External Interface Connections

IB2 (Controller Interface Board) Connections


The IB2 (Controller Interface Board) provides connection points for digital inputs, programmable relay outputs,
and temperature probes. Refer to Figure 14 for the location of the IB2 Board and its connectors. Refer to
Table 1 and Table 2 for pin-out information.
If required to access these connection points, loosen the captive fastener on the front of the IB2 Board, and
slide the assembly partially out of the shelf.
NOTE! Two sets of Alarm Cables are available (see SAG582136800 for part numbers). One set for the
Digital Inputs and another set for the Relay Outputs. Refer to Table 1 and Table 2 for color scheme. If
the Relay Outputs Alarm Cable or Digital Inputs Alarm Cable is ordered, one half is factory connected in
the shelf. The other half has a mating connector on one end and is un-terminated on the other end.
CAUTION! All conductors in this harness may be connected within the cabinet. Shorting or grounding
of unused conductors may result in service interruption or equipment damage. Therefore insulate all
conductor ends not being used in your application.
NOTE! Each Temperature Probe assembly consists of two pieces. If probes are ordered with the Power
System, one piece is factory connected in the shelf. The other piece contains the Temperature Probe
and a mating connector.
Digital Inputs and Programmable Relay Outputs
Digital input and relay output leads are connected to screw-type terminal blocks located on the IB2.
Recommended torque for these connections is 2.2 in-lbs. Refer to Figure 14 for the location of the IB2 Board
and its connectors. Refer to Table 1 and Table 2 for pin-out information.
Digital Inputs
Connect up to eight (8) digital inputs to the IB2. Note that you must supply both paths for the digital input
(either a positive or negative signal and the opposite polarity return path). Observe proper polarity. Refer to
Figure 14 for the location of the IB2 Board and its connectors. Refer to Table 1 for pin-out information. Note
that some of these inputs are factory connected, as listed in Table 1.
The digital inputs can be programmed to provide an alarm when the signal is applied (HIGH) or removed
(LOW). Refer to the Controller User Manual for programming information.
Digital Input Ratings: Refer to the following.
a) Maximum Voltage Rating: 60V DC.
b) Active High: > 19V DC.
c) Active Low: < 1V DC.
The digital inputs may be preprogrammed for specific functions. Refer to the configuration drawing (C-
drawing) supplied with your system for your system’s specific configuration.