Professional Documents
Culture Documents
Operating Instructions: Belt-Driven Screw Compressors Series S 6-... S 29-S 6-... D... S15-... D SD 6... SD 29 SD 6-... SD 29
Operating Instructions: Belt-Driven Screw Compressors Series S 6-... S 29-S 6-... D... S15-... D SD 6... SD 29 SD 6-... SD 29
instructions
Belt-driven
screw compressors
series S 6-...S 29-
S 6-...D...S15-...D
SD 6...SD 29
SD 6-...SD 29-
1 Index
Operating instructions
for the belt-driven
screw compressors
BOGE KOMPRESSOREN
Postfach 10 07 13
D-33507 Bielefeld
Lechtermannshof 26
D-33739 Bielefeld
No. 596.0683.01
Cover charge: € 5,00
Index
Part 4: 4.1 The BOGE ARS control concept (Autotronic) ............................ 4.1
Auto-/ Ratiotronic General .......................................................................................... 4.1
Microcontroller ................................................................................ 4.1
Modular design ............................................................................... 4.1
Safety instructions for 1. Ensure that no commissioning and maintenance work on the compressor
compressor operation is undertaken until these operating instructions are understood.
02. Only use the compressor for its intended use, as described in these
operating instructions.
03. The owner must ensure
– that only appropriately trained and authorized personnel work on this
compressor.
– that the operating, maintenance and repair personnel has been
made fully familiar with all safety instructions, and that they are being
observed.
– that the compressor is only operated in a safe operating condition.
04. Avoid any operating method which may impair the safety of the com-
pressor.
05. Do not exceed the limit value for the final compression pressure specified
on the type plate.
06. Do not operate the compressor without the attendant protection and
safety devices.
Do not dismantle any built-in safety devices or put them out of operation.
Ensure that all safety claddings and doors are closed prior to commis-
sioning/starting up the compressor and is not opened during operation.
07. Place the compressor out of operation as described in these operating
instructions, when dismantling the safety claddings or safety devices for
repair or maintenance work. Reattach and close all cladding and safety
devices immediately upon completion of the repair or maintenance
work.
08 Only operate the compressor using the additional equipment (options)
recommended or authorized by the manufacturer.
09. Undertake conversions and modifications of the compressor only in
agreement with BOGE, taking all relevant safety regulations into consid-
eration.
The manufacturer is not liable for damages resulting from independent
modifications on the compressor.
10. Never start the compressor when one or serveral parts (e.g. cable, plug)
are damaged, when not in perfect working order, when damage is de-
tected or suspected.
11. Observe all safety and danger signs directly attached on the compressor!
12. The compressed air/oil receiver is subject to the pressure receiver regu-
lations "Druckgeräterichtlinie" (Recommendation for compressors) and
has to be checked in prescribed intervals.
Safety instructions for 1. Ensure that maintenance work is only carried out by appropriately trained
maintenance and repair persons.
of the compressor 2. Ensure that setting work, malfunction rectification and repair is only car-
ried out by specialists or appropriately trained persons.
3. Prior to maintenance or repair work:
– Switch off the main switch.
– Secure main switch against unintentional switch-on.
– Check to ensure that all parts currentless.
– Disconnect the compressor from the compressed air network (relieve
or block pressurized lines).
4. Exercise extreme caution during repair or maintenance work requiring
the compressor to be operational.
Ensure that no persons are located in the hazardous area.
5. Ensure that work on the electrical equipment is only undertaken by
qualified electricians.
6. Work on parts and devices under current is prohibited. Exceptions are
governed by the appropriate regulations, e.g. DIN VDE 0105.
7. Only use original spare parts, compressor oils and operating
materials released by BOGE during repair or maintenance.
8. The operator is responsible to check the compressor daily for externally
visible damage and defects, and to immediately report any changes
(including operational behaviour).
9. When the automatic restart (AWAL) is activated the compressor restarts
automatically following a voltage loss.
Prerequisite: The line pressure is lower than the switch-on pressure set.
Accident prevention The owner of a compressor plant is responsible to ensure that it is properly
regulations installed, operated and maintained.
Owners in the Federal Republic of Germany urgently have to read the follow-
ing regulations of the Main Association of the Industrial Employers' Liability
Insurance:
– Accident prevention regulation 13.4 "Compressor" (VBG 16)
– Pressure receiver regulation
– Safety requirements EN 1012 "Compressors"
The regulations are available at the following locations:
Berufsgenossenschaft
Carl-Heymanns-Verlag KG, Luxemburger Str. 449, 50939 Köln
Beuth Verlag GmbH, 10772 Berlin
For operation of the compressor plant outside the Federal Republic of Ger-
many, the accident prevention regulations of the owner country must be
observed in addition to the data contained in these operating instructions.
In the event that measures are required above and beyond the legal regula-
tions specified in the Federal Republic of Germany or the data contained in
these operating instructions, then it is of utmost importance that these be
carried out prior to commissioning the compressor plant.
The purpose of these operating instructions is to familiarize the user with the
function and all application possibilities of the compressor.
The compressor and its additional equipment must not be installed and
commissioned until the operating instructions are understood.
Symbols used In these operating instructions, important safety instructions and tips are
identified by the following symbols:
ATTENTION!
This symbol indicates information warning of dangers to life and limb of the
operator or other persons or dangers, which might destroy or damage the
compressor.
WARNING: Voltage!
This symbol indicates information warning of life threatening electrical volt-
age levels.
It indicates work which must be exclusively performed by skilled electricians.
This symbol indicates information and tips concerning the economical and
careful operation of the compressor.
Symbols on the The following symbols and warning signs are fitted on the compressor:
compressor
Warning:
Hot surfaces: Do not touch!
Warning:
The unit is operated by remote control, and might start without warning.
Note:
Instructions for the operating personnel must be read.
Prohibited:
Never open the valve before the air hose (connection to the compressed air
network) is connected.
Intended use BOGE S series screw compressor, including its additional equipment, is
exclusively intended for the compression of air.
The air taken in must not contain any explosive or chemically instable gases
or vapours.
Do not exceed the specified final compression temperature.
Inadmissible use Never direct the produced compressed air towards persons.
Danger to life!
Transport damage BOGE does not accept any liability for breakage or transport damage.
Please inspect the compressor immediately after delivery and direct dam-
age claims to the last haulier – even when the packing is not damaged!
To safeguard claims against the haulier we recommend leaving the machine,
devices and packing material in the same condition as they were in when
the damage was detected.
In the event of any other complaints, please inform us within six days after
arrival of the delivery.
Data Enter the data of your compressor from the type plate or enclosed data
on the type plate sheet in the illustration below. This will ensure that in the event of enquiries,
you will always have the most important data to hand.
Type
Year of construction
Serial number
F. a. d. CFM
Maximum service pressure PSIG
Motor speed RPM
Motor power HP
Service Please do not hesitate to contact BOGE service if you have any questions.
Please call:
++49 / 52 06 / 6 01-0
In the event of inquiries, always specify the following data of your compres-
sor to prevent any delays.:
– Type
– Year of manufacture
– Machine number
ATTENTION!
