootblower and rotating wash piping seals are
used at the rotating-stationary interface.
Regenerative heating surface Regenerative air
heater surface elements are a compact arrangement
of two specially formed metal plates. Each element
pair consists of a combination of flat, corrugated or un-
dulated plate profiles. The roll formed corrugations
and undulations serve to separate the plates to main-
tain flow paths, increase heating surface area and
maximize heat transfer by creating flow turbulence.
The steel plates, 26 to 18 gauge thick, are typically
spaced 0.2 to 0.4 in. (5 to 10 mm) apart. Closely spaced,
highly profiled element pairs exhibit a high heat
transfer rate, pressure drop and fouling potential while
widely spaced element combinations, where one plate
is flat, exhibit a low heat transfer rate, low pressure
drop and reduced fouling potential. The combination
of plate profile, material and thickness is selected for
maximum heat transfer, minimum pressure drop,
good cleanability and high corrosion resistance.
Surface elements are stacked and bundled into self-
contained baskets and are installed into air heater
rotors and stators in two or more layers. The surface
layer at the air inlet side, designated the cold layer, is
distinguished from other layers by design. Cold lay-
ers, which are subject to corrosion and ash fouling, are
typically 12 in. (305 mm) deep for economical replace- Fig. 20 Rothemühle-type air heater.

Steam 41 / Economizers and Air Heaters 20-11


The Babcock & Wilcox Company

and radiation components as well as the appropriate


gas- and air-side fouling factors. U typically ranges
from 3 to 10 Btu/h ft2 F (17 to 57 W/m2 K).
Performance verification Thermal performance is
measured by comparing the test gas outlet tempera-
ture to its design value. The true outlet temperature
is obtained by correcting the measured temperature for
air heater leakage and deviations from design conditions.
The ASME Performance Test Code, Section 4.3 (PTC
4.3), provides the following equation which is based
on an air heater mass flow heat balance and assumes
that the source of all leakage is from the entering air:

 % lkg  c pa
T2 = T2m +   (T2m − T1 ) (6)
 100  c pg

where
T2 = air heater gas outlet temperature cor-
rected for leakage, F (C)
T2m = measured gas temperature leaving air
heater, F (C)
% lkg = percent air leakage with respect to inlet
gas flow
cpa, cpg = specific heat of air and gas respectively,
Btu/lb F (J/kg C)
T1 = air inlet temperature, F (C)

The measured gas outlet temperature must also be


corrected for deviations in various operating param-
eters such as mass flow rates and operating tempera-
tures in order to accurately assess performance. Sup-
pliers and the ASME Performance Test Codes provide
Fig. 21 Regenerative air heater surface element profiles. various correction curves and factors for this purpose.
Leakage
Advantages and disadvantages Air flow passing from the air side to the gas side is
called leakage. It is quantified in pounds per hour (kg/s)
Many subtle differences exist between air heater but is frequently expressed as a percentage of the gas
designs within a particular type. However, there are inlet flow. Leakage is undesirable primarily because
some general advantages and disadvantages associ- it represents fan power wasted in conveying air which
ated with each type which are listed in Table 1. bypasses the boiler combustion zone. Leakage can also
reduce an air heater’s thermal performance.
Performance and testing Recuperative units may begin operation with essen-
tially zero leakage, but leakage occurs as time and
Air heaters are designed to meet performance require- thermal cycles accumulate. With regular mainte-
ments in three areas: thermal, leakage and pressure nance, leakage can be kept below 3%. Air heater leak-
drop. Low performance in any area increases boiler op- age is inherent with the rotary regenerative design.
erating costs and may cause unit load curtailment. There are two types of leakage, gap and carryover.
Thermal performance
The thermal performance and surface area (A) of a
recuperative air heater can be evaluated by: Table 1
Advantages and Disadvantages of Air Heater Types
A = q / (U LMTD F ) (5)
Type Advantage Disadvantage
where q is the rate of heat transfer [Btu/h (W)], U is Recuperative Low leakage Large and heavy
the overall heat transfer coefficient, LMTD is the log No moving parts Difficult to replace
mean temperature difference between the hot and surface
cold fluids, and F is the heat exchanger arrangement
factor. The performance, U, LMTD and F can be evalu- Regenerative Compact Leakage
Easy to replace High maintenance
ated using the correlations and methodology presented surface Fire potential
in Chapter 4. The overall U should include convection

