You are on page 1of 1

GENERAL REQUIREMENTS 20–15

5.14.9.2 The following devices shall be permitted in the suc- 5.16* Valve Supervision.
tion piping where the following requirements are met:
5.16.1 Supervised Open. Where provided, the suction valve,
(1) Check valves and backflow prevention devices and assem- discharge valve, bypass valves, and isolation valves on the back-
blies shall be permitted where required by other NFPA flow prevention device or assembly shall be supervised open
standards or the authority having jurisdiction. by one of the following methods:
(2) Where the authority having jurisdiction requires positive (1) Central station, proprietary,, or remote station signaling
pressure to be maintained on the suction piping, a

m
service
pressure-sensing line for a low suction throttling valve, (2) Local signaling service that will cause the sounding of an
specifically listed for fire pump service, shall be permitted audible signal at a constantly attended point
to be connected to the suction piping. (3) Locking valves open
(3) Devices shall be permitted to be installed in the suction

o
(4) Sealing of valves and approved weekly recorded inspec-
supply piping or stored water supply and arranged to ac- tion where valves are located within fenced enclosures un-
tivate a signal if the pump suction pressure or water level der the control of the owner
falls below a predetermined minimum.
(4) Suction strainers shall be permitted to be installed in the 5.16.2 Supervised Closed. The test outlet control valves shall

c
suction piping where required by other sections of this be supervised closed.
standard.

.
5.17* Protection of Piping Against Damage Due to Movement.
(5) Other devices specifically permitted or required by this
A clearance of not less than 1 in. (25 mm) shall be provided
standard shall be permitted.
around pipes that pass through walls or floors.
5.14.10* Vortex Plate. For pump(s) taking suction from a 5.18 Relief Valves for Centrifugal Pumps.
stored water supply, a vortex plate shall be installed at the
5.18.1* General.

w
entrance to the suction pipe. (See Figure A.6.3.1.)
5.15 Discharge Pipe and Fittings. 5.18.1.1 Where a diesel engine fire pump is installed and
where a total of 121 percent of the net rated shutoff (churn)
5.15.1 The discharge components shall consist of pipe, pressure plus the maximum static suction pressure, adjusted

x
valves, and fittings extending from the pump discharge flange for elevation, exceeds the pressure for which the system com-
to the system side of the discharge valve. ponents are rated, a pressure relief valve shall be installed.

f
5.15.2 The pressure rating of the discharge components shall 5.18.1.2* Pressure relief valves shall be used only where spe-
be adequate for the maximum total discharge head with the cifically permitted by this standard.
pump operating at shutoff and rated speed, but not less than

z
the rating of the fire protection system. 5.18.1.3 Where an electric variable speed pressure limiting
control driver is installed, and the maximum total discharge
5.15.3* Steel pipe with flanges, screwed joints, or mechanical head adjusted for elevation with the pump operating at shut-
grooved joints shall be used above ground. off and rated speed exceeds the pressure rating of the system
components, a pressure relief valve shall be installed.

b
5.15.4 All pump discharge ge pipe shall be hydrostatically tested
in accordance with NFPA 13, Standard for the Installation of 5.18.2 Size. The relief valve size shall be determined by one of

.
Sprinkler Systems, and NFPA 24, Standard for the Installation of the methods specified in 5.18.2.1 or 5.18.2.2.
Private Firee Service Mains and Their Appurtenances. 5.18.2.1* The relief valve shall be permitted to be sized hy-
5.15.5* The size of pump discharge pipe and fittings shall not draulically to discharge sufficient water to prevent the pump
be less than that given in Section 5.25. discharge pressure, adjusted for elevation, from exceeding the
pressure rating of the system components.

w
5.15.6* A listed check valve or backflow preventer shall be
installed in the pump discharge assembly. 5.18.2.2 If the relief valve is not sized hydraulically, the relief
valve size shall not be less than that given in Section 5.25. (See
5.15.7 A listed indicating gate or butterfly valve shall be in- also 5.18.7 and A.5.18.7 for conditions that affect size.)
stalled on the fire protection system side of the pump dis-
charge
ge check valve. 5.18.3 Location. The relief valve shall be located between the

w
pump and the pump discharge check valve and shall be so
5.15.8 Where pumps are installed in series, a butterfly valve attached that it can be readily removed for repairs without
shall not be installed between pumps. disturbing the piping.
5.15.9 Low Suction Throttling Valves. 5.18.4 Type.
5.18.4.1 Pressure relief valves shall be either a listed spring-

w
5.15.9.1 Low suction throttling valves that are listed for fire
pump service and that are suction pressure sensitive shall be loaded or pilot-operated diaphragm type.
permitted where the authority having jurisdiction requires 5.18.4.2 Pilot-operated pressure relief valves, where attached
positive pressure to be maintained on the suction piping. to vertical shaft turbine pumps, shall be arranged to prevent
relieving of water at water pressures less than the pressure
5.15.9.2 Where required, the low suction throttling valves
relief setting of the valve.
shall be installed between the pump and the discharge check
valve. 5.18.5* Discharge.
5.15.10 No pressure-regulating devices shall be installed in 5.18.5.1 The relief valve shall discharge into an open pipe or
the discharge pipe except as permitted in this standard. into a cone or funnel secured to the outlet of the valve.

2007 Edition

You might also like