Only BOGE service technicians or persons authorized by BOGE in writing
may repair or alter the compressor during the warranty period. Otherwise all
warranty claims will expire!
Type S6 S8 S 10 S 15 S 20 S 24 S 29
Dimensions
– Height (silenced) [mm] 720 720 770 770 930 930 930
– Height (super silenced) [mm] 1650 1650 1750 1750 2120 2120 2120
– Width (silenced / super silenced) [mm] 850 850 890/940 890/940 1200 1200 1200
– Depth (silenced / super silenced) [mm] 690 690 810 810 980 980 980
Weight
– silenced [kg] 140 150 170 180 300 315 315
– silenced / super silenced [kg] 170 180 210 220 350 365 365
Compressor
max. final compression temperature [°C] 110 110 110 110 110 110 110
Volume flow according to
PN 2 CPTC 2 at:
– pmax = 8 bar [m3/min] 0,55 0,83 1,18 1,65 2,40 2,80 3,35
– pmax = 10 bar [m3/min] 0,48 0,72 1,06 1,45 2,06 2,45 2,85
– pmax = 13 bar [m3/min] 0,36 0,58 0,91 1,25 1,70 2,05 2,45
Drive motor
Rated power [kW] 4 5,5 7,5 11 15 18,5 22
Rated speed
– 50 Hz [min-1] 3000 3000 3000 3000 3000 3000 3000
– 60 Hz [min-1] 3600 3600 3600 3600 3600 3600 3600
Protection type IP 55 55 55 55 55 55 55
Design IMB 3 3 3 3 3 3 3
ISO class F F F F F F F
Electrical connection
Mains voltage 1) [V] 400 400 400 400 400 400 400
Frequency 1) [Hz] 50 50 50 50 50 50 50
Min. fuse protection 2) [A] 16 20 35 35 50 50 50
Recommended fuse protection 2) [A] 20 25 35 35 50 63 63
1
) Standard equipment. Mains voltages and frequencies are specified on a plate in the switch cabinet.
2
) Only for 400 V / 50 Hz. The fuse values change in the case of other mains voltages and frequencies.
Dimensions
– Height (silenced) [mm] 1170 1270 1320 1350 1750 1750 1750
– Height (super silenced) [mm] 2100 2200 2300 2330 2930 2930 2930
– Width (silenced / super silenced) [mm] 1550 1700 1700 1850 2000 2000 2000
– Depth (silenced / super silenced) [mm] 690 690 790 790 980 980 980
Weight
– silenced [kg] 215 265 295 330 570 585 585
– silenced / super silenced [kg] 245 295 325 360 600 615 615
Compressor
max. final compression temperature [°C] 110 110 110 110 110 110 110
Volume flow according to
PN 2 CPTC 2 at:
– pmax = 8 bar [m3/min] 0,55 0,83 1,18 1,65 2,40 2,80 3,35
– pmax = 10 bar [m3/min] 0,48 0,72 1,06 1,45 2,06 2,45 2,85
– pmax = 13 bar [m3/min] 0,36 0,58 0,91 1,25 1,70 2,05 2,45
Drive motor
Rated power [kW] 4 5,5 7,5 11 15 18,5 22
Rated speed
– 50 Hz [min-1] 3000 3000 3000 3000 3000 3000 3000
– 60 Hz [min-1] 3600 3600 3600 3600 3600 3600 3600
Protection type IP 55 55 55 55 55 55 55
Design IMB 3 3 3 3 3 3 3
ISO class F F F F F F F
Electrical connection
Mains voltage 1) [V] 400 400 400 400 400 400 400
Frequency 1) [Hz] 50 50 50 50 50 50 50
Min. fuse protection 2) [A] 16 20 35 35 50 50 50
Recommended fuse protection 2) [A] 20 25 35 35 50 63 63
1
) Standard equipment. Mains voltages and frequencies are specified on a plate in the switch cabinet.
2
) Only for 400 V / 50 Hz. The fuse values change in the case of other mains voltages and frequencies.
Dimensions
– Height (silenced) [mm] 1350 1350 1550 1550
– Height (super silenced) [mm] 2240 2240 2540 2540
– Width (silenced / super silenced) [mm] 2150/2180 2150/2180 2220/2270 2220/2270
– Depth (silenced / super silenced) [mm] 570 670 730 730
Compressor
max. final compression temperature [°C] 110 110 110 110
Volume flow according to
PN 2 CPTC 2 at:
– pmax = 8 bar [m3/min] 0,55 0,83 1,18 1,65
– pmax = 10 bar [m3/min] 0,48 0,72 1,06 1,45
– pmax = 13 bar [m3/min] 0,36 0,58 0,91 1,25
Drive motor
Rated power [kW] 2x4 2 x 5,5 2 x 7,5 2 x 11
Rated speed
– 50 Hz [min-1] 3000 3000 3000 3000
– 60 Hz [min-1] 3600 3600 3600 3600
Protection type IP 55 55 55 55
Design IMB 3 3 3 3
ISO class F F F F
Electrical connection
Mains voltage 1) [V] 2 x 400 2 x 400 2 x 400 2 x 400
Frequency 1) [Hz] 50 50 50 50
Min. fuse protection 2) [A] 2 x 16 2 x 20 2 x 35 2 x 35
Recommended fuse protection 2) [A] 2 x 20 2 x 25 2 x 35 2 x 35
1
) Standard equipment. Mains voltages and frequencies are specified on a plate in the switch cabinet.
2
) Only for 400 V / 50 Hz. The fuse values change in the case of other mains voltages and frequencies.
Type SD 6 SD 8 SD 10 SD 15 SD 20 SD 24 SD 29
Dimensions
– Height (super silenced) [mm] 1960 1960 2060 2060 2480 2480 2480
– Width (silenced / super silenced) [mm] 910 910 975 975 1230 1230 1230
– Depth (silenced / super silenced) [mm] 690 690 810 810 980 980 980
Weight
– silenced / super silenced [kg] 210 220 250 260 400 425 425
Compressor
max. final compression temperature [°C] 110 110 110 110 110 110 110
Volume flow according to
PN 2 CPTC 2 at:
– pmax = 8 bar [m3/min] 0,55 0,83 1,18 1,65 2,40 2,80 3,35
– pmax = 10 bar [m3/min] 0,48 0,72 1,06 1,45 2,06 2,45 2,85
– pmax = 13 bar [m3/min] 0,36 0,58 0,91 1,25 1,70 2,05 2,45
Drive motor
Rated power [kW] 4 5,5 7,5 11 15 18,5 22
Electr. power intake dryer [kW] 0,24 0,24 0,25 0,35 0,40 0,46 0,65
Rated speed
– 50 Hz [min-1] 3000 3000 3000 3000 3000 3000 3000
– 60 Hz [min-1] 3600 3600 3600 3600 3600 3600 3600
Protection type IP 55 55 55 55 55 55 55
Design IMB 3 3 3 3 3 3 3
ISO class F F F F F F F
Electrical connection
Mains voltage compressor / dryer 1) [V] 400/230 400/230 400/230 400/230 400/230 400/230 400/230
Frequency 1) [Hz] 50 50 50 50 50 50 50
Min. fuse protection 2) [A] 16 20 35 35 50 50 50
Recommended fuse protection 2) [A] 20 25 35 35 50 63 63
1
) Standard equipment. Mains voltages and frequencies are specified on a plate in the switch cabinet.
