INSTALLATION INSTRUCTIONS
APPLICATION Configure the internal tubing as shown in Fig. 1. Use
small diameter tubing for panel mount configuration.
The P7640U Universal Differential Pressure Sensors
provide reliable, accurate measurement and control. Duct Mount
Proper applications include measurement of extremely 1. Thread probe into the back of the housing.
low pressure applications such as: building/room 2. Configure internal tubing as shown in Fig. 2. Use
pressure, air flow, variable air volume, filter status, and large diameter tubing for duct mounting
duct pressure. They are ideal for clean rooms, hospitals, configuration.
fume hoods, and computer rooms. 3. Unit is typically mounted at the high pressure loca-
tion when used for differential control.
The P7640 Pressure Sensors are designed with field-
selectable 4-20 mA, 0-5 Vdc, or 0-10 Vdc output. The
pressure ranges fall between 0–10 in. w.c./0–2500 Pa.
See Table 2.
CONFIGURATION
Select the proper output, mode, and pressure range
Accessory using the switches and jumpers:
1. Select output using the output switch:
32003169-001 Duct Pressure Pick-up Probe, 4 in. a. Current: mA (then skip to step 3), or
b. Voltage: Volt.
2. Select 0-10 Vdc or 0-5 Vdc using jumper J4.
INSTALLATION 3. Select bi- or uni-directional mode using jumper J5.
62-0282-03
P7640U DIFFERENTIAL PRESSURE SENSORS
ZERO
RESPONSE
FAST/STD
JP8
UNITS
7
IN. W.C./PA
1
JP7
2
4 3
MODE
PWR OUT COM ZERO BI/UNI
JP5
VOLT
mA VOLT SV/10V
OUTPUT JP4
CONTROLLER,
METER OR
RECORDER 3
+ INPUT SIGNAL
– COMMON – + L1
1 2
USE THE L2
SMALLER DIAMETER TUBE FRONT BARB + –
FOR PANEL CONFIGURATION M27485
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
Fig. 1. Tubing for panel mount. PROTECTION AS REQUIRED.
2 POLARIZED SECONDARY INDICATIONS FOR USE WITH DC POWER
SUPPLY ONLY.
3 DRY CONTACT TO AUTOMATICALLY ZERO THE SENSOR UPON
CLOSURE. (OPTIONAL) M27291
CAUTION
Equipment Damage Hazard.
Can damage the device beyond repair.
Do not apply power to output terminal. Permanent
equipment damage will result.
ZERO
RESPONSE
FAST/STD
JP8
UNITS
7
USE THE IN. W.C./PA
6
CAUTION
Equipment Damage Hazard.
CONTROLLER,
METER OR 12 TO 30 Vdc
POWER SUPPLY
RECORDER
Can damage the device beyond repair. +
+ INPUT SIGNAL
Disconnect power supply before installation.
– COMMON –
NOTE: Wiring to the ZERO terminals is optional.
1 DRY CONTACT TO AUTOMATICALLY ZERO THE SENSOR
UPON CLOSURE. (OPTIONAL)
M27292
62-0282—03 2
P7640U DIFFERENTIAL PRESSURE SENSORS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
W7760A E AI AI AI AI AI AI AI AI AI AI AI AI ANALOG
OUT
AO
GND 1 2 GND 3 4 GND 5 6 GND 7 8 GND GND
AO AO
1 2
OUT OUT OUT OUT OUT OUT OUT OUT DI DI DI DI GND GND 24 24 24 24 24 24 24 OUT 21 GND E-BUS E-BUS
1 2 3 4 5 6 7 8 1 2 3 4 VAC VAC VAC VAC VAC VAC VAC COM VDC
COM COM OUT
17 18 19 20 21 22 23 24 25 26 27 28 29 31 32 33 34 35 36 37 38 39 40 41 42 43 44
L1
(HOT)
1
L2
Fig. 5. Typical wiring for three-wire pressure sensor with Vdc output (used with the XL15A Controller).
3 62-0282—03
P7640U DIFFERENTIAL PRESSURE SENSORS