You are on page 1of 56

Original User Manual

Screw compressor
L132 - L250
Speed-controlled screw compressor
L160 - L250 RS


GB Id. no. 100012711 / 07 - November 2013
General Information
These compressors are for compressing atmospheric air and are not suitable for compressing any other gas. They are
designed and manufactured to give optimum performance with long life and reliability.

This manual gives the user all the information required to install and operate the compressors and carry out the regular
schedules for servicing and maintenance, which will ensure the maximum satisfactory service life.

Servicing facilities and the supply of genuine replacement parts are provided through a worldwide network of CompAir
Companies and Distributors. If replacement parts are needed, the user should, in the first instance, contact the local
CompAir Company or Distributor.

The information given in this manual was correct at the time of printing, however, as part of continuous development,
modifications to parts and procedures may be made without notice which could affect the servicing requirements of the
compressors. Before any servicing or maintenance work is undertaken the user is advised to contact the local CompAir
Company or Distributor who is supplied with revised and up-dated information.

In any communication concerning the compressor it is essential to quote the MODEL, SERIAL NUMBER and where
possible the YEAR of MANUFACTURE.

All pressure data given in this manual refer to overpressures (pressure gauge pressures) unless specified otherwise.

Maintenance
To ensure the continued trouble-free operation of the compressor unit it is important that periodic maintenance and
servicing is carried out in accordance with the information given in the ʻMaintenanceʼ section of this manual. To assist in
this matter your local CompAir Company or Distributor can provide a number of optional maintenance agreements to suit
your requirements. These agreements provide the user with the expertise of our factory trained technicians and the
guarantee that only Genuine CompAir parts will be used.

Warranty
The conditions of the Gardner Denver Warranty are set out in the Companyʼs standard Conditions of Sale available from
the CompAir Company or Distributor supplying the machine.

USE ONLY COMPAIR GENUINE PARTS. YOUR WARRANTY


COULD BE AFFECTED IF A SERVICE OR REPAIR IS
CARRIED OUT USING NON-GENUINE PARTS.

Deutsche Basis-BA: 100012710 / 07 1


Data sheet for users

*)

*)

*)

Fig. 1
*) The values on the type plate are maximum values.

Your CompAir distributor

Name:

Address: ______________________________________________________________________________________

______________________________________________________________________________________

______________________________________________________________________________________

Telephone: Fax:

Contact: Spare Parts:

Service:

2
1. Foreword

1 For ew or d

1.1 Notes on the compressor 1.3 Maintenance


CompAir screw compressors are the result of many Carefully performed maintenance is imperative, this
years of research and development. These ensures that your screw compressor can meet all the
prerequisites combined with high quality standards requirements placed upon it. It is therefore imperative to
guarantee the manufacture of screw compressors adhere to the specified maintenance intervals and to
providing a long service life, high reliability and cost- carry out the maintenance work with particular care,
effective operation. It stands to reason that all especially when the unit is utilized under harsh
requirements concerning environmental protection are operating conditions.
met.

Servicing
1.2 Intended use Please contact your authorized CompAir dealer in the
case of malfunctions or when spare parts are required.
The machine/unit has been constructed in accordance
In the case of damage, our fully trained personnel will
with state-of-the-art technology and the recognized
ensure that a quick and proper repair is carried out
safety regulations. Nevertheless, its use may constitute
using genuine CompAir spare parts. Genuine CompAir
a risk to life and limb of the user or third persons or
spare parts are manufactured utilizing state-of-the-art
cause damage to the machine or to other material
technology, thus guaranteeing the further reliable
property, if
operation of the unit.
• it is not used as intended,
• it is operated by unqualified personnel,
• it is improperly modified or changed, In case of queries
• the safety regulations are not observed.
Please enter the data on the nameplate of your
Therefore, any person entrusted with the operation, compressor into the nameplate shown in fig.1 on p. 2.
maintenance or repair of the machine must read and In the case of queries or spare parts orders, please
follow the safety regulations. If required, this has to be refer to the compressor type indicated on the
acknowledged by signature. nameplate, the identification no. and the year of
construction. With this information at hand it can be
In addition,
guaranteed that you will receive the right information or
• relevant accident prevention regulations, required spare parts.
• generally recognized safety regulations and
• national regulations

have to be observed. 1.4 Notes


The machine/unit must only be used in technically General
perfect condition and in accordance with its intended
These operating instructions are intended to familiarize
use and the instructions set out in the operating
the user with the machine/unit and its intended use. The
manual, and only by safety-conscious persons who are
instructions contain important notes on how to operate
fully aware of the risks involved in operating the
the compressor safely, properly and cost-effectively.
machine/unit! Any functional defects, especially those
Observing these instructions helps to avoid risks, to
affecting safety, have to be rectified immediately (or
reduce repair costs and downtimes and to increase the
rectified by others)!
reliability and service life of the machine/unit.
The machine/unit is designed exclusively for the
The operating instructions have to be supplemented by
generation of compressed air to power air-driven
the respective national rules and regulations regarding
devices. Using the machine/unit for purposes other than
the prevention of accidents and environmental
those mentioned above is considered contrary to its
protection. They must always be available at the
intended use. The manufacturer/supplier cannot be held
location of the machine/unit. The operating instructions
responsible for damage resulting from such use. The
must be read and followed by any person carrying out
risk of such misuse lies solely with the user.
work in connection with the machine/unit, e.g.
Operating the machine within the limits of its intended operation, including setting up, trouble-shooting in the
use also involves observing the instructions set out in operation cycles, disposal of production waste, care,
the operating manual and complying with the inspection service, and disposal of waste fuels and consumables,
and maintenance directives. upkeep (maintenance, inspection, repair), transport.

3
1. Foreword

Besides the operating instructions and the binding


regulations for the prevention of accidents, which are
valid in the country and place of operation of the
machine/unit, the generally recognized technical
regulations for safe and proper working have also to be
observed.

Guarantee

Operate this compressor only if you have an exact


knowledge of the machine taking into respect these
instructions.

Gardner Denver cannot be held responsible for the safe


operation of the machine/unit if it is used in a manner
which does not correspond to the intended use, or for
other applications which are not mentioned in these
instructions.

Warranty claims will not be accepted in the case of

• Operating errors
• Incorrect maintenance
• Wrong auxiliary materials
• Use of spare parts other than CompAir genuine
spare parts
• Modifications and changes to the installation

The warranty and liability conditions of the general


terms and conditions of Gardner Denver will not be
extended by the notes above.
Any unauthorized change to the compressor unit/
station, or the installation of components not accepted
by the manufacturer (e.g. fine separator) will result in
the withdrawal of the CE mark. As a consequence, any
liability and warranty claims will not be accepted by the
manufacturer.

Safety regulations

Danger

The safety regulations in chapter 3 of the operating


instructions have to be strictly observed.

Technical changes
In the course of technical development we reserve the
right to modify the units without further notice.

4
2. Table of contents

2 Tab le of co nte nt s

1 Foreword .............................................................................................................................................................................. 3
1.1 Notes on the compressor............................................................................................................................................. 3
1.2 Intended use ................................................................................................................................................................. 3
1.3 Maintenance ................................................................................................................................................................. 3
1.4 Notes ............................................................................................................................................................................. 3
2 Table of contents ................................................................................................................................................................ 5
3 Safety regulations ............................................................................................................................................................... 7
3.1 Identification of safety guidelines................................................................................................................................. 7
3.2 General safety instructions .......................................................................................................................................... 7
3.3 Changes and modifications to the machine ................................................................................................................ 8
3.4 Installation and normal operation ................................................................................................................................ 8
3.5 Special work/maintenance ......................................................................................................................................... 10
3.6 Warning of special dangers ....................................................................................................................................... 12
3.7 Storage of compressors ............................................................................................................................................. 13
3.8 Symbols and explanations ......................................................................................................................................... 14
4 Design and functioning .................................................................................................................................................... 19
4.1 Design of the unit........................................................................................................................................................ 19
4.1.1 Design of air-cooled units ............................................................................................................................. 19
4.1.2 Design of the air-cooled unit RS version...................................................................................................... 20
4.2 Design of the water-cooled unit ................................................................................................................................. 21
4.3 Schematic diagram..................................................................................................................................................... 22
4.4 Oil circuit ..................................................................................................................................................................... 23
4.5 Air circuit ..................................................................................................................................................................... 23
4.6 System control ............................................................................................................................................................ 23
4.6.1 Start/stop/shutdown L132-250...................................................................................................................... 23
4.6.2 Start/stop/shutdown L160-250RS ................................................................................................................ 24
5 Transport and installation................................................................................................................................................ 25
5.1 Transport..................................................................................................................................................................... 25
5.1.1 Transport of the high-voltage variant + L160-250 RS ................................................................................. 25
5.2 Installation................................................................................................................................................................... 26
6 Preparations for commissioning .................................................................................................................................... 27
6.1 Cooling air volume/minimum cross............................................................................................................................ 27
6.2 Compressed air connection ....................................................................................................................................... 28
6.3 Cooling water connection for water-cooled units ...................................................................................................... 29
6.3.1 Limit values of the constituent elements in water........................................................................................ 29
6.4 Electrical connection .................................................................................................................................................. 30
6.4.1 Electrical connection (EUROPE-Version only) ............................................................................................ 30
6.5 Oil level check............................................................................................................................................................. 32
6.6 Sound pressure level.................................................................................................................................................. 32
6.7 Acoustic power level................................................................................................................................................... 32
7 Commissioning.................................................................................................................................................................. 33
7.1 First commissioning.................................................................................................................................................... 33
7.2 Routine commissioning .............................................................................................................................................. 33
7.3 Commissioning after malfunction .............................................................................................................................. 34
7.4 Operating modes ........................................................................................................................................................ 34
7.5 Setting of the operating pressure .............................................................................................................................. 34
7.6 Monitoring ................................................................................................................................................................... 35

5
2. Table of contents

8 Service and maintenance ................................................................................................................................................ 36


8.1 Maintenance recommendations ................................................................................................................................ 36
8.2 Maintenance electric motor ........................................................................................................................................ 36
8.2.1 Lubrication of electric motor.......................................................................................................................... 36
8.2.2 Motor lubrication system (option) ................................................................................................................. 37
8.2.3 Structure of the lubricators............................................................................................................................ 37
8.2.4 Changing the LC unit .................................................................................................................................... 37
8.2.5 Function display on lubricator....................................................................................................................... 38
8.2.6 Troubleshooting and fault rectification for lubricator ................................................................................... 39
8.3 Maintenance and inspection schedule ...................................................................................................................... 39
8.4 Oil change................................................................................................................................................................... 42
8.5 Change of oil filter cartridge ....................................................................................................................................... 43
8.6 Change of the oil fine separator................................................................................................................................. 43
8.7 Change of air intake filter ........................................................................................................................................... 44
8.8 Safety valve ................................................................................................................................................................ 45
8.9 V-belts - automatic tensioning system ...................................................................................................................... 46
8.10 Connecting terminals in the switch cabinet/control transformer setting .................................................................. 47
8.11 Fittings......................................................................................................................................................................... 47
8.12 General maintenance and cleaning........................................................................................................................... 47
8.13 Inspection intervals for pressure vessels and electrical installations ...................................................................... 48
8.14 Maintenance information and lubricant recommendations for stationary compressors ......................................... 48
9 Trouble-shooting............................................................................................................................................................... 49
10 Annex .................................................................................................................................................................................. 51
10.1 Declaration of conformity ........................................................................................................................................... 51