2
) Only for 400 V / 50 Hz. The fuse values change in the case of other mains voltages and frequencies.
Dimensions
– Height (silenced) [mm] 1490 1490 1520 1520 1750 1750 1750
– Height (super silenced) [mm] 2200 2200 2330 2330 2930 2930 2930
– Width (silenced / super silenced) [mm] 1700 1700 1850 1850 2195/2510 2195/2510 2195/2510
– Depth (silenced / super silenced) [mm] 690 690 690 690 955 955 955
Compressor
max. final compression temperature [°C] 110 110 110 110 110 110 110
Volume flow according to
PN 2 CPTC 2 at:
– pmax = 8 bar [m3/min] 0,55 0,83 1,18 1,65 2,40 2,80 3,35
– pmax = 10 bar [m3/min] 0,48 0,72 1,06 1,45 2,06 2,45 2,85
– pmax = 13 bar [m3/min] 0,36 0,58 0,91 1,25 1,70 2,05 2,45
Drive motor
Rated power [kW] 4 5,5 7,5 11 15 18,5 22
Electr. power intake dryer [kW] 0,21 0,28 0,32 0,40 0,46 0,55 0,60
Rated speed
– 50 Hz [min-1] 3000 3000 3000 3000 3000 3000 3000
– 60 Hz [min-1] 3600 3600 3600 3600 3600 3600 3600
Protection type IP 55 55 55 55 55 55 55
Design IMB 3 3 3 3 3 3 3
ISO class F F F F F F F
Electrical connection
Mains voltage compressor / dryer 1) [V] 400/230 400/230 400/230 400/230 400/230 400/230 400/230
Frequency 1) [Hz] 50 50 50 50 50 50 50
Min. fuse protection 2) [A] 16 20 35 35 50 50 50
Recommended fuse protection 2) [A] 20 25 35 35 50 63 63
1
) Standard equipment. Mains voltages and frequencies are specified on a plate in the switch cabinet.
2
) Only for 400 V / 50 Hz. The fuse values change in the case of other mains voltages and frequencies.
Type S6 S8 S 10 S 15 S 20 S 24 S 29
Safety valve
Activation pressure at:
– pmax = 8 bar [bar] 11 11 11 11 11 11 11
– pmax = 10 bar [bar] 11 11 11 11 11 11 11
– pmax = 13 bar [bar] 14 14 14 14 14 14 14
2
) Compressors for other operating pressures Pmin = Pmax – 1 bar
Safety valve
Activation pressure at:
– pmax = 8 bar [bar] 11 11 11 11 11 11 11
– pmax = 10 bar [bar] 11 11 11 11 11 11 11
– pmax = 13 bar [bar] 14 14 14 14 14 14 14
2
) Compressors for other operating pressures Pmin = Pmax – 1 bar
Safety valve
Activation pressure at:
– pmax = 8 bar [bar] 11 11 11 11
– pmax = 10 bar [bar] 11 11 11 11
– pmax = 13 bar [bar] 14 14 14 14
2
) Compressors for other operating pressures Pmin = Pmax – 1 bar
Type SD 6 SD 8 SD 10 SD 15 SD 20 SD 24 SD 29
Safety valve
Activation pressure at:
– pmax = 8 bar [bar] 11 11 11 11 11 11 11
– pmax = 10 bar [bar] 11 11 11 11 11 11 11
– pmax = 13 bar [bar] 14 14 14 14 14 14 14
2
) Compressors for other operating pressures Pmin = Pmax – 1 bar
Safety valve
Activation pressure at:
– pmax = 8 bar [bar] 11 11 11 11 11 11 11
– pmax = 10 bar [bar] 11 11 11 11 11 11 11
– pmax = 13 bar [bar] 14 14 14 14 14 14 14
2
) Compressors for other operating pressures Pmin = Pmax – 1 bar
Function principle The air end operates according to the displacement principle. In the housing,
of the air end the main and secondary screws are driven by means of an electric motor
and V-belt.
Both screws have screw-shaped profiles, intermeshing without contact.
Together with the housing wall, these screws form chambers which gradually
reduce in size, seen in air flow direction.
Rotation of the rotors causes the air taken in to be compressed to the final
pressure in the chambers.
During compression oil is continuously injected into the air end. This having
a cooling, sealing and lubricating function.
Air circuit
1
3 4 5
2
8 7 Fig. 2.1:
6
Components of
the air circuit
1 = Intake filter
The intake filter cleans the air suctioned by the air end.
2 = Intake regulator
The intake regulator opens (load operation) or closes (idling operation or
standstill) the suction line depending on the operating condition of the com-
pressor.
3 = Air end
The air end compresses the suctioned air.
4 = Compressed air/oil receiver
The compressed air separates from the oil under the force of gravity in the
compressed air/oil receiver.
5 = Oil separator
The oil separator separates the residual oil contained in the compressed air.
6 = Minimum pressure check valve
The minimum pressure check valve does not open until the system pressure
has increased to 3.5 bar. This causes a rapid build-up of the system pressure
and ensures lubrication in the starting phase. Once the compressor has been
switched off, the check valve prevents the compressed air from flowing back
out of the mains line.
7 = Compressed air after-cooler (air and water cooled)
The compressed air is cooled in the compressed air after-cooler, causing the
water contained in the air to condensate.
8 = Stop valve
The screw compressor may be isolated from the mains by means of the stop
valve.
Oil circuit The oil injected into the air end has the following function:
– It dissipates the compression heat (cooling)
– It seals the gaps between the screws and between the screws and housing
– It lubricates the bearings
5 6
2
4
Fig. 2.2:
Components of the oil circuit
Network pressure For the compressor, the pressure downstream of the check valve is termed
network pressure. The control system switches the compressor on and off
during operation depending on the network pressure.
Operating states All screw compressor controls are based on three basic operating states:
1. Load operation
– The compressor delivers its maximum amount of compressed air.
– It consumes its maximum energy.
2. Idling operation
– The compressor runs but does not deliver any compressed air.
– It consumes approx. 75% less energy than in load operation.
– When compressed air is required, it switches to load operation with
out delay.
– Idling operation reduces switching frequencies which can damage the
drive motor, and reduces wear of the system.
3. Standstill ready for operation
– The compressor is standing still but ready for operation.
– When compressed air is required, it switches automatically to load
operation.
Operating modes The two most important operating modes are achieved by combining the
three operating states:
1. Intermittent operation
In intermittent operation the energy balance is perfect.
– The compressor operates in load operation.
– Upon reaching the switch-off pressure pmax the compressor switches
to standstill. It does not consume any energy.
– Once the pressure has dropped to the switch-on pressure pmin the
compressor switches back to load operation.
