You are on page 1of 1

GENERAL REQUIREMENTS 20–11

3.3.54.3 Pressure Control Valve. A pilot-operated pressure- 5.3 Pump Operation. In the event of fire pump operation,
reducing valve designed for the purpose of reducing the qualified personnel shall respond to the fire pump location
downstream water pressure to a specific value under both to determine that the fire pump is operating in a satisfac-
flowing (residual) and nonflowing (static) conditions. [14, tory manner.
2007]
5.4 Fire Pump Unit Performance.
3.3.54.4 Pressure-Reducing Valve. A valve designed for the
purpose of reducing the downstream water pressure under 5.4.1* The fire pump unit, consisting of a pump, driver, and

m
both flowing (residual) and nonflowing (static) conditions. controller,, shall perform in compliance with this standard as
[14, 2007] an entire unit when installed or when components have been
replaced.
3.3.54.5 Relief Valve. A device that allows the diversion of
liquid to limit excess pressure in a system. 5.4.2 The complete fire pump unit shall be field acceptance

o
tested for proper performance in accordance with the provi-
3.3.54.5.1 Circulation Relief Valve. A valve used to cool a sions of this standard. (See Section 14.2.)
pump by discharging a small quantity of water, this valve is
separate from and independent of the main relief valve. 5.5 Certified Shop Test.

c
3.3.54.6 Unloader Valve. A valve that is designed to relieve 5.5.1 Certified shop test curves showing head capacity and
brake horsepower of the pump shall be furnished by the

.
excess flow below pump capacity at set pump pressure.
manufacturer to the purchaser.
3.3.55 Variable Speed Pressure Limiting Control. A speed con-
trol system used to limit the total discharge pressure by reduc- 5.5.2 The purchaser shall furnish the data required in 5.5.1
ing the pump driver speed from rated speed. to the authority having jurisdiction.
3.3.56 Velocity Head (hv). See 3.3.23.6. 5.6 Liquid Supplies.

w
3.3.57 Wet Pit. A timber, concrete, or masonry enclosure hav- 5.6.1* Reliability. The adequacy and dependability of the wa-
ing a screened inlet kept partially filled with water by an open ter source are of primary importance and shall be fully deter-
body of water such as a pond, lake, or stream. mined, with due allowance for its reliability in the future.

x
5.6.2* Sources.

f
5.6.2.1 Any source of water that is adequate in quality, quan-
Chapter 4 Reserved tity, and pressure shall be permitted to provide the supply for a
fire pump.

z
5.6.2.2 Where the water supply from a public service main is
Chapter 5 General Requirements not adequate in quality, quantity, or pressure, an alternative
water source shall be provided.
5.1 Pumps. 5.6.2.3 The adequacy of the water supply shall be determined

b
5.1.1 This standard shall apply to centrifugal single-stage and and evaluated prior to the specification and installation of the
multistage pumps of the horizontal or vertical shaft design fire pump.

.
and positive displacement pumps of the horizontal or vertical 5.6.2.4 For liquids other than water, the liquid source for the
shaft design. pump shall be adequate to supply the maximum required flow
5.1.2 Other Pumps. rate for any simultaneous demands for the required duration
and the required number of discharges.
5.1.2.1 Pumps other than those specified in this standard and
5.6.3 Level. The minimum water level of a well or wet pit shall

w
having different design features shall be permitted to be in-
stalled where such pumps are listed by a testing laboratory. be determined by pumping at not less than 150 percent of the
fire pump rated capacity.
5.1.2.2 These pumps shall be limited to capacities of less than
500 gpm (1892 L/min). 5.6.4* Stored Supply.
5.2* Approval
oval Required. 5.6.4.1 A stored supply plus reliable automatic refill shall be

w
sufficient to meet the demand placed upon it for the design
5.2.1 Stationary pumps shall be selected based on the condi- duration.
tions under which they are to be installed and used.
5.6.4.2 A reliable method of replenishing the supply shall be
5.2.2 The pump manufacturer or its authorized representa- provided.
tive shall be given complete information concerning the liq-

w
uid and power supply characteristics. 5.6.5 Head.
5.2.3 A complete plan and detailed data describing pump, 5.6.5.1 The head available from a water supply shall be fig-
driver, controller, power supply, fittings, suction and discharge ured on the basis of a flow of 150 percent of rated capacity of
connections, and liquid supply conditions shall be prepared the fire pump.
for approval. 5.6.5.2 This head shall be as indicated by a flow test.
5.2.4 Each pump, driver, controlling equipment, power sup- 5.7 Pumps, Drivers, and Controllers.
ply and arrangement, and liquid supply shall be approved by
the authority having jurisdiction for the specific field condi- 5.7.1* Fire pumps shall be dedicated to and listed for fire pro-
tions encountered. tection service.

2007 Edition
--```,,`,,``,``,,`,,,```,`,``,,-`-`,,`,,`,`,,`---

You might also like