Professional Documents
Culture Documents
Fence
Type 2 Cable comes out of stainless steel
conduit to connect to fence.
16 mm² bonding
to BS-EN-50525-3-41 G/Y
c/w cable sheath and
insulation rise in hot dipped
galvanized steel conduit
SECTION No6
Ø32mm hot dipped galvanized
steel conduit rise to connect to fence
GRP Earthing enclosure c/w disconnetion links for
testing and maintenance to be installed on the wall
C.H. - 0+793.5
Ø50mm hot dipped galvanized
steel conduit drops to connect to
5.60
PE ducting in the ground
95mm² earth cable buried in
the ground runs in Ø63mm
160 PE Duct
4.84
300 350
installed in concrete manhole
TSB ACCESS ROAD
300
Exothermic welded connection
410
4.20 to join cable and rod
437
1890
1178
4800
1.87
528
Earth rod
Min. 90° bend for ducting length has been sized
duct connects to back of GRP according to BS7430 and soil
enclosure resistity tests.
Ø63mm PE ducting cast in the
Cable ladder 400x85mm concrete slab and retaining Earth rod
wall. 95mm² general earth electrode tip
cable rises to outside in the PE
ducting
Cable tray
300x60mm
Conduit wall fixings to be spaced
at a max of 1m
Fire Cladding
-9
Exothermic Welding to Structure Reinforcement
PK=0+793,500
FOR CONSTRUCTION
CHECKED / ELABORATED APPROVED
VERSION
M&E DESIGN LEADER PROJECT MANAGER
SIGNATURE
DATE 24/10/2018
C01
ELECTRICAL SERVICES
GIBRALTAR AIRPORT AND EARTHING AND LPS INSTALLATION
FRONTIER ACCESS ROAD SECTIONS
C.H. 0+793.5 ME-01-203 C01