You are on page 1of 33

FP 2.4
PAGE 102 VERTICAL TURBINE MOTOR DRIVEN
PERFORMANCE RATINGS
FEB 2018

SUPERSEDES ALL PREVIOUS ISSUES


250 GPM

BOWL MAX MOTOR
PUMP SIZE STAGES DISCHARGE COLUMN UL FM
PSI BHP HP
55 12 15 FP10WALC 3 4 X 12 - 125# 4 X 1.0 X 10' X X
60 13 15 FP10WALC 3 4 X 12 - 125# 4 X 1.0 X 10' X X
65 15 15 FP10WALC 3 4 X 12 - 125# 4 X 1.0 X 10' X X
70 15 15 FP10WALC 4 4 X 12 - 125# 4 X 1.0 X 10' X X
75 16 15 FP10WALC 4 4 X 12 - 125# 4 X 1.0 X 10' X X
80 18 20 FP10WALC 4 4 X 12 - 125# 4 X 1.0 X 10' X X
85 19 20 FP10WALC 4 4 X 12 - 125# 4 X 1.0 X 10' X X
90 20 20 FP10WALC 5 4 X 12 - 125# 4 X 1.0 X 10' X X
95 21 20 FP10WALC 5 4 X 12 - 125# 4 X 1.0 X 10' X X
100 22 20 FP10WALC 5 4 X 12 - 125# 4 X 1.0 X 10' X X
105 24 25 FP10WALC 5 4 X 12 - 125# 4 X 1.0 X 10' X X
110 25 25 FP10WALC 5 4 X 12 - 125# 4 X 1.0 X 10' X X
115 25 25 FP10WALC 6 4 X 12 - 125# 4 X 1.0 X 10' X X
120 27 25 FP10WALC 6 4 X 12 - 125# 4 X 1.0 X 10' X X
125 28 25 FP10WALC 6 4 X 12 - 125# 4 X 1.0 X 10' X X
130 29 30 FP10WALC 6 4 X 12 - 125# 4 X 1.0 X 10' X X
135 29 30 FP10WALC 7 4 X 12 - 125# 4 X 1.0 X 10' X X
140 31 30 FP10WALC 7 4 X 12 - 250# 4 X 1.0 X 10' X X
145 32 30 FP10WALC 7 4 X 12 - 250# 4 X 1.0 X 10' X X
150 34 30 FP10WALC 7 4 X 12 - 250# 4 X 1.0 X 10' X X
155 34 30 FP10WALC 8 4 X 12 - 250# 4 X 1.0 X 10' X X
160 36 40 FP10WALC 8 4 X 12 - 250# 4 X 1.0 X 10' X X
165 37 40 FP10WALC 8 4 X 12 - 250# 4 X 1.0 X 10' X X
170 39 40 FP10WALC 8 4 X 12 - 250# 4 X 1.0 X 10' X X
175 40 40 FP10WALC 8 4 X 12 - 250# 4 X 1.0 X 10' X X
180 40 40 FP10WALC 9 4 X 12 - 250# 4 X 1.0 X 10' X X
185 41 40 FP10WALC 9 4 X 12 - 250# 4 X 1.0 X 10' X X
190 42 40 FP10WALC 9 4 X 12 - 250# 4 X 1.0 X 10' X X
195 44 40 FP10WALC 9 4 X 12 - 250# 4 X 1.0 X 10' X X
200 45 40 FP10WALC 9 4 X 12 - 250# 4 X 1.0 X 10' X X

 TO CALCULATE PUMP RATED PRESSURE, REFER TO FP2.4 PG.1. PRESSURE SHOWN IS BOWL PRESSURE ONLY.

ALL PRICES ARE SUBJECT TO PROVISIONS SET FORTH IN OUR LATEST PRICES SUBJECT TO CHANGE WITHOUT NOTICE.
BUSINESS & PRICE POLICY, FP0.1, PAGES 11 THROUGH 14.

FP 2.4
VERTICAL TURBINE MOTOR DRIVEN PAGE 103
PERFORMANCE RATINGS
FEB 2018

SUPERSEDES ALL PREVIOUS ISSUES


500 GPM

BOWL MAX MOTOR
PUMP SIZE STAGES DISCHARGE COLUMN UL FM
PSI BHP HP
54 23 20 FP11CLC 3 6 X 16.5 - 125# 6 X 1.0 X 10' X X
60 26 25 FP11CLC 3 6 X 16.5 - 125# 6 X 1.0 X 10' X X
65 28 25 FP11CLC 3 6 X 16.5 - 125# 6 X 1.0 X 10' X X
70 31 30 FP11CLC 3 6 X 16.5 - 125# 6 X 1.0 X 10' X X
75 33 30 FP11CLC 3 6 X 16.5 - 125# 6 X 1.0 X 10' X X
80 34.5 30 FP11CLC 3 6 X 16.5 - 125# 6 X 1.0 X 10' X X
85 39 40 FP11CLC 3 6 X 16.5 - 125# 6 X 1.0 X 10' X X
90 39 40 FP11CLC 4 6 X 16.5 - 125# 6 X 1.0 X 10' X X
95 40 40 FP11CLC 4 6 X 16.5 - 125# 6 X 1.0 X 10' X X
100 44 40 FP11CLC 4 6 X 16.5 - 125# 6 X 1.0 X 10' X X
105 46 40 FP11CLC 4 6 X 16.5 - 125# 6 X 1.0 X 10' X X
110 51 50 FP11CLC 4 6 X 16.5 - 125# 6 X 1.0 X 10' X X
115 50 50 FP11CLC 5 6 X 16.5 - 125# 6 X 1.0 X 10' X X
120 53 50 FP11CLC 5 6 X 16.5 - 125# 6 X 1.0 X 10' X X
125 55 50 FP11CLC 5 6 X 16.5 - 125# 6 X 1.0 X 10' X X
130 58 60 FP11CLC 5 6 X 16.5 - 125# 6 X 1.0 X 10' X X
135 61 60 FP11CLC 5 6 X 16.5 - 250# 6 X 1.0 X 10' X X
140 64 60 FP11CLC 5 6 X 16.5 - 250# 6 X 1.0 X 10' X X
145 63 60 FP11CLC 6 6 X 16.5 - 250# 6 X 1.0 X 10' X X
150 66 60 FP11CLC 6 6 X 16.5 - 250# 6 X 1.0 X 10' X X
155 68 60 FP11CLC 6 6 X 16.5 - 250# 6 X 1.0 X 10' X X
160 69 60 FP11CLC 6 6 X 16.5 - 250# 6 X 1.0 X 10' X X
165 76 75 FP11CLC 6 6 X 16.5 - 250# 6 X 1.19 X 10' X X
170 77 75 FP11CLC 6 6 X 16.5 - 250# 6 X 1.19 X 10' X X
175 77 75 FP11CLC 7 6 X 16.5 - 250# 6 X 1.19 X 10' X X
180 80 75 FP11CLC 7 6 X 16.5 - 250# 6 X 1.19 X 10' X X
185 83 75 FP11CLC 7 6 X 16.5 - 250# 6 X 1.19 X 10' X X
190 84 75 FP11CLC 7 6 X 16.5 - 250# 6 X 1.19 X 10' X X
195 85 75 FP11CLC 7 6 X 16.5 - 250# 6 X 1.19 X 10' X X
200 87 100 FP11CLC 7 6 X 16.5 - 250# 6 X 1.19 X 10' X X
205 91 100 FP11CLC 8 6 X 16.5 - 250# 6 X 1.19 X 10' X X

CONTINUED ON FOLLOWING PAGE

 TO CALCULATE PUMP RATED PRESSURE, REFER TO FP2.4 PG.1. PRESSURE SHOWN IS BOWL PRESSURE ONLY.

ALL PRICES ARE SUBJECT TO PROVISIONS SET FORTH IN OUR LATEST PRICES SUBJECT TO CHANGE WITHOUT NOTICE.
BUSINESS & PRICE POLICY, FP0.1, PAGES 11 THROUGH 14.

FP 2.4
PAGE 104 VERTICAL TURBINE MOTOR DRIVEN
PERFORMANCE RATINGS
FEB 2018

SUPERSEDES ALL PREVIOUS ISSUES


500 GPM

BOWL MAX MOTOR
PUMP SIZE STAGES DISCHARGE COLUMN UL FM
PSI BHP HP
210 93 100 FP11CLC 8 6 X 16.5 - 250# 6 X 1.19 X 10' X X
215 97 100 FP11CLC 8 6 X 16.5 - 250# 6 X 1.19 X 10' X X
220 99 100 FP11CLC 8 6 X 16.5 - 250# 6 X 1.19 X 10' X X
225 100 100 FP11CLC 8 6 X 16.5 - 250# 6 X 1.19 X 10' X X
230 99 100 FP11CLC 9 6 X 16.5 - 250# 6 X 1.19 X 10' X X
235 100 100 FP11CLC 9 6 X 16.5 - 250# 6 X 1.19 X 10' X X
240 107 100 FP11CLC 9 6 X 16.5 - 250# 6 X 1.19 X 10' X X
245 112 100 FP11CLC 9 6 X 16.5 - 250# 6 X 1.19 X 10' X X
250 114 100 FP11CLC 9 6 X 16.5 - 250# 6 X 1.19 X 10' X X
256 115 100 FP11CLC 9 6 X 16.5 - 250# 6 X 1.19 X 10' X X

500 GPM – 50 Hz

MAX MOTOR
BOWL PSI PUMP SIZE STAGES DISCHARGE COLUMN UL FM
BHP HP
55 26 25 FP11CHC 3 6 X 16.5 - 125# 6 X 1.0 X 10' X X
60 28 25 FP11CHC 3 6 X 16.5 - 125# 6 X 1.0 X 10' X X
65 31 30 FP11CHC 3 6 X 16.5 - 125# 6 X 1.0 X 10' X X
70 32 30 FP11CHC 4 6 X 16.5 - 125# 6 X 1.0 X 10' X X
75 36 40 FP11CHC 4 6 X 16.5 - 125# 6 X 1.0 X 10' X X
80 38 40 FP11CHC 4 6 X 16.5 - 125# 6 X 1.0 X 10' X X
85 41 40 FP11CHC 4 6 X 16.5 - 125# 6 X 1.0 X 10' X X
90 42 40 FP11CHC 5 6 X 16.5 - 125# 6 X 1.0 X 10' X X
95 44 40 FP11CHC 5 6 X 16.5 - 125# 6 X 1.18 X 10' X X
100 46 40 FP11CHC 5 6 X 16.5 - 125# 6 X 1.18 X 10' X X
105 49 50 FP11CHC 6 6 X 16.5 - 125# 6 X 1.18 X 10' X X
110 52 50 FP11CHC 6 6 X 16.5 - 125# 6 X 1.18 X 10' X X
115 54 50 FP11CHC 6 6 X 16.5 - 125# 6 X 1.18 X 10' X X
120 57 50 FP11CHC 6 6 X 16.5 - 125# 6 X 1.18 X 10' X X
125 59 60 FP11CHC 6 6 X 16.5 - 125# 6 X 1.18 X 10' X X
130 63 60 FP11CHC 6 6 X 16.5 - 125# 6 X 1.18 X 10' X X

CONTINUED ON FOLLOWING PAGE

 TO CALCULATE PUMP RATED PRESSURE, REFER TO FP2.4 PG.1. PRESSURE SHOWN IS BOWL PRESSURE ONLY.

