You are on page 1of 44

Low Voltage Network Design

1 alfanar Technical Sessions


Agenda

• The fault criteria and their protection in low voltage network.


• Protection against indirect contact.
• Type of load and their protective devices.
• Coordination and load flow.

2 alfanar Technical Sessions


The Faults in Low voltage network

• An overload current.
• An overcurrent.
• Earth/Ground fault.
• Others (O/U voltage, O/U frequency, phase lose/sequence/unbalance, power
reverse, Neutral voltage displacement, Arcing fault and etc.).

3 alfanar Technical Sessions


The An overload current definition

IEC 60050 describe it as a situation where a larger than intended


electric current exists through a conductor, leading to generation of
heat, and the risk of fire or damage to equipment.

It can be any current, flowing within the normal circuit path, that is
higher than the normal Full Load Amps (FLA).

4 alfanar Technical Sessions


Protection against overload current

 CB (MCB, RCBO, MCCB, ICCB, MCP, PCB or ACB);


 Fuse (gG, gTr, gM, gR or gB);
 Relay (Thermal Overload Relay, ANSI 49RMS Thermal overload and etc.);

5 alfanar Technical Sessions


An overload selection (cont.). U
Source-U1
Vn = 400 Vac
LLLN / TN-S
P = 35 kW
Suitable overload protection shall satisfy the two following conditions: Q= 17 kvar

1. Ib <= In (Ir) <= R X Iz 2. I2 / IF<= 1.45 X Iz CB-QF1


where: S160-GJ Icu=65 Ka TMA 63-630
R = 1 for circuit breakers
R = 0.75 for gG fuses < 16 A
R = 0.9 for gG fuses ≥ 16 A Cable-WC1
4x(1x10)+1G10
Insulator: XLPE/EPR
Where: XLPE/EPR Cu
dV = 2.15 %
 Ib is the load current (calculation); Ib = 56.1 A
 Iz is the current carrying capacity of the cable (catalogue); Iz = 75.0 A
L = 45 m
 In is the rated current of the protective device; for adjustable protective
releases, the rated current In is the set current (catalogue); Load-L1
L Sr = 38.89 kVA
 I2 / IF is the current ensuring effective operation in the conventional time of Cosphi = 0.90
the protective device (catalogue). Ir = 56.1 A
UF = 100%
dV = 2.15 %

6 alfanar Technical Sessions


Source-U1
U
An overload selection (cont.). Vn = 400 Vac
LLLN / TN-S
P = 35 kW
The formula for the calculation of the load current of a generic load is: Q= 17 kvar

CB-QF1
S160-GJ Icu=65 Ka TMA 63-630

• P is the active power [W];


Cable-WC1
• k = 1 for single-phase systems or for direct current systems;
4x(1x10)+1G10
\/¯3 for three-phase systems; Insulator: XLPE/EPR
• Ur is the rated voltage [V] XLPE/EPR Cu
dV = 2.15 %
for three-phase systems it is the line voltage, Ib = 56.1 A
Iz = 75.0 A
for single-phase systems it is the phase voltage; L = 45 m
• cos φ is the power factor; Load-L1
L
• KO is the oversize factor (Ko, >1) ; Sr = 38.89 kVA
Cosphi = 0.90
• Ku is the utilization factor ( 0< Ku <1) ; Ir = 56.1 A
UF = 100%
• KC/Df/Ks is the demand/diversity/simultaneity factor ( 0< Kc <1). dV = 2.15 %

7 alfanar Technical Sessions


An overload selection (cont.).
Notes:
 When using CBs in compliance with IEC
60898 and/or IEC 60947-2, the relation
(1) is enough;
 The “conventional” setting tripping time
may be 1 hour or 2 hours according to
local standards and the actual value
selected for I2.

8 alfanar Technical Sessions


The An overcurrent definition

IEC 60050 describe it as resulting from a fault of negligible impedance


between live conductors having a difference in potential under normal
operating conditions.

An overcurrent has the following effects:


 Electromagnetic effect;
 Mechanical effects;
 Thermal effect.