20-12 Steam 41 / Economizers and Air Heaters


The Babcock & Wilcox Company

Gap leakage occurs as higher pressure air passes to the square of the mass flow rate. Typical values at full
the lower pressure gas side through gaps between load flows are 2 to 7 in. wg (0.5 to 1.7 kPa).
rotating and stationary parts. Its rate is given by the Air- and gas-side pressure drop values are the dif-
following general expression: ferences between terminal inlet and outlet static gauge
pressures. Correction of measured pressure drops for
wl = KA ( 2 gc ∆P ρ ) deviations from design flows and temperatures is
1/2
(7)
necessary before comparison to design values.
where
wl = leakage flow rate, lb/h (kg/s) Operational concerns
K = discharge coefficient, dimensionless (gener- There are several operating conditions and main-
ally 0.4 to 1.0) tenance concerns common to most air heaters. These
A = flow area, ft2 (m2) include corrosion, plugging and cleaning, leakage per-
g c = 32.17 lbm ft/lbf s2 × (3600 s/h)2 = formance degradation, erosion and fires. Air heaters
4.17 × l08 lbm ft/lbf h2 (1 kg m/N s2) used with high ash and/or high sulfur content fuels
∆P = pressure differential across gap, lb/ft2 (kg/m2) require more attention and maintenance than those
ρ = density of leaking air, lb/ft3 (kg/m3) firing clean fuels such as natural gas.
Carryover leakage is the air carried into the gas Corrosion
stream from each rotor (stator) heating surface com-
partment as the surface passes from the air stream to Air heaters used on units firing sulfur bearing fu-
the gas stream. This leakage is directly proportional els are subject to cold end corrosion of heating elements
to the void volume of the rotor and the rotation speed. and nearby structures. In a boiler, a portion of the
Regenerative air heater design leakage ranges from sulfur dioxide (SO2) produced is converted to sulfur
5 to 15% but increases over time as seals wear. Effec- trioxide (SO3) which combines with moisture to form
tive automatic sealing systems, which nearly elimi- sulfuric acid vapor. This vapor condenses on surfaces
nate leakage rise due to seal wear, have been success- at temperatures below its dew point of 250 to 300F
fully applied. These systems monitor and adjust ro- (121 to 149C). Because normal air heater cold end
tating to stationary seals on-line. metal temperatures are frequently as low as 200F
Another source of boiler air to gas flow leakage, (93C), acid dew point corrosion potential exists. The
which appears as air heater leakage, is outside air in- obvious solution would be to operate at metal tempera-
filtration into lower pressure gas streams. Infiltration tures above the acid dew point but this results in un-
may occur at casing cracks or holes, flue expansion acceptable overall boiler heat losses. Most air heaters
joints and access doors or gaskets. This sometimes ne- are designed to operate at minimum metal tempera-
glected source can be significant and difficult to de- tures (MMTs) somewhat below the acid dew point,
tect if leaks occur under lagging and insulation. where the efficiency gained more than balances the
Air heater leakage can be obtained directly as the additional maintenance costs. B&W recommends lim-
difference between air- or gas-side inlet and outlet iting MMTs to the values in Figs. 22 and 23 when
flows based on velocity measurements. However, be- burning sulfur bearing fuels.
cause velocity measurements are difficult to obtain When fuel sulfur levels are high, or ambient tem-
accurately in large duct cross-sections, air heater leak- peratures or operating loads are low, MMTs may be
age is more accurately based on calculated gas weights unacceptably low. These situations dictate the use of
using gas analysis, boiler efficiency and fuel analysis active or passive cold end corrosion control methods.
data. (See Chapter 10.) Approximate air heater leak- Active systems used to raise MMT include: 1) steam-
age can be determined by the following formula based or water-coil air heaters to preheat inlet air, 2) cold
on gas inlet and outlet oxygen (O2) analysis (dry basis). air bypass, in which a portion of the inlet air is ducted
around the air heater, and 3) hot air recirculation, in
which a portion of the hot outlet air is ducted to com-
% Leakage =
bustion air fan inlets.
% O2 Leaving − % O2 Entering (8)
× 90
21 − % O2 Leaving

Test air heater leakage should be corrected for de-


viations from design cold end air to gas differential
pressure and inlet air temperature before comparison
to design leakage.
Pressure drop
In recuperative air heaters, gas- or air-side pres-
sure drop arises from frictional resistance to flow, in-
let and exit shock losses and losses in return bends be-
tween flow passes. In regenerative air heaters, the
main cause is heating surface frictional flow resis- Fig. 22 Recuperative air heater cold end MMT limits when burning
tance. In both cases, pressure drop is proportional to sulfur-bearing fuels.