ALL PRICES ARE SUBJECT TO PROVISIONS SET FORTH IN OUR LATEST PRICES SUBJECT TO CHANGE WITHOUT NOTICE.
BUSINESS & PRICE POLICY, FP0.1, PAGES 11 THROUGH 14.

FP 2.4
VERTICAL TURBINE MOTOR DRIVEN PAGE 105
PERFORMANCE RATINGS
FEB 2018

SUPERSEDES ALL PREVIOUS ISSUES


500 GPM – 50 Hz

MAX MOTOR
BOWL PSI PUMP SIZE STAGES DISCHARGE COLUMN UL FM
BHP HP
135 64 60 FP11CHC 7 6 X 16.5 - 125# 6 X 1.18 X 10' X X
140 66 60 FP11CHC 7 6 X 16.5 - 125# 6 X 1.18 X 10' X X
145 69 60 FP11CHC 7 6 X 16.5 - 125# 6 X 1.18 X 10' X X
150 72 75 FP11CHC 7 6 X 16.5 - 125# 6 X 1.18 X 10' X X
155 76 75 FP11CHC 7 6 X 16.5 - 125# 6 X 1.18 X 10' X X
160 76 75 FP11CHC 8 6 X 16.5 - 250# 6 X 1.18 X 10' X X
165 79 75 FP11CHC 8 6 X 16.5 - 250# 6 X 1.50 X 10' X X
170 82 75 FP11CHC 8 6 X 16.5 - 250# 6 X 1.50 X 10' X X
175 85 75 FP11CHC 8 6 X 16.5 - 250# 6 X 1.50 X 10' X X
180 85 75 FP11CHC 9 6 X 16.5 - 250# 6 X 1.50 X 10' X X
185 86.25 75 FP11CHC 9 6 X 16.5 - 250# 6 X 1.50 X 10' X X
190 91 100 FP11CHC 9 6 X 16.5 - 250# 6 X 1.50 X 10' X X
195 94 100 FP11CHC 9 6 X 16.5 - 250# 6 X 1.50 X 10' X X
200 100 100 FP11CHC 9 6 X 16.5 - 250# 6 X 1.50 X 10' X X
205 97 100 FP11CHC 10 6 X 16.5 - 250# 6 X 1.50 X 10' X X
210 101 100 FP11CHC 10 6 X 16.5 - 250# 6 X 1.50 X 10' X X
215 103 100 FP11CHC 10 6 X 16.5 - 250# 6 X 1.50 X 10' X X
220 109 100 FP11CHC 10 6 X 16.5 - 250# 6 X 1.50 X 10' X X
225 106 100 FP11CHC 11 6 X 16.5 - 250# 6 X 1.50 X 10' X X
230 111 100 FP11CHC 11 6 X 16.5 - 250# 6 X 1.50 X 10' X X
235 113 100 FP11CHC 11 6 X 16.5 - 250# 6 X 1.50 X 10' X X
240 117 125 FP11CHC 11 6 X 16.5 - 250# 6 X 1.50 X 10' X X
245 122 125 FP11CHC 11 6 X 16.5 - 250# 6 X 1.50 X 10' X X
250 118 125 FP11CHC 12 6 X 16.5 - 250# 6 X 1.50 X 10' X X
255 123 125 FP11CHC 12 6 X 16.5 - 250# 6 X 1.50 X 10' X X
260 126 125 FP11CHC 12 6 X 16.5 - 250# 6 X 1.50 X 10' X X
265 130 125 FP11CHC 12 6 X 16.5 - 250# 6 X 1.50 X 10' X X
270 133 125 FP11CHC 12 6 X 16.5 - 250# 6 X 1.50 X 10' X X

 TO CALCULATE PUMP RATED PRESSURE, REFER TO FP2.4 PG.1. PRESSURE SHOWN IS BOWL PRESSURE ONLY.

ALL PRICES ARE SUBJECT TO PROVISIONS SET FORTH IN OUR LATEST PRICES SUBJECT TO CHANGE WITHOUT NOTICE.
BUSINESS & PRICE POLICY, FP0.1, PAGES 11 THROUGH 14.

FP 2.4
PAGE 106 VERTICAL TURBINE MOTOR DRIVEN
PERFORMANCE RATINGS
FEB 2018

SUPERSEDES ALL PREVIOUS ISSUES


750 GPM

BOWL MAX MOTOR
PUMP SIZE STAGES DISCHARGE COLUMN UL FM
PSI BHP HP
71 45 40 FP11CHC 3 6 X 16.5 - 125# 6 X 1.0 X 10' X X
75 46 40 FP11CHC 3 6 X 16.5 - 125# 6 X 1.0 X 10' X X
80 53 50 FP11CHC 3 6 X 16.5 - 125# 6 X 1.0 X 10' X X
85 57 50 FP11CHC 3 6 X 16.5 - 125# 6 X 1.0 X 10' X X
90 57.5 50 FP11CHC 3 6 X 16.5 - 125# 6 X 1.0 X 10' X X
95 57.5 50 FP11CHC 4 6 X 16.5 - 125# 6 X 1.0 X 10' X X
100 66 60 FP11CHC 4 6 X 16.5 - 125# 6 X 1.0 X 10' X X
105 68 60 FP11CHC 4 6 X 16.5 - 125# 6 X 1.0 X 10' X X
110 69 60 FP11CHC 4 6 X 16.5 - 125# 6 X 1.18 X 10' X X
115 78 75 FP11CHC 4 6 X 16.5 - 125# 6 X 1.18 X 10' X X
120 81 75 FP11CHC 4 6 X 16.5 - 125# 6 X 1.18 X 10' X X
125 80 75 FP11CHC 5 6 X 16.5 - 125# 6 X 1.18 X 10' X X
130 85 75 FP11CHC 5 6 X 16.5 - 125# 6 X 1.18 X 10' X X
135 86 75 FP11CHC 5 6 X 16.5 - 125# 6 X 1.18 X 10' X X
140 86.2 75 FP11CHC 5 6 X 16.5 - 125# 6 X 1.18 X 10' X X
145 97 100 FP11CHC 5 6 X 16.5 - 125# 6 X 1.18 X 10' X X
150 99 100 FP11CHC 5 6 X 16.5 - 125# 6 X 1.18 X 10' X X
155 100 100 FP11CHC 5 6 X 16.5 - 250# 6 X 1.18 X 10' X X
160 99 100 FP11CHC 6 6 X 16.5 - 250# 6 X 1.18 X 10' X X
165 100 100 FP11CHC 6 6 X 16.5 - 250# 6 X 1.18 X 10' X X
170 113 100 FP11CHC 6 6 X 16.5 - 250# 6 X 1.18 X 10' X X
175 114 100 FP11CHC 6 6 X 16.5 - 250# 6 X 1.18 X 10' X X
180 115 100 FP11CHC 6 6 X 16.5 - 250# 6 X 1.18 X 10' X X
185 124 125 FP11CHC 6 6 X 16.5 - 250# 6 X 1.18 X 10' X X
190 115 100 FP11CHC 7 6 X 16.5 - 250# 6 X 1.18 X 10' X X
195 128 125 FP11CHC 7 6 X 16.5 - 250# 6 X 1.18 X 10' X X
200 133 125 FP11CHC 7 6 X 16.5 - 250# 6 X 1.18 X 10' X X
205 139 125 FP11CHC 7 6 X 16.5 - 250# 6 X 1.50 X 10' X X
210 141 125 FP11CHC 7 6 X 16.5 - 250# 6 X 1.50 X 10' X X

CONTINUED ON FOLLOWING PAGE

 TO CALCULATE PUMP RATED PRESSURE, REFER TO FP2.4 PG.1. PRESSURE SHOWN IS BOWL PRESSURE ONLY.

ALL PRICES ARE SUBJECT TO PROVISIONS SET FORTH IN OUR LATEST PRICES SUBJECT TO CHANGE WITHOUT NOTICE.
BUSINESS & PRICE POLICY, FP0.1, PAGES 11 THROUGH 14.

