XXVI International Scientific Conference Electronics - ET2017, September 13 - 15, 2017, Sozopol, Bulgaria

Infrared Survey in Electrical Preventive


Maintenance
Anna Vladova Stoynova and Borislav Borisov Bonev
Department of Microelectronics, Faculty of Electronic Engineering and Technologies
Technical University of Sofia
8 Kliment Ohridski blvd., 1000 Sofia, Bulgaria
ava@ecad.tu-sofia.bg

Abstract – The article discusses the basic elements of efficiency due to heat generation and unnecessary losses
procedure applicable to programs for maintenance of [3].
electrical equipment with infrared inspection. Based on Typical problems regarding heat in electrical equipment
accumulated experience of experimental thermographic are bad contact connections, short circuit, and overload,
measurement of electrical equipment in different companies
defects in the body of the equipment or its components.
was proposed approach to creating a typical procedure,
taking into account the specificities of the studied electrical Two ways to analyze the thermal characteristics in
equipment and targets set. electrical equipment are used - quantitative and qualitative
Keywords – Infrared Thermography, Electrical Preventive evaluation [4], [5]. The quantitative measurements usually
Maintenance are difficult to obtain. It needs determination the real and
accurate temperature value, the true emissivity value and
I. INTRODUCTION atmospheric attenuation. The qualitative measurement,
considers the relative temperature value of a particular
Increasingly widespread introduction into operation of hotspot with respect to other equipment in a similar
advanced technologies for assessment of electrical environment. The second way is widely used to evaluate
installations, leads to ensure safety, reliability and economy electrical systems by employing Delta T (temperature
of enterprises. Infrared thermography (IRT) successfully difference) criteria [6]. The levels of severity of the
has the function of a powerful diagnostic tool for suspected electrical systems were classified into four
predictable maintenance of facilities of various engineering categories, according to the International Electrical Testing
fields [1]. By detection of thermal anomalies often invisible Association (NETA) standards [6]. The temperature criteria
to the human eye, infrared thermography allows take indicating the change in temperature ranges and the
corrective impacts before the work of relevant electrical or recommended action should be taken according to the level
mechanical equipment and production lines get out the of priority are shown in Table. 1. This classification can be
nominal operating parameters. An increasing number of used for qualitative and for quantitative measurements.
industry standards for safety and preventive programs Quantitative measurements use the ambient temperature as
include the use of infrared inspection at least once every the reference. The reference temperature has to be
three years [2] A justification for the additional cost of measured and a greater understanding of the variables
infrared measurements are great possibilities of thermal influencing radiometric measurements.
control. Infrared thermography has established itself as a It is important to be emphasized that the measurement
key element of the thorough electrical preventive errors resulting from inadequate spatial resolution of the
maintenance (EPM) programs due to the destructive nature used infrared camera depends on the magnitude of the error
and the possibility to control the operational status of the and the criticality of the target. For example a high
electrical equipment and components without interrupting resolution IR camera gives twice the delta-T (∆T)
their work. temperature rise compared to a low resolution IR camera
Practical use of infrared technique requires qualified and 25% more than the medium resolution camera. These
engineers to perform the inspection and the use of different differences will only increase as the emissivity is lowered.
procedures for processing and analysis of images. It is Image processing techniques can be used to extract the
often discussed a typical infrared scanning procedure, thermal profiles within the electrical components for an
without a common understanding what is included in it. automatic analysis the condition of electrical systems.
This article presents the vision of the key elements of the The common steps used in evaluating the thermal
inspection procedure of electrical equipment, which is anomaly of electrical systems based on top-down approach
applied to the inspection of several companies in Bulgaria. includes: finding region of interest (ROI), identify the
repeated structure, segmentation on process, relevant
II. THERMAL ANOMALIES MEASUREMENTS BY information, decision making for a result.
Three approaches can be used to determine the thermal
INFRARED THERMOGRAPHY
severity of electrical systems:
 maximum temperature identification of each ROI for
Overheating of electrical components and equipment can direct interpretation;
lead to potential unplanned outages or violation of

978-1-5386-1753-3 /17/$31.00 ©2017 IEEE

Authorized licensed use limited to: Chulalongkorn University provided by UniNet. Downloaded on August 04,2020 at 19:49:01 UTC from IEEE Xplore. Restrictions apply.
 histogram distance evaluation for finding the
similarity between two objects;
 gradient analysis of the segmented region.