Steam 41 / Economizers and Air Heaters 20-13


The Babcock & Wilcox Company

continuously until the surface is deemed clean. Clean-


liness may be proven by observed clarity of wash out-
let water or by the ability to see light directed through
the surface bank.
In cases where low pressure washing is not effec-
tive, high pressure washing is done. Power plant op-
erators employ air heater washing specialists and
equipment with water jets at nozzle pressure above
5000 psi (34.5 MPa). Special care must be taken to avoid
breaking and/or flattening regenerative element plates.
Erosion
Heat transfer surfaces and other air heater parts
can suffer erosion damage through impact of high
velocity, gas-entrained ash particles. Erosion usually
occurs near gas inlets where velocities are highest.
However, areas near seals in regenerative air heat-
ers can also be damaged as ash is accelerated through
seal gaps. The undesirable effects of erosion are struc-
tural weakening, loss of heat transfer surface area and
perforation of components which can cause air to gas
or infiltration leakage. Erosion rate is a function of ve-
locity, gas stream ash loading, physical nature of ash
particles and angle of particle impact. It is controlled
by reducing velocities, removing erosive elements from
the gas stream, or using sacrificial material.
Fig. 23 Regenerative air heater cold end MMT limits when burning In the design stage, air heaters used with fuels con-
sulfur-bearing fuels. taining highly erosive ash can be sized to limit gas
inlet velocities to 50 ft/s (15 m/s). Inlet flues can also
Passive corrosion control methods incorporated in air be designed to evenly distribute gas over the air
heater design include: 1) thicker cold end materials, such heater inlet to eliminate local high velocity areas. Dust
as 11 or 14 gauge (3 or 2 mm) tubes and 18 gauge (1 collectors, or strategically located screens and hoppers,
mm) regenerative surface elements, 2) low or high alloy may be used ahead of air heaters to remove some of the
cold end surface materials which have at least twice the ash. In existing problem air heaters, flow distribution
corrosion life of carbon steel, 3) nonmetallic coating, such baffles may be installed to eliminate local high veloci-
as porcelain enamel, Teflon, or epoxies on cold elements, ties, sacrificial materials such as abrasion resistant steel
4) nonmetallic cold end surface materials such as ex- or ceramics may be placed over critical areas, or parts
truded ceramic in regeneratives and borosilicate glass can be replaced with thicker materials for longer life.
tubes in tubulars, and 5) tubular air heater cold end tube Erosion in tubular air heaters frequently occurs
arrangements which maximize MMT by providing within about 1 ft (0.3 m) of the gas inlet end due to
higher gas flow and lower air flow velocities. turbulence as gas enters the tubes. Replaceable sac-
rificial sleeves may be installed in tube ends or egg
Plugging and cleaning crate-type flow straightening grids can be installed at
Plugging is the fouling and eventual closing of heat tubular air heater inlets to reduce erosion.
transfer flow passages by gas-entrained ash and cor-
rosion products. It can occur at the air heater hot end Fires
but is most common at the cold end where ash par- Air heater fires are rare but do occur, particularly
ticles adhere to acid moistened surfaces. Plugging in- in regenerative units, and may be severe enough to
creases air heater pressure drop and can limit unit completely destroy an air heater. Fires are detected by
load when fan capacity is reached at less than full load. thermocouples in gas and air outlet ducts as well as
Air heater deposits are controlled and removed by with special early warning systems. Fires usually start
periodic on-line sootblowing, and by various methods near the cold end, which can be fouled with unburned
of cold end temperature control as described above to combustible materials. Most fires occur during startup
control corrosion. Deposits may also be controlled by as unburned fuel oil deposited on ash fouled heating
employing regenerative heating surface designs with surfaces is ignited. Leaking bearing lubrication equip-
easier-to-clean, less tortuous flow paths, and by us- ment and heavy accumulations of flyash are also fire
ing smooth enamel coated regenerative surface ele- hazards. Fires can be avoided by maintaining a clean
ments that resist particle adherence. air heater and proper tuning of boiler firing equip-
When on-line cleaning methods are no longer able ment. Frequent sootblowing during startup and just
to stop or reverse fouling, off-line cleaning is neces- before shutdown is a strongly recommended fire pre-
sary. Regenerative and recuperative air heater sur- vention practice.
face is normally washed off-line with permanent, low After a fire is confirmed, typical practice is to trip
pressure wash piping. The surface is deluged (washed) the boiler to stop air flow through the heater, to keep