6
3. Safety regulations

3 Safet y r eg ula tio ns

3.1 Identification of safety guidelines 3.2 General safety instructions


Gardner Denver is not liable for any damage or injury Organizational measures
resulting from the non-observance of these safety
The operating instructions must always be at hand at
instructions or negligence of the usual care and
the place of operation of the machine/unit!
attention required during handling, operation,
maintenance or repair, even if this is not explicitly In addition to the operating instructions, all other
mentioned in these operating instructions. generally applicable legal and other mandatory
regulations relevant to accident prevention and
If any of the regulations contained in these instructions
environmental protection must be adhered to and
- especially with regard to safety - does not correspond
passed on to others! These compulsory regulations
to the local legal provisions, the stricter of both shall
may also deal with the handling of hazardous materials
prevail.
or the issuing/wearing of personal protective equipment,
These safety regulations are general and valid for or traffic regulations.
various types of machines and equipment. It is
Instructions, including supervisory responsibility and
therefore possible that some references do not apply to
duty of notification for taking into account in-plant
the unit(s) described in these instructions.
factors, for example regarding work organization,
Danger sequences of operations, personnel assigned to certain
tasks, are to be added to the operating manual.
Passages marked with this sign indicate a possible
The personnel entrusted with working on the machine
danger to persons.
must have read the operating instructions and in
Important particular the chapter on safety regulations before
starting work. Reading the instructions after work has
Passages marked with this sign indicate a possible begun is too late. This applies especially to persons
danger to machines or part of machines. working only occasionally on the machine, e.g. for
setting up or maintenance.
Note
Check on a regular basis that the personnel are
Passages marked with this sign provide technical carrying out the work in compliance with the operating
information on an optimal cost-effective use of the instructions and that they are paying attention to the
machine. safety requirements!
For safety reasons, long hair must be tied back or
otherwise secured, garments must be close-fitting and
no jewellery - such as rings - may be worn. Injury may
result from being caught up in the machinery or from
rings catching on moving parts! As necessary or as
required by regulations, personal protective equipment
should be used.
Observe all safety and warning notices attached to the
machine/unit!
See to it that safety instructions and warnings attached
to the machine are always complete and perfectly
legible.
In the case of safety-relevant changes to the machine/
unit or its operating behaviour, stop the machine/unit
immediately and report the fault to the responsible
department/person!
Spare parts have to comply with the technical
requirements specified by the manufacturer. This can
always be ensured by using original spare parts.
Hydraulic hoses have to be changed within stipulated
and periodic intervals, even if no safety-relevant faults
have been detected!
Adhere to prescribed intervals or those specified in the
operating instructions for routine checks and
inspections!

7
3. Safety regulations

For the execution of maintenance work, tools and The manufacturer is not liable for damage resulting
workshop equipment adapted to the task on hand are from the use of non-original parts or special
absolutely indispensable. accessories. This applies also to the installation and
setting of safety equipment and valves as well as to
The personnel must be made familiar with the location welding on structural or pressurized parts.
and operation instructions of fire extinguishers !
Observe all fire-warning and fire-fighting procedures!
Limit values (pressures, time settings, etc.) have to be 3.4 Installation and normal operation
permanently identified!
Installation
Selection and qualification of personnel; In addition to the general technical operation in
basic responsibilities accordance with the stipulations of the local authorities,
we would like to refer in particular to the following
Work on/with the machine/unit must be carried out by
regulations.
reliable personnel only. Statutory minimum age limits
must be observed! For the lifting of a compressor, a suitable lifting
mechanism is to be used, which meets the local safety
Employ only trained or instructed personnel and clearly
regulations. All loose or slew able parts must be safely
set out the individual responsibilities of the personnel
fixed before the machine can be lifted. It is strictly
for operation, set-up, maintenance and repair!
prohibited to stay in the danger zone of a lifted load.
Ensure that only authorized personnel work on or with
The correct method of lifting (according to the operating
the machine!
instructions of the load suspension device) has to be
Define the machine operator's responsibilities giving the ensured.
operator the authority to refuse instructions by third
All blind flanges, plugs, caps and bags with drying
persons that are contrary to safety regulations. agent have to be removed prior to the installation of the
Do not allow persons to be trained or instructed or pipes. Distributing pipes and pipe connections have to
persons taking part in a general training course to work be of the proper size and suitable for the relevant
on or with the machine/unit without being permanently operating pressure.
supervised by an experienced person!
The system has to be installed in such a way that it is
Work on the electrical equipment of the machine/unit adequately accessible and the required cooling is
must be carried out only by a skilled electrician in guaranteed. Never block the air intake. Make sure that
accordance with electrical engineering rules and the ingress of humidity via the intake air is kept to a
regulations. minimum.

Work on system elements such as hoses may only be The air intake is to be located so that no hazardous
carried out by personnel with special knowledge and constituent (solvent vapour, etc., but also dusts and
experience of hydraulics! other hazardous material) can be sucked in. This
applies also to flying sparks.
The air intake is to be positioned so that no loose
3.3 Changes and modifications to the clothing of persons can be sucked in. Make sure that
machine the pressure line from the compressor to the after
cooler or the air circuit can expand under heat and does
Do not make any changes, modifications or not come into contact with inflammable material.
attachments to the machine/unit, which could affect
The pressure line connected to the air outlet of the
safety, without the supplier's prior permission!
system must be fitted stress-free. When connecting the
Unauthorized changes to the machine are not permitted compressor on the mains side to the compressed air
for safety reasons. system available at the customerʻs end, check the
operating temperatures and operating pressures
Original parts were especially designed for this required and examine the required connecting flange or
machine. We would like to point out that we have not the connection thread for proper functioning.
released and will not release parts and special
accessories which have not been supplied by us. The In the case of connections by means of connecting
installation and/or use of such products can therefore hoses, take appropriate measures to prevent whipping
affect the active and/or passive safety. of the loose end in the event that the hose connection
tears off.
If a remote control is used, the system must carry a
clearly visible sign with the following note: Attention!
This installation is operated by remote control and can
start up without prior warning!
8
3. Safety regulations

As an additional safety measure, persons, who start If it is possible that the intake temperature of the air will
remotely controlled systems, have to take sufficient exceed, from time to time, the admissible maximum
safety precautions in order to ensure that nobody is specified in the operating instructions, a precooler with
checking the system or working on it. For this, a label condensate drain is to be installed before the dryer.
with a corresponding warning notice has to be attached
to the remote control equipment. Tests or repair work on the coolant circuit may only be
carried out in a well vented room. Never breath in
Compressed air and cooling water lines have to be coolant vapour; if necessary, wear a breathing mask.
clearly marked in line with the local regulations. Always wear protective goggles and gloves. If skin
comes into contact with coolants, rinse well with water.
If a system comprises several compressors, hand Never take off or tear up clothes but rinse them well
operated isolator valves have to be installed in order to with water until the coolant is washed off; then see a
be able to shut off each machine individually. When doctor.
operating pressure systems, do not rely on the
effectiveness of start valves alone to isolate these
systems. Condensate drain

Safety equipment, protective covers or insulation must The drain hose for condensate discharge is to be
not be removed or modified. Any pressure reservoir, connected to the drains or to a collecting reservoir, if
which is located outside the system, the permissible local regulations prohibit direct discharge to the drains.
operating pressure of which is higher than the In connection with this, it must be taken into account
atmospheric pressure and which is fitted with two or that the condensate from compressors with oil-
more pressure supply lines, has to be equipped with lubricated pressure chambers can contain oil.
additional safety equipment, which will automatically
prevent the admissible operating pressure from rising
by more than 10%. Normal operation

The installed unit-specific safety valves only assume Take the necessary precautions to ensure that the
the pressure safeguarding function of the compressor machine is used only when in a safe and reliable state!
unit provided in currently valid standards and Operate the machine only when all protective
regulations. equipment, emergency shut-off equipment, sound-
proofing elements and extraction devices are in place
For pressure components/systems mounted to the and fully functional!
connecting flange on the pressure side, a pressure
safety device (safety valve or similar) has to be installed Check regularly that
taking into account the weakest pressurized • all means of protection are correctly fitted and fixed,
component.
• all hoses and/or pipes within the system are in good
The min. and max. temperatures of +1 °C/33.8 °F and condition, firmly fixed and do not chafe,
+45 °C/113°F are also valid for the intake air. Pipes
and/or other parts with a surface temperature higher • there are no leakages (fuel, oil or coolant),
than 70 °C/158 °F have to be suitably identified and
• all fittings are firmly tightened,
shielded against touching.
• all wires are connected correctly and are in good
Electrical connections must meet the local regulations.
condition,
Power units must be connected to earth and protected
from short-circuits by means of fuses. • all safety valves and other pressure relief
mechanisms are in good order and not blocked by
e.g. dirt or paint,
Cold dryer
• the safety mechanisms are fully functional.
Wherever possible, the cold dryer should be installed in
a place where the ambient air is as clean as possible If compressed air hoses are used, they must be of the
and where the temperatures never rise above or fall proper size and suitable for the relevant operating
below the respective limit values as indicated in the pressure. Do not use chafed, damaged or poor-quality
operating instructions. If required, the cooling air is to hoses.
be taken from a cleaner, cooler or warmer area via an
intake channel; depending on the size of the machine, Only use hose couplings and fittings of the right type
an additional fan could turn out to be necessary. and the correct size.

If the room temperature can fall below zero, the Before blowing through a hose or an air pipe ensure
condensation drain system must be protected from that the open end is positively held. A free end whips
freezing, e.g. by means of a steam heater. and can cause injuries.

Before decoupling a hose ensure that it is pressureless.

9
3. Safety regulations

Refrain from any working method which is doubtful in Checks, maintenance and repair work may only be
terms of safety. carried out with the screw compressor being at rest and
depressurized. Protective equipment to be removed for
Never play around with compressed air! this work, has to be refitted after completion of these
Never aim compressed air at your skin or at other activities. Operation of the machine without protective
persons! equipment is not permitted. When working on a running
screw compressor system, working clothes have to be
Never use compressed air to clean your clothing. close-fitting.
When using compressed air to clean equipment take If the machine/unit is completely shut down for
the utmost care and always wear protective goggles. maintenance and repair work, it must be secured
against inadvertent restarting:
The compressed air generated by these compressors
must never be used for breathing unless it has been • Lock the main command elements and remove the
conditioned for those applications in line with the “safety key and/or
requirements for respiratory air”.
• attach a warning sign to the main switch.
Never use the machine in an environment where
inflammable or poisonous vapour can be sucked in. Always use the correct tools for maintenance and repair
work.
Never operate the system at pressures and
temperatures below or above the values indicated in the Never use inflammable solvents or carbon tetrachloride
technical data sheet. to clean parts. Take precautions against poisonous
vapours from cleaning agents.
The access panels, etc. have to be closed during
operation. In any work concerning the operation, conversion or
adjustment of the machine and its safety-oriented
Check the machine/unit at least once per shift for visible devices or any work related to maintenance, inspection
damage and faults! Report any changes (including and repair, always observe the start-up and shutdown
changes in the machineʼs operating behaviour) to the procedures set out in the operating instructions and the
responsible department/person immediately. If information on maintenance work.
necessary, stop and lock the machine immediately!
Ensure that the maintenance area is adequately secured.
In the case of malfunction, stop the machine/unit
immediately and lock it! Have any defects rectified To lower the risk of accidents, individual parts and large
immediately! assemblies being moved for replacement purposes
should be carefully attached to lifting tackle and
Observe the start-up and stopping procedures and the secured. Use only suitable and technically correct lifting
control displays according to the operating instructions. gear and only utilize suspension systems with adequate
Before starting up or setting the machine in motion, lifting capacity. Never work or stand under suspended
ensure that nobody is at risk. loads!
Do not cut off or remove extraction or venting facilities During maintenance and when carrying out repair work,
while the machine is running. cleanliness is very important. Avoid the ingress of dirt
by covering parts and free openings with a clean cloth,
paper or adhesive tape.
3.5 Special work/maintenance After the completion of each repair, check that tooling or
loose parts have not been left in the or on top of the
Carefulness machine, drive motor or drive equipment and ensure
Observe the adjusting, maintenance and inspection that no cloth has been left inside these units.
activities and intervals set out in the operating Be careful when the screw compressor system is in
instructions, including information on the replacement of operation.
parts and equipment. These activities may be carried
out by skilled personnel only.
Maintenance/rectification of faults
Brief the operating personnel prior to starting special
operations or maintenance work! Appoint a person to The employer has to inform the employee of the
supervise the activities! dangers possibly arising during the repair and
maintenance of the machine/unit as well as on how to
Maintenance and repair work may only be carried out avoid them; the employee has to observe all measures
under the supervision of a person who is qualified for for safety at work. Safety equipment for the prevention
this work. or elimination of danger has to be maintained regularly
Oil losses result in a slippery floor. Therefore, always and functionally checked at least once a year. Faults
clean the floor and the outside of the machine prior to observed have to be immediately rectified and/or
starting the maintenance work. reported to the responsible person.