TABLE 1. CLASSIFICATION OF THERMAL PROFILE OF ELECTRICAL


SYSTEMS

ΔT over ΔT similar Action required Level of


ambient equipment, priority
temperat (ºC)
ure, (ºC)
> 40 > 15 Repair 1
immediately -
major
discrepancy
Fig.1. Block diagram of an IR thermal monitoring system
21 – 40 – Monitor until 2
corrective
measures can be The captured infrared images should be filtered and
accomplished enhanced. Next have to be fulfilled several steps: image
11 - 20 4 – 15 Repair as time 3 preprocessing, feature extraction, type recognition, state
permits - analysis and classification. Infrared image processing can
indicates be divided in two categories - preprocessing and real
probable processing. The preprocessing aim is to improve image
deficiency quality and real processing is to find the ROI. The most
1 - 10 1-3 Warrants 4 frequently used approach for ROI determination is the
investigation - segmentation. Located image features then used as inputs
possible of neural network (ANN) that has been trained. In this step
deficiency the relation to various operating parameters must be
accomplished. A neural network can be applied for fault
Both bottoms-up and top-down approaches can be models. The general structure of the analyzing process as is
successfully implemented using various techniques for shown in the Fig. 2.
fault identification. The thermographic images of electrical
equipment show a very high variation in appearance such
as object distance from camera (scale change) and angle
(view point change). It is important to use the most robust
to this kind of changes approach for describing the IR
image.

III. BASIC ELEMENTS OF THE INFRARED SURVEY


PROCEDURE

Conceptual block diagram of an infrared system used in


Electrical Preventive Maintenance is presented on Fig. 1.
IR survey requires various factors to be considered during
monitoring and a complex analysis of collected data. An
automatically thermal monitoring and analysis system for
the current state of electrical components is good to use
machine learning approach. Advanced decision for the Fig.2. Base structure of data analyzing process
analysis block is the combination of image-processing and
artifcial intelligence techniques.
The accurate determination of the current temperature of
The images of the surveyed electrical equipment are
the monitored electrical equipment depends on two
captured and then send to the monitoring system for
categories factors: external (environmental factors) and
calibration by using the input variables from additional
internal (emissivity of the components and thermal
sensors and further analysis. The electrical equipments
gradient). Prior to analysis, all data for these factors have to
recognition from the complex background is very difficult
be collected by set of sensors. The output of the automated
task. In conventional inspection of electrical equipment
IR systems will be given according to qualitative and
requires a large amount of certified and experienced
quantitative analysis. The level of priority of the suspected
personnel as well as cost and time. In order to assess
electrical equipments can be classified according to Table 1
whether potential troubles would happen and find position
and respective actions will be recommended.
of suspected equipments infrared image processing must be
applied.

Authorized licensed use limited to: Chulalongkorn University provided by UniNet. Downloaded on August 04,2020 at 19:49:01 UTC from IEEE Xplore. Restrictions apply.
IV. EXPERIMENTAL RESULTS

More significant typical applications of IR preventive


diagnostics in electrical equipment for instrumentation
control and automation (IC&A) in thermal power plant
"Bobov Dol" EAD that have substantially reduces costs
and emergency stays are:

• Detection of "bad" contacts in various connection Fig.5. Presence of oxidation of terminal


points;
• Localization of hidden defects in cable channels;
• Inspection of fuses and circuit breakers;
• Monitoring of low and medium voltage devices;
• Opening of unilateral load or misbalance in the
distribution of energy;
• Verification of transformers and small
components;
• Detection of increased electrical loads.

