Professional Documents
Culture Documents
Energy Automation
Fault
Calculations
Fault Calculations Contents
1. Introduction 44
NRJED311332EN 43
Fault Calculations 1. Introduction
44 NRJED311332EN
Fault Calculations 2. Three-phase fault
calculations
Three-phase faults are unique in that they are balanced, that is,
Z '1 Z''1
F symmetrical in the three phases, and can be calculated from the
I single-phase impedance diagram and the operating conditions
existing prior to the fault.
E'
V
E'' A fault condition is a sudden abnormal alteration to the normal
circuit arrangement. The circuit quantities, current and voltage, will
alter, and the circuit will pass through a transient state to a steady
N state. In the transient state, the initial magnitude of the fault current
Figure 3.1:
will depend upon the point on the voltage wave at which the fault 3
occurs. The decay of the transient condition, until it merges into
Network with fault at F steady state, is a function of the parameters of the circuit elements.
The transient current may be regarded as a d.c. exponential current
superimposed on the symmetrical steady state fault current. In a.c.
machines, owing to armature reaction, the machine reactances
pass through ‘sub transient’ and ‘transient’ stages before reaching
their steady state synchronous values. For this reason, the
resultant fault current during the transient period, from fault
inception to steady state also depends on the location of the fault in
the network relative to that of the rotating plant.
In a system containing many voltage sources, or having a complex
network arrangement, it is tedious to use the normal system voltage
sources to evaluate the fault current in the faulty branch or to
calculate the fault current distribution in the system. A more
practical method [3.1] is to replace the system voltages by a single
driving voltage at the fault point. This driving voltage is the voltage
existing at the fault point before the fault occurs.
Consider the circuit given in Figure 3.1 where the driving voltages
are E and E’, the impedances on either side of fault point F are Z’1
and Z’’1, and the current through point F before the fault occurs is I
.
The voltage V at F before fault inception is:
After the fault the voltage V is zero. Hence, the change in voltage is
- V . Because of the fault, the change in the current flowing into the
network from F is:
∆I = −
V
= −V
(
Z1' + Z1'' )
Z1 Z1' Z1''
and, since no current was flowing into the network from F prior to
the fault, the fault current flowing from the network into the fault is:
I f = −∆I = V
( Z1' + Z1'' )
Z1' Z1''
NRJED311332EN 45
Fault Calculations 2. Three-phase fault
calculations
(cont.)
46 NRJED311332EN
Fault Calculations 2. Three-phase fault
calculations
(cont.)
NRJED311332EN 47
Fault Calculations 3. Symmetrical component
analysis of a three-phase
network
E1 =
1
3
(
E a + aE b + a 2 E c )
E2 =
1
3
( 2
E a + a E b + aE c
)
1
E0 =
3
(
Ea + Eb + Ec )
…Equation 3.2
Figure 3.5:
Resolution of a system of unbalanced
vectors
48 NRJED311332EN
Fault Calculations 3. Symmetrical component
analysis of a three-phase
network (cont.)
X
3.1 Positive Sequence Network
ZS1 ΔZ'1 F Z''1 During normal balanced system conditions, only positive sequence
currents and voltages can exist in the system, and therefore the
I'1 I''1
normal system impedance network is a positive sequence network.
Z'1 I1
When a fault occurs in a power system, the current in the fault
E' V1 E'' branch changes from 0 toI and the positive sequence voltage
across the branch changes from V to V1 ; replacing the fault branch
N by a source equal to the change in voltage and short-circuiting all
(a) System diagram normal driving voltages in the system results in a current I flowing 3
I'1 into the system, and:
N
X I '1 Z '1
∆I = −
(V − V ) 1
V Z1
F …Equation 3.3
V'1 + I'1 ΔZ'1
V1
N' where Z1 is the positive sequence impedance of the system viewed
(b) Gradient diagram from the fault. As before the fault no current was flowing from the
fault into the system, it follows that I1, the fault current flowing from
Figure 3.6: the system into the fault must equal - I .
Fault at F, Positive sequence diagrams
Therefore:
V1 = V - I1 Z1 …Equation 3.4
NRJED311332EN 49
Fault Calculations 3. Symmetrical component
analysis of a three-phase
network (cont.)
N Hence:
(a) Negative sequence network V0 = - I0 Z0 …Equation 3.6
F
Also, the zero sequence diagram is that of Figure 3.7, substituting I0
X
for I2, and so on.