10
3. Safety regulations

Use only original spare parts. Check the accuracy of pressure and temperature
indicators at regular intervals. If the admissible
Only carry out maintenance and repair work when the tolerance limits have been exceeded, these devices
system is not in operation and the power supply have to be replaced.
disconnected. Ensure that the power unit cannot be
switched on inadvertently. Before removing or overhauling a compressor, a motor
or another machine, ensure that all moveable parts of a
Before removing or opening pressurized components, mass of more than 15 kg cannot move or roll away.
positively isolate any source of pressure and
depressurize the entire system. After completion of repair work, always verify that no
tools, loose parts or cloths have been left in or on the
Never weld near oil systems or carry out any other work machine, drive motor or drive equipment. Machines
requiring heat. Pressure reservoirs or components and performing a back and forward main movement have to
pipes containing oil have to be drained completely and be cycled at least once, rotating machines have to be
cleaned, for example by means of a steam jet, before cycled several times in order to ensure that there are no
beginning such work. mechanical faults in the machine or the drive member.
Never weld any pressure reservoir or change it in any Check the direction of rotation of the electric motors
way. during first commissioning and after each modification
of the electrical connections in order to prevent the
If work which produces heat, flames or sparks has to be compressor from being damaged.
carried out on a machine, the adjacent components
have to be protected by means of non inflammable The fastening of loads and the instructing of crane
material. operators should be entrusted to experienced persons
only. The person giving the instructions must be within
Before releasing the power unit for operation after sight or voice contact with the operator.
maintenance or overhaul, check that the operating
pressures, temperatures and time settings are correct For carrying out overhead assembly work always use
and that the regulating and shut-down equipment specially designed or otherwise safety-orientated
function properly. ladders and working platforms. Never use machine
parts as a climbing aid. Wear a safety harness when
Examine the pressure tube and the pressure vibration carrying out maintenance work at greater heights.
dampers for carbon deposits every six months.
Excessive deposits have to be removed. Keep all steps, handles, handrails, platforms, landings
and ladders free from dirt, snow and ice! Clean the
Motor, air filter, electrical components and regulating machine, especially connections and threaded unions,
equipment have to protected from the ingress of of any traces of oil, fuel or preservatives before carrying
humidity, e.g. when cleaning the system by means of a out maintenance or repair work! Never use aggressive
steam jet. detergents! Use lint-free cleaning rags!
Under no circumstance must the sound-proofing Before cleaning the machine with water or steam jet
material be removed or modified. (high pressure cleaner) or other cleaning agents,
cover/mask all openings which have to be protected
Never use etching solvents which could attack the
from the ingress of water, steam or detergents for
materials used.
safety and/or functional reasons, in particular electric
If indicated or if there is any suspicion that an internal motors and switch cabinets.
part of the machine has run hot, the machine has to be
After cleaning, remove the covers/masking completely !
shut down.
Check all hydraulic oil lines for leakage, loose fittings,
In order to avoid an increase in the operating
abrasion and damage after cleaning. Any defect must
temperature, check and clean the heat transfer surfaces
be rectified immediately!
(cooling fins, intermediate cooler, water cooling jackets,
etc.) at regular intervals. Prepare a plan of the most Always re-tighten screwed connections which have
favourable cleaning intervals for each machine. been loosened for maintenance and repair work.
Avoid damage to the safety valves and other pressure If the set-up, maintenance or repair require the
reducing components. Check in particular for clogging demounting of safety equipment, this equipment has to
caused by paint, oil carbon or the accumulation of dust, be remounted and checked immediately after these
which could deteriorate the effectiveness of these activities.
components.
Ensure that consumables and replacement parts are
Insulation or protective shielding, the temperature of disposed of in a safe and environmentally friendly
which may exceed 70 °C/158 °F and which could be manner.
erroneously touched by the personnel, must not be
removed before these parts have cooled down to room
temperature.

11
3. Safety regulations

3.6 Warning of special dangers Hydraulics, pneumatics

Work on hydraulic equipment may only be carried out


Electric energy
by persons with special knowledge and experience of
Use only original fuses with the specified current rating. hydraulics.
Switch off the machine/unit immediately if trouble
Check all lines, hoses and screwed connections
occurs in the electric system.
regularly for leaks and obvious damage. Repair
Work on the electrical system or equipment may only damage immediately. High pressure jets of oil may
be carried out by a skilled electrician or by specially cause injury and fire.
instructed personnel under the control and supervision
Depressurize all system sections and pressure pipes
of such an electrician and in line with the relevant
(hydraulic system, compressed-air system) which are to
electrical engineering rules.
be removed in accordance with the specific instructions
If regulations require, the power supply to parts of for the assemblies concerned before carrying out any
machines and plants on which inspection, maintenance repair work.
and repair work is to be carried out must be cut off.
Hydraulic and compressed-air lines must be laid and
Before starting any work, check the deenergized parts
fitted properly. Ensure that no connections are
for the presence of power and ground or short-circuit
exchanged. The fittings, lengths and quality of the
them in addition to insulating adjacent live parts and
hoses must comply with the technical requirements.
elements.
The electrical equipment of the machines/units is to be
Noise
inspected and checked at regular intervals. Defects
such as loose connections or scorched cables must be Sound-proofing elements on the machine/unit have to
rectified immediately. be active during operation (i.e. sound-proofing panels
Necessary work on live parts and elements must be closed, etc.).
carried out in the presence of a second person who can Where necessary, wear the personal hearing protection
cut off the power supply in case of danger by operating prescribed.
the emergency shutdown or main power switch. Secure
the working area with a red-and-white safety chain and Noise, even at a low level, can cause nervousness and
a warning sign. Use insulated tools only. annoyance; over a longer period of time, our nervous
system can suffer serious damage. We therefore
Before starting work on high-voltage assemblies and recommend a separate machine room in order to keep
after having cut out the power supply, the feeder cable the noise of the machine away from the workshop.
must be grounded, and components, such as
capacitors, short-circuited with a grounding rod. • In order to consider all noise-relevant parameters
and to adequately protect the health of the operator,
Always check a correct power supply to the compressor the European Regulation 2003/10/EC must be
before commissioning. The voltage supply has to fulfill satisfied completely by the user.
the requirements of EN60204-1/IEC60204-1 for such
kind of industrial equipment. Insufficient power quality • In states outside the European Community, the
could have a strong effect on health & safety and may respective noise protection directives must be taken
constitute a risk to life and limb of the user or third into consideration.
persons or cause damage to the machine or also the
Take care that the noise transmission through walls and
environment around.
frames does not result in too high a noise level in the
surrounding areas.
Gas, dust, steam and smoke
Carry out welding, flame-cutting and grinding work on Oils, greases and other chemical substances
the machine/unit only if this has been expressly When handling oils, greases and other chemical
authorized, as there may be a risk of explosion and fire. substances, observe the safety regulations for this
Before carrying out welding, flame-cutting and grinding product! Be careful when handling hot fuels and
operations, clean the machine/unit and its surroundings consumables (danger of burning or scalding)!
from dust and other inflammable substances and make
sure that the premises are adequately ventilated (risk of
Rooms subject to explosion hazards
explosion)!
Adhere to the regulations valid for the place of Danger
operation! Compressor units must never be operated in areas
Observe any existing national regulations if work is to subject to explosion hazards!
be carried out in small rooms. (Exception: Special units with the corresponding
technical modifications)

12
3. Safety regulations

3.7 Storage of compressors


All compressors are protected against corrosion at the
factory for transport and for brief storage before
commissioning.

If the compressors are to be stored for period


exceeding six months, additional precautions must be
taken.
Compressors which are to be shut down for a lengthy
period must also be protected from corrosion.
Since corrosion occurs more quickly in damp
atmospheres than in dry conditions, it is not possible to
specify a maximum permissible standstill time which will
apply in all cases.

Note

The following aspects must be taken into account for


storage of storing compressors.

The compressor should be stored in a dry building


which should be heated if possible.

This is particularly true during the months of winter.

If there is a risk that the temperature will fall or rise


above the limits of -10 °C/14 °F to +65 °C/149 °F , the
electrical controller must be removed and stored in
ambient temperatures of +5 °C/41 °F to +30 °C/86 °F.

Before commissioning the compressor all the electrical


and electronic components and units should be
checked for the ingress of water or condensation.

13
3. Safety regulations

3.8 Symbols and explanations


Carefully read the operating manual before
commissioning or servicing this compressor.

Never operate the machine without protective


equipment fitted.

Never breathe in compressed air from this system.

14
3. Safety regulations

Never operate the unit with open doors or loose access


panels.

Warning: Hot surface

Warning: Pressurized part or system

15
3. Safety regulations

Warning: This system can start up by means of a


remote control or automatically after a power
failure.

Warning: The system continues to run for 30 seconds


after pressing the O-key

Warning: Danger of electric shock

16
3. Safety regulations

Attention: Lifting point

Attention: Check and, if required, re-tighten


connection terminals. For further details,
see the operating instructions.

Attention: Opening pressure safety valve = xx bar


(value "xx" see sticker on compressor)

17
3. Safety regulations

Attention: Only lubricate the system while the motor


is running. For further details, see the
operating instructions

18
4. Design and functioning

4 Desig n a n d f un cti oni ng

4.1 Design of the unit

4.1.1 Design of air-cooled units

Fig. 2

1 Pressure reservoir 7 Air cooler


2 Oil filter 8 Cooling air ventilator
3 Oil cooler 9 Air filter
4 Pressure holding and check valve 10 Base frame
5 Intake regulator 11 Electric motor
6 Screw compressor 12 Compressed air mains connection

19
4. Design and functioning

4.1.2 Design of the air-cooled unit RS version

Fig. 3
1 Pressure reservoir 8 Cooling air ventilator
2 Oil filter 9 Air filter
3 Oil cooler 10 Base frame
4 Pressure holding and check valve 11 Electric motor
5 Intake regulator 12 Compressed air mains connection
6 Screw compressor 13 Control cabinet
7 Air cooler

20
4. Design and functioning

4.2 Design of the water-cooled unit

Fig. 4
1 Pressure reservoir 8 Cooling air ventilator
2 Oil filter 9 Air filter
3 Oil cooler 10 Base frame
4 Pressure holding and check valve 11 Electric motor
5 Intake regulator 12 Compressed air mains connection
6 Screw compressor 13 Cooling water solenoid valve
7 Air cooler 14 Cooling water connection

21
4. Design and functioning

4.3 Schematic diagram

Switching point: 50 mbar

Residual pressure:
Opening pressure
1-1,5 bar
4,5-5 bar

Switching
point: 1,2 bar

P2N controller

Orifice diameter: 1,4 mm

Orifice
25,1 mm

Switching point: 1,2 bar


Start of opening:
55 °C

Compressed air line

Oil line

Control line

Cooling water line

Fig. 5
1 Intake filter 19 3/2-way solenoid valve B1 Mains pressure sensor
2 Intake regulator 20 2/2-way solenoid valve B2 Final compression pressure
2.1 Actuating cylinder 21 Oil temperature regulator sensor
2.2 Throttle 22 Oil level indicator
3 Electric motor 23 Intake filter switch(maintenance)* F1 Drive motor bimetal *
4 Screw compressor 24 Fine separator switch F2 Fan motor bimetal *
5 Thermo-sensor + indicator (maintenance)*
6 Pressure reservoir 25 Cooling air ventilator S5 Oil filter monitor
7 Fine separator 26 Orifice S6 Oil fine separator monitor *
8 Oil drain 27 Dirt interceptor (W only) S7 Air filter monitor *
9 Safety valve 28 Cooling-water solenoid valve S10 Monitor of direction of rotation
10 Oil filter switch (maintenance)* (W only) and V-belt
11 Oil filter 29 Manual regulating valve (W only) S12 Oil level *
12 Oil cooler 30 Check valve S13 Bearing monitor SPM *
13 Orifice 31 Frequency converter
14 Pressure reducing valve (RS version only) Y1 Control valve
15 Pressure holding and check 32 Motor lubrication system E4, E5 Y4 Blow-off valve
valve Y6 Cooling water solenoid valve
16 Air cooler R1 Motor temperature (W only)
17 P2N-Regulator (Intake throttle R2 Compressor temperature
regulator)* R6 Air cooler outlet temperature* * Option
18 Pressure monitor + display

22
4. Design and functioning

4.4 Oil circuit • The connection between the pressure reservoir -6-
and the intake channel is closed by the solenoid
The required oil is drawn from the pressure reservoir -6- valve -20-.
, passes through the oil thermostat -21- (closes the
• The pressure reducing valve -14- limits the control
bypass line of the oil cooler -12- and opens the passage
pressure to the actuating cylinder -2.1-.
to the oil cooler at a temperature of > 55 °C (L132-250)
/70°C (L160-250RS), through the oil filter -11- and is fed • The throttle -2.2- in the intake regulator -2- opens.
to the screw compressor -4-.
• The valve combination (pressure holding and check
The oil separated in the oil fine separator -7- is fed valve) -15- opens at a system pressure of approx.
through an oil line to the screw compressor -4-. The 4.5 bar.
entire oil circulation is based on a natural differential
pressure within the system. Considering the pressure • The delivery of compressed air into the consumer
differential of approx. 1.5 bar within the system, at a network starts.
reservoir pressure of, for example, 7 bar, the oil is
injected into the compressor -4- at approx. 5.5 bar. Automatic operation (open/close operation)
• When the mains pressure reaches the preset
maximum value, the solenoid valves -19- + -20- de-
4.5 Air circuit energize.

