Professional Documents
Culture Documents
OMICRON PTL
XRIO Converter
User Manual
V1.000
Contents
1 General Information
The AREVA P443 P445 XRIO converter is designed for testing AREVA MiCOMho P44y (P443 and P445)
distance protection relays by using the OMICRON Test Universe 2.22 software. The converter provides all
necessary data for testing the distance, phase overcurrent and earth fault overcurrent protection functions
of the MiCOMho P44y relays.
Note: The abbreviation P44y is always used for P443 or P445 relays. It is never used for P441, P442 or
P444 relays, as they differ too much from the above named.
Note: This converter was tested with the relay described above. It will also work with AREVA P445
distance protection relays. However, be aware that the P445 relays have less functionality than the P443
relays (e.g. only Mho characteristic for Distance phase zones). In this case, set the additional parameters
accordingly. See the relay documentation for more information.
5 Functional Range
The AREVA P44y XRIO converter implements the following functions:
• 21P/21G Distance protection (Mho and Quad)
• 50/27 Switch on to Fault
• 50/51/67 Phase overcurrent
• 50N/51N/67N Earth/ground overcurrent
Some of the functions listed above use the RIO interface of the Test Universe software. Consequently, the
test modules are configured automatically without using LinkToXRIO.
The following functions are using the RIO interface:
• 21P/21G Distance protection (Mho and Quad)
• 50/51/67 Phase overcurrent
• 50N/51N/67N Earth/ground overcurrent
Although these functions are not supported, their setting values are available in the Relay Parameter
Section.
8 Converter Structure
The converter is divided into two sections: the AREVA P443 P445 section and the RIO section. Both
sections consist of several function blocks.
The parameters contained in the General Information block are linked to the device part of the RIO
section and are available in the test report.
8.1.4.1 NamePlate
The NamePlate block contains all necessary information to identify the protection device to be tested. This
block contains the relay vendor, serial number, model, the relay location and a description.
8.1.4.2 ProtectedObject
The Protected Object block contains the positive sequence line impedance value.
8.1.4.3 PowerSystemParameters
The number of phases, phase rotation and the nominal frequency are stored in this block.
8.1.4.4 DistanceProtection
This block contains all data necessary to test the Phase and Ground Distance protection function and the
Load Blinder function of the relay. The nominal values and CT/VT settings used by this protection function
can be found here. All distance and load blinder zones are modeled as sub blocks of the
DistanceProtection\ImpedanceZoneElements block. Each zone sub block stores information about the
reactive and resistive zone reach, the grounding factor, the trip time and characteristic shape of the
modeled distance zone. The following distance protection and load blinder zones are modeled in the
DistanceProtection block:
• MhoPhaseZone1: Zone 1 (Mho) of the Phase Distance protection function
• MhoPhaseZone2: Zone 2 (Mho) of the Phase Distance protection function
• MhoPhaseZone3: Zone 3 (Mho) of the Phase Distance protection function
• MhoPhaseZoneP: Zone P (Mho) of the Phase Distance protection function
• MhoPhaseZone4: Zone 4 (Mho) of the Phase Distance protection function
• MhoPhaseZone1X: Zone 1 Extended (Mho) of the Phase Distance protection function
• MhoGroundZone1: Zone 1 (Mho) of the Ground Distance protection function
• MhoGroundZone2: Zone 2 (Mho) of the Ground Distance protection function
• MhoGroundZone3: Zone 3 (Mho) of the Ground Distance protection function
• MhoGroundZoneP: Zone P (Mho) of the Ground Distance protection function
• MhoGroundZone4: Zone 4 (Mho) of the Ground Distance protection function
• MhoGroundZone1X: Zone 1 Extended (Mho) of the Ground Distance protection function
• QuadPhaseZone1: Zone 1 (Quad) of the Phase Distance protection function
• QuadPhaseZone2: Zone 2 (Quad) of the Phase Distance protection function
• QuadPhaseZone3: Zone 3 (Quad) of the Phase Distance protection function
• QuadPhaseZoneP: Zone P (Quad) of the Phase Distance protection function
• QuadPhaseZone4: Zone 4 (Quad) of the Phase Distance protection function
• QuadPhaseZone1X: Zone 1 Extended (Quad) of the Phase Distance protection function
• QuadGroundZone1: Zone 1 (Quad) of the Ground Distance protection function
• QuadGroundZone2: Zone 2 (Quad) of the Ground Distance protection function
• QuadGroundZone3: Zone 3 (Quad) of the Ground Distance protection function
• QuadGroundZoneP: Zone P (Quad) of the Ground Distance protection function
• QuadGroundZone4: Zone 4 (Quad) of the Ground Distance protection function
• QuadGroundZone1X: Zone 1 Extended (Quad) of the Ground Distance protection function
The directional element supervising the distance protection function of the P44y relay is modeled as sub
block of the DistanceProtection\DirectionalElements block.
The minimum current sensitivities for the tripping zones are stored in the sub blocks of the
DistanceProtection\StartingElements block.
8.1.4.5 SwitchOnToFaultFunction
This block contains all necessary data to test the switch on to fault protection function. The nominal values
and the CT/VT settings used by this protection function can be found here. The main setting parameters
of the switch on to fault are:
• SOTF Delay
• TOC Reset Delay
These main setting parameters are stored in the SwitchOnToFaultElement1 of the
SwitchOnToFaultElements block, as pre-fault states under the TestCondition block.
8.2 RIO
The RIO section of the converter contains all specialized RIO functions which are needed to use the more
specialized test modules (like Advanced Distance or Overcurrent) provided by the OMICRON Test
Universe software.
Warning: Do not change any values in this section. The values have been set using the relay settings of
the Relay Parameter Section.
Note: Do not activate the former test object view in the advanced mode of the XRIO test object. Changing
parameters in this view may disable formulas in the RIO section.
8.2.1 Distance
This RIO function provides all necessary values for testing the Phase Distance, Ground Distance and
Load Blinder functions with the Advanced Distance test module.
The following RIO functions for testing this protection functions are available:
• Phase Overcurrent Forward direction
• Phase Overcurrent Reverse direction
The AREVA P44y XRIO converter constructs a resulting characteristic curve for each direction of the
phase overcurrent elements. This means that directional and non-directional stages are compared for
forward and reverse direction. The three smaller stages (of each forward and reverse direction) are
combined and the resulting characteristic curve is shown in the correspondent RIO overcurrent function
block. Non-directional stages will be considered for both forward and reverse directions.
The following RIO functions for testing this protection functions are available:
• Earth Fault Forward direction
• Earth Fault Reverse direction
The AREVA P44y XRIO converter constructs a resulting characteristic curve for each direction of the
earth fault elements. This means that directional and non-directional stages are compared for forward and
reverse direction. The three smaller stages (of each forward and reverse direction) are combined and the
resulting characteristic curve is shown in the correspondent RIO overcurrent function block. Non-
directional stages will be considered for both forward and reverse directions.
The converter doesn't support Mutual coupling compensation between two parallel lines. The replica
impedance is not adjusted due to the mutual compensation factor kZm (settings 30.07; 30.08; 30.09 and
30.0A).
Because of that, the internal calculation by the RIO Distance function is deactivated and the loop
impedances are used instead. Phase to phase zones are not covered by this specialty.
In the converter, the user must enter these values with the corresponding binary code as a string of zeros
and ones. Pay attention to the number of required bits of each setting value.