North American (Note) DP2-20F(-P) DP2-40N DP2-60N - DP2-21F(-P) DP2-41N DP2-61N DP2-22F(-P) DP2-42N DP2-62N or coupling to the pressure
Item European - DP2-40E DP2-60E - - DP2-41E DP2-61E - DP2-42E DP2-62E port, hold the hexagonal
Type of pressure Gauge pressure part of the pressure port
Rated pressure range 0 to -101.3kPa 0 to 100.0kPa 0 to 1.000MPa with a 12mm spanner and
Set pressure range 5.1 to -101.3kPa -5.0 to 100.0kPa -0.050 to 1.000MPa make sure that the
Pressure withstandability 490kPa 1.47MPa tightening torque is 9.8N・m or less. Also, in order to
Applicable fluid Non-corrosive gas prevent any leakage, wind a sealing tape on the
Selectable units kgf/cm2, bar, psi, mmHg, inHg kgf/cm2, bar, psi coupling when connecting.
Supply voltage 12 to 24V DC +10 However, sealing tape is not required for North
-15 % Ripple P-P 10% or less
Current consumption 50mA or less
American type using NPTF 1/8 coupling. (Sealing tape
is required if NPT 1/8 coupling is used.)
Asian <North American (Standard PNP output type), European>
North American (Standard NPN output, Flat, IP67 types) PNP open-collector transistor Flat type, Light weight type
Comparative outputs NPN open-collector transistor ・Maximum source current: 100mA
Comparative Output 1 ・Maximum sink current: 100mA ・Applied voltage: 30V DC or less ● Setting of pressure lead direction
Comparative Output 2 ・Applied voltage: 30V DC or less (between comparative output and 0V) (between comparative output and +V) ・ The pressure lead direction can be changed by dismantling
・Residual voltage: 1V or less (at 100mA sink current) ・Residual voltage: 2V or less (at 100mA source current) the pressure port attachment and changing the mounting
0.4V or less (at 16mA sink current) direction. The tightening torque of the hexagon-socket-head
Output modes
Equipped with 4 types of modes: hysteresis mode, window comparator mode, dual output mode, automatic sensitivity bolt (length 9mm or less) should be 0.29N・m or less.
setting mode (selectable by key operation)
Pressure port attachment
Hysteresis 1 digit (However, variable in hysteresis mode and 2 digits when using psi unit)
Hexagon-socket-
Repeatability Within ±0.2% F.S. ±1 digit head bolts
Response time 2.5ms or less
Main body
Short-circuit protection Incorporated
Output voltage (V)
Sensor mounting bracket Description Function 0 Set Value 1 (P1) Set Value 2 (P2)
MS-DPX (optional) 31/2 digit LED Displays measured pressure, settings, High pressure
① (Positive pressure type)
display (Red) error messages and key-protect status.
High vacuum
Comparative Output 1
<MS-DPX-4> (Vacuum pressure type)
② operation indicator Lights up when Comparative Output 1 is ON.
(Orange) Window comparator mode ( )
Comparative Output 2 ● The comparative outputs can be turned ON or OFF by a pressure
Sensor mounting ③ operation indicator Lights up when Comparative Output 2 is ON.
bracket (Green)
which is within the pressure range set by Set Value 1 and Set Value 2.
MS-DPX-4 (optional)
・ In the initial setting mode, pressing Hysteresis Hysteresis
–10
OU
T1
Output 2 OFF
● NPN output type
Color code 7 ERROR MESSAGES 0 Set Value 1 (P1) Set Value 2 (P2)
High pressure
D (Brown) +V ● When an error occurs, take the following corrective action. (Positive pressure type)
(Gray) Analog
1kΩ Error message Cause
Corrective action High vacuum
Sensor circuit
voltage output
Load
Z D1
(Note)
Load + Switch off the power (Vacuum pressure type)
(Black) Comparative Output 1 12 to 24V DC Overcurrent due to
Tr1 +10 supply and check the Automatic sensitivity setting mode ( )
100mA max. - % short-circuit.