The aspired air passes through the intake filter -1- and • The throttle -2.2- is closed by a spring in the
the intake regulator -2- into the screw compressor -4-. actuating cylinder of the intake regulator -2.1-. The
During the compression process, the intake air is control air is discharged via the de-energized
cooled by injected oil and the compressed air/oil solenoid valve -19- into the intake channel.
mixture thus created flows tangentially into the pressure
reservoir -6-. After preseparation and subsequent fine • The screw compressor -4- runs in the off-load
separation in the oil fine separator -7-, the compressed mode.
air that has now a low oil content passes through the • The pressure reservoir -6- is relieved.
valve combination -15-, the oil cooler -16- and the
condensate separator (optional) into the consumer • If the mains pressure does not fall to the preset
mains. minimum value within the programmed run-on time,
the system is stopped.
The condensate separated in the condensate separator
(option) is carried outside via a solenoid valve (option) • The cooling water solenoid valve -28- (only W-unit)
that is controlled by a Kondensomat (option) and must deenergizes and closes.
be installed by the customer.
• If the preset minimum value is reached before the
programmed run-on time has elapsed, the solenoid
valves -19- + -20- are re-energized.
4.6 System control • The unit changes over to on-load operation.

4.6.1 Start/stop/shutdown L132-250


Throttling operation (option)
(See also operating instructions for the compressor
control Delcos-3100) • In the control, the upper switching point is
programmed to the maximum operating pressure
Starting the system (0.3 bar higher than the setting of the proportional
regulator). The standard proportional regulator can
• The electric motor -3- starts up in the Y-mode. only be used for a pressure range from 7 bar to
nominal pressure.
• The intake regulator -2- is closed.
• The regulating range can be set lower by adjusting
• The oil supply to the screw compressor -4- is
theproportional regulator accordingly.
provided by the vacuum pressure at the place of
injection. • At an increasing inlet pressure (increasing pressure
in the pressure reservoir -6-), the proportional
• The cooling water solenoid valve -28- (only in W-
regulator outputs a decreasing outlet pressure within
units) opens as it is energized.
the regulating range (corresponds to a decreasing
• When changing over to Δ-operation, the solenoid control pressure in the actuating cylinder -2.1-).
valves -19- + -20- switch due to being energized.
• As a result of the pressure drop in the actuating
• The air in the system circulates via the solenoid cylinder of the intake regulator -2.1- the throttle -2.2-
valve -19- into the actuating cylinder of the intake closes partially and thus causes throttling of the
regulator -2.1- intake flow.

23
4. Design and functioning

Note Speed-controlled operation

Throttling operation provides only a restricted throttling The revving speed is controlled with the help of a PI
function that is to reduce the supply flow to approx. controller implemented in the software. It adjusts the
70 %. When this value is reached, the control is to speed in dependence upon the demand for compressed
switch the screw compressor unit over to off-load air. The controller tries to maintain the line pressure
operation. within the values set for line pressure max. and line
pressure min. in the control (setpoint pressure).

Stopping of the system:


Automatic operation (open/close operation)
• Pressing the OFF key on the operator panel causes
the solenoid valves -19- + -20- to de-energize. • When the line pressure reaches the pre-set
maximum value, the speed of electric motor -3- is
• The throttle -2.2- in the intake regulator -2- closes reduced in order to adjust the delivery volume to the
and the system is relieved. actual compressed air consumption.
• After 30 seconds, the electric motors -3- + -25- shut • When the minimum motor speed is reached, the
down. system is controlled according to the open/close
principle.
• The cooling water solenoid valve -28- (only -W-unit)
deenergizes and closes. • Solenoid valves -19+20- are de-energised.

• Throttle -2.2- is closed by the spring in the actuator


Standstill of the system of intake regulator -2.1-. The pilot air is discharged
via the de-energised solenoid valve -19- into the
• When the system is at rest, the intake regulator -2-
intake channel.
is closed by a compression spring in the actuating
cylinder -2.1-. • Screw compressor -4- runs in the off-load mode.
• The solenoid valves -19- + -20- are de-energized. • Pressure reservoir -6- is unloaded.
• The pressure reservoir -6- is bled into the intake • If the line pressure does not fall to the setpoint value
channel via the solenoid valve -20-. within the programmed run-on time, the system is
shut down.
4.6.2 Start/stop/shutdown L160-250RS • If the setpoint value is reached before the
programmed run-on time has elapsed, solenoid
(See also operating instructions for the compressor
valves -19- + -20- are re-energised.
control Delcos-3100)
• The system changes over to the on-load mode.
Start of the unit:

• Electric motor -3- starts up. Stopping the unit:


• Intake regulator -2- is closed. • Press the OFF key on the operator panel to
• Screw compressor -4- is supplied with oil due to deenergise solenoid valves -19+20-.
vacuum pressure at the place of injection. • Throttle -2.2- in intake regulator -2- closes and the
• After the start-up, solenoid valves -19- + -20- are system is unloaded.
operated, since they are energised. • After 30 seconds, electric motors -3+25- shut down.
• The air circulating in the system flows through
solenoid valve -19- into the actuator of the intake Standstill of the system
regulator -2.1- The connection between pressure
reservoir -6- and intake channel is closed by • When the system is at rest, intake regulator -2- is
solenoid valve -20-. closed by a compression spring in actuator -2.1-.

• Pressure reducing valve -14- limits the pilot • Solenoid valves -19 + 20- are de-energised.
pressure to the actuator -2.1-.
• Pressure reservoir -6- is bled via solenoid valve -20-
• Throttle -2.2- in intake regulator -2- opens. into the intake channel.

• The valve combination (pressure holding and check


valve) -15- opens at a system pressure of approx.
4.5 bar.

• The delivery of compressed air into the consumer


network starts.

24
5. Transport and installation

5 Tr ans por t an d i ns tall ati on

Weights (with electric motor IP55)


5.1 Transport
The values listed below are approximate values, they
refer to a screw compressor unit including oil fill:

Version: A AS W
L132 4095 4245 4045 kg
L160 4215 4365 4165 kg
L200 4800 4950 4630 kg
L250 4950 5100 4780 kg

Weights (RS version)


The values listed below are approximate values, they
refer to a screw compressor unit including oil fill:

Version: A AS
L160 RS 4535 4695 kg
L200 RS 4910 5070 kg
L250 RS 5380 5540 kg

5.1.1 Transport of the high-voltage


Fig. 6 variant + L160-250 RS
Danger

The screw compressor unit must be transported


using suitable lifting gear (Fig. 6). The minimum
values specified for :

α = 45 ° - 60 °
L = 2.0 - 2.8 m
H = 1.4 - 2.4 m

must strictly be adhered to.


Before lifting, all loose or slewable parts of the
machine have to be firmly secured.
It is strictly prohibited to work or stand in the
danger zone of a lifted load.
The proper lifting of the load (according to the
operating instructions of the load suspension
device) has to be ensured.
Fig. 7
Important
Important
Only use the identified lifting points. Do not slide
the unit when it is standing on the floor. The high-voltage version and L160-L250RS may only
be transported using suitable lifting gear. (Fig. 7).
Transporting this variant by means of a forklift truck
Transport by means of fork lift truck (only L132-250)
is impossible.
The screw compressor unit may also be transported
using a fork lift truck. To do this, remove the relevant
panels from the baseframe.

Important
The separation of the forks and their length must
be taken into account. The length of the forks must
correspond at least to the width of the unit.

25
5. Transport and installation

5.2 Installation

A = 1.5 m
B = 1.2 m

Fig. 8

Danger
• The weight carrying capacity of the foundation
has to be taken into account when installing the
compressor.
• Provide for a solid and plane base.
• The system may not be operated on the transport
pallet.
• The intakes are to be located so that no
hazardous constituent (solvent vapour, etc., but
also dusts and other hazardous material) can be
sucked in. This applies also to flying sparks.
• Pipes and/or other parts with a surface
temperature higher than 70 °C/158 °F have to be
suitably identified and secured against
touching.
See also the safety regulations in chapter 3 of the
operating instructions.

Important
The operator has to provide adequate ventilation
for the compressor station.
The screw compressor unit has to be levelled. A
minimum distance from walls, other machines, etc.
should be maintained so that there is sufficient
clearance for maintenance and repair work (Fig. 8).
During operation of the screw compressor unit, heat is
generated by the electric motor and the compression
process. The screw compressor radiates a part of this
heat into the surroundings.
Proper ventilation has a considerable effect on the
service life and the performance of a compressor.

26
6. Preparations for commissioning

6 Pr epar ati on s f or com m iss io nin g

6.1 Cooling air volume/minimum cross

Fig. 9 Air-cooled system L132-L250A

Fig. 12 L160RS-L250RS

Legends Fig. 9 - Fig. 12:

1 Cooling air intake


2 Cooling air outlet
3 Intake ais inlet
4 Cooling air outlet on control cabinet (RS version)
4a 4aCooling air inlet on control cabinet (RS version)

The cooling air volume required by these screw


Fig. 10 Air-cooled system with exhaust air sound compressors is as follows:
insulation L132-L250 AS
3
L132 A/AS ca. 315 m /min.
3
L160/RS A/AS ca. 405 m /min.
3
L200-L250/RS A/AS: ca. 530 m /min.
3
L132-L160 W: ca. 135 m /min.
3
L200-L250 W: ca. 135 m /min.
Under unfavourable local conditions, we recommend
the installation of venting ducts. However, the velocity
of the cooling air should not exceed 5 m/s/ 17 ft/sec.
We recommend a minimum duct cross-section of
2
approx. 1.8 m .

Important

The stated minimum cross-section refers to a


maximum duct length of 5 m/16.4 ft and a maximum
of one bend. In the event of differing values (over
5 m/16.4 ft, more than one bend, filter cartridges,
screens, etc.), please contact your technical
Fig. 11 Water-cooled system L132-L250 W adviser.

27
6. Preparations for commissioning

CompAir screw compressors are rated for ambient The compressed air mains is connected at the tapping
temperatures and cooling temperatures of +1°C/ flange of the screw compressor (Fig. 13 + Fig. 14).
33.8°F to +45°C/113°F. In the case of temperatures A compensator (Fig. 15) is available as optional extra.
other than the above limiting values, please consult
your technical adviser.

Note

In order to ensure a good heat dissipation, auxiliary


fans should be rated to process approximately 15 to
20% more air volume than the total cooling air
quantity required by the compressors installed in the
compressed air station.