20-14 Steam 41 / Economizers and Air Heaters


The Babcock & Wilcox Company

the air heater rotating, and to introduce as much water Hot


Gas In
as possible through the permanent water wash sys- Secondary
tem. Drains in air- and gas-side duct hoppers below the Air Out
air heater must be opened to remove water and ash. Primary
Air Out

Utility applications
Gas to air recuperative and regenerative air heat-
ers are usually used in utility units, primarily to en-
hance unit efficiency. Small increments of increased
efficiency in large units amount to substantial fuel
savings. Utility units generally use multiple air heat-
ers for plant arrangement convenience, type of firing
and maximum unit availability.
Pulverized coal-fired units require two streams of
hot combustion air, i.e., primary air supplied at high
pressure to pulverizers and secondary air supplied at
lower pressure directly to burners. Two basic air flow
systems are used, hot primary air and cold primary Rotation
air. Each system uses air heaters. In the hot primary
air scheme, used for smaller units, about one third of
the combustion air heated in a secondary heater is
ducted to hot primary air fans, where it is boosted in
pressure and passed to the pulverizers; the remain-
ing two thirds is ducted to the burners. The cold pri-
Secondary
mary air system uses separate air heaters supplied by Cool Air In
Gas Out
separate primary and secondary (forced draft) fans. Primary
In some units, both primary and secondary air are Air In
heated in a single regenerative unit which is more cost Fig. 24 Ljungström-type tri-sector air heater.
effective than separate air heaters. Fig. 24 shows a
schematic Ljungström-type air heater for primary and
secondary air, referred to as a tri-sector. objectionable flue gas constituents, NOx and SO2, may
If separate regenerative primary and secondary air require the use of specially modified heat exchangers.
heaters are used, the primary air heaters, which op- NOx removal
erate at high air to gas pressure differentials, exhibit
twice as much leakage as the secondary units. For this When selective catalytic reduction (SCR) technol-
reason, low leakage recuperative air heaters may be ogy is used on a boiler to control NOx emissions, air
used for primary air heating and regeneratives may heaters operating downstream of the SCR require
be used for secondary air heating. special consideration. A typical, popular arrangement
Recuperative and regenerative air heaters are used is to place the SCR reactor in the boiler flue gas stream
on oil- and gas-fired units. In general, regardless of between the economizer outlet and air heater inlet
fuel type, larger units use regenerative air heaters (high dust arrangement).
because of their smaller size and lower initial cost. The SCR reduces NOx by injecting ammonia (NH3)
However, for air to gas pressure differentials above into the flue gas just upstream of a catalyst which
40 in. wg (10 kPa), in fluidized-bed applications for ex- converts the NOx to water and elemental nitrogen (N2).
ample, recuperative air heaters are usually preferred. However, the catalyst also converts some of the sul-
fur dioxide (SO2) in the flue gas to sulfur trioxide (SO3)
which combines with unreacted NH3 to form ammo-
Industrial applications nium bisulfate (NH4HSO 4). This condenses on air
Industrial units fire a variety of fuels such as wood, heater surface elements in the 510 to 340F (266 to
municipal refuse, sewage sludge and industrial waste 171C) temperature range. The objectionable
gases as well as coal, oil and natural gas. As a result, NH4HSO4 fouling and corrosion in regenerative air
many air heater types are used. In the small units, heaters can be controlled to manageable levels by
tubular, plate and cast iron heaters are widely used. design features including:
Fuels fired on stoker grates, such as bituminous coal, 1. Arranging heating surface basket layers so that
wood and refuse, do not require high air temperatures, NH4HSO4 deposition occurs within a layer rather
therefore water- or steam-coil air heaters can be used. than between layers. Deposition in the space be-
tween basket layers is more difficult to remove
and keep clean. It is typical to provide two rather
Environmental air heater application than three air heater basket layers.
For environmental reasons, emission of certain fos- 2. Employing a closed profile heating element which
sil-fired combustion products may be limited by law. (See allows deeper and more effective sootblower clean-
Chapter 32.) Systems developed to limit emissions of two ing. Closed profile elements are designs in which

