Network Protection & Automation Guide
Industrial & Commercial Contents
Power System Protection
1. Introduction 539
3. Discrimination 542
17
538 NRJED311332EN
Industrial & Commercial 1. Introduction
Power System Protection
17
Figure 17.1:
Large modern industrial plant
NRJED311332EN 539
Industrial & Commercial 2. Busbar Arrangement
Power System Protection
HV supply HV supply
1 2
Transformer Transformer
1 2
Figure 17.2:
Typical switchboard configuration for an
industrial plant 2 out of 3
mechanical or
electrical interlock
540 NRJED311332EN
Industrial & Commercial 2. Busbar Arrangement
Power System Protection
(cont.)
110kV
*
33kV
NO
*
A B 6kV
NO
EDG
NO
* NC
A B C 0.4kV
NO
Figure 17.3: NO
A B 6kV
Typical industrial power system
*
NO
* NC B
A C
0.4kV
NO
NO
* NC
0.4kV
A NO B C
Bus section C - Essential supplies
EDG - Emergency generator
* - Two out of three interlock
NRJED311332EN 541
Industrial & Commercial 3. Discrimination
Power System Protection
4. HRC Fuses
542 NRJED311332EN
Industrial & Commercial 4. HRC Fuses
Power System Protection
(cont.)
Curve of asymmetrical
prospective short-circuit
current
Current trace
Ip
Figure 17.4:
HRC fuse cut-off feature Time
Start of
short-circuit
Arcing
Pre-arcing time
time
NRJED311332EN 543
Industrial & Commercial 4. HRC Fuses
Power System Protection
(cont.)
1000
100 1250A
710A 800A
500A 630A
400A
200A 315A
1.0 6A
2A
0.1
0.1 1.0 10 100 500
544 NRJED311332EN
Industrial & Commercial 4. HRC Fuses
Power System Protection
(cont.)
Fusing factor =
Minimum Fusing Current
Current Rating
NRJED311332EN 545
Industrial & Commercial 5. Industrial Circuit Breakers
Power System Protection
546 NRJED311332EN
Industrial & Commercial 5. Industrial Circuit Breakers
Power System Protection
(cont.)
NRJED311332EN 547
Industrial & Commercial 5. Industrial Circuit Breakers
Power System Protection
(cont.)
548 NRJED311332EN
Industrial & Commercial 5. Industrial Circuit Breakers
Power System Protection
(cont.)
Inverse
Very Inverse
Ultra Inverse
Short Circuit
1000
100
10
Time (s)
Figure 17.6:
Typical tripping characteristics of an ACB
0.1
17
0.01
1 10 20
Current (multiple of setting)
NRJED311332EN 549
Industrial & Commercial 5. Industrial Circuit Breakers
Power System Protection
(cont.)
550 NRJED311332EN
Industrial & Commercial 6. Protection Relays
Power System Protection
When the circuit breaker itself does not have integral protection,
then a suitable external relay will have to be provided. For an
industrial system, the most common protection relays are time-
delayed overcurrent and earth fault relays. Chapter ”Overcurrent
Protection for Phase and Earth Faults” provides details of the
application of overcurrent relays.
Traditionally, for three wire systems, overcurrent relays have often
been applied to two phases only for relay element economy. Even
with modern multi-element relay designs, economy is still a
consideration in terms of the number of analogue current inputs that
have to be provided. Two overcurrent elements will detect any
interphase fault, so it is conventional to apply two elements on the
same phases at all relay locations. The phase CT residual current
connections for an earth fault relay element are unaffected by this
convention. Figure 17.7 illustrates the possible relay connections
and limitations on settings.
17
NRJED311332EN 551
Industrial & Commercial 6. Protection Relays
Power System Protection
(cont.)
A B C
A B C
(i) Ph. - Ph.
