Professional Documents
Culture Documents
• An overload current.
• An overcurrent.
• Earth/Ground fault.
• Others (O/U voltage, O/U frequency, phase lose/sequence/unbalance, power
reverse, Neutral voltage displacement, Arcing fault and etc.).
It can be any current, flowing within the normal circuit path, that is
higher than the normal Full Load Amps (FLA).
CB-QF1
S160-GJ Icu=65 Ka TMA 63-630
Where:
Icu/Ics ultimate short circuit breaking capacity/service short Cable-WC1
circuit breaking capacity; 4x(1x10)+1G10
Insulator: XLPE/EPR
IKLLL is the MAX fault level (short circuit value 3PH + NE+ PE). XLPE/EPR Cu
dV = 2.15 %
Ib = 56.1 A
Iz = 75.0 A
L = 45 m
Load-L1
L Sr = 38.89 kVA IKmin= 23 Ka
Ir = 56.1 A Cosphi = 0.90
UF = 100%
dV = 2.15 %
CB-QF1
Where: S160 TMD63-630 Icu=65 Ka
Ikmin is MIN fault level (min short circuit value PH to PE);
I (t< 5 s) is interrupted be the protection device (breaker or
fuse). Cable-WC1
4x(1x10)+1G10
Insulator: XLPE/EPR
XLPE/EPR Cu
dV = 2.15 %
Ib = 56.1 A
Iz = 75.0 A
L = 45 m
Load-L1
L Sr = 38.89 kVA IKmin= 23 Ka
Ir = 56.1 A Cosphi = 0.90
Ikmin =23000 A=> I (t< 5 s) = 750A UF = 100%
dV = 2.15 %
CB (MCB, RCCB, RCBO, GFCI, AFCI, DFCI, MCCB, ICCB, MCP, PCB or
ACB);
Fuse (gG or aG);
Relay (ANSI 50N/51N or 50G/51G Earth fault or sensitive earth fault and
etc.);
To keep voltage as constant in the healthy phase (If fault occurs on any
one phase);
communication;
There are three families, using the two-letter codes TT, TN and IT.
The first letter:
"T" — Direct connection of a point with earth (Latin: terra).
"I" — No point is connected with earth (isolation).
The second letter:
"T" — Earth connection is direct connection to earth (Latin: terra),
usually via a ground rod.
"N" — Earth connection is supplied by the electricity supply Network,
either as a separate (PE) or combined with the neutral conductor.
Ik = U0 / Zs
Where:
Zs is the impedance of the fault
loop;
U0 is the rated voltage between
phase and ground.
Cable-WC1
3x(1x35)+ 1x(1x25)+ 1G16
XLPE/EPR Cu
Iz = 110
L = 50 m
Load-L1
L IKLLL= 6.4 Ka
IKLG= 3 Ka
Cable-WC1
3x(1x95)+ 1x(1x95)+ 1G50
XLPE/EPR Cu
Iz = 207
L = 50 m
Load-L1
L IKLLL= 9.9 Ka Ib = 200.0 A
IKLG= 0.2 Ka
CBR-F1
ZS250-GJ TMD+RC Icu=65 Ka
Cable-WC1
3x(1x95)+ 1x(1x95)+ 1G50
XLPE/EPR Cu
Iz = 207
L = 50 m
Load-L1
L IKLLL= 9.9 Ka Ib = 200.0 A
IKLG= 0.2 Ka
Where:
Zs is the impedance of the fault
loop;
U0 is the rated voltage between
phase and ground.
Ik = U0 / RA
RA = RT+ RN
RT= U0 / Ik Ground resistance for load
RN=0 Ground resistance for source
Cable-WC1
4x(1x10)+1G10
Insulator: XLPE/EPR
XLPE/EPR Cu
dV = 2.15 %
Ib = 56.1 A
Iz = 75.0 A
L = 45 m
Load-L1
L Sr = 38.89 kVA
Cosphi = 0.90
Ir = 56.1 A
UF = 100%
dV = 2.15 %
Where:
Zs is the impedance of the
fault loop;
U0 is the rated voltage
between phase and ground.
Note:
It is strongly recommended not to distribute the N-conductor.
PROTECTIONS TT TN S TN C IT
OVERLOAD*
Ib<= In <= Iz Ib<= In <= Iz Ib<= In <= Iz Ib<= In <= Iz
bimetal or L
1) Icu > Ik LLL 1) Icu > Ik LLL 1) Icu > Ik LLL
1) Icu > Ik LLL
SHORT CIRCUIT**
magnetic coil, S and I
2) I²t <= K²S² 2) I²t <= K²S² 2) I²t <= K²S²
2) I²t <= K²S²
3) Ikmin => I (t < 5s) 3) Ikmin => I (t < 5s) 3) Ikmin => I (t< 5s)
3) Ikmin => I (t < 5s)
INDIRECT TOUCH 1) Rt x Ia <= UL
magnetic Rt <= 50/Ia or Rt <= 50/Idn Zs x Ia <= U0 Zs x Ia <= U0 2) Zs <= Ur/2 Ia
coil,S,I,G,RCDs 3) Z's <= Uo/2 Ia
N° wires L-N-PE L-L-L-PE L-L-L-N-PE L-N-PE L-L-L-PE L-L-L-N-PE L-PEN L-L-L-PEN L-N-PE L-L-L-PE L-L-L-N-PE
N° opening poles 2 3 4 1 or 2 3 3 or 4 1 3 2 3 4
G protection and RCDs
Note don't work!!
1) For OVERLOAD Protection In is the setting current of the release
2) In SHORT CIRCUIT Protection Icu or Ics,according to the project, could be considered
Protection of transformers;
Protection of capacitors;
Protection of generators;
Cables or conductors;
Motors;
PSC;
Etc.