2. Continuous operation
Continuous operation limits the drive motor switching cycles and reduces
wear to the system.
– The compressor operates in load operation.
– Upon reaching the switch-off pressure pmax the compressor switches
to idling operation.
– Once the pressure has dropped to the switch-on pressure pmin the
compressor switches from idling operation back to load operation.
Proportional controller The proportional controller is an additional control device intervening in the
(Option) sequences of the intake regulator.
The intake regulator only opens as far as necessary to supply the current
compressed air requirement. Thus the compressor saves compression
energy.
A compressor with proportional controller is able to supply its ’delivered
quantity variable between 0% and 100%. However, the energy consumption
does not reduce accordingly. Therefore, a control is only practical between
50% and 100% of the delivered quantity.
The proportional controller is factory set to a delivered quantity between
50% and 100% of the compressor capacity.
The proportional controller closes when the desired delivered quantity has
dropped below 50% of the compressor capacity. The compressor then oper-
ates in idling operation (continuous operation) or switches off (intermittent
operation).
General The safety devices guarantee a high degree of operational safety, in connec-
tion with the BOGE ARS monitoring system.
When one of the safety devices responds, the control system reacts as
follows:
– The compressor is immediately switched off.
– A flashing fault number in the left field of the display indicates the cause
of the fault.
ATTENTION!
Do not operate the compressor without built-in safety devices.
Do not dismantle the safety devices or put them out of operation.
Safety temperature The safety temperature limiting device switches off the compressor once
limiting device the maximum admissible final compression temperature has been reached.
The compressor does not switch on when dropping below the minimum
temperature.
– Switch off the compressor (OFF button). Fault is acknowledged.
– Rectify the fault.
– Switch on the compressor (ON button).
Safety valve The safety valve on the compressed air/oil receiver prevents the maxi-
mum admissible pressure being exceeded. When the maximum pressure is
exceeded (e.g. incorrect setting of the operating pressure value), the entire
delivery volume of the compressor is ejected.
Monitoring The following monitoring devices are standard for BOGE ARS control sys-
the drive motor tems:
The drive motor is monitored by PTC resistors.
General Please observe the generally accepted safety and accident prevention regu-
lations when transporting the compressor. BOGE accepts no liability for
damage caused by improper transport!
ATTENTION!
The compressor is delivered filled with oil.
Do not tilt during transport!
Crane transport
ATTENTION!
Do not subject the safety cladding to force during transport.
Protect the compressor using wooden spacers (see arrows).
Remove the transport timbers.
Installation, mainte- – Protect compressed air receivers against damage through mechanical
nance conditions and effects (e.g. falling objects).
application for pressure – Operate the compressed air receiver and its equipment from a safe
receivers arranged location.
below or separately – Adhere to safety areas and safety clearances.
– Ensure that the compressed air receiver stands securely. It must not shift
or tilt due to external forces. This also includes the additional weight dur-
ing a pressure test!
– Ensure that the compressed air receiver is easily accessible from all sides
(for recurring tests).
– Ensure that the factory label is clearly visible.
– Ensure that compressed air receivers are adequatly protected against
corrosion.
– Only use the compressed air receiver for compressors operating with cut-
in and cut-out mode if the pressure fluctuation range amounts to ∆ p ≤ 20%
of the maximum operating pressure.
Installation surface A level industrial floor without foundation is adequate for the installation of
the compressor. No special fastening elements are required.
Fire protection The following applies to rooms in which compressors with oil injection cool-
ing are to be installed:
– For compressors with motor ratings exceeding 40 kW, ensure that the
compressor room is equipped with special fire protection.
– Install compressors with motor ratings exceeding 100 kW in a separate
fire protected room.
Sound protection Only install compressors in workrooms if the sound pressure level of
their measuring surfaces does not exceed 85 dB(A).
Admissible The compressor room must be clean, dry, cool and free of dust.
environmental
influences Admissible ambient temperatures
Maximum ambient temperature (for air cooling): + 40°C
Minimum ambient temperature: + 5°C
ATTENTION!
Nonobservance of the admissible ambient temperature may lead to the
following problems:
– The compressor will switch off when the admissible final compres-
sion temperature is exceeded or gone below.
– Pipe lines and valves will freeze up at low temperatures.
– Damage due to reduced lubricating ability of the compressor oil.
Ventilation If the following instructions are not observed, the admissible final com-
pression temperature may be exceeded.
In this case, the compressor will switch off automatically.
Attention!
Arrange the compressor intake openings or ducts such, that dangerous
admixtures (e.g. explosive or chemically unstable materials) cannot be
drawn in.
Ventilators
Ensure that the heated exhaust air is not aken in again.
If necessary, the heated air must be extracted by ventilators.
To ensure perfect cooling even at higher temperatures in the summer, the
ventilators must be designed as follows:
– The ventilator capacity must be rated approx. 10 - 15% higher than the
sum of the cooling air quantity required for all machines operated in the
room (VDMA Code of Practice sheet 4363 "Ventilation of compressor
rooms").
– For free-standing installation, the cooling air requirement specified in the
table corresponds to the required ventilator capacity.
Cooling air Please refer to the following table for the cooling air requirement and size of
requirement the supply air openings for your compressor. Ensure that flaps and weather
protection grids have the necessary free cross section. We generally recom-
mend contacting a specialist company for performing the duct construction
work and planning.
Table 1: Cooling air requirement, required opening and duct cross sections.
* The cooling air requirement was based on a 4°C temperature difference between the ambient
temperature and the outside temperature.
Ventilation
possibilities
A B
C D
Condensate The air taken in contains water in form of vapour, which turns into conden-
disposal sation during compression.
ATTENTION!
The condensate contains oil. Never lead it into the public sewage system
without prior treatment.
Strictly observe the effluent disposal laws of your local authorities.
Oil-water separator
The BOGE-oil-water-separator separates the oil from the condensate.
The cleaned water may be fed directly into the public sewage system.
The oil is collected in a separate container. Dispose of the oil according to
environmental regulations.
If, due to special operating conditions, the oil should emulsify, use an emul-
sion cracking plant.
General BOGE screw compressor units are supplied ready for connection. Only the
work described in the following paragraphs needs to be carried out during
the installation.
ATTENTION!
Only have the installation work carried out by appropriately trained persons
or specialists.
Connecting the – Connect the compressor to the compressed air network or a compressed
compressor to the air receiver.
compressed air For this, use a BOGE high pressure hose.
network Do not install a check valve in the pressure line.
The compressor is already equipped with a check valve.
Fig. 3.1:
Remove warm air hood
ATTENTION!
To avoid damage to the cooler, support the screw connection at the cooler
outlet using a spanner.
2
Electrical connection
Compressed air connection
Fig. 3.2:
Connecting the compressor
ATTENTION!
Do not loosen or change the sealed nuts for setting the spring tension.
1
1
Checking the oil level BOGE compressors are supplied with a complete oil filling.
Prior to commissioning/start up, check the oil level as described in chapter
6.3.
