OMICRON PTL
XRIO Converter
User Manual
V1.001
Contents
1 General Information
The Siemens 7SJ6x XRIO converter is designed for testing Siemens 7SJ6x overcurrent protection relays
by using the OMICRON Test Universe 2.11 software. The converter provides all necessary data for
testing the overcurrent protection functions (see section 2) of the 7SJ6x relays. The converter is tested
with the following relay:
• 7SJ64 V4.6
• MLFB: 7SJ6412-5EA91-3RH7/DD
Note: This converter is tested with the relay described above. It will work with 7SJ6x relays with firmware
version V4.6. It may work with similar relays, too.
5 Functional Range
The Siemens 7SJ6x XRIO converter implements the following functions:
• 50/51 Overcurrent
• 67/67-TOC overcurrent
• (Sensitive) ground fault
• 46 Unbalanced load protection (negative sequence overcurrent protection)
• 49 Thermal overload protection
For some of the functions listed above use the RIO interface of the Test Universe software. Consequently,
the test modules are configured automatically without using LinkToXRIO.
The following functions are using the RIO interface:
• 50/51 Overcurrent
• 67/67-TOC overcurrent
• Unbalanced load protection
Some functions are modeled in the custom section of the converter. These functions include:
• Cold load pickup
• 2nd Harmonic inrush restraint
• Startup supervision of motors
• Startup counter for motors
• Under/Overvoltage
• Over/Underfrequency
• Breaker failure protection
Notice, that these functions are not linked to the RIOPlus interface. They will be linked to the RIOPlus
interface as soon as the 7SJ6x motor protection template will be available.
8 Converter Structure
The converter is divided into two sections: the 7SJ6x section and the RIO section. Both sections consist of
several function blocks. The converter comes up in standard view; the RIOplus section and the template
controller section only be seen in advanced view.
The General Information block contains the parameters which are important for the test report, e.g.
information about the substation and the feeder. Furthermore it contains power system parameters which
are important for the test modules. These parameters are linked to the device part of the RIO section and
are available in the test report.
8.1.2.1 NamePlate
The NamePlate block contains all necessary information to identify the protection device to be tested. This
block contains the relay vendor, serial number, model, the relay location and a description.
8.1.2.2 PowerSystemParameters
The number of phases, phase rotation and the nominal frequency are stored in this block.
8.1.2.9 AutoRecloserProtection
The AutoRecloserProtection block delivers all necessary information needed for tests of the autorecloser
function. The action and reclaim times and autorecloser cycles are modeled in this block.
8.2 RIO
The RIO section of the converter contains all specialized RIO functions which are needed to use the more
specialized test modules (like Advanced Distance or Overcurrent) provided by the OMICRON Test
Universe software.
Warning: Do not change any values in this section. The values have been set using the relay settings of
the Customer Input section.
Note: Do not activate the former test object view in the advanced mode of the XRIO test object. Changing
parameters in this view could disable formulas in the RIO section.
The following RIO functions for testing these overcurrent protection functions are available:
• Overcurrent forward direction
• Overcurrent reverse direction
The Siemens 7SJ6x XRIO converter constructs a resulting characteristic curve for each direction of the
overcurrent elements. This means that directional and non-directional stages are compared for forward
and reverse direction. The three stages with the smallest pickup values are combined and the resulting
characteristic curve is shown in the RIO overcurrent function block.
The overcurrent stages tested with the RIO Overcurrent reverse direction function are modeled as
forward stages in the RIO function with the CT star point being automatically set opposite to the device's
CT star point setting. If the device's CT star point is set to towards protection object, the CT star-point
property in the RIO Overcurrent reverse direction function automatically switches to from protection
object.