ZD2 (White) Comparative Output 2
-15 load.
100mA max. Applied pressure at the pressure ● Using actual objects, if the pressure values for OK objects
Tr2 ZD3 Pressure is being
(Blue) 0V port should be brought to and NG objects are input, then the sensor is automatically
applied during
zero-point adjustment.
atmospheric pressure and zero-point set to the optimum pressure value (mid-value).
Internal circuit Users’ circuit adjustment should be done again.
Hysteresis
Note: The analog voltage output is not incorporated with a Applied pressure exceeds
Vacuum Positive Vacuum Positive
pressure pressure pressure pressure
ON
short-circuit protection circuit. Do not directly connect the upper limit of
type
Comparative
a power supply or a capacitive load. When using the displayable pressure range. Hysteresis: 1 digit
Output 1 OFF
analog voltage output, take care to connect external Applied pressure exceeds 2 digits when using
ON psi unit
equipment of proper input impedance. the lower limit of
type
Comparative
displayable pressure range. Applied pressure should
Also, when a cable extension is used, voltage drop be brought within the Output 2 OFF
due to cable resistance should be taken into account. Applied pressure exceeds rated pressure range.
the lower limit of 0 Set Value 1 (P1) Set Value 2 (P2)
type
Symbols...D: Reverse supply polarity protection diode displayable pressure range. Set Value 3 (P3) High pressure
ZD1, ZD2, ZD3: Surge absorption zener diode Applied pressure exceeds (Positive pressure type)
Tr1, Tr2: NPN output transistor the upper limit of High vacuum
type
0-ADJ
MODE
0-ADJ
MODE
0-ADJ
MODE
: Vacuum pressure type : Positive pressure type
Note: 'MPa' in case of DP2-22□, DP2-42□ and DP2-62□.
11 SETTING ③ Setting of pressure values
● If key-protect has been set, make sure to release For the case when output mode is set to either the hysteresis For the case when the output mode is set to automatic
key-protect before operating the keys. (Please refer to mode ( ), window comparator mode ( ) or dual output mode ( ). sensitivity setting mode ( )
' 15 KEY-PROTECT FUNCTION' for the procedure.) ● [Set Value 1 (P1)] and [Set Value 2 (P2)] of the ● Comparative outputs' [Set Value 1 (P1)], [Set Value 2
● The conditions which are set are stored in an EEPROM. comparative outputs are set. (P2)] and [Set Value 3 (P3)] are set.
Please note that the EEPROM has a life span and its
・The setting of Set Value 2 (P2) with respect to Set Value 1 ・The setting of Set Value 2 (P2) with respect to Set Value 1
guaranteed life is 100,000 write operation cycles.
(P1) can only be towards the high pressure side in case of (P1) can only be towards the high pressure side in case of
Setting procedure the positive pressure type sensor and only towards the high the positive pressure type sensor and only towards the high
vacuum side in case of the vacuum pressure type sensor. vacuum side in case of the vacuum pressure type sensor.
① ② ③
Zero-point Initial Pressure Measurement ・Set Value 1 (P1) and Set Value 2 (P2) can be made common ・Set Value 3 (P3) is automatically set to the mid-value of Set
adjustment setting value setting for all the output modes. However, when a changeover is Value 1 (P1) and Set Value 2 (P2). However, if Set Value 1 (P1)
Adjust Set [Display], Enter Commence made to the automatic sensitivity setting mode, since Set is set to a value on the vacuum pressure side for a positive
zero-point [Output mode], Set Value 1 (P1) measurement Value 3 (P3) has not been set, make sure to carry out the
and [Unit] Set Value 2 (P2) on completion pressure type sensor or to the positive pressure side for a
Set Value 3 (P3) of setting pressure value settings for the automatic sensitivity mode. vacuum pressure type sensor, Set Value 3 (P3) is automatically
set to the mid-value of 'zero' (atmospheric pressure) and Set
① Zero-point adjustment Set to Set Value 1 (P1) set mode
Value 2 (P2). Further, if both, Set Value 1 (P1) and Set Value 2
● The displayed pressure when the pressure port is left DP2-20 -101.3kPa
・In the sensing mode, press key.MODE
(P2) are set to a value on the vacuum pressure side for a
open is adjusted to zero. ・ and Set Value 1 (P1) which positive pressure type sensor or to the positive pressure side
is being set are displayed for a vacuum pressure type sensor, Set Value 3 (P3) is
Set to sensing mode
OUT1 OUT2
DP2-20 -101.3kPa
・The sensor will automatically enter the ・ The figure on the left shows the ・The automatically set Set Value 3 (P3) can be changed manually.