6.2 Compressed air connection

Fig. 15
1 Compressed air connection
2 Thread identification compressed air connection
3 Cooling water inlet
4 Cooling water outlet

Danger

When connecting the compressor on the mains


side to the compressed air system available at the
customerʻs end, check the operating temperatures
and operating pressures required and examine the
required connecting flange or the connection
Fig. 13 Air-cooled units thread for proper type, size and functioning.
1 Compressed air outlet SAE 3 1/2” In the case of connections by means of connecting
hoses, take appropriate measures to prevent
whipping of the loose end in the event that the hose
connection tears off (see Fig. 15).

Note

After-coolers, separators, collecting reservoirs and


compressed air lines must be equipped with drain
facilities at their lowest point to drain collected fluids.
These facilities must allow the draining process of the
fluid to be observed.
Hand-operated facilities have to be actuated in
accordance with the operating instructions.
Automatic drain facilities have to be checked for proper
function at regular intervals. If condensate is drained to
a collecting line, which also collects the condensate
from other machines, make sure that the collecting line
Fig. 14 Water-cooled units
is free from counterpressure. Take suitable precautions
1 Compressed air outlet DN 100, PN 16 to ensure that counterpressure cannot build up.
2 Cooling water intake
Condensate may contain oil! When draining
3 Cooling water outlet
condensate, observe the relevant regulations for waste
The screw compressor unit is completely assembled in water disposal.
the factory.

28
6. Preparations for commissioning

6.3 Cooling water connection for water- Note


cooled units If possible, the cooling water outlet temperature should
be lower than 50 °C to avoid an increased precipitation
Danger of lime.
If open cooling towers are used in the cooling water
circuit, it is possible for legionella (Legionella
pneumophila) and other bacteria to grow and 6.3.1 Limit values of the constituent
spread. The growth and spread of bacteria must be
elements in water
prevented by corresponding service and water
treatment methods. Note
Important The information set out below is intended for guidance
and may differ under certain conditions of operation.
During danger of frost or extended periods of
The total composition and the operating temperature
standstill of the screw compressor unit, the cooling
are always decisive. Warranty claims may not be
water must be drained.
derived from this..
Maintenance and repair work must be carried out
carefully. Constituent elements of Pass-
Circulating
water / characteristic through
Dismantled bundles of pipes have to be checked water
values water
for integrity before being reinstalled. In the case of
even the slightest damage, replace the pipe bundle. pH value
6–9 6–9
Always use new seals when carrying out assembly (at 25 °C / 77 °C)
work. Carbonate CaCO3 < 100 mg/l < 50 mg/l
hardness (5.6 °dH) (2.8 °dH)
Note
Total hardness < 2 mmol/l < 0.5 mmol/l
When operating water-cooled screw compressor units, < 200 ppm < 50 ppm
the following must be taken into account: < 11.5 °dH < 2.8 °dH
• As a result of leakage in oil/water coolers, some oil < 20 °fH < 5 °fH
may get into the cooling water circuit. -
Chloride Cl < 200 mg/l < 50 mg/l
• Cooling water must not be drained in an 2-
Sulphate SO4 < 200 mg/l < 50 mg/l
uncontrolled manner into public sewage systems. −
Uncontrolled overflowing of the oil separation Nitrate NO3 < 100 mg/l < 100 mg/l
reservoir into public sewage systems must be ruled Organic substances
out. < 25 mg/l < 10 mg/l
(KMnO4 absorption)
Strictly observe the relevant waste water regulations. free aggressive
CO2 < 20 mg/l < 20 mg/l
carbonic acid
The cooling water circuit in the screw compressor unit
is completely assembled. Silicium oxide SiO2 < 10 mg/l < 10 mg/l
free chloride Cl2 < 4 mg/l < 2 mg/l
The water connections of L are as follows:
Oxygen O2 < 2 mg/l < 2 mg/l
Water inlet : G 1 1/2"/ NPT 1 1/2" +
Water outlet: G 1 1/2"/ NPT 1 1/2" Ammonium NH4 < 1mg/l < 1mg/l
Iron Fe < 0.2 mg/l < 0.2 mg/l
Permissible cooling water data:
Manganese Mn <0.1 mg/l <0.1 mg/l
Cooling water pressure: >>min./max.<<: 2/5 bar
2-
Cooling water inlet temp.: >>min./max.<<: 5 / 35 °C Sulphide S 0 0
Cooling water outlet temperature: >>max.<<: 55 °C
Ammoniac NH3 0 0
The values refer to fresh water quality without additives
> 50. < 800 > 50. < 200
(e.g. anti-freeze). Should the cooling water data differ, Conductivity
please consult CompAir. µS/cm µS/cm

Adjust the cooling water flow for the air cooler during
commissioning using a manual regulating valve.
Compressed air outlet temperature: 30 - 35 °C at a
cooling water inlet temperature of 20 °C.

29
6. Preparations for commissioning

6.4 Electrical connection

6.4.1 Electrical connection (EUROPE-Version only)


Recommended supply cable cross-sections and fuses

Power supply fulfilling VDE 0100, Part 523 - Group 3, single-wire

L132 - L250 Installed nominal Nominal motor Fuse protection Line cross section
400/415 V/50 Hz motor power power of fan A (W) (slow-blow fuse) at 30°C
2
[kW] [kW] [A] [mm ]
L132 132 3.0 (1.1) 6 x 200 6 x 70 PE 70
L160 160 2 x 3.0 (1.1) 6 x 250 6 x 95 PE 95
L200 200 2 x 3.0 (1.1) 6 x 315 6 x 120 PE 120
L250 250 2 x 3.0 (1.1) 6 x 315 6 x 120 PE 120

L160RS - L250RS Installed nominal Nominal motor Fuse protection Line cross section
400/415 V/50 Hz motor power power of fan A (W) (slow-blow fuse) at 30°C
2
[kW] [kW] [A] [mm ]
L160RS 160 2x3 425 2 x 3 x 120 PE 120
L200RS 200 2x3 500 2 x 3 x 150 PE 150
L250RS 250 2x3 630 2 x 3 x 185 PE 185

Notes on the table: The customer has to connect a main switch in the
incoming line of the compressor unit (unless
We do not know the cable type used by you, its length factory-mounted as special accessories)
and the installation conditions (temperatures, grouping). (DIN EN 1012 - 1).
The table above can therefore only be regarded as a
guideline. If this switch does not provide short-circuit and
overload protection for the system, suitable
The supply cable cross-sections given in the table back-up fuses have to be installed according to
comply with VDE 0298, part 4 - table 13, column 7. EN 60269-1 (low voltage directive ) (see table).
(Rubber hose line at 30 °C/86 °F and max. line length of
50 m). In the case of differing conditions (line length, The main switch must meet the requirements of the
temperature and grouping), establish the cross sections safety standard EN 60 204 part 5.3 (supply
in accordance with DIN VDE 0298, part 4 or BS7671 disconnecting device).
taking into account the cable type.
The electrical connection and protective measures
The setting value of the motor protective switch for the have to be installed in accordance with VDE, BS or
fan drive depends on the individual ambient and local regulations. As a rule, additional instructions
installation conditions on site. For safety reasons, the of the relevant power supplier have also to be
exact setting values should be obtained from the adhered to.
manufacturer.
The electrical connections must be made by an
Isetting = Inom x 1.15 x voltage correction, if required authorized specialist.

Inom see nameplate Attention: Interference voltage!


Compressor units are finished in the factory according If external electric circuits, which cannot be cut out
to standard EN60204 (industrial machinery). Please via the main switch, are connected to the control,
observe the following important notes: these have to be identified according to EN60204.
Warning signs have to be fixed near the main
Danger switch and near these electric circuits. In addition,
these conductors have to be laid separately and/or
The power supply to the compressor side has to be identified by colors. Work on control cabinets may
fitted for industrial equipment and fulfilling the only be carried out by electrotechnical specialists.
requirements of EN60204-1/IEC60204-1. To avoid If the installation conditions of the system differ
strong damages and fire on the power electric from the conditions described in EN60204, please
components, any kind of operation outside of the contact your technical adviser.
stated limits of EN60204-1/IEC60204-1 is
inadmissible.

30
6. Preparations for commissioning

Checking the setting of the control-power Start-up of the unit after connection to the electric
transformer network/Checking the direction of rotation

The control-power transformer is factory-preset to the After connection to the electrical network the unit can
rated voltage. However, practice has shown that the be started up for the first time. Make sure that the
actual supply voltage often differs from this value. In compressed air lines are connected and observe the
order to adjust the unit to the local conditions, the following notes:
setting of the control-power transformer must be
checked by measuring the control-power transformer Important
output voltages during under load operation and, if
When connecting a compressor unit to the electric
required, re-set. Several tapping points are provided for
network for the first time, it is necessary to check
this purpose (see circuit diagram). Fig. 16 illustrates an
the drive motor for the correct direction of rotation
example.
(see arrow).
In the case of a wrong direction of rotation stop the
unit immediately by actuating the emergency OFF
Serie push-button. The normal stop push-button stops
the drive only after the soft stop time (several
seconds).
Even a short operation of the drive in the wrong
direction of rotation (approx. 2 seconds) results in
Option
severe damage or consequential damage to the
compressor.

Connecting terminals for heater (option)

For L132-250 at 380/400 V:


• Connecting terminals for heater
• 400 V –10%/ + 6%
Fig. 16 • 5.0 kW, 3P/N/PE
• Integrated thermostat.
Danger
For L132-250 at 415 V:
When carrying out adjustment work on the control
power transformer, the unit must be electrically • Connecting terminals for heater 415 V +/- 5%
isolated and locked off. • 6.0 kW, 3P/N/PE
• External thermostat
Work on the control cabinet may only be carried out
by electrotechnical specialist personnel.

Important

A wrong setting of the control-power transformer


jeopardizes the trouble-free operation of
compressor units and can result in malfunction or
damage.
The verification of the control-power transformer
setting is a must during commissioning and
periodic inspection/maintenance, as the voltage
supply conditions may vary.
The correct setting should be checked during
under load operation of the unit by measuring the
control power transformer output voltages.

31
6. Preparations for commissioning

6.5 Oil level check 6.6 Sound pressure level

Danger Sound pressure level measured in dB(A) according to


PN8NTC 2.2 under full load at a distance of 1 m
Only check the oil level when the screw com- (tolerance: ± 3 dB(A)):
pressor unit is out of operation and depressurized!
Air-cooled Water-cooled
The pressure reservoir can be under pressure and
A AS WS
the oil hot. Warning: Danger of scalding!
L132 78 75 73
Do not spill oil! Check for leakage!
L160/L160 RS 81 77 75
L200/L200 RS 82 78 77
L250/L250 RS 82 78 79

Subject to technical revision.

6.7 Acoustic power level


Acoustic power level measured in dB(A):

Air-cooled Water-cooled
A AS WS
L132 97 95 92
L160/L160 RS 100 97 94
Fig. 17
L200/L200 RS 101 98 96
Important L250/L250 RS 101 98 98
Do not mix oils of different specifications.
Subject to technical revision.

Check the oil level as follows:

• Check the oil level with the help of the Tecalan tube
at the pressure reservoir (Fig. 17) after every stop
and at regular intervals.
• The oil should have settled and the air entrapped
should have been dispersed. This procedure may
take up to one hour (depending on the conditions).
• Check the oil level, it must be above the minimum
marking on the Tecalan tube. If required, top up oil.
Also see chapter 8 “Service and maintenance”

32
7. Commissioning

7 Com m issio ni ng

7.1 First commissioning • Ensure cooling water supply in accordance with


Chapter 6.3. (only Lxx W – water-cooled units).
Danger • Operate main power supply switch.

Make sure before commissioning that nobody is in • Before each commissioning, check the safety
the danger zone of the screw compressor. valve (Fig. 18) for function by turning the
knurled cap at the safety valve (at operating
Only operate the screw compressor with closed pressure).
access panels.
• When switching the power supply on, an LED
The safety valve can be hot as a result of preceding test is run that must be acknowledged by
operation. A functional check must only be carried pressing the [ Θ ] key before the system starts.
out at operating pressure. Be careful with escaping The unit can be started by pressing the [ I ] key.
air (danger of burning and scalding). Before that, any faults must have been rectified.
Important Note
Although every CompAir screw compressor has Before first commissioning or re-commissioning after
been subjected to a test run at the factory and has maintenance of the water-cooled units, the air cooler
again been thoroughly inspected before shipment, must be bled via the bleed screw.
damage during shipment cannot be excluded. For
this reason, every screw compressor should be
checked once again for damage before being com-
missioned. In addition, it should be observed
during the first operating hours. 7.2 Routine commissioning
The screw compressor unit is completely factory-
assembled. It can be directly connected to the com-
pressed air mains by means of a flexible connection.

