Issue:

FC-1312 Customer-defined Fault


Distributor: Cummins Chile
DFSEc: Markos Herrera
Factory Representative: Anthony Cairns
Issue Description:
FC 1312 is a customer-defined fault, and is activated via customer input 2 and is
configurable. It can be configured to a shutdown or warning. FC 1312 is being
activated after 1 hour of dynamic testing.

Customer Description:
The coolant level murphy gauges for the LTA & JW are wired into customer
input 2, this input is becoming active after 1 hour of dynamic testing. The
LTA murphy gauge indication shows the contact closed indicating low
coolant level, the actual coolant level was investigated & the standard
coolant level sight glass indicated correct coolant level. However when the
radiator filler cap was removed foam and froth was observed

Model Number: QSK60 G8 / C2500D5A

TSR Number: 1-9281847221

2 Cummins Confidential
Pictures

Indicating normal coolant level

Indicating coolant level warning

3 Cummins Confidential
Pictures

Foam and froth is visual

4 Cummins Confidential
Pictures
murphy gauges for the LTA & JW

Low coolant level sender

5 Cummins Confidential
Step 2 – Possible Causes
▪ Possible Causes
– Incorrect Routing of the lower pipe to the Murphy Gauge
– Loose connections vent lines between engine thermostat
and radiator connections
– General routing of the coolant pipes

The plumbing on the lines to and from


the Murphy gauges has been reviewed
by the service department & Bearwood
engineering the plumbing observed in
the photos supplied from site may be
contributing to aerating the coolant.

6 Cummins Confidential
Short Term Recommendation
Suction Pipe

7 Cummins Confidential
Short Term Recommendation

Vent Pipes

8 Cummins Confidential
Short Term Recommendation

Murphy Gauge Position

9 Cummins Confidential
Short Term Recommendation
Wiring Connections and terminations

Due to limited customer inputs, wire both JW and LTA into customer input 2
and set to a warning in the PCC3201

TB3-17

10 Cummins Confidential
Short Term Recommendation
Wiring Connections and terminations

TB3-14 TB3-17

11 Cummins Confidential
Long Term Fix

▪ We are currently working with our design team to


validation the Murphy gauge position, plumbing &
routing of pipes in this radiator installation

12 Cummins Confidential