Main switch
According to accident prevention regulation VBG 5, §12, the customer is
responsible to provide the following safety measures:
Compressor plants having a drive motor larger than 3 kW and current inten-
sities larger than 16 amperes must be equipped with a lockable main switch
(DIN VDE 0660, ...0105) and series fuses.
Please refer to the technical data (chapter 2.1) for the design and fuse rating.
Rated voltage
The data of your mains (operating voltage, control voltage, type of current,
frequency, ...) must coincide with the data on the type plate on the switch
cabinet.
In the event of deviations, please contact the BOGE service or your supplier.
Never omit a single safety step! Otherwise, you will risk injuries due to
restarting, electric shock or self-releasing parts.
WARNING!
When the automatic restart (AWAL) is activated, the compressor will auto-
matically restart following a power failure.
Prerequisite: the mains pressure is lower than the switch-on pressure set on
the operating pressure sensor.
Ensure that the rotational direction coincides with the rotational direction
arrow on the air end.
– Switch on the main switch.
– Switch the compressor on and immediately off again to check the rota-
tional direction.
Opening the stop valve Open ball valve 1 on the compressor delivery.
Commissioning Following an extended stoppage of more than 2 months, fill a small amount
following extended of oil in the suction controller prior to starting the compressor.
stoppages
ATTENTION!
Only fill the suction controller with the grade of oil used to operate the com-
pressor.
Never mix different oil grades and brands.
Refrigeration Before commissioning the refrigeration compressed air dryer see separate
compressed air dryer operating instructions series D-, DP- or DU-.
General BOGE screw compressors are equipped with the modern ARS control system
concept (Autotronic, Ratiotronic, Supertronic).
One of these control systems will be built into your compressor, depending
on the desired equipment and the monitoring functions.
ARS is an integrated control and monitoring concept, having two objectives:
– Energy savings and thus reduction of ongoing costs
– Prolonging the service life of the compressor due to wear which is as low
as possible
All programmed data is stored in a memory module (EEPROM). Thus the
stored information is even available following a power failure.
Microcontroller The BOGE ARS control system concept dynamically adapts to the respective
operating conditions. A micro-controller assumes the following three tasks:
1. Automatic selection of the most economical operating mode
The micro-controller calculates the optimum operating mode from the
current operating state and a programmed ideal value, also taking into
account the constant compressor system data (e.g. delivery quantity,
receiver volume, motor switching cycles) as well as the current variables
(e.g. compressed air consumption, supply and non-supply times, pressure
increase and decrease speed).
In order to save operating costs, it always strives for the most economical
intermittent operation.
2. Automatic optimization of the motor switching cycles
The micro-controller calculates the optimum number of motor switching
cycles. This protects the drive motor and prolongs the service life of the
plant.
3. Automatic reminder of the maintenance intervals
The microcontroller monitors the maintenance intervals.
Modular design All ARS control systems comprise of standard components which can be
purchased separately. They are also easy to retrofit. In this manner, the
control systems can be optimally adapted to individual customer wishes.
Rapid replaceability of the controls in the event of failures increases the
availability of the compressor. This eliminates time consuming and costly
trouble shooting by specialists.
EMERGENCY OFF switch To switch off the – Press the EMERGENCY OFF switch.
compressor The switch engages and interrupts the control
in an emergency voltage.
All displays are cut off from the power.
Important!
Always switch the compressor off
with the OFF key. Only use EMER-
GENCY OFF in an emergency!
OFF switch To switch the Compressor may continue to run for 30 seconds
compressor off idling mode
Lamp = green Ready The green lamp indicates that the machine is
ready.
3-digit 7-segment display Displays: Shown in bar with a decimal point between the
P: Pressure second and third digit
bar
°C
Operation Autotronic
green red
green
Operation Autotronic
Operation Autotronic
red
Operation,
servicing periods,
display test
and software-No.
Operation Autotronic
Motor servicing Press i a fourth time and the display shows the
interval operating time ntil the next Motor servicing and
the symbols O (here for motor), running tme and
servicing (spanner).
Receiver servicing Press i a fifth time and the display shows the
interval 1000-output cycle servicing counter with the
single exponent 103 (x 1000), the load speed sym-
bol, the circle (here for the receiver) and the ser-
vicing symbol (spanner), meaning the number of
possible output cycles until the next receiver in-
spection.
Means: 20 x 103 = 20000 Load
cycles until the next receiver
servicing.
Operation Autotronic
red green
General The control unit calculates from the current operating data the respective
best operating mode and automatically selects it.
The parameters are adjustable.
In order to prevent unintentional changes to pre-set parameters, these pa-
rameters are codeword-protected.
ATTENTION!
Never change the value of a parameter if you do not know what it means!
This may cause incorrect behaviour of the control unit!
Do not experiment with parameter settings!
Always call BOGE-Service if you are unsure or have any doubts.
Parameterization From the main display the first step in parameterization is performed by re-
peated pressing of the INFO key i until the display the software-no., and
then proceeding as follows:
1. Press ENTER ↵ → and the parameterization symbol is shown on the
left, followed by three zeros, the left of which blinks.
2. Press i to change the first digit.
3. Press ↵ → and now the middle zero blinks.
4. Press i to change the second digit.
5. Press ↵ → and now the right zero blinks.
6. Press i to change the third digit.
7. Press ↵ → the display will now branch off depending on the set number
– if the value is invalid the main display will reappear.
Set the compressor To make changes easier, the respective setting is changed in large steps.
servicing interval and 1. Enter Code 111 as described under coded parameterization → and the
zero the counter display shows, as already described, the compressor servicing interval
in blinking digits
2. Press the INFO key i to change the value.
3. Press ENTER ↵ to overwrite the non-volatile EEPROM with the blinking
value, and the main display reappears.
Set the motor To make changes easier, the respective setting is changed in large steps.
servicing interval and 1. Enter Code 222 as described under coded parameterization → and the
zero the counter display shows, as already described, the motor servicing interval in blink-
ing digits
2. Press the INFO key i to change the value.
3. Press ENTER ↵ to overwrite the non-volatile EEPROM with the blinking
value, and the main display reappears.
Set receiver inspection To make changes easier, the respective setting is changed in large steps.
load cycles and restart 1. Enter Code 333 as described under coded parameterization → and the
display shows, as already described, the receiver inspection interval in
blinking digits.
2. Press the INFO key i to change the value.
3. Press ENTER ↵ to overwrite the non-volatile EEPROM with the blinking
value, and the main display reappears.
Change target If changes are made to these target values, the value of Pmin is automatically
pressure values held or brought outside any applicable minimum hysteresis range.
(Pmax and Pmin) 1. Enter Code 360 as described under coded parameterization → and the
display shows, as already described, the upper target pressure value,
but blinking.
2. Press the INFO key i to change the value.
3. Press ENTER ↵ to overwrite the non-volatile EEPROM with the blinking
value, and the lower target pressure value apears (blinking).
4. This value can now be changed by pressing the INFO key i.
5. Press ENTER ↵ to overwrite the non-volatile EEPROM with the blinking
value, and the main display reappears.
External output enable If the output of a compressor is to be enabled by a higher level control unit,
its parameterization must be changed as follows:
1. Enter Code 210 as described under parameterization → and the display
shows Fig. left.