FP 2.4
VERTICAL TURBINE MOTOR DRIVEN PAGE 107
PERFORMANCE RATINGS
FEB 2018

SUPERSEDES ALL PREVIOUS ISSUES


750 GPM

BOWL MAX MOTOR
PUMP SIZE STAGES DISCHARGE COLUMN UL FM
PSI BHP HP
215 142 125 FP11CHC 7 6 X 16.5 - 250# 6 X 1.50 X 10' X X
220 142 125 FP11CHC 8 6 X 16.5 - 250# 6 X 1.50 X 10' X X
225 143 125 FP11CHC 8 6 X 16.5 - 250# 6 X 1.50 X 10' X X
230 143.7 125 FP11CHC 8 6 X 16.5 - 250# 6 X 1.50 X 10' X X
235 158 150 FP11CHC 8 6 X 16.5 - 250# 6 X 1.50 X 10' X X
240 162 150 FP11CHC 8 6 X 16.5 - 250# 6 X 1.50 X 10' X X
245 165 150 FP11CHC 8 6 X 16.5 - 250# 6 X 1.50 X 10' X X
250 164 150 FP11CHC 9 6 X 16.5 - 250# 6 X 1.50 X 10' X X
255 166 150 FP11CHC 9 6 X 16.5 - 250# 6 X 1.50 X 10' X X
260 168 150 FP11CHC 9 6 X 16.5 - 250# 6 X 1.50 X 10' X X
265 171 150 FP11CHC 9 6 X 16.5 - 250# 6 X 1.50 X 10' X X
270 172.5 150 FP11CHC 9 6 X 16.5 - 250# 6 X 1.50 X 10' X X
275 182 200 FP11CHC 9 6 X 16.5 - 250# 6 X 1.50 X 10' X X
280 185 200 FP11CHC 9 6 X 16.5 - 250# 6 X 1.50 X 10' X X
285 190 200 FP11CHC 10 6 X 16.5 - 250# 6 X 1.50 X 10' X X
290 194 200 FP11CHC 10 6 X 16.5 - 250# 6 X 1.50 X 10' X X
295 197 200 FP11CHC 10 6 X 16.5 - 250# 6 X 1.50 X 10' X X
300 198 200 FP11CHC 10 6 X 16.5 - 250# 6 X 1.50 X 10' X X
305 199 200 FP11CHC 10 6 X 16.5 - 250# 6 X 1.50 X 10' X X
310 200 200 FP11CHC 10 6 X 16.5 - 250# 6 X 1.50 X 10' X X
315 206 200 FP11CHC 10 6 X 16.5 - 250# 6 X 1.50 X 10' X X

 TO CALCULATE PUMP RATED PRESSURE, REFER TO FP2.4 PG.1. PRESSURE SHOWN IS BOWL PRESSURE ONLY.

ALL PRICES ARE SUBJECT TO PROVISIONS SET FORTH IN OUR LATEST PRICES SUBJECT TO CHANGE WITHOUT NOTICE.
BUSINESS & PRICE POLICY, FP0.1, PAGES 11 THROUGH 14.

FP 2.4
PAGE 108 VERTICAL TURBINE MOTOR DRIVEN
PERFORMANCE RATINGS
FEB 2018

SUPERSEDES ALL PREVIOUS ISSUES


750 GPM – 50 Hz

MAX MOTOR
BOWL PSI PUMP SIZE STAGES DISCHARGE COLUMN UL FM
BHP HP
41 26 25 FP12CHC 2 6 X 16.5 - 125# 6 X 1.00 X 10' X X
45 30 30 FP12CHC 2 6 X 16.5 - 125# 6 X 1.00 X 10' X X
50 34.5 30 FP12CHC 2 6 X 16.5 - 125# 6 X 1.00 X 10' X X
55 34.5 30 FP12CHC 3 6 X 16.5 - 125# 6 X 1.00 X 10' X X
60 39 40 FP12CHC 3 6 X 16.5 - 125# 6 X 1.00 X 10' X X
65 44 40 FP12CHC 3 6 X 16.5 - 125# 6 X 1.00 X 10' X X
70 48 50 FP12CHC 3 6 X 16.5 - 125# 6 X 1.00 X 10' X X
75 52 50 FP12CHC 3 6 X 16.5 - 125# 6 X 1.00 X 10' X X
80 53 50 FP12CHC 4 6 X 16.5 - 125# 6 X 1.18 X 10' X X
85 57 50 FP12CHC 4 6 X 16.5 - 125# 6 X 1.18 X 10' X X
90 61 60 FP12CHC 4 6 X 16.5 - 125# 6 X 1.18 X 10' X X
95 66 60 FP12CHC 4 6 X 16.5 - 125# 6 X 1.18 X 10' X X
100 68 60 FP12CHC 4 6 X 16.5 - 125# 6 X 1.18 X 10' X X
105 68 60 FP12CHC 5 6 X 16.5 - 125# 6 X 1.18 X 10' X X
110 74 75 FP12CHC 5 6 X 16.5 - 125# 6 X 1.18 X 10' X X
120 84 75 FP12CHC 5 6 X 16.5 - 125# 6 X 1.18 X 10' X X
125 85 75 FP12CHC 5 6 X 16.5 - 125# 6 X 1.18 X 10' X X
130 86 75 FP12CHC 6 6 X 16.5 - 125# 6 X 1.18 X 10' X X
135 91 100 FP12CHC 6 6 X 16.5 - 250# 6 X 1.50 X 10' X X
140 96 100 FP12CHC 6 6 X 16.5 - 250# 6 X 1.50 X 10' X X
145 100 100 FP12CHC 6 6 X 16.5 - 250# 6 X 1.50 X 10' X X
150 104 100 FP12CHC 6 6 X 16.5 - 250# 6 X 1.50 X 10' X X
155 104 100 FP12CHC 7 6 X 16.5 - 250# 6 X 1.50 X 10' X X
160 108 100 FP12CHC 7 6 X 16.5 - 250# 6 X 1.50 X 10' X X
165 112 100 FP12CHC 7 6 X 16.5 - 250# 6 X 1.50 X 10' X X
170 115 100 FP12CHC 7 6 X 16.5 - 250# 6 X 1.50 X 10' X X
175 115 100 FP12CHC 8 6 X 16.5 - 250# 6 X 1.50 X 10' X X
180 121 125 FP12CHC 8 6 X 16.5 - 250# 6 X 1.50 X 10' X X
185 126 125 FP12CHC 8 6 X 16.5 - 250# 6 X 1.50 X 10' X X
190 131 125 FP12CHC 8 6 X 16.5 - 250# 6 X 1.50 X 10' X X

CONTINUED ON FOLLOWING PAGE

 TO CALCULATE PUMP RATED PRESSURE, REFER TO FP2.4 PG.1. PRESSURE SHOWN IS BOWL PRESSURE ONLY.

ALL PRICES ARE SUBJECT TO PROVISIONS SET FORTH IN OUR LATEST PRICES SUBJECT TO CHANGE WITHOUT NOTICE.
BUSINESS & PRICE POLICY, FP0.1, PAGES 11 THROUGH 14.

FP 2.4
VERTICAL TURBINE MOTOR DRIVEN PAGE 109
PERFORMANCE RATINGS
FEB 2018

SUPERSEDES ALL PREVIOUS ISSUES


750 GPM – 50 Hz

MAX MOTOR
BOWL PSI PUMP SIZE STAGES DISCHARGE COLUMN UL FM
BHP HP
195 136 125 FP12CHC 8 6 X 16.5 - 250# 6 X 1.50 X 10' X X
200 139 125 FP12CHC 8 6 X 16.5 - 250# 6 X 1.50 X 10' X X
205 139 125 FP12CHC 9 6 X 16.5 - 250# 6 X 1.50 X 10' X X
210 143.75 125 FP12CHC 9 6 X 16.5 - 250# 6 X 1.50 X 10' X X
215 143.75 125 FP12CHC 10 6 X 16.5 - 250# 6 X 1.50 X 10' X X
220 143.75 125 FP12CHC 10 6 X 16.5 - 250# 6 X 1.50 X 10' X X
225 153 150 FP12CHC 10 6 X 16.5 - 250# 6 X 1.50 X 10' X X
230 157 150 FP12CHC 10 6 X 16.5 - 250# 6 X 1.50 X 10' X X
235 161 150 FP12CHC 10 6 X 16.5 - 250# 6 X 1.50 X 10' X X
240 167 150 FP12CHC 10 6 X 16.5 - 250# 6 X 1.50 X 10' X X
245 170 150 FP12CHC 10 6 X 16.5 - 250# 6 X 1.50 X 10' X X
250 172.5 150 FP12CHC 10 6 X 16.5 - 250# 6 X 1.50 X 10' X X
255 172.5 150 FP12CHC 11 6 X 16.5 - 250# 6 X 1.50 X 10' X X
260 171 150 FP12CHC 12 6 X 16.5 - 250# 6 X 1.50 X 10' X X
265 172.5 150 FP12CHC 12 6 X 16.5 - 250# 6 X 1.50 X 10' X X
270 182 200 FP12CHC 12 6 X 16.5 - 250# 6 X 1.50 X 10' X X
275 182 200 FP12CHC 12 6 X 16.5 - 250# 6 X 1.50 X 10' X X
280 192 200 FP12CHC 12 6 X 16.5 - 250# 6 X 1.50 X 10' X X
285 192 200 FP12CHC 12 6 X 16.5 - 250# 6 X 1.50 X 10' X X
290 200 200 FP12CHC 12 6 X 16.5 - 250# 6 X 1.50 X 10' X X
295 204 200 FP12CHC 12 6 X 16.5 - 250# 6 X 1.50 X 10' X X
300 208 200 FP12CHC 12 6 X 16.5 - 250# 6 X 1.68 X 10' X

 TO CALCULATE PUMP RATED PRESSURE, REFER TO FP2.4 PG.1. PRESSURE SHOWN IS BOWL PRESSURE ONLY.

ALL PRICES ARE SUBJECT TO PROVISIONS SET FORTH IN OUR LATEST PRICES SUBJECT TO CHANGE WITHOUT NOTICE.
BUSINESS & PRICE POLICY, FP0.1, PAGES 11 THROUGH 14.