sensing mode when power is supplied. display of a vacuum pressure ・Since display of error messages is not possible during pressure
Displayed
OUT1 OUT2 The figure on the left shows the display type sensor when the pressure value setting in the automatic sensitivity setting mode, make
alternately
when the pressure unit and display are set unit has been set to 'kPa'. sure that the sensor is used within the rated pressure range.
MODE
0-ADJ
DP2-20
to 'kPa' and 'digital display', respectively.
-101.3kPa
DP2-20 -101.3kPa
・Let the pressure port be at atmospheric pressure (i.e., OUT1 OUT2
is being set are displayed
alternately.
MODE
OUT1 OUT2 ously, the increment and decrement keys continuously. Enter Set Value 1 (P1) ・ The figure on the left shows the
MODE
・ is displayed and, when the fingers are display of a vacuum pressure
・ Enter using key and key. Displayed
0-ADJ
DP2-20 -101.3kPa
DP2-20 -101.3kPa
・ If pressure has been applied during zero-point 0-ADJ
MODE
value changes towards the high
adjustment, is displayed when pressure side by 1 digit and if key is OUT1 OUT2
OUT1 OUT2 the keys are pressed. Bring the applied pressed once the set value changes 0-ADJ
MODE
MODE
pressure to atmospheric pressure (i.e., no Displayed
0-ADJ
towards the low pressure side by 1 digit.
applied pressure condition) and carry out the alternately
In case of the vacuum pressure type
zero-point adjustment once again. DP2-20 -101.3kPa
DP2-20 -101.3kPa
pressed once the set value changes pressure range, having created a
comparative outputs are set. towards the low vacuum side by 1 digit. OUT1 OUT2 pressure state which is nearest to the
Set to initial setting mode ・ If key or key is pressed continu- 0-ADJ
MODE
atmospheric pressure, press key.
ously, the set value changes quickly. ・ The pressure value at the time of
DP2-20 -101.3kPa
・In the sensing mode, press key whileMODE
If the set pressure range is exceeded, pressing key is entered as Set
pressing key. Displayed
either (upper limit exceeded) or Value 1 (P1). Set Value 1 (P1) and
OUT1 OUT2
・ Initial setting is displayed. (lower limit exceeded) is displayed. alternately
MODE are displayed alternately.
0-ADJ
・ If sensor is being used for the first DP2-20 -101.3kPa
MODE
DP2-20 -101.3kPa
・In the Set Value 1 (P1) set mode, press 0-ADJ
pressed. key.
MODE 0-ADJ
0-ADJ MODE
Displayed
: kgf/cm 2 : Window : Analog alternately
pressure type pressure type
mode display
: bar : Dual output Enter Set Value 2 (P2)
Positive
mode
・Within the required permissible pressure
OUT1 OUT2
DP2-20 -101.3kPa
MODE
: psi : Automatic
sensitivity OUT1 OUT2
which is nearest to the high pressure
setting mode MODE
end (for a positive pressure type sensor)
: mmHg If the output mode has been set to the window 0-ADJ
Vacuum
comparator mode ( ) in the initial setting mode, Set or the high vacuum end (for a vacuum
Value 1 (P1) and Set Value 2 (P2) should be set with a pressure type sensor), press key.
Displayed
: inHg difference of 3 digits or more. However, when unit is set alternately ・ The pressure value at the time of
to 'psi', the difference should be 6 digits or more. pressing key is entered as Set
Value 2 (P2). Set Value 2 (P2) and
DP2-20 -101.3kPa
DP2-20 -101.3kPa
・ Press key.