(b) 3Ph. 3w (ii) Ph. - E*
* Earth-fault protection
only if earth-fault
current is not less
(i) Ph. - Ph. than twice primary
(c) 3Ph. 4w (ii) Ph. - E* operating
(iii) Ph. - N current
A B C
Figure 17.7:
Overcurrent and A B C
earth fault relay Earth-fault settings
(e) 3Ph. 3w (i) Ph. - Ph.
may be less than full
connections (ii) Ph. - E
load
Earth-fault settings
(i) Ph. - Ph. may be less than full
(f) 3Ph. 4w (ii) Ph. - E load, but must be
(iii) Ph. - N greater than largest
Ph. - N load
A B C N
17
A B C N
552 NRJED311332EN
Industrial & Commercial 7. Co-Ordination Problems
Power System Protection
NRJED311332EN 553
Industrial & Commercial 7. Co-Ordination Problems
Power System Protection (cont.)
Figure 17.9:
Dual fed four-wire systems: use of 3-pole
CB’s
Supply 1 Supply 2
Neutral busbar
Bus section CB
17
If only one incoming supply breaker is closed, the earth fault relay
on the energised side will see only a proportion of the fault current
flowing in the neutral busbar. This not only significantly increases
the relay operating time but also reduces its sensitivity to low-level
earth faults.
The solution to this problem is to utilise 4-pole CB’s that switch the
neutral as well as the three phases. Then there is only a single
earth fault path and relay operation is not compromised.
554 NRJED311332EN
Industrial & Commercial 7. Co-Ordination Problems
Power System Protection
(cont.)
RS2
Supply 1 Supply 2
Figure 17.10:
Dual fed four-wire systems: use of single
point neutral earthing
N
When operating with both incoming main circuit breakers and the
bus section breaker closed, the bus section breaker must be
opened first should an earth fault occur, in order to achieve
discrimination. The co-ordination time between the earth fault
relays and should be established at fault level for a
substation with both incoming supply breakers and bus section
breaker closed.
When the substation is operated with the bus section switch closed
17
and either one or both of the incoming supply breakers closed, it is
possible for unbalanced neutral busbar load current caused by
single phase loading to operate relay and/or and
inadvertently trip the incoming breaker. Interlocking the trip circuit
of each relay with normally closed auxiliary contacts on the bus
section breaker can prevent this.
NRJED311332EN 555
Industrial & Commercial 7. Co-Ordination Problems
Power System Protection
(cont.)
17
556 NRJED311332EN
Industrial & Commercial 8. Fault Current Contribution
Power System Protection
from Induction Motors
NRJED311332EN 557
Industrial & Commercial 8. Fault Current Contribution
Power System Protection
from Induction Motors
(cont.)
9. Automatic Changeover
Systems
558 NRJED311332EN
Industrial & Commercial 9. Automatic Changeover
Power System Protection
Systems
(cont.)
NRJED311332EN 559
Industrial & Commercial 10. Voltage and Phase Reversal
Power System Protection
Protection
17
560 NRJED311332EN
Industrial & Commercial 11. Power Factor Correction and
Power System Protection
Protection of Capacitors
kW V
Figure 17.12:
Power factor correction principle
kVA lo
2 a
with co d current
kV mpens
A ation
co load
1
m cu
pe rr
Compensating kvar
ns en
at t w
Magnetising kvar
ion it
ho
ut
17
NRJED311332EN 561
Industrial & Commercial 11. Power Factor Correction and
Power System Protection
Protection of Capacitors
(cont.)
Reduction in
If the kW load and uncorrected power factors are known, then the
capacitor rating in kvar to achieve a given degree of correction may
be calculated from:
Capacitor ∠ 1 ∠ 2
A spreadsheet can easily be constructed to calculate the required
amount of compensation to achieve a desired power factor.
562 NRJED311332EN
Industrial & Commercial 11. Power Factor Correction and
Power System Protection
Protection of Capacitors
(cont.)
From
incoming transformer
Metering
11kV
Trip
Lockout
P1
>> >>
> >
Figure 17.14:
Metering
Protection of double star capacitor banks
PFC/V
Controller
A
P2
B
Capacitor bank 17
Capacitor
bank
> > >
* * *
IU >
NRJED311332EN 563
Industrial & Commercial 11. Power Factor Correction and
Power System Protection
Protection of Capacitors
(cont.)