V2 The currents and voltages in the zero sequence network are
co-phasal, that is, all the same phase. For zero sequence currents
V2 + I'2ΔZ'1 to flow in a system there must be a return connection through either
a neutral conductor or the general mass of earth. Note must be
N taken of this fact when determining zero sequence equivalent
(b) Gradient diagram circuits. Further, in general Z1 ≠ Z 0 and the value of Z 0 varies
according to the type of plant, the winding arrangement and the
Figure 3.7: method of earthing.
Fault at F, Positive sequence diagrams
50 NRJED311332EN
Fault Calculations 4. Equations and network
connections for various
types of faults
b. Phase-phase (B-C)
Ia = 0
Ib = −Ic
V b = V c
…Equation 3.8
c. Phase-phase-earth (B-C-E)
Ia = 0
Vb = 0
V c = 0
…Equation 3.9
It should be noted from the above that for any type of fault there are
three equations that define the fault conditions.
NRJED311332EN 51
Fault Calculations 4. Equations and network
connections for various
types of faults (cont.)
(b) Equivalent circuit Substituting for V1, V2 and V0 in Equation 3.13 from Equations 3.4,
3.5 and 3.6:
Figure 3.8 :
Single-phase-earth fault at F V - I1 Z1 = I2 Z2 + I0 Z0
but, from Equation 3.12, I1 = I2 = I0 , therefore:
V = I1 (Z1 + Z2 + Z3) …Equation 3.14
F Va
A
Ia The constraints imposed by Equations 3.12 and 3.14 indicate that
Vb
B the equivalent circuit for the fault is obtained by connecting the
Vc sequence networks in series, as shown in Figure 3.8(b).
C
Ib
Ic
4.2 Phase-phase Fault (B-C)
Ia =0 From Equation 3.8 and using Equations 3.1 and 3.2:
Ib =-Ic
Vb=-Vc I1 = I2
(a) Definition of fault
I0 = 0 …Equation 3.15
V1 = V2 …Equation 3.16
F1 F2 F0
From network Equations 3.4 and 3.5, Equation 3.16 can be re-
Z1 Z2 Z0 written:
N2 N0 V - I1 Z1 = I2 Z2 + I0 Z0
V V - I1 Z1 = I2 Z2
N1
and substituting for I2 from Equation 3.15:
(b) Equivalent circuit V = I1 (Z1 + Z2) …Equation 3.17
Figure 3.9 : The constraints imposed by Equations 3.15 and 3.17 indicate that
Phase-Phase fault at F there is no zero sequence network connection in the equivalent
circuit and that the positive and negative sequence networks are
connected in parallel. Figure 3.9 shows the defining and equivalent
circuits satisfying the above equations.
52 NRJED311332EN
Fault Calculations 4. Equations and network
connections for various
types of faults (cont.)
Z 0 I1
I2 = −
Z0 + Z 2
F1 F2 F0 …Equation 3.21
or
I1 = V
(Z 0 + Z2 )
Z1 Z 0 + Z1 Z 2 + Z 0 Z 2 …Equation 3.22
NRJED311332EN 53
Fault Calculations 4. Equations and network
connections for various
types of faults (cont.)
Ia+Ib+Ic=0 and
3
Va+Vb+Vc=0 I0 = 0 …Equation 3.24
I1 I2 I0 V2 = 1/3 Va
P1 P2 P0
N1 +ve N2 -ve N0 Zero
Sequence n1 Sequence n2 Sequence n0
Network Q1 Network Q2 Network Q0
and therefore:
(b) Equivalent circuit
V1 = V 2 = V0 = 1 3 V a
Figure 3.12 :
Open circuit on phase A I a = I1 + I 2 + I 0 = 0
…Equation 3.28
54 NRJED311332EN
Fault Calculations 4. Equations and network
connections for various
types of faults (cont.)
F F'
4.6 Cross-country Faults
a-e b-e
A cross-country fault is one where there are two faults affecting the
same circuit, but in different locations and possibly involving
different phases. Figure 3.13(a) illustrates this.
(a) `A' phase to ground at F and `B' phase to ground at F'
a) At point F
Va1 V'a1
I b + I c = 0 3
N1 N'1
Va = 0
2
a I'a2
F2 Ia2 I'a2 F'2 1 2
a
Therefore:
2
Va2 V'a2
a V'a2
I a1 = I a 2 = I a 0
N2 N'2
aI'a0 V a1 + V a 2 + V a 0 = 0
F0 Ia0 I'a0 F'
0 1 …Equation 3.29
a
b) At point F’
aV'a0
Va0 V'a0
I ' a = I ' c = 0
N0 N'0
Converting:
a2 V’a1 + a V’a2 +V’a0 = 0
or
V’a1 + a2 V’a2 + a V’a0 = 0 …Equation 3.34
NRJED311332EN 55
Fault Calculations 5. Current and voltage
distribution in a system
due to a fault
56 NRJED311332EN
Fault Calculations 5. Current and voltage
distribution in a system
due to a fault (cont.)
