P7640U

Differential Pressure Sensors

INSTALLATION INSTRUCTIONS
APPLICATION Configure the internal tubing as shown in Fig. 1. Use
small diameter tubing for panel mount configuration.
The P7640U Universal Differential Pressure Sensors
provide reliable, accurate measurement and control. Duct Mount
Proper applications include measurement of extremely 1. Thread probe into the back of the housing.
low pressure applications such as: building/room 2. Configure internal tubing as shown in Fig. 2. Use
pressure, air flow, variable air volume, filter status, and large diameter tubing for duct mounting
duct pressure. They are ideal for clean rooms, hospitals, configuration.
fume hoods, and computer rooms. 3. Unit is typically mounted at the high pressure loca-
tion when used for differential control.
The P7640 Pressure Sensors are designed with field-
selectable 4-20 mA, 0-5 Vdc, or 0-10 Vdc output. The
pressure ranges fall between 0–10 in. w.c./0–2500 Pa.
See Table 2.
CONFIGURATION
Select the proper output, mode, and pressure range
Accessory using the switches and jumpers:
1. Select output using the output switch:
32003169-001 Duct Pressure Pick-up Probe, 4 in. a. Current: mA (then skip to step 3), or
b. Voltage: Volt.
2. Select 0-10 Vdc or 0-5 Vdc using jumper J4.
INSTALLATION 3. Select bi- or uni-directional mode using jumper J5.

NOTE: Setting for 0 to 10 in. w.c. and bi-direc-


When Installing this Product... tional will give output from -10 to 10 in.
1. Read these instructions carefully. Failure to follow w.c.
them could damage the product or cause a hazard-
ous condition. 4. Select inches w.c. or Pascal scale using jumper J7.
2. Check ratings given in instructions and on the 5. Select fast or standard response time using jumper
product to ensure the product is suitable for your J8.
application. 6. Select appropriate full-scale pressure range using
3. Installer must be a trained, experienced service the rotary switch. Align arrow (not the slot) to the
technician. desired range. See Table 2 for the range selection
4. After installation is complete, check out product guide.
operation as provided in these instructions. NOTE: The universal model is marked full scale.
IMPORTANT When the range is changed, the LCD
All wiring must agree with applicable codes, models momentarily indicate selected
ordinances and regulations. range.

7. Set output according to Table 1.


Mounting Table 1. Controller Compatibility
Screw holes are accessed inside the enclosure (with the and Output Settings.
cover removed) and are located in the upper left and
lower right corners. Required Sensor LONSPEC™
Controller Output Setting Setting
Panel Mount W7750, W7760, W7761 4-20 mA FilterPress or
P7610B
Run tubing from one (static) or both (differential) barb
fittings, making sure the typically higher pressure source W7750B, W7760C, 0-10 Vdc (default) FilterPress or
is connected to the port labeled HI, and the typically W7753, W7760 P7610F, or voltage
lower pressure source is connected to the port labeled Non-Honeywell 0-5 Vdc n/a
LO.

62-0282-03
P7640U DIFFERENTIAL PRESSURE SENSORS

ZERO

RESPONSE
FAST/STD
JP8

UNITS
7
IN. W.C./PA

1
JP7

2
4 3
MODE
PWR OUT COM ZERO BI/UNI
JP5
VOLT
mA VOLT SV/10V
OUTPUT JP4

CONTROLLER,
METER OR
RECORDER 3

+ INPUT SIGNAL
– COMMON – + L1
1 2
USE THE L2
SMALLER DIAMETER TUBE FRONT BARB + –
FOR PANEL CONFIGURATION M27485
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
Fig. 1. Tubing for panel mount. PROTECTION AS REQUIRED.
2 POLARIZED SECONDARY INDICATIONS FOR USE WITH DC POWER
SUPPLY ONLY.
3 DRY CONTACT TO AUTOMATICALLY ZERO THE SENSOR UPON
CLOSURE. (OPTIONAL) M27291

Fig. 3. Wiring for voltage (Vdc) output.