9 alfanar Technical Sessions


Protection against overcurrent

 CB (MCB, RCBO, MCCB, ICCB, MCP, PCB or ACB);


 Fuse (gG, aG, gM, aM, gTr, aTr, gR, aR or gB or aB);
 Relay (Overcurrent Relay, ANSI 50/51 Phase overcurrent and etc.);

10 alfanar Technical Sessions


Source-U1
An overcurrent selection (cont.). U Vn = 400 Vac
LLLN / TN-S
S = 1000 Kva
Suitable overcurrent protection shall satisfy the three following conditions: IKLLL= 43 Ka

1. Icu/Ics (catalogues) > IKLLL (calculation or measurement) CB-QF1


S160 TMD63-630 Icu=65 Ka

Where:
 Icu/Ics ultimate short circuit breaking capacity/service short Cable-WC1
circuit breaking capacity; 4x(1x10)+1G10
Insulator: XLPE/EPR
 IKLLL is the MAX fault level (short circuit value 3PH + NE+ PE). XLPE/EPR Cu
dV = 2.15 %
Ib = 56.1 A
Iz = 75.0 A
L = 45 m
Load-L1
L Sr = 38.89 kVA IKmin= 23 Ka
Ir = 56.1 A Cosphi = 0.90
UF = 100%
dV = 2.15 %

11 alfanar Technical Sessions


An overcurrent selection (cont.).

2. I²t (catalogues) <= K²S² (catalogues)


Cable K²S²
Where: I²t
 I²t is the specific let-through energy of the
protective device;
 K²S² is withstand energy level of cable;
 S is the cable cross section [mm2]; in the case of
Circuit breaker I²t
conductors in parallel it is the cross section of the
single conductor;
 k is a factor that depends on the cable insulating
and conducting material;
 Icp is the fault level (short circuit value) at the
incoming terminals;
 Icc is the prospective short circuit value.
Icp max ls

12 alfanar Technical Sessions


Source-U1
An overcurrent selection (cont.). U Vn = 400 Vac
LLLN / TN-S
S = 1000 Kva
3. Ikmin (Calculation or measure) => I (t< 5 s) (catalogues) IKLLL= 43 Ka

CB-QF1
Where: S160 TMD63-630 Icu=65 Ka
 Ikmin is MIN fault level (min short circuit value PH to PE);
 I (t< 5 s) is interrupted be the protection device (breaker or
fuse). Cable-WC1
4x(1x10)+1G10
Insulator: XLPE/EPR
XLPE/EPR Cu
dV = 2.15 %
Ib = 56.1 A
Iz = 75.0 A
L = 45 m
Load-L1
L Sr = 38.89 kVA IKmin= 23 Ka
Ir = 56.1 A Cosphi = 0.90
Ikmin =23000 A=> I (t< 5 s) = 750A UF = 100%
dV = 2.15 %

13 alfanar Technical Sessions


The ground fault definition

IEC 60050 describe it as a An occurrence of an accidental conductive


path between a live conductor and the Earth.

An overcurrent has the following effects:


 Initial arc currents;
 The danger to persons caused by indirect contact.

14 alfanar Technical Sessions


Protection against ground fault (cont.).

 CB (MCB, RCCB, RCBO, GFCI, AFCI, DFCI, MCCB, ICCB, MCP, PCB or
ACB);
 Fuse (gG or aG);
 Relay (ANSI 50N/51N or 50G/51G Earth fault or sensitive earth fault and
etc.);

15 alfanar Technical Sessions


Protection against ground fault (cont.).

 The Unrestricted Earth Fault Protection (UEFP);


 The Restricted Earth Fault Protection (REFP);
 The Source Ground Return, which is also called “Standby
Earth Fault Protection” (SEFP).

16 alfanar Technical Sessions


Protection against indirect contacts

 SELV (Safety Extra-Low Voltage);


 PELV (Protection Extra-Low Voltage).

By using SELV or PELV protection systems, there are no


dangers of indirect contacts since the supply voltage is
so low that it does not cause hazards for persons.

A PELV system has the same characteristics of SELV but it


shall have an earthed point.

17 alfanar Technical Sessions


The grounding or earthing definition
To connect the metallic (conductive) parts of an electric
appliance or installations to the earth (ground) is called
Earthing or Grounding.

In other words, to connect the metallic parts of electric


machinery and devices to the earth plate or earth electrode
(which is buried in the moisture earth) through a thick
conductor wire (which has very low resistance) for safety
purpose is known as Earthing or Grounding.

18 alfanar Technical Sessions


Why earthing is important

 To protect human lives as well as provide safety to electrical devices

and appliances from leakage current;

 To keep voltage as constant in the healthy phase (If fault occurs on any

one phase);

 To protect electric system and buildings form lighting;

 To serve as a return conductor in electric traction system and

communication;

 To avoid the risk of fire in electrical installation systems.

