You are on page 1of 2

Models:

FUJI MINIATURE DIN TIMER MANUAL ST7P-2A15S-ADC,


ST7P-2A13T-ADC,
Safety Precautions ST7P-2A16T-ADC,
To ensure safe and proper operation, read this manual ST7P-2A11N-ADC
before installation, wiring, operation, maintenance, and ST7P-2A16N-ADC
inspection. Manual should be furnished to the final user. Original Edition
May 2003

WARNING: Incorrect installation or operation may cause death or serious injury, and damage to equipment. It may also be necessay
to use fail-safe measures if controlling a critical process or safety application.

• Remove input power before installation, wiring, maintenance or inspection to prevent electrical shock.
• Do not use this device if damaged when unpacked.
• Only qualified personnal should perform installation, maintenance or inspection of this device.
• To prevent fire, accidents and malfunction of this device, do not install in environments
with high temperature, high humidity, dust, corrosive gases, water, direct sunlight or excessive vibration. Do no expose the case
to solvents or corrosive substances such as benzene, strong acids or alkaloids.
• Use this device within the range of its rated voltage and current.
• Fire may occur if the power supply and load are incorrectly connected.
• To prevent poor contact operation, keep timer from exposure to dust, concrete chips, iron filings and similar materials.
• To prevent terminal malfunction, tighten periodically.
• Never disassemble, modify or repair this device.
• If replacing this device, be sure to dispose of it properly.
Operation
• Set the time within the range of the timing scale divisions. To make timer output a signal as soon as power is turned on, turn
timer dial fully counterclockwise.
• The timer dial can be turned while the timer is operating, but the time for that operation will not be correct.
• Do not try to turn the timer dial outside the timing range. Turn dial carefully and do not force.
• Do not remove the timer case, or the operating characteristics will change.

Control Dimensions (Timer and Socket Shown Attached)

O u tput P ower 32.4 85.6


In d icator ON
I ndi cat or
UP
4 6
2 8

0 10
860 Set t i ng
ST7 Dial
69
4.5

Fuji Miniature DIN Timer Manual 1


Specifications
Approvals UL file no.: Body - E44592, Socket - E90265; CSA file no.:
LR20479; TÜV license no: R9551799
Repeat Accuracy ±01% at maximum setting time
Reset Time 0.1 second or less
Maximum Operating Cycle 1800 cycles/hour
85-132VAC 20.4-26.4VDC
ST7P-2A15S-ADC ST7P-2DE5S-ADC
Operating Voltage Range ST7P-2A13T-ADC ST7P-2DE3T-ADC
ST7P-2A16T-ADC ST7P-2DE6T-ADC
ST7P-2A11N-ADC ST7P-2DE1N-ADC
ST7P-2A16N-ADC ST7P-2DE6N-ADC
Operating Temperature Range -10 to +50°C (14 to 122°F)
Humidity 35 to 85% (no condensation)

Contact Ratings 3A @ 240VAC resistive load, 1A @120VAC inductive load;


3A @ 30VDC resistive load, 0.5A @ 30VDC inductive load
Power Consumption Approx. 1.2VA at 100VAC, approx. 1.5VA at 200VAC, 1.1W
at 24VDC.
Insulation Resistance 100M at 500VDC insulation tested
Surge Voltage* 3000 Volts
2000VAC 1 min. between current carrying part and non-
current carrying part
Dielectric Strength 2000VAC 1 min. between output contact and control circuit
1000VAC 1 min. between open contacts
Malfunction durability: 10 to 55Hz, 0.5mm double amplitude
Vibration Mechanical durability: 10 to 55Hz, 0.7mm double amplitude

Malfunction durability: 50m/s2


Shock Mechanical durability: 1000m/s2

Mechanical: 50 million operations


Life Expectancy Electrical: 500,000 operations

Weight 36.288g (1.28 oz.)

Dimensions - ST7P Body 5.7 2.2 All dimensions in mm


0.5

UP 1 4
5 8
18.5

27.8

9 12

ON
13 14

X1 X10 4 52.6 1.8


21

Dimensions - TP88X2 Body Panel Drilling


32.4 Approx. 56.6 29
6.8 22.6
4 1 10.5

8 5
59
69

12 9

24.5 2- 4 (M3, M4)


Terminal M3.5x8 34
14 13
10.6

Wiring Diagram Sockets/Screw Terminal and Rail Mounting Timing Diagram


4 1
1 4
8 5 Power (13-14)
5 8
9 12 Timed NO (9-5) t
(12-8)
13 14
(- ) (+ )
Timed NC (9-1)
12 9 (12-4)
INPUT 14 13

2 Fuji Miniature DIN Timer Manual

You might also like