CAUTION
Equipment Damage Hazard.
Can damage the device beyond repair.
Do not apply power to output terminal. Permanent
equipment damage will result.

ZERO

RESPONSE
FAST/STD
JP8

UNITS
7
USE THE IN. W.C./PA
6

FRONT BARB JP7


LARGER DIAMETER TUBE
5

FOR DUCT CONFIGURATION M27484 4 3


MODE
PWR OUT COM ZERO BI/UNI
Fig. 2. Tubing for duct mount JP5
VOLT
mA VOLT SV/10V
OUTPUT
WIRING (FIG. 3 THROUGH 5)
JP4

CAUTION
Equipment Damage Hazard.
CONTROLLER,
METER OR 12 TO 30 Vdc
POWER SUPPLY
RECORDER
Can damage the device beyond repair. +
+ INPUT SIGNAL
Disconnect power supply before installation.
– COMMON –
NOTE: Wiring to the ZERO terminals is optional.
1 DRY CONTACT TO AUTOMATICALLY ZERO THE SENSOR
UPON CLOSURE. (OPTIONAL)
M27292

Fig. 4. Wiring for current (mA) output.

62-0282—03 2
P7640U DIFFERENTIAL PRESSURE SENSORS

P7640 P7640 H76XX

+ PWR + PWR + Vin (Vac) +


2
– COM – COM – Gnd –
O OUT O OUT O Vo (0-10 Vdc)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
W7760A E AI AI AI AI AI AI AI AI AI AI AI AI ANALOG
OUT
AO
GND 1 2 GND 3 4 GND 5 6 GND 7 8 GND GND
AO AO
1 2

OUT OUT OUT OUT OUT OUT OUT OUT DI DI DI DI GND GND 24 24 24 24 24 24 24 OUT 21 GND E-BUS E-BUS
1 2 3 4 5 6 7 8 1 2 3 4 VAC VAC VAC VAC VAC VAC VAC COM VDC
COM COM OUT

17 18 19 20 21 22 23 24 25 26 27 28 29 31 32 33 34 35 36 37 38 39 40 41 42 43 44

L1
(HOT)
1
L2

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 TEMPERATURE SIGNAL CONNECTIONS ARE NOT POLARITY SENSITIVE. M18302B

Fig. 5. Typical wiring for three-wire pressure sensor with Vdc output (used with the XL15A Controller).

The display momentarily indicates “SET” when a selection


Table 2. Range Selection Guide. is made. In normal operation, pressure indications are in.
w.c.
Rotary Switch
Position 0–10 in. w.c. 0–2500 Pascal Zeroing
0 0.1 25
1 0.25 50 IMPORTANT
Perform zeroing only when both Zero ports are
2 0.5 100 exposed to the same pressure.
3 1 250
Zeroing the device automatically resets the output and
4 2.5 500 displays zero pressure. To do this either:
5 5 1000 — Press and hold the ZERO pushbutton for 2 seconds, or
— Provide contact closure on the ZERO terminals. To
6 10 2500
ensure this, place a piece of jumper tubing between HI
7 10 2500 and LO.

NOTE: To avoid accidental zero, this feature is


OPERATION enabled only while detected pressure is
within 5% of factory calibration.
IMPORTANT
During the first few minutes of operation, read-
ings at zero pressure and lowest pressure
ranges appear erroneous. Following this initial
warm-up period, the P7640 maintains specified
accuracy and stability.

3 62-0282—03
P7640U DIFFERENTIAL PRESSURE SENSORS

LonSpec™ is a trademark of Echelon® Corporation.

By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to,
the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages,
including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.

Automation and Control Solutions


Honeywell International Inc.
1985 Douglas Drive North
® U.S. Registered Trademark
Golden Valley, MN 55422 © 2014 Honeywell International Inc.
62-0282—03 M.S. Rev. 07-14
customer.honeywell.com Printed in United States