MODE MODE
0-ADJ
exceeded, either (upper limit
・The sensor returns to sensing mode DP2-20 -101.3kPa
・Press key.
MODE
exceeded) or (lower limit
after the initial conditions have been set. ・The sensor returns to sensing
exceeded) are displayed and Set
OUT1 OUT2
・Since the initial conditions which mode after Set Value 1 (P1) and
MODE
EEPROM, they are not erased even ・Since the values which have been
set pressure range.
if the power supply is switched off. set are stored in an EEPROM,
・The figure on the left shows the display they are not erased even if the ・ The setting of Set Value 2 (P2)
can be repeated several times in
when the unit and display are set to power supply is switched off.
the Set Value 2 (P2) set mode.
'kPa' and 'digital display', respectively.
13 CONVERSION OF PRESSURE UNITS
● In the DP2 series, the conversion to different units is automatically done on changing the setting of the pressure unit.
Set to Set Value 3 (P3) set mode However, this conversion can also be obtained by multiplying the values by the coefficients given in the following table.
DP2-20 -101.3kPa
・In the Set Value 2 (P2) set mode, press Conversion procedure
key.
MODE
・ For example, if 2kPa is to be expressed in kgf/cm2, since 1kPa=1.01972×10-2kgf/cm2, 2kPa becomes 2×1.01972×10-2
・ and the automatically set Set Value
≒0.020kgf/cm2
OUT1 OUT2
MODE
Digits smaller than the displayed 1MPa 1×103 1 1.01972×10 1×10 1.45038×102 7.50062×103 0.2953×103 9.86923
0-ADJ
digits are discarded.
2
1kgf/cm 9.80665×10 9.80665×10-2 1 9.80665×10-1 1.42234×10 7.35559×102 2.8959×10 9.67841×10-1
In case Set Value 3 (P3) is to be changed
1bar 1×102 1×10-1 1.01972 1 1.45038×10 7.50062×102 2.953×10 9.86923×10-1
The automatically set Set Value 3 (P3) can be manually
changed to a value between Set Value 1 (P1) and Set Value 2
(P2). However Set Value 3 (P3) cannot be set to a value on the 1psi 6.89473 6.89473×10-3 7.03065×10-2 6.89473×10-2 1 5.17147×10 2.036 6.80457×10-2
vacuum pressure side for a positive pressure type sensor or to 1mmHg
the positive pressure side for a vacuum pressure type sensor. 1.33322×10-1 1.33322×10-4 1.35951×10-3 1.33322×10-3 1.93368×10-2 1 3.9370×10-2 1.31579×10-3
(1Torr)
Hysteresis
ON 1inHg 3.3864 3.3864×10-3 3.4531×10-2 3.3864×10-2 0.4912 2.5400×10 1 3.342×10-2
Comparative
Output 1 OFF Hysteresis: 1 digit 1atm 1.01325×102 1.01325×10-1 1.03323 1.01325 1.46960×10 7.60000×102 2.9921×10 1
Changeable
range 2 digits when psi
ON
Comparative unit is used
Output 2 OFF
14 PEAK HOLD & BOTTOM HOLD FUNCTIONS 15 KEY-PROTECT FUNCTION
0 Set Value 1 (P1) Set Value 2 (P2) ● Peak hold and bottom hold functions enable the display ● Key-protect is a function which prevents any
Set Value 3 (P3) High pressure of the peak value (maximum pressure value in case of unintentional change in the conditions which have
(Positive pressure type)
the positive pressure type sensor and maximum vacuum been entered in each setting mode by making the
High vacuum
(Vacuum pressure type) pressure value in case of the vacuum pressure type sensor not to respond to the key operations.