19 alfanar Technical Sessions


Earthing arrangements as per IEC 60364

There are three families, using the two-letter codes TT, TN and IT.
The first letter:
"T" — Direct connection of a point with earth (Latin: terra).
"I" — No point is connected with earth (isolation).
The second letter:
"T" — Earth connection is direct connection to earth (Latin: terra),
usually via a ground rod.
"N" — Earth connection is supplied by the electricity supply Network,
either as a separate (PE) or combined with the neutral conductor.

20 alfanar Technical Sessions


Earthing arrangements TN (cont.).

Main application in industries and big installations with “MV


power” supply (power supply is distributed to users by
transformer substation).

 TN-C: less cost and reliability than “TN-S”;


 TN-S: higher cost and more reliability than “TN-C”;

21 alfanar Technical Sessions


Earthing arrangements TN (cont.).
TN-C-S: less cost than TN-S and more cost than TN-
C and more reliability than TN-C and less reliability
than TN-S.

A combined earth/neutral conductor hence the name


PME within BS7671 and IEE Wiring Regulations.

22 alfanar Technical Sessions


Indirect contact protection selection in TN-S (cont.).

Ik = U0 / Zs

Where:
 Zs is the impedance of the fault
loop;
 U0 is the rated voltage between
phase and ground.

It’s a short circuit

23 alfanar Technical Sessions


Indirect contact protection selection in TN-S (cont.). Source U
U Vn = 400 Vac
LLLN / TN-S
Protection device should comply with this:
IkLG (Calculation or measure) => I (t< 5 s) (catalogues)
CB-F1
S160 TMA 125-1250 Icu=65 Ka

Cable-WC1
3x(1x35)+ 1x(1x25)+ 1G16
XLPE/EPR Cu
Iz = 110
L = 50 m

Load-L1
L IKLLL= 6.4 Ka
IKLG= 3 Ka

24 alfanar Technical Sessions


Indirect contact protection selection in TN-S (cont.). Source U
U Vn = 400 Vac
LLLN / TN-S
Protection device should comply with this:
IkLG (Calculation or measure) => I (t< 5 s) (catalogues)
CB-F1
S250-GE LSIG Icu=65 Ka

Cable-WC1
3x(1x95)+ 1x(1x95)+ 1G50
XLPE/EPR Cu
Iz = 207
L = 50 m

Load-L1
L IKLLL= 9.9 Ka Ib = 200.0 A
IKLG= 0.2 Ka

25 alfanar Technical Sessions


Indirect contact protection selection in TN-S Source U
U Vn = 400 Vac
LLLN / TN-S

CBR-F1
ZS250-GJ TMD+RC Icu=65 Ka

Cable-WC1
3x(1x95)+ 1x(1x95)+ 1G50
XLPE/EPR Cu
Iz = 207
L = 50 m

Load-L1
L IKLLL= 9.9 Ka Ib = 200.0 A
IKLG= 0.2 Ka

26 alfanar Technical Sessions


Indirect contact protection selection in TN-C (cont.).
Ik = U0 / Zs

Where:
 Zs is the impedance of the fault
loop;
 U0 is the rated voltage between
phase and ground.

It’s a short circuit

27 alfanar Technical Sessions


Indirect contact protection selection in TN-C

In TN-C systems disconnection of the neutral and use


of the residual current devices or of devices with similar
operating principle (function G against earth faults) are
not possible.

28 alfanar Technical Sessions


Indirect contact protection selection in TN-S (cont.).

 Circuit-breakers with thermomagnetic releases;


 Circuit-breakers with electronic releases;
 Residual current devices (TN-S only);
 Fuse.

Max admissible voltage IEC 60038

29 alfanar Technical Sessions


TN earthing system advantages

 It is possible to have both TN-S and TN-C-S supplies taken


from the same transformer;
 The low impedance earth path so RCD is not must to
detect earth faults.

30 alfanar Technical Sessions


Earthing arrangements TT

Main application in domestic installations and small


industries where the distribution of the (PE) is impossible
and when the user is responsible for the protection
against indirect contact.

Such as supplies to mobile homes and telecommunication


sites.

31 alfanar Technical Sessions


Indirect contact protection selection in TT (cont.).