FP 2.4
PAGE 110 VERTICAL TURBINE MOTOR DRIVEN
PERFORMANCE RATINGS
FEB 2018

SUPERSEDES ALL PREVIOUS ISSUES


1000 GPM

BOWL MAX MOTOR
PUMP SIZE STAGES DISCHARGE COLUMN UL FM
PSI BHP HP
85 69 60 FP12CHC 3 6 X 16.5 - 125# 6 X 1.18 X 10' X X
90 78 75 FP12CHC 3 6 X 16.5 - 125# 6 X 1.18 X 10' X X
95 83 75 FP12CHC 3 6 X 16.5 - 125# 6 X 1.18 X 10' X X
100 88 100 FP12CHC 3 6 X 16.5 - 125# 6 X 1.18 X 10' X X
105 94 100 FP12CHC 3 6 X 16.5 - 125# 6 X 1.18 X 10' X X
110 86.2 75 FP12CHC 4 6 X 16.5 - 125# 6 X 1.18 X 10' 0 X
115 95 100 FP12CHC 4 6 X 16.5 - 125# 6 X 1.18 X 10' X X
120 100 100 FP12CHC 4 6 X 16.5 - 125# 6 X 1.18 X 10' X X
125 108 100 FP12CHC 4 6 X 16.5 - 125# 6 X 1.18 X 10' X X
130 113 100 FP12CHC 4 6 X 16.5 - 125# 6 X 1.18 X 10' X X
135 118 125 FP12CHC 4 6 X 16.5 - 125# 6 X 1.18 X 10' X X
140 125 125 FP12CHC 4 6 X 16.5 - 125# 6 X 1.50 X 10' X X
145 115 100 FP12CHC 5 6 X 16.5 - 250# 6 X 1.18 X 10' X X
150 130 125 FP12CHC 5 6 X 16.5 - 250# 6 X 1.50 X 10' X X
155 135 125 FP12CHC 5 6 X 16.5 - 250# 6 X 1.50 X 10' X X
160 138 125 FP12CHC 5 6 X 16.5 - 250# 6 X 1.50 X 10' X X
165 143.7 125 FP12CHC 5 6 X 16.5 - 250# 6 X 1.50 X 10' X X
170 140 125 FP12CHC 6 6 X 16.5 - 250# 6 X 1.50 X 10' X X
175 143.7 125 FP12CHC 6 6 X 16.5 - 250# 6 X 1.50 X 10' X X
180 156 150 FP12CHC 6 6 X 16.5 - 250# 6 X 1.50 X 10' X X
185 159 150 FP12CHC 6 6 X 16.5 - 250# 6 X 1.50 X 10' X X
190 166 150 FP12CHC 6 6 X 16.5 - 250# 6 X 1.50 X 10' X X
195 167 150 FP12CHC 6 6 X 16.5 - 250# 6 X 1.50 X 10' X X
200 168 150 FP12CHC 6 6 X 16.5 - 250# 6 X 1.50 X 10' X X
205 168 150 FP12CHC 7 6 X 16.5 - 250# 6 X 1.50 X 10' X X
210 172.5 150 FP12CHC 7 6 X 16.5 - 250# 6 X 1.50 X 10' X X
215 185 200 FP12CHC 7 6 X 16.5 - 250# 6 X 1.50 X 10' X X
220 189 200 FP12CHC 7 6 X 16.5 - 250# 6 X 1.50 X 10' X X

CONTINUED ON FOLLOWING PAGE

 TO CALCULATE PUMP RATED PRESSURE, REFER TO FP2.4 PG.1. PRESSURE SHOWN IS BOWL PRESSURE ONLY.

ALL PRICES ARE SUBJECT TO PROVISIONS SET FORTH IN OUR LATEST PRICES SUBJECT TO CHANGE WITHOUT NOTICE.
BUSINESS & PRICE POLICY, FP0.1, PAGES 11 THROUGH 14.

FP 2.4
VERTICAL TURBINE MOTOR DRIVEN PAGE 111
PERFORMANCE RATINGS
FEB 2018

SUPERSEDES ALL PREVIOUS ISSUES


1000 GPM

BOWL MAX MOTOR
PUMP SIZE STAGES DISCHARGE COLUMN UL FM
PSI BHP HP
225 193 200 FP12CHC 7 6 X 16.5 - 250# 6 X 1.50 X 10' X X
230 196 200 FP12CHC 7 6 X 16.5 - 250# 6 X 1.50 X 10' X X
235 198 200 FP12CHC 7 6 X 16.5 - 250# 6 X 1.50 X 10' X X
240 200 200 FP12CHC 7 6 X 16.5 - 250# 6 X 1.50 X 10' X X
245 200 200 FP12CHC 8 6 X 16.5 - 250# 6 X 1.50 X 10' X X
250 211 200 FP12CHC 8 6 X 16.5 - 250# 6 X 1.50 X 10' X X
255 215 200 FP12CHC 8 6 X 16.5 - 250# 6 X 1.50 X 10' X X
260 225 200 FP12CHC 8 6 X 16.5 - 250# 6 X 1.50 X 10' X X
265 227 200 FP12CHC 8 6 X 16.5 - 250# 6 X 1.50 X 10' X X
270 230 200 FP12CHC 8 6 X 16.5 - 250# 6 X 1.50 X 10' X X
275 227 200 FP12CHC 9 6 X 16.5 - 250# 6 X 1.50 X 10' X X
280 230 200 FP12CHC 9 6 X 16.5 - 250# 6 X 1.50 X 10' X X
285 240 250 FP12CHC 9 6 X 16.5 - 250# 6 X 1.50 X 10' X X
290 247 250 FP12CHC 9 6 X 16.5 - 250# 6 X 1.68 X 10' X X
295 249 250 FP12CHC 9 6 X 16.5 - 250# 6 X 1.68 X 10' X X
300 247 250 FP12CHC 10 6 X 16.5 - 250# 6 X 1.68 X 10' X X
305 249 250 FP12CHC 10 6 X 16.5 - 250# 6 X 1.68 X 10' X X
310 270 250 FP12CHC 9 6 X 16.5 - 250# 6 X 1.68 X 10' X X
315 276 250 FP12CHC 9 6 X 16.5 - 250# 6 X 1.68 X 10' X X
320 270 250 FP12CHC 10 6 X 16.5 - 250# 6 X 1.68 X 10' X X
325 276 250 FP12CHC 10 6 X 16.5 - 250# 6 X 1.68 X 10' X X
330 285 250 FP12CHC 10 6 X 16.5 - 250# 6 X 1.68 X 10' X X
335 287.5 250 FP12CHC 10 6 X 16.5 - 250# 6 X 1.68 X 10' X X
340 292 300 FP12CHC 10 6 X 16.5 - 250# 6 X 1.68 X 10' X X
345 299 300 FP12CHC 10 6 X 16.5 - 250# 6 X 1.68 X 10' X X
350 300 300 FP12CHC 10 6 X 16.5 - 250# 6 X 1.68 X 10' X X
352 300 300 FP12CHC 10 6 X 16.5 - 250# 6 X 1.68 X 10' X X

 TO CALCULATE PUMP RATED PRESSURE, REFER TO FP2.4 PG.1. PRESSURE SHOWN IS BOWL PRESSURE ONLY.

ALL PRICES ARE SUBJECT TO PROVISIONS SET FORTH IN OUR LATEST PRICES SUBJECT TO CHANGE WITHOUT NOTICE.
BUSINESS & PRICE POLICY, FP0.1, PAGES 11 THROUGH 14.

FP 2.4
PAGE 112 VERTICAL TURBINE MOTOR DRIVEN
PERFORMANCE RATINGS
FEB 2018

SUPERSEDES ALL PREVIOUS ISSUES


1000 GPM – 50 Hz

MAX MOTOR
BOWL PSI PUMP SIZE STAGES DISCHARGE COLUMN UL FM
BHP HP
40 41 40 FP14RJHC 2 8 X 16.5 - 125# 8 X 1.00 X 10' X X
45 46 40 FP14RJHC 2 8 X 16.5 - 125# 8 X 1.00 X 10' X X
50 53 50 FP14RJHC 2 8 X 16.5 - 125# 8 X 1.18 X 10' X X
55 59 60 FP14RJHC 2 8 X 16.5 - 125# 8 X 1.18 X 10' X X
60 61 60 FP14RJHC 3 8 X 16.5 - 125# 8 X 1.18 X 10' X X
65 66 60 FP14RJHC 3 8 X 16.5 - 125# 8 X 1.18 X 10' X X
70 72 75 FP14RJHC 3 8 X 16.5 - 125# 8 X 1.18 X 10' X X
75 79 75 FP14RJHC 3 8 X 16.5 - 125# 8 X 1.18 X 10' X X
80 81 75 FP14RJHC 4 8 X 16.5 - 125# 8 X 1.50 X 10' X X
85 86 75 FP14RJHC 4 8 X 16.5 - 125# 8 X 1.50 X 10' X X
90 93 100 FP14RJHC 4 8 X 16.5 - 125# 8 X 1.50 X 10' X X
95 99 100 FP14RJHC 4 8 X 16.5 - 125# 8 X 1.50 X 10' X X
100 105 100 FP14RJHC 4 8 X 16.5 - 125# 8 X 1.50 X 10' X X
105 112 100 FP14RJHC 4 8 X 16.5 - 125# 8 X 1.50 X 10' X X
110 118 125 FP14RJHC 4 8 X 16.5 - 125# 8 X 1.50 X 10' X X
115 118 125 FP14RJHC 5 8 X 16.5 - 125# 8 X 1.50 X 10' X X
120 126 125 FP14RJHC 5 8 X 16.5 - 125# 8 X 1.50 X 10' X X
125 135 125 FP14RJHC 5 8 X 16.5 - 125# 8 X 1.50 X 10' X X
130 138 125 FP14RJHC 5 8 X 16.5 - 125# 8 X 1.50 X 10' X X
135 143 125 FP14RJHC 5 8 X 16.5 - 125# 8 X 1.50 X 10' X X
140 151 150 FP14RJHC 5 8 X 16.5 - 125# 8 X 1.50 X 10' X X
145 155 150 FP14RJHC 5 8 X 16.5 - 125# 8 X 1.50 X 10' X X
150 160 150 FP14RJHC 5 8 X 16.5 - 125# 8 X 1.50 X 10' X X

 TO CALCULATE PUMP RATED PRESSURE, REFER TO FP2.4 PG.1. PRESSURE SHOWN IS BOWL PRESSURE ONLY.

ALL PRICES ARE SUBJECT TO PROVISIONS SET FORTH IN OUR LATEST PRICES SUBJECT TO CHANGE WITHOUT NOTICE.
BUSINESS & PRICE POLICY, FP0.1, PAGES 11 THROUGH 14.