DP2-20 -101.3kPa
・Enter using key and key. sensor) and the bottom value (minimum pressure value Setting of key-protect
・In case of a positive pressure type in case of the positive pressure type sensor and
minimum vacuum pressure value in case of the vacuum DP2-20 -101.3kPa
・ In the sensing mode, press key MODE
sensor, if key is pressed once, the
continuously for about 3 sec. and release
OUT1 OUT2
MODE
set value changes towards the high pressure type sensor) of the varying measured pressure.
● These functions are convenient for finding the it immediately when is displayed.
0-ADJ
0-ADJ
MODE
pressed once the set value changes ・Please take care to remember if the key-protect
Peak hold display function has been set.
towards the low vacuum side by 1 digit.
・If key or key is pressed continu- Initiating peak hold display Release of key-protect
ously, the set value changes quickly.
If the set pressure range is exceeded,
DP2-20 -101.3kPa
・In the sensing mode, keep key DP2-20 -101.3kPa
・ In the sensing mode, press key MODE
either (upper limit exceeded) or pressed until is displayed. (4 sec. continuously for about 3 sec. and release
(lower limit exceeded) is displayed.
OUT1 OUT2 approx.) When the finger is released OUT1 OUT2
it immediately when is displayed.
after is displayed, the peak value Key-protect is released and the
MODE MODE
0-ADJ 0-ADJ
MODE
0-ADJ -101.3kPa用 100kPa用 1MPa用
Procedure to check initial conditions Procedure to check set values -1.033kgf/cm2 1.020kgf/cm2 10.20kgf/cm2
OUT1 OUT2
MODE
-14.70psi 14.50psi 145.0psi 0-ADJ
Set to sensing mode Set to sensing mode Bottom hold display -1.013bar 1.000bar 10.00bar
-760mmHg
Press key
MODE
Initiating bottom hold display -29.9inHg
while pressing Press MODE
key. Stick the pressure
key. DP2-20 -101.3kPa
・In the sensing mode, keep key
圧力センサ用 単位切り換え銘板 N2L58 unit label at the
position shown.
Sensor enters initial setting mode Sensor enters Set Value 1 (P1) set mode pressed until is displayed. (4 sec.
approx.) When the finger is released
17 INTENDED PRODUCTS FOR
OUT1 OUT2
Initial conditions which have been set Set Value 1 (P1) which has been set 0-ADJ
MODE
after is displayed, the bottom value
are displayed and can be checked. is displayed and can be checked.
and are displayed alternately.
Press MODE
key. Press MODE
key. ・If the applied pressure exceeds the CE MARKING
Displayed
Sensor returns to sensing mode Sensor enters Set Value 2 (P2) set mode displayable pressure range, error ● The models listed under ' 1 SPECIFI-CATIONS'
alternately
message ( or ) and come with CE Marking.
Set Value 2 (P2) which has been set DP2-20
are displayed alternately. In this
-101.3kPa
is displayed and can be checked. As for all other models, please contact our office.
case, bring back the applied pressure Contact for CE
Press MODE
key. to within the rated pressure range. ● Panasonic Marketing Europe GmbH Panasonic
OUT1 OUT2
MODE
In case of auto-matic
0-ADJ
・The figure on the left shows the Testing Center
sensitivity setting display of a vacuum type sensor when Winsbergring 15, 22525 Hamburg,Germany
mode only the pressure unit has been set to 'kPa'.
Sensor enters Set Value 3 (P3) set mode
Set Value 3 (P3) which has been set Ending bottom hold display
is displayed and can be checked. http://panasonic.net/id/pidsx/global
DP2-20 -101.3kPa
・Press key.
Press key.MODE
(Sensor returns to sensing mode.) Overseas Sales Division (Head Office)
Sensor returns to sensing mode OUT1 OUT2 2431-1 Ushiyama-cho, Kasugai-shi, Aichi, 486-0901, Japan
0-ADJ
MODE
Phone: +81-568-33-7861 FAX: +81-568-33-8591
Please note that if any key, except key, is pressed in MODE
For sales network, please visit our website.
any setting mode, the set conditions shall get changed. © Panasonic Industrial Devices SUNX Co., Ltd. 2015
PRINTED IN JAPAN