The ‚square’ at the top right blinks. This display means: no additional
enabling device is programmed.
2. Press the INFO key i to change to Fig. (or press again to toggle
back...).
The 7-segmente range blinks. This display means: an enabling device
(e.g., MCS) is programmed.
3. Press ENTER ↵ to overwrite the non-volatile EEPROM as per the blink-
ing symbol, and the main display reappears.
If the compressor is set for an output enabling device, the bottom of the
main display shows the appropriate Symbol .
The following applies even with external enabling: if the upper target
pressure value in the compressor is exceeded, the output will be shut
off. Only when the the pressure drops to the lower target pressure value
does external control resume.
Change after-running For compressors that are seldom in operation there is an option to change
time the after-running time:
1. Code 019 as described under parameterization → and the display shows
the Fig. on the left
The number 30 blinks. The quotation mark symbol here stands for sec-
onds. A run-out curve is indicated on the two right positions.
2. Press the INFO key i to change the value.
3. Press ENTER ↵ to overwrite the non-volatile EEPROM with the blinking
value, and the main display reappears.
Set continuous mode If pressure drops in relatively small receiver/pneumatic network volumes
must be avoided at any price, continuous operation can be set as follows:
1. Enter Code 733 as described under parameterization → and the display
shows Fig. on the left.
The shading of the left arrow blinks. this means: automatic power economy
operating mode selection.
2. Press the INFO key i to change to Fig. links (press again to toggle
back...).
The shading of the right arrow blinks. this means: continuous operation.
3. Press ENTER ↵ to overwrite the non-volatile EEPROM with the blinking
symbol, and the main display from the selected symbol appears.
Anti-freeze idling The compressor is set to automatically start an idling phase from standby
(only in mode: Ready for when the temperature drops to below +4°C, and to remain idling until reach-
operation) ing +20°C final compression temperature.
Motor switching Motor switching limitation is only activated when the air requirement makes
limitation it necessary, ie, after the "Motor start count per quarter hour" is reached be-
fore time.
Only now does it switch from intermittent to a limited continuous operation –
synchronous DB control. The control unit calcuates the through time so
that on the one hand the maximum allowed switch count per 12 minutes can
not be exceeded, and that unnecessary idling times can be saved on the
other.
Star phase time control The star time is fixed in the control unit according to the type of compressor.
Idling control with If the compressor automatically (eg, on reaching the upper target pressure
extremely short level) from load to idling, it will continue to run until the after-running time
(max. 655 sec.) has expired.
operating time (option)
To change the after-running time see page 4.14.
Pre-acknowledgement
If a service message is acknowledged, the cause of which has not (yet)
been attended to, the spanner symbol continues to appear (but no longer
blinking).
Configure binary Opener contacts (closed in good condition) should normally be connected
input pre-processing with this input. Also, in many cases a warning message from the compressor
messages control unit is sufficient. Both can be parameterized as follows:
1. Enter Code 245 as described under parameterization → and the display
shows the following figure (Fig. left).
The "dash" lines blink. They represent an opener contact. The thermom-
eter stands here for compressed air pre-processing.
2. Press INFO i to switch to Fig. left (press again to toggle back...).
The "dash" lines blink. They represent an closer contact.
3. Press ENTER ↵ to overwrite the non-volatile EEPROM as per the blink-
ing symbol and Fig. on the left is shownon the display.
The spanner blinks. It stands here for warning message assignment.
Here too, The thermometer stands here for compressed input air pre-
processing.
4. Press INFO i to switch to Fig. left (press again to toggle back...).
The circle blinks. It stands here for error message assignment (compres-
sor cut-out).
5. Press ENTER ↵ to overwrite the non-volatile EEPROM as per the blink-
ing symbol and the main display from which the symbol was selected is
shown.
Fuses CPU supply (5 V): automatic reset by power cutout after cooling.
I/O supply (20 V/5 V): automatic reset by power cutout after cooling.
next
Enter OFF
information
previous
Main display ON
information
EMERGENCY OFF switch To switch off the – Press the EMERGENCY OFF switch.
compressor The switch engages and interrupts the control
in an emergency voltage.
All displays are cut off from the power.
Important!
Always switch the compressor off
with the OFF key. Only use EMER-
GENCY OFF in an emergency!
OFF switch To switch the Compressor may continue to run for 30 seconds
compressor off idling mode
Lamp = green Ready The green lamp indicates that the machine is
ready.
3-digit 7-segment display Displays: Shown in bar with a decimal point between the
P: Pressure second and third digit
bar
°C
Operation Ratiotronic
green red
green
Operation Ratiotronic
red
Operation Ratiotronic
Operation time,
output cycles
servicing periods,
display test
and software-No.
Idling hours Press a third time and the display shows the
Idling time counter and the Idling symbol:
Operation Ratiotronic
Motor servicing Press ↓ (a sixth time) → and the display shows the
interval operating time until the next Motor servicing and
the symbols O (here for motor), running time and
servicing (spanner).
Output cycles until Press ↓ (a seventh time) → and the display shows
the next receiver the 1000-output cycle servicing counter with the
servicing/change of exponent 103 (x 1000), the Load-cycle symbol, the
wearing parts circle (here for receiver) and the servicing symbol
(spanner), meaning the number of possible output
cycles until the next receiver inspection or change
of wearing parts
Means: 20 x 103 = 20000
20 x 103 = 20000 Load cycles
until the next receiver servicing
or change of wearing parts
Upper target Press ↓ (an eighth time) → and the segment dis-
pressure play shows the Upper target pressure and an
(Network pressure) underscore at the top right next to it.
Operation Ratiotronic
red green
General The control unit calculates from the current operating data the respective
best operating mode and automatically selects it.
The parameters are adjustable.
In order to prevent unintentional changes to pre-set parameters, these pa-
rameters are codeword-protected.
ATTENTION!
Never change the value of a parameter if you do not know what it means!
This may cause incorrect behaviour of the control unit!
Do not experiment with parameter settings!
Always call BOGE-Service if you are unsure or have any doubts.
Set the compressor 1. Enter Code 111 as described under coded parameterization → and the
servicing interval and display shows the compressor servicing interval in blinking digits (Com-
zero the counter pressor servicing).
2. Press the ↑ or ↓-key to change the value in big steps.
3. Press ↵-key to overwrite the non-volatile EEPROM with the blinking
value, and the main display reappears.
Set the motor 1. Enter Code 222 as described under coded parameterization → and the
servicing interval and display shows the motor servicing interval in blinking digits (Motor servic-
ing).
zero the counter
2. Press the ↑ or ↓-key to change the value in big steps.
3. Press ↵-key to overwrite the non-volatile EEPROM with the blinking
value, and the main display reappears.
Set load cycles receiver 1. Enter Code 333 as described under coded parameterization → and the
servicing/ change display shows the receiver inspection interval in blinking digits (receiver
of wearing parts and inspection/change of wearing parts).
restart 2. Press the ↑ or ↓ keys to change the value in big steps.