FP 2.4
VERTICAL TURBINE MOTOR DRIVEN PAGE 113
PERFORMANCE RATINGS
FEB 2018

SUPERSEDES ALL PREVIOUS ISSUES


1500 GPM

BOWL MAX MOTOR
PUMP SIZE STAGES DISCHARGE COLUMN UL FM
PSI BHP HP
52 68 60 FP14RJHC 2 8 X 16.5 - 125# 8 X 1.18 X 10' X X
55 69 60 FP14RJHC 2 8 X 16.5 - 125# 8 X 1.18 X 10' X X
60 80 75 FP14RJHC 2 8 X 16.5 - 125# 8 X 1.18 X 10' X X
65 86.2 75 FP14RJHC 2 8 X 16.5 - 125# 8 X 1.18 X 10' X X
70 95 100 FP14RJHC 2 8 X 16.5 - 125# 8 X 1.18 X 10' X X
75 105 100 FP14RJHC 2 8 X 16.5 - 125# 8 X 1.18 X 10' X X
80 105 100 FP14RJHC 3 8 X 16.5 - 125# 8 X 1.18 X 10' X X
85 113 100 FP14RJHC 3 8 X 16.5 - 125# 8 X 1.18 X 10' X X
90 115 100 FP14RJHC 3 8 X 16.5 - 125# 8 X 1.18 X 10' X X
95 124 125 FP14RJHC 3 8 X 16.5 - 125# 8 X 1.18 X 10' X X
100 138 125 FP14RJHC 3 8 X 16.5 - 125# 8 X 1.50 X 10' X X
105 143.75 125 FP14RJHC 3 8 X 16.5 - 125# 8 X 1.50 X 10' X X
110 150 150 FP14RJHC 3 8 X 16.5 - 125# 8 X 1.50 X 10' X X
115 162 150 FP14RJHC 3 8 X 16.5 - 125# 8 X 1.50 X 10' X X
120 165 150 FP14RJHC 4 8 X 16.5 - 125# 8 X 1.50 X 10' X X
125 168 150 FP14RJHC 4 8 X 16.5 - 125# 8 X 1.50 X 10' X X
130 172.5 150 FP14RJHC 4 8 X 16.5 - 125# 8 X 1.50 X 10' X X
135 172.5 150 FP14RJHC 5 8 X 16.5 - 125# 8 X 1.50 X 10' X X
140 192 200 FP14RJHC 4 8 X 16.5 - 125# 8 X 1.50 X 10' X X
145 200 200 FP14RJHC 4 8 X 16.5 - 125# 8 X 1.50 X 10' X X
150 200 200 FP14RJHC 5 8 X 16.5 - 250# 8 X 1.50 X 10' X X
155 211 200 FP14RJHC 4 8 X 16.5 - 250# 8 X 1.50 X 10' X X
160 227 200 FP14RJHC 4 8 X 16.5 - 250# 8 X 1.50 X 10' X X
165 227 200 FP14RJHC 5 8 X 16.5 - 250# 8 X 1.50 X 10' X X
170 230 200 FP14RJHC 5 8 X 16.5 - 250# 8 X 1.50 X 10' X X
175 230 200 FP14RJHC 6 8 X 16.5 - 250# 8 X 1.50 X 10' X X
180 240 250 FP14RJHC 5 8 X 16.5 - 250# 8 X 1.50 X 10' X X

CONTINUED ON FOLLOWING PAGE

 TO CALCULATE PUMP RATED PRESSURE, REFER TO FP2.4 PG.1. PRESSURE SHOWN IS BOWL PRESSURE ONLY.

ALL PRICES ARE SUBJECT TO PROVISIONS SET FORTH IN OUR LATEST PRICES SUBJECT TO CHANGE WITHOUT NOTICE.
BUSINESS & PRICE POLICY, FP0.1, PAGES 11 THROUGH 14.

FP 2.4
PAGE 114 VERTICAL TURBINE MOTOR DRIVEN
PERFORMANCE RATINGS
FEB 2018

SUPERSEDES ALL PREVIOUS ISSUES


1500 GPM

BOWL MAX MOTOR
PUMP SIZE STAGES DISCHARGE COLUMN UL FM
PSI BHP HP
185 249 250 FP14RJHC 5 8 X 16.5 - 250# 8 X 1.50 X 10' X X
190 249 250 FP14RJHC 5 8 X 16.5 - 250# 8 X 1.50 X 10' X X
195 270 250 FP14RJHC 5 8 X 16.5 - 250# 8 X 1.68 X 10' X X
200 270 250 FP14RJHC 5 8 X 16.5 - 250# 8 X 1.68 X 10' X X
205 276 250 FP14RJHC 6 8 X 16.5 - 250# 8 X 1.68 X 10' X X
210 287.5 250 FP14RJHC 6 8 X 16.5 - 250# 8 X 1.68 X 10' X X
215 285 250 FP14RJHC 6 8 X 16.5 - 250# 8 X 1.68 X 10' X X
220 287.5 250 FP14RJHC 6 8 X 16.5 - 250# 8 X 1.68 X 10' X X
225 299 300 FP14RJHC 7 8 X 16.5 - 250# 8 X 1.68 X 10' X X
230 326 300 FP14RJHC 6 8 X 16.5 - 250# 8 X 1.68 X 10' X X
235 326 300 FP14RJHC 6 8 X 16.5 - 250# 8 X 1.68 X 10' X X
240 336 300 FP14RJHC 6 8 X 16.5 - 250# 8 X 1.68 X 10' X X
245 345 300 FP14RJHC 6 8 X 16.5 - 250# 8 X 1.68 X 10' X X
250 345 300 FP14RJHC 7 8 X 16.5 - 250# 8 X 1.68 X 10' X X
255 345 300 FP14RJHC 7 8 X 16.5 - 250# 8 X 1.68 X 10' X X
260 365 350 FP14RJHC 7 8 X 16.5 - 250# 8 X 1.68 X 10' X X
265 370 350 FP14RJHC 7 8 X 16.5 - 250# 8 X 1.68 X 10' X X
270 376 350 FP14RJHC 7 8 X 16.5 - 250# 8 X 1.68 X 10' X X
275 383 350 FP14RJHC 7 8 X 16.5 - 250# 8 X 1.93 X 10' X X
280 393 350 FP14RJHC 7 8 X 16.5 - 250# 8 X 1.93 X 10' X X
285 400 350 FP14RJHC 7 8 X 16.5 - 250# 8 X 1.93 X 10' X X
290 405 400 FP14RJHC 7 8 X 16.5 - 250# 8 X 1.93 X 10' X X
295 405 400 FP14RJHC 7 8 X 16.5 - 250# 8 X 1.93 X 10' X X

 TO CALCULATE PUMP RATED PRESSURE, REFER TO FP2.4 PG.1. PRESSURE SHOWN IS BOWL PRESSURE ONLY.

ALL PRICES ARE SUBJECT TO PROVISIONS SET FORTH IN OUR LATEST PRICES SUBJECT TO CHANGE WITHOUT NOTICE.
BUSINESS & PRICE POLICY, FP0.1, PAGES 11 THROUGH 14.

FP 2.4
VERTICAL TURBINE MOTOR DRIVEN PAGE 115
PERFORMANCE RATINGS
FEB 2018

SUPERSEDES ALL PREVIOUS ISSUES


1500 GPM – 50 Hz

MAX MOTOR
BOWL PSI PUMP SIZE STAGES DISCHARGE COLUMN UL FM
BHP HP
40 54 50 FP14RHHC 2 10 X 16.5 - 125# 10 X 1.18 X 10' X X
45 63 60 FP14RHHC 2 10 X 16.5 - 125# 10 X 1.18 X 10' X X
50 72 75 FP14RHHC 2 10 X 16.5 - 125# 10 X 1.18 X 10' X X
55 79 75 FP14RHHC 2 10 X 16.5 - 125# 10 X 1.18 X 10' X X
60 81 75 FP14RHHC 3 10 X 16.5 - 125# 10 X 1.18 X 10' X X
65 90 100 FP14RHHC 3 10 X 16.5 - 125# 10 X 1.18 X 10' X X
70 98 100 FP14RHHC 3 10 X 16.5 - 125# 10 X 1.18 X 10' X X
75 106 100 FP14RHHC 3 10 X 16.5 - 125# 10 X 1.50 X 10' X X
80 115 100 FP14RHHC 4 10 X 16.5 - 125# 10 X 1.50 X 10' X X
85 115 100 FP14RHHC 4 10 X 16.5 - 125# 10 X 1.50 X 10' X X
90 126 125 FP14RHHC 4 10 X 16.5 - 125# 10 X 1.50 X 10' X X
95 134 125 FP14RHHC 4 10 X 16.5 - 125# 10 X 1.50 X 10' X X
100 142 125 FP14RHHC 4 10 X 16.5 - 125# 10 X 1.50 X 10' X X
105 150 150 FP14RHHC 4 10 X 16.5 - 125# 10 X 1.50 X 10' X X
110 159 150 FP14RHHC 4 10 X 16.5 - 125# 10 X 1.50 X 10' X X
115 177 200 FP14RHHC 4 10 X 16.5 - 125# 10 X 1.50 X 10' X X
120 171 150 FP14RHHC 5 10 X 16.5 - 125# 10 X 1.50 X 10' X X
125 180 200 FP14RHHC 5 10 X 16.5 - 250# 10 X 1.68 X 10' X X
130 188 200 FP14RHHC 5 10 X 16.5 - 250# 10 X 1.68 X 10' X X
135 195 200 FP14RHHC 5 10 X 16.5 - 250# 10 X 1.68 X 10' X X
140 206 200 FP14RHHC 5 10 X 16.5 - 250# 10 X 1.68 X 10' X X
145 221 200 FP14RHHC 5 10 X 16.5 - 250# 10 X 1.68 X 10' X X
150 213 200 FP14RHHC 6 10 X 16.5 - 250# 10 X 1.68 X 10' X X
155 221 200 FP14RHHC 6 10 X 16.5 - 250# 10 X 1.68 X 10' X X
160 232 250 FP14RHHC 6 10 X 16.5 - 250# 10 X 1.68 X 10' X X
165 238 250 FP14RHHC 6 10 X 16.5 - 250# 10 X 1.68 X 10' X X
170 252 250 FP14RHHC 6 10 X 16.5 - 250# 10 X 1.68 X 10' X X
175 248 250 FP14RHHC 7 10 X 16.5 - 250# 10 X 1.68 X 10' X X
180 258 250 FP14RHHC 7 10 X 16.5 - 250# 10 X 1.68 X 10' X X
185 268 250 FP14RHHC 7 10 X 16.5 - 250# 10 X 1.68 X 10' X X
190 278 250 FP14RHHC 7 10 X 16.5 - 250# 10 X 1.68 X 10' X X

CONTINUED ON FOLLOWING PAGE

 TO CALCULATE PUMP RATED PRESSURE, REFER TO FP2.4 PG.1. PRESSURE SHOWN IS BOWL PRESSURE ONLY.

ALL PRICES ARE SUBJECT TO PROVISIONS SET FORTH IN OUR LATEST PRICES SUBJECT TO CHANGE WITHOUT NOTICE.
BUSINESS & PRICE POLICY, FP0.1, PAGES 11 THROUGH 14.