Ik = U0 / RA
RA = RT+ RN
RT= U0 / Ik Ground resistance for load
RN=0 Ground resistance for source

Very low current

32 alfanar Technical Sessions


Indirect contact protection selection in TT (cont.). U
Source-U1
Vn = 400 Vac
LLLN / TN-S
P = 35 kW
Q= 17 kvar
 For Magnetic coil, (RT = 230 / 750 = 0.3 Ω);
 For electronic trip unit with S, (RT = 230 / 510 = 0.45 Ω); CB-QF1
 For electronic trip unit with G, (RT = 230 / 24 = 9.6 Ω);
 If we have RCD then RT = 230 / 0.03 = 7666.6 Ω;

Cable-WC1
4x(1x10)+1G10
Insulator: XLPE/EPR
XLPE/EPR Cu
dV = 2.15 %
Ib = 56.1 A
Iz = 75.0 A
L = 45 m
Load-L1
L Sr = 38.89 kVA
Cosphi = 0.90
Ir = 56.1 A
UF = 100%
dV = 2.15 %

33 alfanar Technical Sessions


Indirect contact protection selection in TT

 Circuit-breakers with thermomagnetic releases;


 Circuit-breakers with electronic releases;
 Residual current devices;
 Fuse.

34 alfanar Technical Sessions


Earthing arrangements TT advantages

 There is no serious risks in the case of a broken neutral;


 In locations where power is distributed overhead, earth
conductors are not at risk of becoming live.

35 alfanar Technical Sessions


Earthing arrangements TT disadvantages

 The fault loop impedance is high so we should always have


an RCD (GFCI) as its first isolator to protect against
indirect contact.

36 alfanar Technical Sessions


Earthing arrangements IT

Main application in industrial or utilities installations


(especially chemical, petrochemical and
telecommunications) for which a very high level of
service continuity is required.

Exposed conductive part

37 alfanar Technical Sessions


Indirect contact protection selection in IT (cont.).
Ik = U0 / Zs

Where:
 Zs is the impedance of the
fault loop;
 U0 is the rated voltage
between phase and ground.

An extremely low current

38 alfanar Technical Sessions


Indirect contact protection selection in IT

A monitoring of insulation to earth of the network,


so that the occurrence of any fault is signaled.

39 alfanar Technical Sessions


Earthing arrangements IT advantages

 Small values of short circuit currents to earth (1st fault),


typically 1 to 10 A (0.1A/km cable);
 Medium-high values of short circuit currents to earth (2nd
fault).

Note:
It is strongly recommended not to distribute the N-conductor.

40 alfanar Technical Sessions


Summary for faults protection

PROTECTIONS TT TN S TN C IT
OVERLOAD*
Ib<= In <= Iz Ib<= In <= Iz Ib<= In <= Iz Ib<= In <= Iz
bimetal or L
1) Icu > Ik LLL 1) Icu > Ik LLL 1) Icu > Ik LLL
1) Icu > Ik LLL
SHORT CIRCUIT**
magnetic coil, S and I
2) I²t <= K²S² 2) I²t <= K²S² 2) I²t <= K²S²
2) I²t <= K²S²
3) Ikmin => I (t < 5s) 3) Ikmin => I (t < 5s) 3) Ikmin => I (t< 5s)
3) Ikmin => I (t < 5s)
INDIRECT TOUCH 1) Rt x Ia <= UL
magnetic Rt <= 50/Ia or Rt <= 50/Idn Zs x Ia <= U0 Zs x Ia <= U0 2) Zs <= Ur/2 Ia
coil,S,I,G,RCDs 3) Z's <= Uo/2 Ia
N° wires L-N-PE L-L-L-PE L-L-L-N-PE L-N-PE L-L-L-PE L-L-L-N-PE L-PEN L-L-L-PEN L-N-PE L-L-L-PE L-L-L-N-PE
N° opening poles 2 3 4 1 or 2 3 3 or 4 1 3 2 3 4
G protection and RCDs
Note don't work!!
1) For OVERLOAD Protection In is the setting current of the release
2) In SHORT CIRCUIT Protection Icu or Ics,according to the project, could be considered

41 alfanar Technical Sessions


Type of Load and its Protective Devices

 Protection of transformers;
 Protection of capacitors;
 Protection of generators;
 Cables or conductors;
 Motors;
 PSC;
 Etc.

42 alfanar Technical Sessions


Coordination and load flow

alfanar is working to have tool in 2018.

43 alfanar Technical Sessions


Thank you for your time and attendance

44 alfanar Technical Sessions

You might also like