You are on page 1of 18

Line to Ground Voltage Monitoring

on Ungrounded and Impedance


Grounded Power Systems
December 2010/AT301

by Reza Tajali, P.E.


Square D Power Systems Engineering

Make the most of your energy SM

Revision #1 12/10
Abstract
Power monitoring devices are sometimes used on ungrounded and impedance grounded systems to record
and alarm on line to ground voltages. This recorded line to ground voltage data can be manipulated using a
host of data analysis tools to evaluate insulation stress on power system components . However, ungrounded
and impedance grounded systems have specific issues that impact proper application of metering equipment.
Get connected
Voltage transformers are especially prone to misapplication. This paper is intended to provide a road map for
to power
proper application of power monitoring in these circuits. The subject of grounding is explored to demonstrate
the basic issues with ungrounded systems. A discussion of metering principles is provided to identify the
limitations for this type of metering. Ample discussion is provided on the subject of controlling ferro-resonance.

I. Introduction
Power monitors are generally designed for two basic metering connections. Three element metering is normally
used on 3φ 4w feeders where system neutral is available. These systems are solidly grounded. Two element
metering is generally applied to any 3φ 3w feeder. A 3φ 3w feeder is one for which system neutral is not
available or can not be used. Specifically this includes ungrounded Delta, ungrounded wye and impedance
grounded wye systems. See Figure 1.

The special application discussed in this paper utilizes three element metering on an ungrounded or impedance
grounded system. This is a variation from the norm in metering electricity. This method of metering is applied to
measure line to ground voltages.
Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

II. Metering Accuracy


The principle behind all electricity meters, most popularly known as Blondel theorem, is stated as follows:

“The total power of a general n-phase system is the sum of n powers. These powers are given by n currents
which issue from the n terminals, with the n potential differences of these terminals against any arbitrary
Get connected
terminal.”
to power

For a three phase system this principle is shown graphically in Figure 2. The reference point for voltages (Vx)
can be any point. In the case of the metering system discussed in this paper, this point is taken to be the earth
potential. This point does not have to be the neutral of the system.

With voltages measured line to ground in an ungrounded or impedance grounded system, the individual phase
power values (KW, KVAR, KVA) may be meaningless . Some of these individual phase powers may come out
positive, some may come out negative. But, per Blondel’s theorem, the total 3 phase power will always add up
to the correct value. Additionally, if the meter calculates power factor by dividing 3 phase power with 3 phase
KVA, the power factor values will be correct. If the meter displays any individual phase power factor values,
those values will be meaningless.

There is not one consistent method for calculating the power factor – especially in the presence of current and
voltage distortion. Different power monitors use different methods. Individual manufacturer must be consulted.

Disturbance monitoring is an important feature of power monitors which will be affected by the connection
method. With the three element connection discussed in this paper, disturbances (sag, swell, transients) are
measured with respect to ground. Voltage distortion is also measured with respect to ground. Care must be
exercised when interpreting these data.

Vc Ic

Va Ia
Vx

Ib
Vb

Figure 2: Blondel theorem

III. What to Measure


The following values are of particular interest on ungrounded systems:

1.) RMS value of line to ground voltages: A significant increase in voltage unbalance will signify a ground fault
condition.

2.) Line to ground voltage transients: If the system is ungrounded, be prepared to see a great number of
transients on some feeders – especially on an aging power system. These transients may disrupt sensitive
electronic equipment and stress the insulation on electrical machinery. Waveform captures from these
transients can be used to evaluate possibility of partial (arcing) ground faults and ferro-resonance.

AT301 | 3
Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

IV. Impedance Grounded Systems


Figure 3 depicts the voltage connection used for monitoring line to ground voltages on an impedance
grounded systems. By monitoring line to ground voltages it is possible to detect and alarm in case of ground
faults.

Get connected
In addition to individual phase currents, the power monitor will measure and display the vector sum of the
to power
phase currents. With the connection under discussion, this vector sum will be equal to the ground current.
Some power monitors have the capability to directly measure the ground current. See Figure 4.

Even though the voltage transformers are connected line to ground, it is recommended that the transformers’
primary side have a voltage rating at least equal to the system’s line to line voltage. This is because a line to
ground fault on any phase will impress the line to line voltage on the transformers on the other two phases.