17 C
>
Alarm Trip
(b)
Figure 17.15:
Differential protection of split phase
capacitor banks
564 NRJED311332EN
Industrial & Commercial 12. Examples
Power System Protection
In this section, examples of the topics dealt with in the Chapter are
considered.
Rating
1000A
Rating
Rating 30A
400A each
Figure 17.16:
Fuse protection: effect of layout on
(a) Incorrect layout giving rise to problems in discrimination
discrimination
Rating
1000A
17
Rating Rating Rating Rating
400A 100A 500A 500A
Rating
30A
NRJED311332EN 565
Industrial & Commercial 12. Examples
Power System Protection
(cont.)
The sub-circuit fuse may now have its rating reduced from 500A to
a value, of say 100A, appropriate to the remaining sub-circuit. This
800A arrangement now provides a discriminating fuse distribution
scheme satisfactory for an industrial system.
However, there are industrial applications where discrimination is a
secondary factor. In the application shown in Figure 17.17, a
400V
contactor having a fault rating of 20kA controls the load in one
sub-circuit. A fuse rating of 630A is selected for the minor fuse in
the contactor circuit to give protection within the through-fault
630A
Fuse
400A
1MVA
Figure 17.18: 2000/1A
LV board fault
Network diagram for protection
level = 30kA
co-ordination example – fuse/MCCB/relay
3300/415V
MCCB
>
400A
17
Discrimination is required between the relay and both the fuse and
MCCB up to the 40kA fault rating of the board. To begin with, the
time/current characteristics of both the 400A fuse and the MCCB
are plotted in Figure 17.19.
566 NRJED311332EN
Industrial & Commercial 12. Examples
Power System Protection
(cont.)
1000
= = 1443 A
0.4 × 3
With the CT ratio of 2000/1A and a relay reset ratio of 95% of the
Fuse
0.1 nominal current setting, a current setting of at least 80% would be
satisfactory, to avoid tripping and/or failure to reset with the
transformer carrying full load current. However, choice of a value at
MCCB
the lower end of this current setting range would move the relay
characteristic towards that of the MCCB and discrimination may be
lost at low fault currents. It is therefore prudent to select initially a
0.01
relay current setting of 100%.
1000 10,000 100,000
Operating current (A) to 415V base
Original relay characteristic
Revised relay characteristic
12.2.2 Relay characteristic and time multiplier selection
NRJED311332EN 567
Industrial & Commercial 12. Examples
Power System Protection
(cont.)
1.6 MVA
11/0.4kV
Z=6.25%
>> >>
Relay C1 > 2500/1 2500/1 I Relay C2
>> Trip
>
Relay B
>>
300/1 Relay A
Motor cable
M
160kW
568 NRJED311332EN
Industrial & Commercial 12. Examples
Power System Protection
(cont.)
NRJED311332EN 569
Industrial & Commercial 12. Examples
Power System Protection
(cont.)
Relay
Relay
Re-acceleration
Relay setting
Relay setting
1000
Figure 17.21:
Grading of relays A and B 100
Time (s)
10
0.1
17
0.01
100 1000 10000 100000
Current (A) referred to 0.4kV
570 NRJED311332EN
Industrial & Commercial 12. Examples
Power System Protection
(cont.)
Relay Re-acceleration
Relay Relay setting
Relay Relay setting
Relay setting
Parameter Value Parameter Value Parameter Value Parameter Value
Relay 300A Time const 1200s 2320A 0
Relay 2500A TMS 0.175 12500A 0.32s
Relay 2750A TMS 0.25 15000 0.62s
(a) Relay settings
1000
10
1
and I> and I>>
and
0.1
and
0.01
100 1000 10000 100000
Current (A) referred to 0.4kV
(b) Grading curves
17
NRJED311332EN 571
Industrial & Commercial 12. Examples
Power System Protection
(cont.))
17 13. References