Some of the results on significant IC&A systems, which


are responsible for trouble-free and safe operation of
equipment in the plant, are presented. These are terminals,
circuit breakers, contactors, relays, circuit boards, fuses,
cable channels, transformers, electrical loads (motors),
inverters, systems of protection and others.
Fig.6. Results from preventive diagnosis of contactors and relays
A. Thermograms of terminal blocks and check the
electrical connections C. Thermograms of fuses

Fig. 3 and Fig. 4 present optical and infrared images Fig. 7 shows pictures of fuses in panel for lighting.
from the diagnosis of terminal blocks.

Fig.7. There is an increase in temperature of one of the fuses due


Fig.3. Presence of loosened bolting leading to a rise in
to unilateral load or misbalance in the distribution
temperature of one of the conductors

D. Thermograms of transformers and rectifiers

Fig. 8 shows pictures from diagnosis of transformers and


rectifiers in the signaling panel. (above) and transformer
and rectifier elements in the automation cabinet (below).

Fig.4. Temperature increase of several conductors due to


unilateral load or misbalance in the distribution of energy

B. Thermograms of circuit breakers, contactors and relays

Fig. 5 shows pictures of the circuit breaker in the power


supply of automation panel in IC&A system. Fig. 6 shows
images of contactors and relays in automation panel in Fig.8. Presence of loosened bolting leading to a rise in
temperature of one of the conductors
IC&A system.

Authorized licensed use limited to: Chulalongkorn University provided by UniNet. Downloaded on August 04,2020 at 19:49:01 UTC from IEEE Xplore. Restrictions apply.
Fig. 9 shows pictures from diagnosis transformer and IV. CONCLUSION
rectifier elements in the automation cabinet.
Enhancing and preserving system reliability and
reducing maintenance costs are top priorities for electric
utilities today. The infrared inspections of electrical
systems are beneficial to reduce the number of costly and
catastrophic equipment failures and unscheduled plant
shutdowns leading to the improvement of system efficiency
and power quality. Using cost-effective electrical
preventive maintenance infrared survey, strongly depend
Fig.9. Presence of loosened bolting leading to a rise in on the specific features of the inspection of electrical
temperature of one of the conductors equipment and targets. These factors are important when
choosing a procedure of investigation and relevant
economically justified program. An automatic infrared
E. Thermograms of PCB and low voltage electronics thermal diagnosis system in Electrical Preventive
Maintenance can provide more accurate and faster analysis.
Fig. 10 shows pictures of power bus bars of voltage Important part in a predictive and preventive maintenance
inverter (above) and input circuit boards for low signal program is the presence of a classification procedure.
levels with built-in multiplexer, part of the management
system of energy block (below). REFERENCES

[1] C. Kolakowski, Infrared Thermography: Determining failure


or problems in electrical systems, Risk
Bulletin, No 38, May, 2011, pp. 1-2
[2] Standard for an Electrical Preventive Maintenance (EPM)
Program, Munich RE, April 2013, pp.1-10.
[3] I. Bedir, A. Azmy, F. Selim, High Quality Circuit Breakers
Thermal Inspections, International Journal of control, automation
and systems, vol. 2 no. 2, 2013, pp. 19-33.
[4] A. Huda, S. Taib, K. Ghazali, M. Jadin, A new thermographic
NDT for condition monitoring of electrical components using
ANN with confidence level analysis, ISA Transactions, vol. 53,
2014, pp. 717–724
[5] M. Jadin, S. Taib, Recent progress in diagnosing the
reliability of electrical equipment by using infrared
thermography, Infrared Phys. Technol., vol. 55, no. 4, 2012, pp.
236–245.
[6] Standard for Infrared Inspection of Electrical Systems &
Rotating Equipment, Infraspection Institute, Burlington, USA,
2008.
Fig.10. Presence of loosened bolting leading to a rise in
temperature of one of the conductors