This type of system is not prone to voltage transformer ferro-resonance. Therefore, the metering circuit will not
require any burdening resistors (the subject of ferro-resonance will be discussed later in this paper.)

Figure 3: Optional voltage connection for impedance grounded systems.

AT301 | 4
Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

Get connected
to power

Figure 4: Current transformer connections for impedance grounded system

V. Ungrounded Systems

A. Ungrounded Systems’ Inherent Instability

Historically, there has been a gradual trend in American practice from ungrounded systems to solidly grounded
or impedance grounded systems. Initially, most systems were ungrounded - this was the natural thing to do as
the ground connection was not necessary for the actual transfer of power. This method had a strong argument
in it’s favor as insulation failure on one of the phases could be tolerated for some time until the fault could be
located and repaired.

A major limitation to the ungrounded system has been the arcing ground fault. By arcing ground is meant a
process by which alternate clearing and re-striking of the arc causes recurring high surge voltages. These
surge voltages stress the insulation on other parts of the system causing premature equipment failure.

Additionally, in an ungrounded system, the voltages to ground are inherently unstable. To understand these
principles a simplified model of the system is drawn (Figure 5).

AT301 | 5
Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

c
Ic
a
Ia
b
Ib
Co Get connected
to power
c

Ia
Ic a
Ib

Figure 5 – Simple ungrounded system

The system capacitance to ground is modeled by three shunt capacitors C. Under ideal conditions, with
system impedances balanced, the charging currents from the three capacitors add to zero. So far as voltages
are concerned, a virtual neutral point can be envisioned in the delta transformer which will be at ground
potential in such an ideal system.

In actual practice the system impedances are not exactly balanced and the virtual neutral point, discussed
above, is not at earth potential. Therefore, the individual phase voltages to ground will not be equal.

Figure 6 illustrates the situation encountered in a line to ground fault. During an arcing ground fault the circuit
depicted in Figure 6 is opened and re-struck due to the action of the arcing fault. This action creates significant
voltage transients.

1.73
c

3.0
a
1.73
b
1.73 0 1.73 IF
Co

3.0
G
c
Vcg IF
Igb
Igc
G

b Vbg

Figure 6 – Ground fault on simple ungrounded system

AT301 | 6
The solution to these problems of ungrounded systems is to provide system grounding, either directly or
through an impedance. In case of a wye connected system the neutral point is directly available and can be
used. In case of a delta connected system, the neutral point can be derived through grounding transformers.
Figure 7 demonstrates two approaches in using grounding transformers.

The grounding resistance is sized so that the magnitude of ground current during a line to ground fault would Get connected
be slightly larger than the system capacitive charging current. This provides the highest value of resistance that to power
is acceptable (hence High Resistance Ground). The grounding resistance can be smaller than this value. But at
these lower values the magnitude of ground fault current increases.

Such properly sized grounding resistance will provide damping to voltage transients during arcing ground
faults. It can be said that it stabilizes the power distribution system. Essentially, this kind of system has all the
advantages of ungrounded systems plus the added benefit of controlling line to ground voltage transients and
voltage transformer ferro-resonance (Ferro-resonance will be discussed later in this paper).

Once the magnitude of the ground fault current is established, the transformers in Figure 7 are sized to carry
this current. This establishes the thermal rating of the transformers.

Figure 3: Ground Fault on Load Bus #1 Could Shut Down the Entire Data Center

B. Ground Fault Indicating Circuits for Ungrounded Systems

Despite the advantages of grounding through impedance, many installations remain ungrounded. This is
primarily because of economic reasons. In these instances, the circuit depicted in Figure 8 has been commonly
used. During a phase A to ground fault, the phase A pilot light would burn dimly while phase B and C pilot
lights would be brighter than normal. The problem with this system has been that the pilot lights are usually not
under continuous supervision. Therefore, relay “CR” is introduced to alarm in case of a ground fault.