3. Press ↵-key to overwrite the non-volatile EEPROM with the blinking
value, and the main display reappears.
Change target pressure If changes are made to these target values, the value of Pmin is automatically
values held or brought outside any applicable minimum hysteresis range.
(Pmax and Pmin) 1. Enter Code 360 as described under coded parameterization → and the
display shows the upper target pressure value, but blinking.
2. Press ↑ or ↓-key to change the value.
3. Press ↵-key to overwrite the non-volatile EEPROM with the blinking value,
and the lower target pressure value apears (blinking).
4. This value can now be changed by pressing the ↑ or ↓-key.
5. Press ↵-key to overwrite the non-volatile EEPROM with the blinking value,
and the main display reappears.
External output enable If the output of a compressor is to be enabled by a higher level control unit,
its parameterization must be changed as follows:
1. Enter Code 210 as described under parameterization → and the display
shows Fig. left.
The 'square' at the top right blinks. This display means: no additional
enabling device is programmed.
2. Press ↑ or ↓-key to change to Fig. (or press again to toggle back...).
The 7-segmente range blinks. This display means: an enabling device
(eg, MCS) is programmed.
3. Press ↵-key to overwrite the non-volatile EEPROM as per the blinking
symbol, and the main display reappears.
If the compressor is set for an output enabling device, the bottom of the
main display shows the appropriate Symbol .
The following applies even with external enabling: if the upper target pres-
sure value in the compressor is exceeded, the output will be shut off.
Only when the the pressure drops to the lower target pressure value does
external control resume.
Remote On/Off control If the compressor has to be switched On/Off from a control room – without
key switch – the parameterization has to be changed as follows:
1. Enter Code 451 as described under parameterization → iand the display
shows Fig. left.
The 'square' at the top right blinks. This display means: no remote On/Off
control enabled.
2. Press the ↑ or ↓-key to change to Fig. (or press again to toggle back...).
The 7-segmente range blinks. This display means: an enabling device for
remote On/Off control (continuous mode) is programmed.
3. Press ↵-key to overwrite the non-volatile EEPROM as per the blinking
symbol, and the main display reappears.
If the control unit registers Remote On/Off, it is not possible to switch over
via keyboard.
If the compressor is set for Remote On/Off control, the bottom of the
main display shows at the bottom of the display the appropriate Symbol
.
Now the compressor can only be switched on/off via remote control. This
does not concern the Emergency Off function. It remains unchanged.
Change min. after- After an output phase the compressor switches to an idling phase before
running time decreasing the system pressure and finally switching into stand-by.
For compressors that are seldom in operation there is an option to change
the min. after-running time:
1. Code 019 as described under parameterization → and the display shows
the Fig. on the left: The number (here 1) blinks. The quotation mark
symbol here stands for seconds. A run-out curve is indicated on the two
right positions.
2. Press the ↑ or ↓-key to change the value. Above 119 minutes appear
and the apostrophe Symbol instead of the quotation mark symbol.
3. Press ↵-key to overwrite the non-volatile EEPROM with the blinking
value, and the main display reappears.
Set continuous mode If pressure drops in relatively small receiver/pneumatic network volumes
must be avoided at any price, continuous operation can be set as follows:
1. Enter Code 733 as described under parameterization → and the display
shows Fig. on the left.
The shading of the left arrow blinks.This means: automatic power economy
operating mode selection.
2. Press the ↑ or ↓-key to change to Fig. on the left (press again to toggle
back...).
The shading of the right arrow blinks. This means: continuous operation.
3. Press ↵-key to overwrite the non-volatile EEPROM with the blinking
symbol, and the main display from the selected symbol appears.
Anti freeze operation The compressor is set to automatically start an idling phase – in star mode
(only in mode: Ready for i.e. without switching on a probably existing ventilator motor – from standby
operation) when the temperature drops to below +4°C. During this phase in the main
display a thermometer blinks left of the temperature display. The idling phase
is finished as soon as the min. after-running time or +20°C final compression
temperature are reached.
This anti-freeze function can be switched off as follows:
1. Enter Code 056 as described under parameterization → and the display
shows Fig. on the left: the 'curve' left of the thermometer blinks.
This display means: automatic idling phase in frost.
2. Press ↑ or ↓-key to change to Fig. left (press again to toggle back...)
The 3x dotted line left of the thermometer blinks.
This display means: no automatic running phase in frost, shown by means
of the right dash as to the thermometer.
3. Press ↵-key to overwrite the non-volatile EEPROM with the blinking sym-
bol, and the main display from the selected symbol appears.
Idling control If the compressor changes automatically (e.g., on reaching the upper target
with extremely short pressure level) from load to idling, it will continue to run in cold condition
until +20°C final compression temperature is reached and the min. after-
operating time
running time has expired.
General The tables on the following pages give information on the possible causes of
operating faults and measures for their rectification.
ATTENTION!
Ensure that any work required to rectify faults is only carried out by trained
personnel or specialists.
Ensure that components which have a safety function are only set, repaired
or exchanged by BOGE Service!
Oil in suction filter Minimum pressure non- Check the minimum pressure check valve and
return valve is leaking replace, if necessary
Suction controller is leaking Check the suction controller and replace,
if necessary
Excessive oil Drain line is blocked Dismantle and clean drain line
consumption
Defective oil separator Check oil separator and replace, if necessary
element
Excessive oil filling Drain off oil
Safety valve blows Operating pressure switch Set operating pressure to the maximum permissible
has been misadjusted pressure of the screw compressor
Defective safety valve Replace safety valve
System pressure Venting valve does not open Check venting valve and replace, if necessary
does not decrease
when switching off Check valve is leaking Check the check valve and replace, if necessary
Compressed air Malfunction of the con- Service or repair compressed air treatment unit
0 treatment
(option)
nected compressed air
treatment unit
Note:
This message does not lead to a switch-off of the
compressor in the standard configuration
System pressure Air relief valve does not Check air relief valve and replace, if necessary
9 build-up
(option)
close
Suction controller does not Check suction controller and replace, if necessary
open
Leakage in system Check system, overcome leaks
ATTENTION!
Ensure that maintenance work is ony carried out by specialists or appro-
priately trained person.
– In case of removing any cladding or safety devices prior to starting any
maintenance work, always stop the compressor as described in these
operating instructions. Refit the cladding or safety devices immediately
upon completion of the maintenance work.
– Only use original spare parts, compressor oils and operating materials
released by BOGE for the maintenance work.
– When the automatic restart (AWAL) is activated, the compressor will
start automatically following a voltage loss.
Prerequisite: The line pressure is lower than the switch-on pressure set
on the operating pressure sensor.
Maintenance through Have BOGE-Service check your compressor every 3000 operating hours or
BOGE service annually.
Maintenance agreement
Enter into a maintenance agreement with BOGE.
BOGE service will carry out the proper maintenance on your compres-
sor at regular intervals.This guarantees maximum safety and realiability
of your compressed air supply.