FP 2.4
PAGE 116 VERTICAL TURBINE MOTOR DRIVEN
PERFORMANCE RATINGS
FEB 2018

SUPERSEDES ALL PREVIOUS ISSUES


1500 GPM – 50 Hz

MAX MOTOR
BOWL PSI PUMP SIZE STAGES DISCHARGE COLUMN UL FM
BHP HP
195 287.5 250 FP14RHHC 7 10 X 16.5 - 250# 10 X 1.68 X 10' X X
200 299 300 FP14RHHC 7 10 X 16.5 - 250# 10 X 1.68 X 10' X X
205 305 300 FP14RHHC 7 10 X 16.5 - 250# 10 X 1.68 X 10' X X
210 305 300 FP14RHHC 7 10 X 16.5 - 250# 10 X 1.68 X 10' X X

2000 GPM

BOWL MAX MOTOR
PUMP SIZE STAGES DISCHARGE COLUMN UL FM
PSI BHP HP
55 92 100 FP14RHHC 2 10 X 16.5 - 125# 10 X 1.18 X 10' X X
60 102 100 FP14RHHC 2 10 X 16.5 - 125# 10 X 1.18 X 10' X X
65 114 100 FP14RHHC 2 10 X 16.5 - 125# 10 X 1.18 X 10' X X
70 125 125 FP14RHHC 2 10 X 16.5 - 125# 10 X 1.18 X 10' X X
75 136 125 FP14RHHC 2 10 X 16.5 - 125# 10 X 1.50 X 10' X X
80 148 150 FP14RHHC 2 10 X 16.5 - 125# 10 X 1.50 X 10' X X
85 142 125 FP14RHHC 3 10 X 16.5 - 125# 10 X 1.50 X 10' X X
90 152 150 FP14RHHC 3 10 X 16.5 - 125# 10 X 1.50 X 10' X X
95 164 150 FP14RHHC 3 10 X 16.5 - 125# 10 X 1.50 X 10' X X
100 172.5 150 FP14RHHC 3 10 X 16.5 - 125# 10 X 1.50 X 10' X X
105 188 200 FP14RHHC 3 10 X 16.5 - 125# 10 X 1.50 X 10' X X
110 200 200 FP14RHHC 3 10 X 16.5 - 125# 10 X 1.50 X 10' X X
115 195 200 FP14RHHC 4 10 X 16.5 - 125# 10 X 1.50 X 10' X X
120 200 200 FP14RHHC 4 10 X 16.5 - 125# 10 X 1.50 X 10' X X
125 220 200 FP14RHHC 4 10 X 16.5 - 125# 10 X 1.50 X 10' X X
130 229 200 FP14RHHC 4 10 X 16.5 - 125# 10 X 1.50 X 10' X X
135 230 200 FP14RHHC 4 10 X 16.5 - 125# 10 X 1.50 X 10' X X
140 230 200 FP14RHHC 5 10 X 16.5 - 250# 10 X 1.50 X 10' X X

CONTINUED ON FOLLOWING PAGE

 TO CALCULATE PUMP RATED PRESSURE, REFER TO FP2.4 PG.1. PRESSURE SHOWN IS BOWL PRESSURE ONLY.

ALL PRICES ARE SUBJECT TO PROVISIONS SET FORTH IN OUR LATEST PRICES SUBJECT TO CHANGE WITHOUT NOTICE.
BUSINESS & PRICE POLICY, FP0.1, PAGES 11 THROUGH 14.

FP 2.4
VERTICAL TURBINE MOTOR DRIVEN PAGE 117
PERFORMANCE RATINGS
FEB 2018

SUPERSEDES ALL PREVIOUS ISSUES


2000 GPM

MAX MOTOR
BOWL PSI PUMP SIZE STAGES DISCHARGE COLUMN UL FM
BHP HP
145 250 250 FP14RHHC 4 10 X 16.5 - 250# 10 X 1.50 X 10' X X
150 250 250 FP14RHHC 5 10 X 16.5 - 250# 10 X 1.50 X 10' X X
155 284 250 FP14RHHC 4 10 X 16.5 - 250# 10 X 1.68 X 10' X X
160 276 250 FP14RHHC 5 10 X 16.5 - 250# 10 X 1.68 X 10' X X
165 287.5 250 FP14RHHC 5 10 X 16.5 - 250# 10 X 1.68 X 10' X X
170 280 250 FP14RHHC 6 10 X 16.5 - 250# 10 X 1.68 X 10' X X
175 285 250 FP14RHHC 6 10 X 16.5 - 250# 10 X 1.68 X 10' X X
180 287.5 250 FP14RHHC 6 10 X 16.5 - 250# 10 X 1.68 X 10' X X
185 340 300 FP14RHHC 5 10 X 16.5 - 250# 10 X 1.68 X 10' X X
190 345 300 FP14RHHC 5 10 X 16.5 - 250# 10 X 1.68 X 10' X X
195 340 300 FP14RHHC 6 10 X 16.5 - 250# 10 X 1.68 X 10' X X
200 345 300 FP14RHHC 6 10 X 16.5 - 250# 10 X 1.68 X 10' X X
205 345 300 FP14RHHC 6 10 X 16.5 - 250# 10 X 1.68 X 10' X X
210 350 350 FP14RHHC 6 10 X 16.5 - 250# 10 X 1.68 X 10' X X
215 383 350 FP14RHHC 6 10 X 16.5 - 250# 10 X 1.68 X 10' X X
220 392 350 FP14RHHC 6 10 X 16.5 - 250# 10 X 1.93 X 10' X X
225 393 350 FP14RHHC 6 10 X 16.5 - 250# 10 X 1.93 X 10' X X
230 402.5 350 FP14RHHC 6 10 X 16.5 - 250# 10 X 1.93 X 10' X X
235 434 400 FP14RHHC 6 10 X 16.5 - 250# 10 X 1.93 X 10' X X
240 443 400 FP14RHHC 6 10 X 16.5 - 250# 10 X 1.93 X 10' X X
245 450 400 FP14RHHC 6 10 X 16.5 - 250# 10 X 1.93 X 10' X X
250 478 450 FP14RHHC 6 10 X 16.5 - 250# 10 X 1.93 X 10' X X
255 480 450 FP14RHHC 6 10 X 16.5 - 250# 10 X 1.93 X 10' X X
257 480 450 FP14RHHC 6 10 X 16.5 - 250# 10 X 1.93 X 10' 0 X

 TO CALCULATE PUMP RATED PRESSURE, REFER TO FP2.4 PG.1. PRESSURE SHOWN IS BOWL PRESSURE ONLY.

ALL PRICES ARE SUBJECT TO PROVISIONS SET FORTH IN OUR LATEST PRICES SUBJECT TO CHANGE WITHOUT NOTICE.
BUSINESS & PRICE POLICY, FP0.1, PAGES 11 THROUGH 14.

FP 2.4
PAGE 118 VERTICAL TURBINE MOTOR DRIVEN
PERFORMANCE RATINGS
FEB 2018

SUPERSEDES ALL PREVIOUS ISSUES


2500 GPM

BOWL MAX MOTOR
PUMP SIZE STAGES DISCHARGE COLUMN UL FM
PSI BHP HP
77 164 150 FP16DMC 2 10 X 16.5 - 125# 10 X 1.50 X 10' X X
80 168 150 FP16DMC 2 10 X 16.5 - 125# 10 X 1.50 X 10' X X
85 172.5 150 FP16DMC 2 10 X 16.5 - 125# 10 X 1.50 X 10' X X
90 194 200 FP16DMC 2 10 X 16.5 - 125# 10 X 1.50 X 10' X X
95 200 200 FP16DMC 2 10 X 16.5 - 125# 10 X 1.50 X 10' X X
100 221 200 FP16DMC 2 10 X 16.5 - 125# 10 X 1.50 X 10' X X
105 230 200 FP16DMC 2 10 X 16.5 - 125# 10 X 1.50 X 10' X X
110 230 200 FP16DMC 3 10 X 16.5 - 125# 10 X 1.50 X 10' X X
115 240 250 FP16DMC 3 10 X 16.5 - 125# 10 X 1.50 X 10' X X
120 249 250 FP16DMC 3 10 X 16.5 - 125# 10 X 1.50 X 10' X X
125 258 250 FP16DMC 3 10 X 16.5 - 125# 10 X 1.50 X 10' X X
130 276 250 FP16DMC 3 10 X 16.5 - 125# 10 X 1.68 X 10' X X
135 285 250 FP16DMC 3 10 X 16.5 - 250# 10 X 1.68 X 10' X X
140 292 300 FP16DMC 3 10 X 16.5 - 250# 10 X 1.68 X 10' X X
145 307 300 FP16DMC 3 10 X 16.5 - 250# 10 X 1.68 X 10' X X
150 332 300 FP16DMC 3 10 X 16.5 - 250# 10 X 1.68 X 10' X X
155 345 300 FP16DMC 3 10 X 16.5 - 250# 10 X 1.68 X 10' X X
160 345 300 FP16DMC 3 10 X 16.5 - 250# 10 X 1.68 X 10' X X
165 375 350 FP16DMC 3 10 X 16.5 - 250# 10 X 1.68 X 10' X X
170 392 350 FP16DMC 3 10 X 16.5 - 250# 10 X 1.68 X 10' X X
175 400 350 FP16DMC 3 10 X 16.5 - 250# 10 X 1.68 X 10' X X
180 405 400 FP16DMC 3 10 X 16.5 - 250# 10 X 1.68 X 10' X X
186 410 400 FP16DMC 3 10 X 16.5 - 250# 10 X 1.68 X 10' X X

 TO CALCULATE PUMP RATED PRESSURE, REFER TO FP2.4 PG.1. PRESSURE SHOWN IS BOWL PRESSURE ONLY.

ALL PRICES ARE SUBJECT TO PROVISIONS SET FORTH IN OUR LATEST PRICES SUBJECT TO CHANGE WITHOUT NOTICE.
BUSINESS & PRICE POLICY, FP0.1, PAGES 11 THROUGH 14.