This diagram shows a “Resistor” installed in the open delta. This resistor is used to dampen the effect of ferro-
resonance. The subject of ferro-resonance will be discussed in the next section.
Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

Get connected
to power

Figure 8 – Ground fault indicating lights

It is of particular interest to compare Figure 7b and Figure 8 above. There is a similarity in transformer
connections (both schemes use Y-Δ connections and a resistor.) But the similarity is in schematic only and the
two systems differ in thermal withstand and selection of the resistors. The resistor in Figure 7b is sized to allow
sufficient current flow to stabilize the power system while the resistor in Figure 8 is significantly larger in ohmic
value. This resistor (Figure 8) is installed to dampen the ferro-resonance condition that could be caused by
voltage transformers. It does not allow sufficient current flow to stabilize the ungrounded power system.

A better approach to the alarm system depicted in Figure 8 would be to replace the pilot lights with a power
monitoring Device and connect the transformers in a wye-wye configuration (Figures 9). In this case three
damping resistors are installed –one on each phase. Data on the sizing of the resistors will be provided in the
next section.

With a power monitor we have the capability to evaluate the line to ground voltages as well as the line to line
voltages. This provides a complete monitoring of the voltage quality.

Figure 9 – Voltage transformer connections for ungrounded system

AT301 | 8
Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

VI. Ferro-Resonance
The following discussion on ferro-resonance is provided with the assumption that voltage transformers are
used (existing installations predominantly use voltage transformers). Some newer power monitor designs
can accept voltage inputs up to 600 volts without any need for voltage transformers. These units pose as
a large resistance when connected to the power system. Where voltage transformers are not used, there is
Get connected
no concern for this type of ferro-resonance. However, care must be exercised when applying these power
to power
monitors without voltage transformers. Many of these units do not have the proper rating to be used on
ungrounded systems. Consult with the power monitor manufacturer.

In this context, ferro-resonance refers to the circuit created by a variable or saturable inductor and power
system’s distributed capacitance (Figure 10).

Normal
Operating
Range
Rated
Primary
Voltage

Existing Current

Figure 10 – Ferro-resonance Figure 11 – Transformer magnetizing curve

The magnetizing impedance of transformers is nonlinear as depicted in the transformer’s magnetizing curve
(Figure 11). Transformer’s magnetizing impedance and system’s capacitance can cause this special type
of resonant condition. In order to excite this circuit the voltage must rise into the saturated region of the
transformer’s magnetizing curve. Voltage transients caused by switching or arcing ground faults can trigger this
condition.

The result of this resonant condition is that high voltages will appear, especially across the open delta of a
set of VT’s connected per Figure 8. Depending on the size of the system, significant voltages to ground may
appear in the power system itself. The resistors in Figures 8 and 9 are introduced to provide damping to the
ferro-resonance circuit. It must be noted that there is not a fixed value of “R” that would solve every ferro-
resonance problem.

Due to the complex nature of the varying magnetizing reactance, direct analytical solutions were not possible
until recent times. Using digital simulation, it is now possible to model the network. But these simulations are
rather complex and they are invariably based on some fundamental assumptions about the power system’s
distributed capacitance and varying inductance. Validity of the results is tempered by the inherent error in these
assumptions. Therefore, the results must be proven by actual field measurement.

AT301 | 9
Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

Prior to the advent of digital simulation, however, several empirical formulas were developed based on
significant testing and field experience. The results of these tests and the empirical formulas have been
published in IEEE papers since 1930’s. Of particular interest is the work by 2H. A. Peterson and the work
by 1Taylor and Carlicek (See the list of References). It must be noted that no conclusive standard has been
developed on the sizing of “R”. Therefore, there is no “guarantee” of results.
Get connected
It is generally agreed that there is a critical value of “R” below which ferro-resonance is unlikely. However, the to power
two papers mentioned above recommend different methods, arriving at somewhat different results. Readers
are encouraged to study the original references for a full description of the methodology and the results.

According to Peterson’s findings:

Rmax = Xm / 3N2 (1)

Where N is the transformer ratio and Xm is the voltage transformer’s magnetizing impedance at the rated
voltage in ohms. Specifically, the magnetizing impedance is the ratio of the rated RMS primary voltage to the
RMS value of magnetizing current at this voltage. It must be noted that the value of Xm is not readily available
from manufacturer’s catalog. It is much easier to simply take a measurement.