Change
oil filter
Change oil separator
Check V-belts
Oil change
Fig. 6.1: Review of regular maintenance work
Check automatic
condensate draining (see
operating instructions
refrigeration compressed
air dryer)
Maintenance intervals The maintenance intervals specified in the table are based on average oper-
ating and ambient conditions.
Extreme conditions may require shorter maintenance intervals.
Note down any maintenance work in the table on the last page.
This will facilitate trouble shooting for Boge service.
1. Oil change
Change the oil and the oil filter after the first 500 operating hours!
Retighten the electrical connections.
Retighten the electrical connection in the switch cabinet after the first 50
operating hours.
General
CAUTION: Risk of injury!
information
Oil presents a potential danger to health and environment due to their
concerning additives.
the lubricants – Avoid contact with skin and eyes.
used Wear protective gloves made of resistant synthetic material.
Wash yourself thoroughly after contact with oils.
– Do not inhale the fumes or mist.
– Protect your environment.
Ensure that no oil is spilt.
– Fire, naked flames and smoking is strictly prohibited when handling
oil.
– Only use BOGE compressor oil Longlife S 46. The specified maintenance
intervals are based exclusively on this special oil!
Longlife S 46 can only be purchased from BOGE retailers.
– Never mix different oil types and brands. The additives may be incompatible.
It may lead to foam formation, premature ageing or loss of lubricating ability.
Disposal of ATTENTION!
used operating The handling and disposal of mineral oils is subject to legal regulations.
material It is an offense not to ensure correct and safe disposal of old oil!
Please instruct one of the known service companies to dispose of used
operating materials or deliver them to an authorized disposal point.
Draining off the Draining: If no automatic condensate darining is fitted, then drain off the
condensate from the condensate at least once a week.
compressed air
The compressor is lubricated with oil. The condensate contains oil and may
receiver not be drained off into the public sewage system!
Pay attention to the pertaining rules and regulations of your local authorities!
Fig. 6.3:
Draining off the condensate manually
Draining off the The fully automatic, electronically controlled condensate separator is equipped
condensate from the with a wear free sensor which monitors the condensate level in the integrated
compressed air receiver collecting basin. As soon as the collecting basin is full, a solenoid valve opens
and the condensate is drained off.
with automatic
condensate Unlike the Konsatronik the fuilly automatic condensate separator operates
without causing any pressure losses. In the event of a malfunction a red
separator LED lights up and a potential-free contact is switched.
Regularly check the function using the additional test switch on the device.
Condensate
Condensate
outlet (to oil-
shut-off valve
water separator)
on receiver
Lubricating the As a rule, the bearings of the drive motors are provided with a maintenance
drive motor free permanent lubrication.
bearings The drive motor of some series are equipped with a post-lubricating unit.
These motors can be easily recognised by the two grease nipples on the
upper side of the housing. In addition, plates on the compressor indicate the
type of motor lubrication.
Drive motors with Under normal operating conditions (coolant temperature max. 40°C,
permanent lubrication continous operation) the bearings are maintenance free for the service
life.
ATTENTION!
Have BOGE service dismantle and regrease the bearings once the specified
service life has expired!
The BOGE GM drive system automatically adjusts the V-belt to the correct
V-belt tension in any operating mode.
Thus maintenance of the V-belt drive is limited to the above mentioned work.
S 8 – SD 8 10 46 98
S 8 – SD 8 13 46 98
S 10 – SD 10 8 66 105
S 10 – SD 10 10 66 105
S 10 – SD 10 13 66 105
S 15 – SD 15 8 77 105
blue 1
S 15 – SD 15 10 77 105
S 15 – SD 15 13 77 105
S 24 – SD 24 10 89 108
S 24 – SD 24 13 89 108
S 29 – SD 29 8 98 99
S 29 – SD 29 10 98 99
S 29 – SD 29 13 98 99
blue 1
The settings shown in the table are fixed by the manufacturer and may not
be changed. Slight deviations are allowed and compensated by the GM
drive system.
The current settings are also shown on a sticker on the GM drive system.
With special versions the settings on the sticker may deviate from the stand-
ard values.
ATTENTION!
Always use the same oil type when topping up.
Never mix different oil types and brands.
ATTENTION!
Do not use tools to screw in the new oil filter!
You might damage the oil filter or its sealing ring.
A hand tight seating of the oil filter is sufficient.
– Reattach safety warm air hood.
– Close safety sound insulation hood.
– Open ball valve at the compressed air outlet.
– Switch on the compressor and heat up to operating temperature.
– Subsequently, check the oil filter for leaks once again and tighten by
hand, if necessary (Procedure as described above).
Changing the oil Change: – When warning message "8" appears on the control
separator system display (Ratiotronic only).
– After 3000 operating hours,
however, no later than after one year.
If the prescribed maintenance intervals are not observed, the oil sepa-
rators might become blocked. In this case, the differential pressure will
increase until the safety valve blows.
ATTENTION!
Do not use tools to screw in the new oil separators!
You might damage the oil separators or their sealing rings.
A hand tight seating of the oil filter is sufficient.
– Close safety sound insulation hood.
– Open ball valve at the compressed air outlet.
– Switch on the compressor and heat up to operating temperature.
– Subsequently, check the oil filter for leaks once again and tighten by hand,
if necessary (Procedure as described above).
Fig. 6.9:
Changing the oil separator
The service life of the oil, the oil filter and oil separators is reduced under the
following conditions:
– When the compressor is operated at extreme ambient temperatures.
– When the intake air is extremely soiled.
ATTENTION!
Always fill with the same oil type as previously used. Never mix different oil
types and brands.
The oil circuit must be flushed prior to changing the oil type (see page 6.15).
– Close safety sound insulation hood.
– Open ball valve at the compressed air outlet.
– Conduct trial run.
Flushing the oil circuit Flushing the oil circuit with clean oil becomes necessary:
– when the oil is excessively soiled.
– prior to changing the oil type.
ATTENTION!
To flush out the oil circuit, only use oil of the same type to that which is to be
used later.
– Drain off old oil completely (see page 6.14).
– Leave old oil filter and oil separator in the compressor.
– Fill oil/compressed air receiver with clean oil up to approx. one third of the
total capacity.
– Close oil filling socket.
– Let compressor run for approx. 10 minutes.
– Drain off flushing oil and dispose of it properly.
– Change oil filter and oil separator cartridges (see page 6.11 and 6.12).
– Fill up with oil to the specified level (see page 6.10).
Fig. 6.13:
Flushing the oil circuit
ATTENTION!
Do not use any sharp objects for cleaning!
These could damage the cooling unit!
– Blow down the dirt with compressed air in the opposite direction to the
normal cooling air flow. Vacuum out the dirt using an industrial vacuum
cleaner (see Fig. 6.14).
– Reattach safety warm air hood.
Air Air
IN IN
Compressed
Compressed air OUT
air OUT
Page 7.2
Date Operating Line System Tempe- Intake Air intake Oil- Oil- Oil Cooling Motor Com- Remarks
hours pressure pressure rature filter filter filter level separator unit mainte- pressed
* ** cleaning nance air dryer
Appendix
7.2
List of maintenance and service work
* R = Cleaning ** K = Check
W = Change W = Change