I ' a = ( 2 C1 + C 0 ) I 0
3
I ' b = − (C1 − C 0 ) I 0
I ' c = − (C1 − C 0 ) I 0
…Equation 3.35
b. phase-phase (B-C)
I'a = 0
(2
)
I ' b = a − a C1 I1
( )
I ' c = a − a 2 C1 I1
…Equation 3.36
c. phase-phase-earth (B-C-E)
I ' a = − (C1 − C 0 ) I 0
Power system
( Z
)
I ' b = a − a 2 C1 0
Z1
2
− a C1 − C 0 I 0
A B
O
( Z
I ' c = a 2 − a C1 0
Z1
)
− aC1 + C 0 I 0
…Equation 3.37
NRJED311332EN 57
Fault Calculations 5. Current and voltage
distribution in a system
due to a fault (cont.)
The vector diagram for the above fault condition is shown in Figure
3.15.
Using the above equation, the fault voltages at bus B in the previous
example can be found.
From the positive sequence distribution diagram Figure 3.8(c):
[ {
V '1 = V − I1 Z1 − j (0.395 × 0.75 ) + (0.373 × 0.45 ) }]
[
V ' 2 = V − I1 Z1 − j 0.464 ]
From the zero sequence distribution diagram Figure 3.8(b):
[ {
V ' 0 = I 0 Z 0 − j (0.165 × 2.6 ) + (0.112 × 1.6 ) }]
[
= I 0 Z 0 − j 0.608 ]
58 NRJED311332EN
Fault Calculations 5. Current and voltage
distribution in a system
due to a fault (cont.)
V'c = 61.5-116.4∞
For earth faults, at the fault I1 = I2 = I0 = j31.2A,
when V = 63.5 volts and is taken as the reference vector.
Further, Z1 = Z2 = j0.68 ohms.
I'b=I'c =8.15-90∞
Hence:
NRJED311332EN 59
Fault Calculations 6. Effect of system earthing
on zero sequence quantities
60 NRJED311332EN
Fault Calculations 6. Effect of system earthing
on zero sequence quantities
(cont.)
a. Single-phase-earth (A-E)
3V 3 V
IR = =
2 Z1 + Z 0 (2 + K ) Z1
where K = Z0 / Z1
V
I3φ =
Z1
Thus:
IR 3
=
I3φ (2 + K ) …Equation 3.45
b. Phase-phase-earth (B-C-E)
3 Z1 I1 =
(
V Z1 + Z 0 )
I R = 3I0 = − I1
Z1 + Z 0 2 Z1 Z 0 + Z12
Hence:
3 V Z1 3 V
IR = − = −
2 Z1 Z 0 + Z12 ( )
2 K + 1 Z1
Therefore:
IR 3
= −
I3ϕ 2K +1( ) …Equation 3.46
NRJED311332EN 61
Fault Calculations 6. Effect of system earthing
on zero sequence quantities
(cont.)
2.0
…Equation 3.47
1.5
b. Phase-phase-earth (B-C-E)
3 1.0 Residual voltage for 3K
VR = V
( )
Double-Phase-Earth fault
2K +1
0.5 …Equation 3.48
62 NRJED311332EN
Fault Calculations 6. Effect of system earthing
on zero sequence quantities
(cont.)
ZS X
IF ZL F A At relaying point X:
B
C VR = VXn + Vbn + Vcn
VR VFn VR VXn
Figure 3.20:
Resistance fault-solid neutral
NRJED311332EN 63
Fault Calculations 7. References
3.1
Circuit Analysis of A.C. Power Systems,Volume I.
Edith Clarke. John Wiley & Sons.
3.2
Method of Symmetrical Co-ordinates Applied to the
Solution of Polyphase Networks.
C.L. Fortescue.
Trans. A.I.E.E.,Vol. 37, Part II, 1918, pp 1027-40
3 3.3
Power System Analysis.
J.R. Mortlock and M.W. Humphrey Davies.
Chapman and Hall.
3.4
Neutral Groundings.
R Willheim and M. Waters,
Elsevier.
3.5
Fault Calculations.
F.H.W. Lackey,
Oliver & Boyd.
64 NRJED311332EN