Important

If the screw compressor is newly connected to a


power supply, check the direction of rotation of the
drive motor!
With a wrong direction of rotation, shut down the
unit immediately by actuating the emergency
shutdown, otherwise the compressor might suffer
serious damage.
The access panels may temporarily be opened for Fig. 18
checking the direction of rotation (wear ear
protectors). Danger
Make sure before commissioning that nobody is in
Moreover, the following points must be taken into the danger zone of the motor/screw compressor.
account : After completion of work: Verify that all safety
• Fasteners (if any) used for securing the unit devices have been refitted and that all tools have
during transportation have to be removed prior been removed.
to commissioning. Only operate the screw compressor unit with
• Before first commissioning, panels and doors closed access panels.
should be realigned, if required. Before each commissioning, check the safety valve
(Fig. 18) for function by turning the knurled cap at
• Check and, if necessary, correct the pre-set
the safety valve - at operating pressure. The safety
values at the Kondensomat (option).
valve can be hot as a result of preceding operation.
• Re-tighten all connecting terminals of the A functional check must only be carried out at
electrical control before commissioning. operating pressure.

• Check the oil levels in the pressure reservoir Be careful with escaping air (danger of burning and
scalding).
before each commissioning.

• Open isolator valves between the screw


compressor, reservoir and pipe,

33
7. Commissioning

Note 7.4 Operating modes


The condensate separator (option) and condensate Automatic operation L132-L250 + L160-L250RS
drain (option) have to be installed by the customer.
Before first commissioning or re-commissioning after The generation of compressed air is stopped when the
maintenance of the water-cooled units, the air cooler set maximum operating pressure has been reached,
must be bled via the bleed screw. and the electric motor stops after a corresponding run-
on time (dependent upon the electrical network). The
generation of compressed air commences and the
Before each commissioning of the screw electric motor cuts in, when the operating pressure has
compressor follow the steps below: decreased to the set minimum value.
• Check oil level in the pressure reservoir.
• Open shut-off valves between the screw Throttling operation L132-L250
compressor, reservoir and pipe. The delivery of compressed air is throttled as soon as
• Ensure cooling water supply in accordance with the pressure range set at the proportional regulator has
Chapter 6.3. (only Lxx W – water-cooled units). been reached.

• Switch on the power supply master switch.


Speed-controlled operation (RS version only)
• Check the safety valve at operating pressure.
The unit adjusts the delivered amount of compressed
• For testing purposes, all LEDs on the operator panel air to the current compressed air consumption by
light up. controlling the speed of the electric motor.
• Press the [ Θ ] key for acknowledgement.
• Press the [ I ] key, the LEDs in the [ I ] field light up
to acknowledge that the drive motor is running. 7.5 Setting of the operating pressure

Start-up protection of the electric motor Danger

The screw compressor unit will not start up if the final The operating pressure must be set by a specialist
compression pressure is more than 0.4 bar. only.

The operating pressure must not be set higher.


Temperature start-up protection
Important
The screw compressor unit will not start up if the ambi-
ent temperature is lower than + 1 °C/33.8 °F. The operating pressure is indicated on the
nameplate.

Higher settings are not permitted.


7.3 Commissioning after malfunction It is possible to throttle the operating pressure
down to a minimum pressure of 5 bar.
Important
The DELCOS electronics controls the maximum
Do not switch the screw compressor on repeatedly permissible number of operating cycles of the motor.
without having rectified the malfunction, since this
may cause considerable damage to the machine.

Re-start after an automatic shutdown due to a


malfunction as follows:

• Operate emergency shutdown

• Rectify malfunction

• Unlock emergency shutdown

• Press acknowledgement key


• The screw compressor unit can only be restarted
when the acknowledgement key was pressed

• Start the screw compressor unit by pressing the [ I ]


key.

34
7. Commissioning

7.6 Monitoring
The operating temperature and the compressing
temperature are indicated in the plain text field on the
control panel.

Compressors with oil-lubricated pressure chambers are


to be operated in a manner that avoids exceeding of the
preset final compression temperature.
The screw compressor unit is provided with an
automatic operation monitoring system that shuts the
unit down in the case of the following faults:
1- Excessive temperature of screw compressor
2- Excessive temperature of electric motor
3- Overloading of fan motor (air-cooled)
4- Excessive temperature of cooling water
(watercooled)

Important

Warning : Electric voltage !

Encoders for automatic operation monitoring must


not be bridged !
The screw compressor unit must not be operated
with bridged encoders!

35
8. Service and maintenance

8 Ser vice an d m ai nte na nce

8.1 Maintenance recommendations Note

If the bearing temperature or the running noise


Note
increases during operation, the compressor unit must
The screw compressor unit can only operate to your be shut down immediately and the responsible service
complete satisfaction when the maintenance work is department informed.
carefully carried out at the specified intervals.
Repairs on electrical machines may only be carried out
In order to facilitate this task, the scope of supply of the by qualified specialist personnel!
screw compressor unit comprises the “Maintenance and
inspection manual for CompAir compressors”, in which
you can list your performed maintenance work at the
specified intervals.

The operating hours stated herein are recommended


maintenance intervals for average operating conditions.
Depending on the intake conditions, the operating times
may differ.
You can also have this maintenance work performed by
our trained technicians. Please ask your CompAir
distributor for a maintenance contract.

Fig. 19

8.2 Maintenance electric motor


The maintenance of the electric motor is to be
performed in line with the motor operating instructions.

8.2.1 Lubrication of electric motor


The two bearings of the electric motor must be
lubricated at certain intervals that are determined by the
type of motor.
For the motor-specific lubricating intervals and the
amount and type of grease required for the electric Fig. 20 RS-Version
motor, please refer to the motor nameplate.
1 GS = Bearing on the opposite side of the motor
Note 2 AS = Bearing on the motor drive side

In the case of 60 Hz drives, strictly observe the details Important


given on the nameplate!
Manual lubrication of the electric motor is only
The motor must be lubricated at the marked lubrication required for compressors without automatic motor
points using a grease gun while the compressor unit is lubrication system.
in operation .
To check the amount of grease required for lubricating,
weigh the grease gun before and after lubricating the
individual bearings of the electric motor.

Important

The operational reliability of the electric motor and


the entire compressor unit depends to a great
extent on the lubrication intervals. Poor or no
lubrication of the electric motors can lead to
considerable damage to the machine and results in
liability and warranty claims being invalidated.

36
8. Service and maintenance

8.2.2 Motor lubrication system (option) 8.2.4 Changing the LC unit


The screw air compressor unitʼs drive motor is fitted An empty LC unit or a fault on the lubricator is indicated
with an automatic motor lubrication system. on the compressor control by means of a message
[Warning: Mot.lubr. sys] (also refer to the operating
instructions for the compressor control DELCOS 3100).
Function of the motor lubrication system
The automatic motor lubrication system ensures that Important
the motor mounting is lubricated at all times. The Regularly check the level of grease in the
installed lubricators are powered (24 V DC) via the
transparent LC unit.
compressor control when the drive motor is running.
The volume of grease set on the lubricator is dispensed The red and green LEDs will light up
over several cycles depending on the motor runtime simultaneously to indicate when the empty LC unit
measured. needs replacing. This indication will only appear
when the screw air compressor unitʼs drive motor
is running.
8.2.3 Structure of the lubricators
(2x per drive motor) The drive system and control plate must be
protected from dampness.

Procedure for changing the LC unit


a) Disconnect plug from lubrication system.
b) Unscrew lubricator (LC unit with drive and cover)
from the lubrication point.
c) Unscrew drive cover.
d) Remove drive from LC unit.
e) Check setting of decode switches (see Settings
section). (The decode switches are preset and
locked in the factory. They must not be changed.)
f) Place drive on new LC unit until the gears mesh.
Only use completely filled genuine CompAir LC
units.
g) Screw down drive cover to LC unit (hand tight).
(MLS 120)
h) Remove seal plug from LC unit.
i) Screw lubricators into lubrication point (hand tight).
j) Reconnect plug in drive.
k) After a reset, the lubrication system starts the
applicable pause time.
l) Check function: A green LED indicates a continuous
signal if the screw air compressor unitʼs drive motor
is running.
m) The lubricant in one LC unit MLS 120 or MLS250 is
sufficient for approx. 4000 operating hours (this
figure doesnʼt include compressor downtimes).

(MLS 250)

Fig. 21
1 Drive motor
2 LC (Lubrication Canister) unit MLS120 or MLS250
filled with grease. The LC unit is not intended to be
refilled.
3 Cover (can be reused)
4 Drive with control plate and LED function display
(can be reused)
5 Cable and plug (can be reused)

37
8. Service and maintenance

8.2.5 Function display on lubricator


The LEDs for the function display are located on the
control plate and can be viewed through the transparent
cover.
The function display is only active if the screw air
compressor unitʼs drive motor is running.
The lubricators are fitted with one red and one green Fig. 21 b)
LED. These LEDs signal the following operating modes
or faults to the operator. Operating parameters of the lubricant dispenser
(Fig. 21 b)

LED Signal Explanation Grease volume / 100 service hours 2.78 cm³/0.17 in³
Green Continuous signal OK. “System Pause time between two approx. 9 Oh
running” dispensing processes
Red Continuous signal Dispensing process
Runtime of LC unit MLS 120 approx. 4000 Oh
<30 sec.
Red Continuous signal Error/fault
1)
>30 sec.
1)
Green and Continuous signal LC unit empty,
red please change

1) When the lubricator issues this signal, the following


message is output on the compressor control:
[Warning: Mot.lubr. sys] (also refer to the operating
instructions for the compressor control DELCOS 3100).

Settings available on the control plate


Fig. 21 c
Important

The coding switches are preset in the factory and 1 Function display (LED)
must not be modified! 2 Protruding “TIME” switches
3 Recessed “VOL” switches
There are two decode switches on the control plate. 4 Plug connection
5 Plate
The protruding switches inscribed with “TIME” are for
setting the dispensing volume and the recessed
For screw compressor series L200 to L250+RS / 50Hz +
switches inscribed with “VOL” are for setting the size of
60 Hz / IP55 with standard el. motor the following setting
the LC unit. is valid:
MLS 120

Fig. 21 d

Operating parameters of the lubricant dispenser


Fig. 21 a
(Fig. 21 d)
1 Function display (LED)
2 Protruding “TIME” switches Grease volume / 100 service hours 5,79 cm³/0,35 in³
3 Recessed “VOL” switches Pause time between two approx. 9 Oh
4 Plug connection dispensing processes
5 Plate
Runtime of LC unit MLS 250 approx. 4000 Oh
For screw compressor series L132 to L160+L160RS /
50Hz + 60 Hz / IP55 with standard el. motor the
following setting is valid:

38
8. Service and maintenance

8.2.6 Troubleshooting and fault rectification for lubricator


If faults occur when operating the lubricator, please check the possible causes of error using the following table. If an
error occurs that isnʼt listed in the table, please contact CompAir customer service.

Fault Possible cause Remedy


Lubrication system not working 1. Cable incorrectly connected 1. Connect up cable correctly
2. No voltage 2. Check voltage at plug
3. Cable failure 3. Connect up new cable
Lubrication system signalling 1. Incorrect setting of "VOL“ switches
“System running” (green LED)
2. Partly filled LC unit replaced with one Install full LC unit, type MLS120 or
although the LC unit is empty.
that is almost empty MLS250 as required
Lubrication system signalling 1. Line and/or connection parts blocked Clean line and connection parts,
“Fault" (red LED) then switch lubrication system off
2. Back pressure too high
and on again
Lubrication system signalling 1. Incorrect setting of "VOL“ switches
“End of dispensing” (red and
2. An LC unit that is almost empty has Install full LC unit, type MLS120 or
green LED) although the LC unit
been replaced with a partly filled one MLS250 as required
is not empty.