FP 2.4
VERTICAL TURBINE MOTOR DRIVEN PAGE 119
PERFORMANCE RATINGS
FEB 2018

SUPERSEDES ALL PREVIOUS ISSUES


3000 GPM

BOWL MAX MOTOR
PUMP SIZE STAGES DISCHARGE COLUMN UL FM
PSI BHP HP
103 287.5 250 FP18DMC 2 12 X 24.5 - 125# 12 X 1.68 X 10' X X
105 287.5 250 FP18DMC 2 12 X 24.5 - 125# 12 X 1.68 X 10' X X
110 313 300 FP18DMC 2 12 X 24.5 - 125# 12 X 1.68 X 10' X X
115 326 300 FP18DMC 2 12 X 24.5 - 125# 12 X 1.68 X 10' X X
120 345 300 FP18DMC 2 12 X 24.5 - 125# 12 X 1.68 X 10' X X
125 365 350 FP18DMC 2 12 X 24.5 - 125# 12 X 1.93 X 10' X X
130 383 350 FP18DMC 2 12 X 24.5 - 125# 12 X 1.93 X 10' X X
135 393 350 FP18DMC 2 12 X 24.5 - 125# 12 X 1.93 X 10' X X
140 419 400 FP18DMC 2 12 X 24.5 - 125# 12 X 1.93 X 10' X X
144 448 400 FP18DMC 2 12 X 24.5 - 125# 12 X 1.93 X 10' X X

3500 GPM

BOWL MAX MOTOR
PUMP SIZE STAGES DISCHARGE COLUMN UL FM
PSI BHP HP
94 277 250 FP18DMC 2 12 X 24.5 - 125# 12 X 1.68 X 10' X X
100 291 300 FP18DMC 2 12 X 24.5 - 125# 12 X 1.68 X 10' X X
105 310 300 FP18DMC 2 12 X 24.5 - 125# 12 X 1.68 X 10' X X
110 331 300 FP18DMC 2 12 X 24.5 - 125# 12 X 1.68 X 10' X X
115 348 350 FP18DMC 2 12 X 24.5 - 125# 12 X 1.68 X 10' X X
120 371 350 FP18DMC 2 12 X 24.5 - 125# 12 X 1.93 X 10' X X
125 388 350 FP18DMC 2 12 X 24.5 - 125# 12 X 1.93 X 10' X X
130 413 400 FP18DMC 2 12 X 24.5 - 125# 12 X 1.93 X 10' X X
135 438 400 FP18DMC 2 12 X 24.5 - 125# 12 X 1.93 X 10' X X
141 450 400 FP18DMC 2 12 X 24.5 - 125# 12 X 1.93 X 10' X X

 TO CALCULATE PUMP RATED PRESSURE, REFER TO FP2.4 PG.1. PRESSURE SHOWN IS BOWL PRESSURE ONLY.

ALL PRICES ARE SUBJECT TO PROVISIONS SET FORTH IN OUR LATEST PRICES SUBJECT TO CHANGE WITHOUT NOTICE.
BUSINESS & PRICE POLICY, FP0.1, PAGES 11 THROUGH 14.

FP 2.4
PAGE 120 VERTICAL TURBINE MOTOR DRIVEN
PERFORMANCE RATINGS
FEB 2018

SUPERSEDES ALL PREVIOUS ISSUES


4000 GPM

BOWL MAX MOTOR
PUMP SIZE STAGES DISCHARGE COLUMN UL FM
PSI BHP HP
106 365 350 FP18DHC 2 12 X 24.5 - 125# 12 X 1.68 X 10' X X
110 382 350 FP18DHC 2 12 X 24.5 - 125# 12 X 1.68 X 10' X X
115 399 350 FP18DHC 2 12 X 24.5 - 125# 12 X 1.68 X 10' X X
120 416 400 FP18DHC 2 12 X 24.5 - 125# 12 X 1.93 X 10' X X
125 437 400 FP18DHC 2 12 X 24.5 - 125# 12 X 1.93 X 10' X X
130 450 400 FP18DHC 2 12 X 24.5 - 125# 12 X 1.93 X 10' X X
135 470 450 FP18DHC 2 12 X 24.5 - 125# 12 X 1.93 X 10' X X
141 480 450 FP18DHC 2 12 X 24.5 - 125# 12 X 1.93 X 10' X X

4500 GPM

BOWL MAX MOTOR
PUMP SIZE STAGES DISCHARGE COLUMN UL FM
PSI BHP HP
56 223 200 FP20EHC 1 14 X 24.5 - 250# 14 X 1.68 X 10' X X
60 230 200 FP20EHC 1 14 X 24.5 - 250# 14 X 1.68 X 10' X X
65 264 250 FP20EHC 1 14 X 24.5 - 250# 14 X 1.68 X 10' X X
70 287 250 FP20EHC 1 14 X 24.5 - 250# 14 X 1.68 X 10' X X
73 300 300 FP20EHC 1 14 X 24.5 - 250# 14 X 1.68 X 10' X X
114 450 400 FP20EHC 2 14 X 24.5 - 250# 14 X 1.93 X 10' X X
120 460 400 FP20EHC 2 14 X 24.5 - 250# 14 X 1.93 X 10' X X
125 495 450 FP20EHC 2 14 X 24.5 - 250# 14 X 1.93 X 10' X X
129 528 500 FP20EHC 2 14 X 24.5 - 250# 14 X 1.93 X 10' X X

 TO CALCULATE PUMP RATED PRESSURE, REFER TO FP2.4 PG.1. PRESSURE SHOWN IS BOWL PRESSURE ONLY.

ALL PRICES ARE SUBJECT TO PROVISIONS SET FORTH IN OUR LATEST PRICES SUBJECT TO CHANGE WITHOUT NOTICE.
BUSINESS & PRICE POLICY, FP0.1, PAGES 11 THROUGH 14.

FP 2.4
VERTICAL TURBINE MOTOR DRIVEN PAGE 121
PERFORMANCE RATINGS
FEB 2018

SUPERSEDES ALL PREVIOUS ISSUES


5000 GPM

BOWL MAX MOTOR
PUMP SIZE STAGES DISCHARGE COLUMN UL FM
PSI BHP HP
55 249 250 FP20EHC 1 14 X 24.5 - 250# 14 X 1.68 X 10' X X
60 250 250 FP20EHC 1 14 X 24.5 - 250# 14 X 1.68 X 10' X X
65 283 250 FP20EHC 1 14 X 24.5 - 250# 14 X 1.68 X 10' X X
72 300 300 FP20EHC 1 14 X 24.5 - 250# 14 X 1.68 X 10' X X
111 460 400 FP20EHC 2 14 X 24.5 - 250# 14 X 1.93 X 10' X X
115 480 450 FP20EHC 2 14 X 24.5 - 250# 14 X 1.93 X 10' X X
120 500 450 FP20EHC 2 14 X 24.5 - 250# 14 X 1.93 X 10' X X
126 517.5 450 FP20EHC 2 14 X 24.5 - 250# 14 X 1.93 X 10' X X

 TO CALCULATE PUMP RATED PRESSURE, REFER TO FP2.4 PG.1. PRESSURE SHOWN IS BOWL PRESSURE ONLY.

ALL PRICES ARE SUBJECT TO PROVISIONS SET FORTH IN OUR LATEST PRICES SUBJECT TO CHANGE WITHOUT NOTICE.
BUSINESS & PRICE POLICY, FP0.1, PAGES 11 THROUGH 14.
FIRE PUMP SYSTEMS A-C Fire Pump Systems FP 2.4
General Information and Page 1
Engineering Data
Vertical Turbine Fire Pump
February, 1996
Supersedes 5/95 issue

ENG. DATA
FP 2.4 A-C Fire Pump Systems FIRE PUMP SYSTEMS
Page 2 General Information and
Engineering Data
Vertical Turbine Fire Pump
August 2002

PSI 49-139 140-206 54-130 131-256 71-150

Pump Size 10WALC 10WALC 11CLC 11CLC 11CHC

Approval Flow Rate 250 250 500 500 750

DISCHARGE HEAD
DESIGN DATA
Discharge Flange Rating 125 250 125 250 125

Head Material Cast Iron Cast Iron Cast Iron Cast Iron Cast Iron

Max Working Pressure (PSIG) 175 psi 400 psi 175 psi 400 psi 175 psi

Minimum Submergence Above Bell 17.3 17.3 23.0 23.0 29.0

STUFFING BOX DATA


Minimum 1.00 1.00 1.00 1.00 1.00
Shaft O.D.
Maximum 1.00 1.00 1.00 1.19 1.19

Packing: No. Rings/Size Square 5/.38 5/.38 5/.38 5/.38 5/.38

IMPELLER DESIGN DATA


No. of Vanes 5 5 5 5 8
Inlet Area 8.60 8.60 15.60 15.60 15.60

Maximum Diameter 7.31 7.31 6.63 6.63 7.13

Minimum Diameter 6.50 6.50 8.13 8.13 8.13

Maximum Sphere 0.45 0.45 0.68 0.68 0.68

WR2 for Max. Dia. (Lbs-Ft2) Per Stage 0.58 0.58 0.89 0.89 0.89

Wear Ring Clearance-Diametral .015 in. ±.001 .015 in. ±.001 .016 in. ±.002 .016 in. ±.002 .016 in. ±.002

No. of Stages Min/Max 3/7 7/9 3/5 5/9 3/5

SHAFT AND BEARING DATA


Shaft Diameter (Bowl) 1.50 1.50 1.69 1.69 1.69

Maximum Shaft Span (Brg. to Brg.) 120 120 120 120 120

All dimensions are in inches


FIRE PUMP SYSTEMS A-C Fire Pump Systems FP 2.4
General Information and Page 3
Engineering Data
Vertical Turbine Fire Pump
August 2002

PSI 151-323 85-140 141-352 50-145 146-295

Pump Size 11CHC 12CHC 12CHC 14RJHC 14RJHC

Approval Flow Rate 750 1000 1000 1500 1500

DISCHARGE HEAD
DESIGN DATA
Discharge Flange Rating 250 125 250 125 250

Head Material Cast Iron Cast Iron Cast Iron Cast Iron Cast Iron

Max Working Pressure (PSIG) 400 psi 175 psi 400 psi 175 psi 400 psi

Minimum Submergence Above Bell 29.0 34.0 34.0 42.0 42.0

STUFFING BOX DATA


Minimum 1.19 1.19 1.19 1.19 1.50
Shaft O.D.
Maximum 1.50 1.19 1.50 1.50 1.93

Packing: No. Rings/Size Square 5/.38 5/.38 5/.38 5/.38 5/.38

IMPELLER DESIGN DATA


No. of Vanes 8 8 8 8 8
Inlet Area 15.60 20.43 20.43 30.24 30.24

Maximum Diameter 7.13 7.75 7.75 7.75 7.75

Minimum Diameter 8.13 8.69 8.69 9.82 9.82

Maximum Sphere 0.68 0.73 0.73 0.98 0.98

WR2 for Max. Dia. (Lbs-Ft2) Per Stage 0.89 1.65 1.65 3.12 3.12

Wear Ring Clearance-Diametral .016 in. ± .002 .016 in. ± .002 .016 in. ± .002 .016 in. ± .002 .016 in. ± .002