According to Taylor / Karlicek’s findings:

Rmax = 100a / 3N2 (2)

Where N is the transformer ratio and La is the saturated or air core inductance of the voltage transformer
primary windings in millihenrys. La can be easily calculated from the geometry of the windings.

Equation (2) may derive a lower value for “Rmax” compared to equation (1).

The laymen, having to solve the problem day to day, came up with a rather interesting “rule of thumb” as the
solution. The value of “R” was selected to provide the maximum allowed burden on the transformer under
worst conditions. The worst case burden is placed on the transformer during a line to ground fault. During a
line to ground fault the voltage across the transformer will be equal to the system line to line voltage, providing
maximum current flow. The value of “R” is selected such that transformer’s burden rating is not exceeded. This
is the lowest value of “R” that can be used on this transformer.

If this value of “R” would not do the job, it would be necessary to select a transformer with a higher burden
rating. The resistor can not be any smaller! It must be noted that this selection for the value of “R” is rather
arbitrary in that a larger value may do as good of a job as the minimum value calculated by this method.
Additionally, the accuracy of the voltage transformer is severely taxed by being burdened to its limit. If the
user can perform some testing of his own, he can determine a more optimum value for “R”. The calculations
presented above can be used as a sanity check, or a starting point.

In case of Figure 8, the value of the resistor across the open delta will be three times the value calculated by
equations 1 and 2.

AT301 | 10
Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

Sample Calculations:

Three voltage transformers with primary rating of 480 volts (4 to 1 ratio) are to be connected per Figure 9.
The transformers have a continuous thermal rating of 500VA, a burden rating of 200VA for 1.2 accuracy class
and 75VA for 0.3 accuracy class. The power system is 480V delta, ungrounded. Design the metering circuit
components. Get connected
to power

A. Peterson’s Method

Apply, to the primary of the transformer, a voltage as close as possible to the full rated transformer primary
voltage and measure the exciting current. A sample transformer was selected. 472 volts RMS was applied and
the RMS value of magnetizing current was measured at .03 amperes. The critical value of “R” is calculated as
follows:

Xm = 472 /.03 = 15733


Rmax = Xm / 3N2 = 15733 / (3x42) = 328Ω

B. Maximum Burden Method

The 1.2 accuracy class is the lowest acceptable for metering. So the maximum burden of 200VA is used for
calculations.

The value of “R” will be calculated to produce maximum allowed burden (lowest allowed resistance):

Rmin = 1202/200 = 72Ω

A standard 75Ω, 225W resistor can be used. In case of the circuit in Figure 8, the value of the resistance
across the open delta will be three times the value calculated above.

A value closer to the thermal rating of this transformer (500VA) could have been used for this calculation. At
that level of burden, the accuracy of the transformer would not be suitable for metering. However, at high
burden, this set of transformers would still work as a ground fault detection circuit. In actual application, it
is possible that the requirements of metering accuracy and ground fault detection come in conflict with one
another.

In order to avoid this potential conflict, for ungrounded systems, it is recommended that a separate set of
voltage transformers (and a separate power monitor) be installed for ground fault detection. This set of voltage
transformers will be dedicated to monitoring and alarming for ground faults. By keeping the metering circuit
separate from the ground fault detection circuit, each circuit can be optimized.

C. Voltage Transformer Overcurrent Protection

The customary practice is to size voltage transformer primary fuses to provide short circuit protection and
withstand transformer inrush current. Generally, the primary fuses do not provide satisfactory overload
protection in case ferro-resonance is encountered. So it is important to remove ferro-resonance by damping
the circuit as discussed above.

AT301 | 11
Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

D. Resistor Installation Considerations

Select a resistor that carries UL listing. Listed devices are evaluated for safety and are generally approved by
local jurisdictions.

Also note that resistors generate heat. Contact the switchgear manufacturer for recommendations about Get connected
resistor installation. Switchboard standard UL891 allows a maximum of 250 watts of this type of resistance to power
heat in each section of the switchboard. Therefore, the resistors may have to be mounted outside of the
switchgear enclosure.