Steam 41 / Economizers and Air Heaters 20-15


The Babcock & Wilcox Company

individual flow passages are closed through the


depth of the element layer and do not allow soot- Flue Gas
blowing media to quickly dissipate. from
Particulate
ID Fan Stack
3. Using porcelain enamel coated bottom layer heat- Collector
ing surface which resists corrosion and deposition,
and is easier to clean because of the smooth surface.
Untreated Treated
4. Fitting the heater with hot and cold end sootblow- Hot Gas Warm Gas
ers which can be used to water wash heating sur- 277F 194F
face off-line. (136C) (90C)

Heat exchangers with these features can typically


operate reliably without off-line water washing for a Gas-to-Gas Heater
year or more. As discussed in Chapter 34, some regen-
erative air heaters have been modified to simultaneously
serve as selective catalytic NOx reduction systems. Untreated Treated
Cool Gas Cool Gas
SO2 reduction 197F 115F
(92C) (46C)
When sulfur emission reduction is required, flue gas
desulfurization (FGD) systems are frequently used. Demister
These systems remove SO2 from the flue gas by reac-
tion with injected compounds such as limestone. In
most cases, the scrubbed flue gas exits the FGD sys-
tem at a saturation temperature of 120 to 130F (49 to
FGD
54C) before entering the stack. In cases where acid Spray Tower
dew point corrosion of flues and stack liners is a con-
cern or increased gas buoyancy is needed to improve
stack plume dispersal, gas exiting the FGD system is
reheated to 180F (82C) or higher.
Regenerative heat exchangers similar to those for
combustion air heating are used in FGD systems. The
heat exchangers, referred to as gas-to-gas heaters
(GGH), extract heat from untreated warm flue gas to Fig. 25 Gas-to-gas heater in an FGD system.
heat treated (scrubbed) flue gas leaving an FGD tower
before it enters the stack. A typical arrangement with
controlled to low levels. The following features incor-
gas temperatures is shown in Fig. 25.
porated into GGH design can reduce the leakage to
Several necessary GGH design features distinguish
less than 1% of the untreated inlet gas flow:
them from air heaters and permit them to operate in
a very corrosive environment without compromising 1. Designing the rotor with radial heating surface di-
FGD system SO2 removal performance. Measures taken vision plates so that, during operation, there are
to protect a GGH from the corrosive flue gas include: always two under the radial and axial seal plates.
Leakage flow, in this case, is forced to pass two
1. Fabricating rotors of low alloy corrosion-resistant
seals rather than one seal producing a labyrinth
steel and adding a corrosion margin to all rotor
effect which lowers leakage flow.
plate thicknesses.
2. Employing an automatic sealing system to hot end
2. Using porcelain enamel coated heating surface el-
radial seal plates that follows stator distortion to
ement plates.
minimize seal leakage at all loads.
3. Using stainless and/or non-metallic circumferen-
3. Purging stator compartments of untreated gas
tial, radial and axial leaf seal materials.
with treated gas just before they pass under ra-
4. Applying a layer of vinyl ester flake glass on in-
dial seals and into the treated gas stream. Purg-
ternal surfaces of the untreated gas outlet duct,
ing minimizes carryover leakage which is a com-
treated gas inlet duct, treated gas outlet duct, and
ponent of total leakage. A purge system consists
rotor housing.
of a dedicated purge fan and associated ducting
5. Employing hot and cold end air sootblowers for on-
and controls.
line cleaning, fitted with water wash nozzles for
4. Reducing rotor speed to the lowest possible level
off-line washing.
without significantly compromising thermal per-
Leakage of the untreated gas into the treated gas formance. Operation at low speed reduces
reduces FGD SO2 reduction performance and must be carryover leakage.

20-16 Steam 41 / Economizers and Air Heaters


The Babcock & Wilcox Company

Bibliography
Dubbel, H., Taschenbuch für den Maschinenbau, 11th Mayer, E.H., and McCarver, G.M., Economizer Technol-
Ed., Springer Verlag GmbH & Company, Berlin, Ger- ogy for Utility and Industrial Boilers, Course for the
many, 1958. Center for Professional Advancement, East Brunswick,
Ledinegg, M., Dampferzeugung, Dampfkessel, Feuerungen New Jersey, 1991.
Springer Verlag-Wien, 1952. McAdams, W.H., Heat Transmission, Third Ed., McGraw-
Hill Company, New York, New York, 1954.

Ljungström is a trademark of Alstom Power Inc.


Rothemühle is a trademark of Balcke-Dürr GmbH.

Steam 41 / Economizers and Air Heaters 20-17


The Babcock & Wilcox Company

Typical utility boiler economizer.

20-18 Steam 41 / Economizers and Air Heaters

You might also like