No. of Stages Min/Max 5/10 3/5 5/10 2/4 4/7

SHAFT AND BEARING DATA


Shaft Diameter (Bowl) 1.69 1.69 1.69 1.94 1.94

Maximum Shaft Span (Brg. to Brg.) 120 120 120 120 120

All dimensions are in inches


FP 2.4 A-C Fire Pump Systems FIRE PUMP SYSTEMS
Page 4 General Information and
Engineering Data
Vertical Turbine Fire Pump
August 2002

PSI 55-135 136-257 77-145 146-186 101-147

Pump Size 14RHHC 14RHHC 16DMC 16DMC 18DMC

Approval Flow Rate 2000 2000 2500 2500 3000

DISCHARGE HEAD
DESIGN DATA
Discharge Flange Rating 125 250 125 250 125

Head Material Cast Iron Cast Iron Cast Iron Cast Iron Cast Iron

Max Working Pressure (PSIG) 175 psi 400 psi 175 psi 400 psi 175 psi

Minimum Submergence Above Bell 50.0 50.0 50.0 50.0 87.0

STUFFING BOX DATA


Minimum 1.18 1.50 1.50 1.68 1.68
Shaft O.D.
Maximum 1.50 1.93 1.68 1.68 1.93

Packing: No. Rings/Size Square 5/.38 5/.38 5/.38 5/.38 5/.38

IMPELLER DESIGN DATA


No. of Vanes 7 7 7 7 7
Inlet Area 36.06 36.06 40.37 40.37 49.00

Maximum Diameter 8.00 8.00 9.31 9.31 10.63

Minimum Diameter 9.88 9.88 11.63 11.63 12.75

Maximum Sphere 1.18 1.18 0.72 0.72 0.75

WR2 for Max. Dia. (Lbs-Ft2) Per Stage 5.05 5.05 9.65 9.65 13.3

Wear Ring Clearance-Diametral .016 in. ± .002 .016 in. ± .002 .020 in. ± .002 .020 in. ± .002 .020 in. ± .002

No. of Stages Min/Max 2/4 4/6 2/3 3/3 2/2

SHAFT AND BEARING DATA


Shaft Diameter (Bowl) 2.19 2.19 2.44 2.44 2.69

Maximum Shaft Span (Brg. to Brg.) 120 120 120 120 120

All dimensions are in inches


FIRE PUMP SYSTEMS A-C Fire Pump Systems FP 2.4
General Information and Page 5
Engineering Data
Vertical Turbine Fire Pump
August 2002

PSI 94-141 105-141 56-129 55-126

Pump Size 18DMC 18DHC 20EHC 20EHC

Approval Flow Rate 3500 4000 4500 5000

DISCHARGE HEAD
DESIGN DATA
Discharge Flange Rating 125 125 150 150

Head Material Cast Iron Cast Iron Fab. Steel Fab. Steel

Max Working Pressure (PSIG) 175 psi 175 psi 285 psi 285 psi

Minimum Submergence Above Bell 87.0 221.0 71.0 71.0

STUFFING BOX DATA


Minimum 1.68 1.68 1.68 1.68
Shaft O.D.
Maximum 1.93 1.93 1.93 1.93

Packing: No. Rings/Size Square 5/.38 5/.38 5/.38 5/.38

IMPELLER DESIGN DATA


No. of Vanes 7 7 6 6
Inlet Area 49.00 49.00 80.70 80.70

Maximum Diameter 10.63 10.63 11.62 11.62

Minimum Diameter 12.75 12.69 13.31 13.31

Maximum Sphere 0.75 0.75 1.75 1.75

WR2 for Max. Dia. (Lbs-Ft2) Per Stage 13.3 13.3 17.16 17.16

Wear Ring Clearance-Diametral .020 in. ± .002 .020 in. ± .002 .021 in. ± .003 .021 in. ± .003

No. of Stages Min/Max 2/2 2/2 1/2 1/2

SHAFT AND BEARING DATA


Shaft Diameter (Bowl) 2.69 2.69 2.44 2.44

Maximum Shaft Span (Brg. to Brg.) 120 120 120 120

All dimensions are in inches


FP 2.4 A-C Fire Pump Systems FIRE PUMP SYSTEMS
Page 6 Lineshaft Turbine – Water Lube –
Cast Head – Threaded Column –
Motor/Gear Driver VHS
August 2002

Discharge Head Assembly


Material Material
Item Description Code Description
608 Headshaft 2227 SST 416
604 Adjusting Nut 2130 Brass
730 GIB Key 2242 Steel
622 Slinger 5121 Rubber Sbr
618 Stuffing Box Split Gland 1193 Aluminum Bronze
600 Discharge Head 1003 Cast Iron
616 Stuffing Box 1003 Cast Iron
617 Stuffing Box Bearing 1109 Bronze
735 Stuffing Box Stud Nut 2229 SST 316
739 Stuffing Box Stud 2229 SST 316
779 Stuffing Box Gasket 5136 Rubber Sbr
620 Packing 5026 Carbon Non-Asbestos
621 Lantern Ring 6359 Teflon (PTFE)
637 Hanger Flange 1003 Cast Iron

Column & Lineshaft Assembly


Material Material
Item Description Code Description
642 Column Pipe 6501 Black Pipe
645 Column Coupling 6501 Black Pipe
646 Lineshaft 2227 SST 416
656 Lineshaft Bearing 5121 Rubber Sbr
649 Lineshaft Coupling 2265 SST 416
652 Bearing Retainer 1102 Bronze

Bowl Assembly
Material Material
Item Description Code Description
660 Bowl Shaft 2227 SST 416
661 Discharge Bowl 1003 Cast Iron
791 Discharge Bearing 1109 Bronze
670 Intermediate Bowl 6911 Coated Cast Iron
672 Inter Bowl Bearing 1109 Bronze
673 Impeller 1102 Bronze
677 Impeller Taper Lock 2242 Steel
680 Wear Rings 1117 Aluminum Bronze
760 Hex Bolt 2298 Grade 8
692 Sand Collar 1109 Bronze
688 Suction Bell 1003 Cast Iron
690 Suction Bearing 1109 Bronze
698 Suction Strainer 1102 Bronze
743 O-Ring 5302 Rubber Nbr
747 Plug 1046 Mal Iron
FIRE PUMP SYSTEMS A-C Fire Pump Systems FP 2.4
Lineshaft Turbine – Water Lube – Page 7
Fab Head – Flanged Column –
Motor/Gear Driver VHS
August 2002

Discharge Head Assembly


Material Material
Item Description Code Description
608 Headshaft 2227 SST 416
604 Adjusting Nut 2130 Brass
730 GIB Key 2242 Steel
622 Slinger 5121 Rubber Sbr
618 Stuffing Box Split Gland 1193 Aluminum Bronze
600 Discharge Head 9645 Fab Steel
616 Stuffing Box 1003 Cast Iron
617 Stuffing Box Bearing 1109 Bronze
739 Stuffing Box Stud 2229 SST 316
735 Stuffing Box Stud Nut 2229 SST 316
779 Stuffing Box Gasket 5136 Rubber Sbr
620 Packing 5026 Carbon Non-Asbestos
621 Lantern Ring 6359 Teflon (PTFE)

Column & Lineshaft Assembly


Material Material
Item Description Code Description
642 Column Pipe 9645 Fab Steel Pipe
646 Lineshaft 2227 SST 416
656 Lineshaft Bearing 6108 Steel/Rubber Sbr
649 Lineshaft Coupling 2265 SST 416

Bowl Assembly
Material Material
Item Description Code Description
660 Bowl Shaft 2227 SST 416
670 Intermediate Bowl 5853 Coated Cast Iron
672 Inter Bowl Bearing 1109 Bronze
673 Keyed Impeller 1102 Bronze
680 Wear Ring 1117 Aluminum Bronze
760 Hex Bolt 2298 Grade 8
692 Sand Collar 1109 Bronze
688 Suction Bell 1003 Cast Iron
690 Suction Bearing 1109 Bronze
698 Suction Strainer 1102 Bronze
725 Thrust Ring 2217 SST 316
743 O-Ring 5302 Rubber Nbr
747 Plug 1046 Mal Iron
A-C FIRE PUMP SYSTEMS FP 2.4
Dimensions – Vertical Turbine Page 401
Accessories
August, 2007

Supersedes all previous issues

AUTOMATIC AIR RELEASE VALVE


A-C FIRE PUMP SYSTEMS FP 2.7
Dimensions – Vertical Turbine Sole Page 403
Plate
October 07

Supersedes all previous issues

SOLE PLATE

(4) PLACES

DISCHARGE WT
FLOW A B C D E F
FLANGE (lb)
250 4 18.00 (457.2) 16.00 (406.4) 0.63 (16.002) 12.00 (304.8) 19.00 (482.6) 95
500
750 6 20.00 (508) 18.00 (457.2) 0.88 (22.352) 14.50 (368.3) 21.00 (533.4) 115
1000
1500 8 22.00 (558.8) 19.00 (482.6) 0.88 (22.352) 14.50 (368.3) 23.00 (584.2) 140
2000
10 26.00 (660.4) 23.00 (584.2) 0.75 (19.05) 0.88 (22.352) 18.00 (457.2) 27.00 (685.8) 195
2500
3000
3500 12 34.00 (863.6) 31.00 (787.4) 1.00 (25.4) 24.00 (609.6) 35.00 (889) 330
4000
4500
14 38.75 (984.25) 36.00 (914.4) 1.25 (31.75) 30.00 (762) 39.75 (1009.65) 430
5000

DIMENSIONS IN INCHES (mm)

You might also like