VII. The Case of Y-Y Connected Power Transformer


Power system transformers are often connected in a wye–wye configuration. These transformers may be
ungrounded, grounded or they may be provided with a tertiary delta winding. A number of combinations of
grounding arrangements are possible. Under certain conditions, significant voltage to ground distortion will be
present on the secondary side of these transformers. The subject is discussed in the Westinghouse Electrical
Transmission and Distribution Reference Book (see the references at the end of this paper). This section
describes the basic reason why the voltages to ground become distorted and their effect on metered values.
This discussion also serves to demonstrate a basic problem in interpretation of data when only line to ground
voltages are measured.

The magnetizing current of power transformers is inherently nonlinear. This is because power transformers are
normally worked into the saturation region of their magnetic core. This inherent non-linearity of the magnetic
B-H curve causes the magnetizing current to be non-linear.

This magnetizing current has a significant third harmonic component. Where this third harmonic magnetizing
current is able to flow, the flux in the transformer core and the voltages remain essentially sinusoidal. The
problem arises where this third harmonic current can not flow.

Figure 12 shows examples of where the third harmonic magnetizing current can and can not flow.

AT301 | 12
Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

Get connected
to power

Figure 12 – Connections that influence the flow of third harmonic exciting current (per Westinghouse Electrical
Transmission and Distribution Reference Book)

Where the third harmonic current can not flow, the voltages to ground will be distorted. These cases normally
occur where:

1.) The power transformer is wye-wye connected.

2.) Either the system generation or the transformer primary is not grounded.

3.) The transformer secondary is ungrounded or impedance grounded. Also, in some cases, with grounded
secondary.

4.) Tertiary delta winding is not provided to circulate the third harmonic magnetizing current.

In these instances, the line to ground voltages will have a peaking third harmonic component as illustrated by
the waveform capture in Figure 13. Lines to line voltages, however, are not affected. Figure 15 shows line to
line voltages calculated from the line to ground waveforms.

AT301 | 13
Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

A-N Voltage Waveform


800
Max: 695.351
Min: -693.615
600 Avg: 273.943
Abs: 695.351
400 RMS: 372.379
CF: 1.86732
FF: 1.35933
200
Get connected
0 to power
-200

-400

-600

-800
0 20 40 60 80
Time (mS)

Figure 13 – Line to ground voltage on transformer secondary

Harmonic Analysis of L-N Voltage


350
Freq: 60
Fund: 334.644
300 THD: 48.8058
TID: 0
TD: 48.8058
250 RMsh: 163.326
RMSi: 0
RMSfh: 372.373
200 RMS: 372.373
ASUM: 537.824
TIF: 81.0579
150 IT: 30183.8

100

50

0
0 600 1200 1800 2400
Frequency (Hz)

Figure 14 – Harmonic spectrum of line to ground voltage shows significant third harmonic component

L-L Voltage Waveform


1000
Max: 839.486
Min: -839.772
750 Avg: 524.785
Abs: 839.772
500 RMS: 583.223
CF: 1.43988
FF: 1.11136
250

-250

-500

-750

-1000
0 20 40 60 80
Time (mS)

Figure 15 – Line to line voltage calculated from line to ground voltages

AT301 | 14
Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

When configured for three element metering, power monitors utilize only the line to ground voltage values
for calculations. This includes sag/swell detection and waveform capture. Care must be exercised when
interpreting these data.

The waveforms captured (line to ground voltage waveform) and the calculated harmonic data should not be
directly used to evaluate the quality of the voltage provided by the utility. However, as shown in Figure 15, the Get connected
third harmonic component of the line to ground voltages will not appear in the line to line voltages. Therefore to power
line to line voltages can be used to evaluate the voltage quality. The line to line waveform must be calculated
from the line to ground waveforms. The calculations can be performed by a waveform analysis software.

The above discussion is an extreme example of the problem in interpretation of data. This applies to all line
to ground voltage measurements in ungrounded and impedance grounded systems: If you look at the line
to ground voltage measurements directly, you will not obtain a usable estimate of voltage quality from the
standpoint of distortion and voltage sags (two main indices of power quality).