8.3 Maintenance and inspection Service packages


schedule Package C Oil filter cartridge, air filter cartridge
Package D Oil separator element
Danger Package E Worn parts
Package V V-belts
When performing control, adjusting and mainte-
nance work, be careful with hot surfaces of
machine parts.
Intervals are valid for normal industrial environments
Checks and maintenance work may only be carried and operating conditions.
out when the following points are observed:
For order numbers see the spare parts list.
• Press the STOP button on the control panel and
wait until the screw compressor unit has come
to rest and the screw compressor unit is
depressurized
• The pressure display does no longer indicate
pressures < 0.3 bar/4.4 PSI.
• Shortly after switching the screw compressor
off, the system can contain a low residual
pressure.
• The screw compressor unit must therefore be
depressurised prior to any maintenance work by
slowly opening the lock (oil filler cap) with
integral vents
• The customer-installed main switch is set to "O"
(OFF) and locked off
• Warning:
Electrical voltage: Only work on the screw
compressor unit when it is disconnected.

39
8. Service and maintenance

2,000 h
4,000 h
6,000 h
8,000 h
30 m 10,000 h
36 m 12,000 h
42 m 14,000 h
48 m 16,000 h
54 m 18,000 h
60 m 20,000 h
Commissioning
Due at x service hours

6m
12 m
18 m
24 m
At the latest after x months

Package C Oil filter cartridge, air filter cartridge          


Package D Oil separator element     
Package E Wearing parts  
Package V V-belts 
Maintenance every 2000 h, although at least every 6 months:
Replacement of air filter cartridge          
Replacement of oil filter cartridge          
Cleaning/replacement of cooling air inlet filter          
Maintenance every 4000 h, although at least each year:
Checking/tightening of connecting terminals in the switch cabinet/ and
     
checking of the “control transformer” setting
Checking/tightening screw connections      
General maintenance/cleaning     
Oil change when using CompAir - 4000 hours oil (only European version)     
Oil change when using SSL-50 or SSL-35-F Food Grade (only USA version)     
Oil change when using CSS20 Food Grade oil (only Canadian version)     
Oil analysis when using CS6000XL, SSL-46 or CompLube “10” oil     
Replacement of oil fine separator cartridge     
Replacement of lubrication cartridges     
Visual check of V-belt     
Intake regulator: Clean piston, control rod and cylinder and check for wear     
L160RS-L250RS only: Replacement of control-cabinet cooling air filter mat     
Lxx W – water-cooled units only: Cleaning of dirt interceptor (In the case of
    
dirty cooling-water, the cleaning intervals have to be shortened as required)
Maintenance every 6000 h, although at least every 18 months:
Oil change when using CS6000XL oil (only Canadian version)   
Maintenance every 8000 h, although at least every 2nd year:
Oil change when using SSL-46 oil (only USA version)  
Maintenance every 12000 h, although at least every 3rd year:
Oil change when using CompLube “10“ oil (only USA version) 
Replacing the V-belt (only complete sets) 
Inspection every 4 years:
Inspection of the electrical installation by a qualified electrician 
Inspection every 5 years:
Internal inspection of the pressure vessel by a qualified person 
Inspection every 10 years:
Strength test of the pressure vessel by the appointed body

 These maintenance intervals must be observed!


x For your own benefit, put a cross on the servicing schedule against maintenance work when performed.

40




66 m 22,000 h





















72 m 24,000 h

 
 
 
 
78 m 26,000 h



















84 m 28,000 h






90 m 30,000 h






















96 m 32,000 h





102 m 34,000 h























108 m 36,000 h





114 m 38,000 h
8. Service and maintenance






















120 m 40,000 h





126 m 42,000 h


















132 m 44,000 h




138 m 46,000 h

























144 m 48,000 h




150 m 50,000 h


















156 m 52,000 h





162 m 54,000 h




















168 m 56,000 h



174 m 58,000 h























180 m 60,000 h



186 m 62,000 h





















192 m 64,000 h





198 m 66,000 h


















204 m 68,000 h



210 m 70,000 h
























216 m 72,000 h



222 m 74,000 h


















228 m 76,000 h





234 m 78,000 h























240 m 80,000 h

41
8. Service and maintenance

8.4 Oil change

Fig. 23

Note

When changing the oil, the waste oil is to be drained


completely, since used oil reduces the service life of the
Fig. 22 new oil fill considerably.
Danger Do not mix lubricating oils of different makes. When
changing over to a new oil type, the oil in the oil circuit
Only change the oil when the screw compressor must be drained completely.
unit is not in operation and is depressurized!
For the oil change intervals, see maintenance schedule.
Be careful when draining hot oil:
Danger of scalding!
When changing the oil, proceed as follows:
Important
• Switch the screw compressor unit off and ensure
Remove oil residues and other deposits from unit that it is depressurized, electrically isolate and
parts and from the coolers of compressors, which locked off.
are exposed to hot compressed air, according to • Slowly open the oil filler cap (- 2 - Fig. 22), to
the operating instructions. depressurize the screw compressor by releasing
any residual pressure in the unit.
Note
• Open the oil filling opening
Collect the waste oil, do not allow it to seep into the
ground! • Open the oil drain (- 6 - Fig. 22) for the pressure
reservoir and the oil cooler
Disposal in accordance with the regulations! Do not spill
• Drain oil at operating temperature through the drain
oil! Check for leakage!
hose (- 7 - Fig. 22)
With these compressors, the oil change intervals • Close the oil drain for the pressure reservoir and the
strongly depend on the degree of contamination of the oil cooler
circulating oil. It must therefore be taken care that no
oil-deteriorating matter (dusts, vapours, gases) are • Fill in oil (approx. 135 litres)
transported through the air intake filter into the oil circuit • Close the oil filling opening using the plug screw
of the compressor unit. Also a high content of humidity
in the intake air and the formation of condensate within • Let the screw compressor unit run for approx.
the machine affect the service life of the lubricant oil so 2 minutes
that a reduction in the oil change intervals may become • Check for leakages
necessary. The specified oil change intervals refer to an
intake air from a normal environment without a high • Switch the screw compressor unit off
content of foreign matter (dusts, vapours, gases). If, • Wait at least 5 minutes for the oil to settle and for
under favourable conditions, it is intended that the oil the air to disperse
service life be extended, oil samples have to be
• Check oil level (see chapter 6.5)
examined, and the extension of the operating time
determined on the basis of these analysis results. • The oil level is sufficient when it is visible in the
upper third of the transparent Tecalan tube
• If required, top up oil

42
8. Service and maintenance

Changing intervals for lubricants • Unscrew the oil filter cartridge using an appropriate
tool. If required remove the plug screw (Fig. 24) in
The operating conditions (e.g. coolant temperatures), order that the oil in the annular gap can drain.
the operating modes and the quality of the intake air
(e.g. content of dust, content of gaseous foreign matter • Dispose of the oil filter cartridge according to the
such as SO2, solvent vapours) have a strong influence regulations.
on the oil change intervals. • Oil the gasket of the new oil filter cartridge slightly
In this case the oil must be analyzed to check the • Screw on the new oil filter cartridge and tighten
permissible length of time that the oil can be used (see manually (take notice of the instructions on the oil
also chapter 8.14). Under no circumstances should the filter cartridge), refit plug screw (Fig. 24)
oil be used beyond its design life.
• Let the screw compressor unit run for approx.
2 minutes
• Check for leakage
8.5 Change of oil filter cartridge
• Check oil level
• If required, top up oil.

Changing intervals for oil filter cartridge


The operating conditions (e.g. coolant temperatures),
the operating modes and the quality of the intake air
(e.g. content of dust, content of gaseous foreign matter
such as SO2, solvent vapours, etc.) have a strong
influence on the service life of the filters (air filters, oil
filters, fine separators).
Where such conditions exist the filter element may
require changing more frequently.

8.6 Change of the oil fine separator


Fig. 24

Danger
Only replace the oil filter cartridge when the screw
compressor unit is out of operation and
depressurized!
Be careful with hot oil: Danger of scalding! Do not
spill oil!

Note
Dispose of the oil filter cartridge in line with the
regulations - special waste ! Check for leakage!
For the changing intervals, see the maintenance
schedule.
If the oil filter cartridge is monitored (option), a high
differential pressure is indicated in the plain text field.
When the associated LED lights up, change the oil filter
Fig. 25
cartridge.
Danger
Change the oil filter cartridge as follows:
The pressure reservoir is under pressure! Only
• Switch the screw compressor unit off and ensure work on the screw compressor unit when it is out of
that it is depressurized, electrically isolate and operation and depressurized!
locked off.
Be careful with hot oil: Danger of scalding!
• Wait at least 5 minutes for the oil to settle and for Do not spill oil!
the air to disperse.

43
8. Service and maintenance

Note 8.7 Change of air intake filter


Dispose of the fine separator cartridge in line with the
regulations - special waste! Check for leakage!
For the changing intervals, see the maintenance
schedule.
If the oil fine separator is monitored (option), too high a
differential pressure is indicated on the keypad of the
compressor control DELCOS 3100. When the
corresponding warning lights up, change the oil fine
separator.

Change the oil fine separator as follows:


• Make sure that the screw compressor unit is
depressurized.
Fig. 26
• Remove the pressure pipe
Danger
• Disconnect all lines from the pressure reservoir cover
Only perform checks and carry out work on the
• Unscrew all hexagon bolts on the outer rim of the screw compressor when the unit is out of operation
pressure reservoir cover and depressurized!
• Remove the pressure reservoir cover with the valve
Important
combination (or turn the cover around the bolt with
the red marking, which may only be loosened Never operate the screw compressor unit without
slightly) the air filter (even a short operating time without
• Pull out the oil fine separator this filter can result in considerable damage to the
machine)!
• Clean the sealing surface pressure reservoir/oil fine
separator and, if required, remove and clean O-rings Clogged air filter cartridges must be cleaned or
replaced at the time of scheduled maintenance.
• Lay the seal on the sealing surface pressure
reservoir/oil fine separator If air filter cartridges are monitored (option), the clear
text display indicates a high pressure differential. When
• Insert new oil fine separator into the pressure reservoir the relevant LED lights up, the air filter cartridges are to
be replaced.
• Relocate the pressure reservoir cover with valve
combination, Check the air filter for accumulated dust at least once a
week or, if required, daily.
• Screw in all the hexagon bolts on the outer rim of
the pressure reservoir cover and tighten them During maintenance work, take care that no dirt enters
crosswise the clean air side of the air filter.

• Refit all the removed lines properly to the pressure


reservoir cover Maintenance of the air filter

• Adjust the oil extraction tube; it should end 1 - 2 mm The air filter must be cleaned intermediately or replaced
above the bottom of the oil fine separator, by a new one (refer to the instructions on intermediate
cleaning).
• Refit the pressure pipe with new seals.

Intermediate cleaning of the air filter


Changing intervals for oil fine separator
Note
The operating conditions (e.g. coolant temperatures),
the operating modes and the quality of the intake air Intermediate cleaning can be done no more than five
(e.g. content of dust, content of gaseous foreign matter times.
such as SO2, solvent vapours, etc.) have a strong
The air filter must be replaced when damaged, after five
influence on the service life of the filters (air filters, oil
intermediate cleaning procedures or after two years at
filters, fine separators).
the latest.
Where such conditions exist the filter element may Clean the filter carefully in order to avoid damage to the
require changing more frequently. filter material and ensure that no dust enters the clean
air side of the filter.