AT301 | 15
Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

VIII. Conclusions
1.) Power monitors can be configured to measure line to ground voltages in ungrounded and impedance
grounded systems. Whether a power monitor is connected in this fashion or in the classical 2 element
fashion depends on the purpose behind taking measurements. The user must understand the limitations of
this connection type to correctly make this choice.
Get connected
2.) The primary function of this type of metering has been ground fault detection. It must be noted that this
to power
feature is not a “protection” feature - which is normally left to protective relaying. In this application, power
monitors are used for monitoring and alarming purposes. On ungrounded systems, significant line to
ground voltage unbalance can signify a ground fault. Arcing grounds and ferro-resonance conditions can be
detected using transient capabilities of the power monitor – where the device is provided with this capability.

3.) This type of connection will have an impact on the transient recording and sag/swell features of the power
monitor. All these values will be referenced to ground. Additionally, the voltage harmonic measurements
and waveform capture feature will be referenced to ground. The user must weigh this limitation against the
advantages provided by this connection.

4.) The basic metering values are calculated correctly. Power monitors have different methods for calculating
the power factor (displacement and total). Whether the power factor values will be correctly depicted
depends on the power monitor design.

5.) Some power monitors are designed for direct connection to circuits up to 600 VRMS. Care must be
exercised when applying these devices in a three element configuration to ungrounded systems. Voltage to
ground levels may exceed the rating of the power monitor, especially in the presence of ferro-resonance.
Manufacturer of the device must be consulted. It may be necessary to use voltage transformers.

6.) When applying three element metering with voltage transformers on an impedance grounded system,
burdening resistors are not required. It is recommended that the voltage transformers’ primary be rated for
system’s line to line voltage.

7.) When applying three element metering on an ungrounded system, the voltage transformers may need to
be burdened to avoid ferro-resonance. Additionally, voltage transformer primary must be rated for system’s
line to line voltage. The selection of the burdening resistor is an art in its own. It may be required to place
such burden on the transformer that the transformer accuracy will be severely reduced. Therefore, it is
common practice to use separate voltage transformers for ground fault detection and metering circuits. (3
element connection for line to ground monitoring, and 2 element connection for metering).

8.) Wye-Wye connected power transformers can be a special problem in the application of three element
metering for line to ground voltage detection. Under certain conditions significant peaking third harmonic
line to ground voltages can be present on the secondary of the power transformer. Care must be exercised
when interpreting the disturbance recording and harmonic measurement values.

AT301 | 16
Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

References
1.) Ferro-resonance of Grounded Potential Transformers on Ungrounded Power Systems, R. F. Karlicek & E. R.
Taylor, Jr., AIEE Transactions,

2.) Transients in Power Systems, Harold A. Peterson, Wiley Press, New York, 1951

3.) Electrical Transmission and Distribution Reference Book, Central Station Engineers of Westinghouse Electric Get connected
Corporation, Westinghouse Electric Corporation, Pittsburgh, 1964 to power
4.) Voltage Transformer Ferro-resonance in cogeneration substation, William S. Vilcheck and Michael V.
Haddad, IEEE, 1992

5.) Criteria for Neutral Stability of Wye-Grounded-Primary Broken-Delta-Secondary Transformer Circuits, H.S.
Scott and H.A. Peterson, AIEE Transactions, November 1941

6.) Physical Nature of Neutral Instability, A. Boyajian and O.P. McCarty, AIEE, 1930

7.) Neutral Inversion of a Single Potential Transformer Connected Line-to-Ground on an Isolated Delta System,
Lyle L. Gleason, AIEE, 1951

AT301 | 17
Reza Tajali, a registered electrical engineer in several states, is an engineering manager for Schneider Electric's
Square D Power Systems Engineering group in Nashville, Tennessee. He has more than 20 years experience with
electrical power distribution and control. Tajali holds two United States patents on switchgear products. He manages

©2010 Schneider Electric Industries SAS, All Rights Reserved.


a group of engineers who are responsible for power system analysis and reliability assessment on industrial and
commercial facilities. That work includes inspection, measurement, analysis and simulation of power systems.

Schneider Electric USA, Inc.


Data Center Solutions
1010 Airpark Center Drive
Nashville, TN 37217
615-844-8300
sedatacenters.com

Document Number AT301 December 2010 tk

You might also like