44
8. Service and maintenance

Intermediate cleaning is to be carried out as follows : Where such conditions exist the filter element may
require changing more frequently.
• Remove screws from the cover

• Remove cover

• Remove nut of the air filter cartridge holder 8.8 Safety valve
• Remove holder and take air filter cartridge out

• Clean the air filter cartridge (observe note


”Intermediate cleaning”) or replace it by a new one

• Remount the holder using the nut

• Attach cover and fasten it using the screws

Intermediate cleaning of the air filter by blowing


through with compressed air

Danger

When blowing through an air filter, observe the


following : Fig. 27
• Wear protective goggles and a breathing mask Danger
• The compressed air pressure must not exceed
Never operate a screw compressor system with a
5 bar
defective safety valve or without safety valve!
• Blow through the air filter from the inside to the
Before each commissioning, check the safety valve
outside until the formation of dust has consider-
for function by turning the knurled cap on the
ably decreased.
safety valve at operating pressure.
If the safety valve does not function properly, it
Intermediate cleaning of the air filter by rinsing
must be immediately replaced by a new safety valve
Danger with the corresponding pressure rating.
The safety valve can be hot as a result of previous
Never use gasoline, alkaline solutions or hot liquids
operation!
for cleaning !
Escaping air can be hot and contain oil (danger of
Rinse the filter as follows:
burning/scalding)!
• Swirl the air filter cartridge in luke-warm water which
contains a special non-foaming rinsing agent

• Let the air filter dry


• Never install wet or damp air filters.

Check the air filter for damage


Before reinstalling the cleaned air filter, it must be
thoroughly checked for cracks, holes or other damage
by examining it against the light using a bright light
source (portable lamp). Check also the seals.

Changing intervals for air filter cartridge


The operating conditions (e.g. coolant temperatures),
the operating modes and the quality of the intake air
(e.g. content of dust, content of gaseous foreign matter
such as SO2, solvent vapours, etc.) have a strong
influence on the service life of the filters (air filters, oil
filters, fine separators).

45
8. Service and maintenance

8.9 V-belts - automatic tensioning When installing or replacing the V-belt set, it must be
adjusted by pretensioning the compression spring. For
system this purpose, a blue marking is provided on the
threaded rod.
Danger

Only perform checks and carry out work when the Replacing the V-belt
screw compressor unit is out of operation and
depressurized ! Relieve the automatic tensioning system before
replacing the V-belt set. To do this, the pressure spring
Any safety equipment which had to be removed for (12) is released and the pivoting motor base is raised
the replacement of the V-belt set must be with the lifting aid and an additional hexagon nut. See
remounted after completion of this work. Fig. 29. When the new V-belt set is installed, pretension
the compression spring (12) to its original pretensioning
Work on the tensioned V-belt system is forbidden
rate.
due to risk of injury.

Important

The replacement of a single V-belt is not permitted,


always replace a complete V-belt set.

During the entire service life of the V-belt set, no


readjustment of the automatic V-belt tensioning
system will be necessary.

Fig. 29

Fig. 28
1 Baseframe
2 Compressor
3 V-belt pulley - compressor
4 V-belt set
5 Electric motor
6 V-belt pulley - electric motor
7 Pillow block
8 Anti-vibration mount
9 Threaded rod
10 Nut
11 Guide ring
12 Compression spring
13 Fork and clevis combination
It is not permitted to loosen the pillow block screws
(anti-vibration mount).
Any changes to the motor's anti-vibration mount can
result in a drastic reduction of the drive system's service
life.
The required pre-tensioning rate of the V-belt for each
screw compressor type is set in the factory.

46
8. Service and maintenance

8.10 Connecting terminals in the switch When operating water-cooled screw compressor units,
the following points must be taken into account:
cabinet/control transformer setting
• As a result of leakage in oil/water coolers, some oil
Danger can get into the cooling water circuit.
In the case of electric voltage: • Cooling water must not be discharged in an
uncontrolled manner into public sewage systems.
• Actuate STOP button at the operating panel Uncontrolled overflowing of the oil separator tray
• Set the customer-fitted main power switch to into public sewage systems must be ruled out.
"O" (OFF). Strictly observe the relevant waste-water
The connecting terminals in the switch cabinet have to regulations.
be checked and, if required, re-tightened during first • Maintenance and repair work has to be carried out
commissioning and later on in line with the maintenance carefully.
schedule. Check dismantled bundles of pipes for damage prior
The setting of the control transformer must be checked to reinstalling them. In the case of even the slightest
according to chapter 6.4 “Electrical connection”. damage, the pipes have to be replaced.
Always use new seals when carrying out assembly
and installation work.

• When operating a speed-controlled screw


compressor (RS version), replace the filter mats
8.11 Fittings (Fig. 30) of the outlet filter and filter/fan unit (4 off) in
the case of severe clogging.
The fittings of the air, water and oil circuits have to be
checked and, if required, re-tightened according to the
maintenance schedule.

Check the hose and piping for unsealed areas.

8.12 General maintenance and cleaning

Important

Remove oil residues and other deposits from unit


parts and from the coolers of compressors, which
are exposed to hot compressed air, according to
the operating instructions.
Blow off the screw compressor unit with
compressed air at the specified intervals (never
Fig. 30
direct compressed air towards persons) paying
particular attention to:
• Regulating elements
• Fittings
• Compressor block
• Cooler
• Electric motor
• Filter mats of the filter/fan unit and outlet filter
on the control cabinet (L160-250RS)

Note
Before first commissioning or re-commissioning - after
maintenance - of water-cooled units, bleed the air
cooler through the bleed screw.

47
8. Service and maintenance

8.13 Inspection intervals for pressure 8.14 Maintenance information and


vessels and electrical installations lubricant recommendations for
stationary compressors
Pressure vessels
As per the requirements of the 97/23/EC Pressure Lubricant recommendations
Equipment Directive, a qualified person must inspect Please note that proper lubrication will considerably
the pressure vessel from inside every five years. increase the service life of your compressor unit.
As per the requirements of the 97/23/EC Pressure According to regulations relating to the prevention of
Equipment Directive, an appointed body must perform a accidents, use lubricants the properties of which meet
strength test on the pressure vessel after ten years. the requirements of the operating conditions on site.
Do not mix lubricating oils of different makes. When
changing over to a new oil type, drain the old oil
Electrical installation completely from the system.
The electrical installation must be inspected by a If final compression temperatures of more than 90 °C/
qualified electrician after four years and also each time 195 °F occur continually, the oil change intervals given
work has been performed on it. in section 1.1 (maintenance schedule) are halved.
Should stricter inspection intervals apply in your The oil change intervals should be calculated more
country, these must be observed. accurately in accordance with the actual operating
conditions by analyzing the oil.

Use the following oil type:

European version

CompAir „4000“

USA-version:
a) SSL-50
b) SSL-35-F Food Grade (Optional)
c) SSL-46 (Optional)
d) CompLube “10“ (Optional)
For further information, please contact your local
CompAir Distributor or Gardner Denver-USA at
(937) 498-2500.

CANADA-Version:

a) CS6000XL
b) CSS20 Food Grade (Optional)
For further information, please contact your local
CompAir Distributor or Gardner Denver-Canada at
(905) 847-0688.

48
9. Trouble-shooting

9 Tr ou ble -s ho oti ng

In the case of faults or warnings that are detected by the compressor control Delcos-3100, please refer to the
chapter “Fault/warning table” in the operating instructions of the DELCOS 3100.

Malfunction Possible cause Remedy

Unit cannot be started 1. No operating or control voltage 1. Check fuses, main switch and supply line

2. Malfunction not acknowledged 2. Acknowledge fault message

3. Pressure reservoir not depressurized 3. Wait until depressurized. Screw


compressor does not start up, when
reservoir pressure is > 0.4 bar

4. Electric motor defective 4. Check connections, winding, etc.

5. Compressor defective 5. Turn the compressor manually;


if required, replace

6. Ambient temperature less than 6. Make sure that the ambient temperature
+1 °C/ 33.8 °F is not less than +1 °C/ 33.8 °F; install an
auxiliary heater, if required

Unit stops during the 1. Intake regulator only closes partly 1. Fix intake regulator or, if required,
start-up phase replace; check solenoid valves

2. Short-circuit in the unit 2. Determine and eliminate cause; replace


defective fuses

3. Connecting terminals in the switch 3. Check and re-tighten


cabinet are loose

4. No or insufficient pressure builds up in 4. Check the pressure holding valve and


the pressure reservoir during the D the opening function of the intake
phase regulator

5. Oil too viscous 5. Select the type of oil according to the


ambient conditions or install an auxiliary
heater

6. Maximum motor switching cycles 6. Avoid frequent manual on and off-


exceeded due to too frequent manual switching, let electric motor cool down
on and off-switching

Unit does not reach the 1. Intake regulator opens only partly 1. Fix intake regulator or, if required,
set mains pressure replace; check solenoid valves

2. Excessive air consumption 2. Reduce consumption or cut in a further


compressor

3. V-belt slips 3. Replace the V-belt set

4. Fine separator clogged 4. Replace fine separator cartridge

5. Air filter clogged 5. Replace air filter cartridge

6. Heavy leakage in the compressor 6. Check unit


system

49
9. Trouble-shooting

Malfunction Possible cause Remedy

Unit switches off 1. Ambient temperature too high 1. Ventilate compressor room

2. Fan defective 2. Check/replace fan

3. Cross section of the electric supply 3. Measure power requirement,


lines too small if necessary, replace lines

4. Power requirement too high 4. Oil fine separator clogged,


replace, if necessary

5. Oil level too low 5. Top up oil in the pressure reservoir

6. Oil injection pressure too low 6. Replace oil filter cartridge,


clean oil system

7. Excessive oil temperature 7. Check oil cooler and fan/


Check oil thermostat

Excessive idling pressure 1. Intake regulator does not close correctly 1. Check intake regulator

2. System not unloaded 2. Check solenoid valve (19) and lines

Oil in the compressed air 1. Oil fine separator defective 1. Replace

2. Oil foams 2. Change oil, blow-off time too short


3. Oil level too high 3. Drain off oil
4. Opening pressure of the pressure 4. Check pressure holding valve
holding valve too low

Oil in the air filter 1. Packing spool in the intake regulator 1. Check sliding fit and sealing surface and
defective replace, if necessary
2. Intake regulator does not close correctly 2. Check intake regulator
Check solenoid valves (19 and 20)
3. Blow-off time too short 3. Extend time (nozzle)

Safety valve opens 1. Safety valve defective 1. Replace

2. Oil fine separator clogged 2. Replace

3. Intake regulator closes too slowly 3. Check intake regulator and solenoid
valves (19 and 20)

4. Mains pressure sensor defective 4. Replace

5. Electronics defective 5. Replace

6. Solenoid valves 19 and 20 defective 6. Replace

Danger

Never operate the screw compressor with defective safety valve!

50
10. Annex

10 Ann ex

10.1 Declaration of conformity

1. EC Declaration of conformity
in accordance with the EC Machinery Directive 2006/42/EC, Supplement II A

2. We, hereby declare Gardner Denver Deutschland GmbH


Argenthaler Str.11
D-55469 Simmern

that the product: Kompressor

type: L07; L11; L15; L18; L22; L23; L26; L29; L30; L37; L45; L50; L55;
L75; L80; L90; L110; L132; L160; L200; L250; L07RS; L11RS;
L15RS; L18RS; L22RS; L23R; L26R; L29R; L30RS; L37RS;
L45RS; L55RS; L75RS; L90RS; L110RS; L132RS; L160RS;
L200RS; L250RS; L07FS; L11FS; L15FS; L18FS; L22FS

trade mark:

manufacturer no.:

in the form as shipped by us complies with the following relevant provisions:

2009/ 105/ EG 2006/ 42/ EG 2006/95/EG

This machine is exempt from the Pressure Equipment Directive. Please refer to Article 1, clauses 3.3
and 3.6 for information on this exemption.

3. If the machine is modified in a way not agreed upon with us, this statement will be void.

4. Harmonised standards applied, particularly

EN 1012-1 EN ISO 12100 EN 60034-1 EN 61000-6-4


EN 29001 EN 60204-1 EN 61000-6-2

5. National engineering standards and specifications applied

AD-S1/2000 BetrSichV DIN 3230 VDE 0298

6. Recording agency: CompAir Drucklufttechnik -


Zweigniederlassung der
Gardner Denver Deutschland GmbH
Qualitätsmanagement: Christian Mair

Simmern,
Date Signature

51
Gardner Denver Deutschland GmbH
Argenthaler Str. 11
55469 Simmern
Deutschland

Tel. ++49 (0)6761 832-0


Fax ++49 (0)6761 832-409

www.compair.com
e-mail: sales@compair.com

You might also like